GENERAL NOTES :

ALL GENERAL ELECTRICAL WORKS SHALL BE EXECUTED IN ACCORDANCE WITH THE PROVISIONS OF
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, LAWS AND ORDINANCES OF THE LOCAL PANELBOARD : MDPB ( MAIN DISTRIBUTION PANEL BOARD)
MUNICIPALITY, RULES AND REGULATIONS OF THE LOCAL POWER COMPANY.
LEGEND:
POWER SERVICE TO THE BUILDING SHALL BE 220 V, THREE PHASE, THREE WIRES, 60Hz. PPB
PARSONAGE PANEL BOARD
WIRING SHALL BE AS FOLLOWS: SPB2
SCHOOL PANEL BOARD NO. 2
a ) SERVICE ENTRANCE - RIGID STEEL CONDUIT / IMC PIPES "MATSUSHITA"
SPB1
b ) FOR LIGHTINGS - PVC FLEXIBLE PIPES SCHOOL PANEL BOARD NO. 1
GPB
c ) FOR POWER - PVC FLEXIBLE PIPES GYM PANEL BOARD
d ) FOR TELEPHONE SYSTEM - PVC FLEXIBLE PIPES CPB
CHURCH PANEL BOARD
SMALLEST CONDUCTOR TO BE USED SHALL BE NO. 3.5mm(12) AWG AND SMALLEST RACEWAY SHALL MDPB
BE 15mm(1/2) DIAMETER TRADE SIZE CONDUIT. CONDUCTORS SHALL BE INSULATED FOR 600 VOLTS MAIN DISTRIBUTION PANEL BOARD
THHN OR THW OR AS INDICATED IN THE PLANS, PHELPS DODGE.
G GENERATOR, 50Kva/40Kw
FEEDERS AND BRANCH CIRCUITS SHALL BE INSTALLED AS INDICATED IN THE PLANS. HOMERUN SHALL
NOT BE COMBINED IN THE SAME RACEWAY UNLESS SO NOTED.
M KW-HR METER
NO BRANCH CIRCUIT CONDUCTOR SHALL HAVE A LOAD OF MORE THAN 80% OF ITS RATING.
SERVICE ENTRANCE, FROM
WIRE GUTTERS, SQUARE BOXES AND PULL BOXES SHALL BE PROVIDED ON CIRCUITS AND HOMERUN
IN EXCESS OF 30 METERS OR WHERE NECESSARY.
NEECO POWER SOURCE I
OUTLET BOXES SHALL BE GAUGE NO. 16 (MIN) PRESSED STEEL GALVANIZED DEEP TYPE. CIRCUIT BREAKER (SQUARE D OR GE)
a ) CEILING LIGHT OUTLETS - 40mm (1 1/2) DEEP, 100mm (4") OCTAGONAL BOX
MANUAL TRANSFER SWITCH,
FOR 1 OR 2 RACEWAY EMTRIES, 50mm (21/8") DEEP, 100mm(4") OCTAGONAL BOX BREAKER TYPE, (MTS)
FOR 3 OR 4 RACEWAY ENTRIES.
b ) WALL SWITCHES - 55mm (2 1/8") DEEP; UTILITY BOX FOR 1 OR 2 SWITCHES ON
STRAP, 40mm (1 1/2") DEEP, 100mm (4") SQUARE BOX WITH ONE GANG RAISED PANELBOARD : GENERATOR PANEL BOARD
COVER FOR 3 SWITCHES ON STRAPS.
c ) WALL OR COLUMN RECEPTACLE - 55mm (2 1/8") DEEP, UTILITY BOX FOR 1 OR 2
RACEWAY ENTRIES, 40mm (1 1/2") DEEP, 100mm (4") SQUARE BOX WITH ONE GANG
RAISED COVER FOR 3 OR MORE RACEWAY ENTRIES.
d ) WALL OR COLUMN TELEPHONE OUTLET - 55mm (2 1/8") DEEP, UTILITY BOX UNLESS
OTHERWISE INDICATED ON THE PLANS.
ALL BRANCH CIRCUIT CONDUCTORS SHALL BE COLOR CODEDAS PER REQUIREMENT OF PEC ARTICLES
GROUNDED CONDUCTOR SHALL BE IDENTIFIED BY A CONTINUOS COLOR WHITE. GROUNDING CONDUCTOR
OF BRANCH CIRCUITS SHALL BE IDENTIFIED BY A CONTINUOS GREEN COLOR UNLESS IT IS BARE
LINE 1-RED, LINE 2-BLUE, LINE 3-BLACK, GROUND-GREEN.
10. EXPOSE WIRING FOR LIGHTING AND CONVENIENCE OUTLETS SHALL BE IN RIGID STEEL CONDUIT (RSC) OR
ELECTRICAL METALLIC TUBING (EMT) PIPE RUN PARALLEL TO BEAM AND TRUSSES.
11. MOUNTING HEIGHTS SHALL BE AS FOLLOWS :
a ) LIGHT CONTROL SWITCHES - 1.40m. ABOVE FLOOR FINISH
b ) CONVENIENCE OUTLET ( GROUND FLR ) - 2.00m. BELOW CEILING FINISH
c ) TELEPHONE OUTLET - 0.30m. ABOVE FLOOR FINISH
e ) PANEL BOARDS AND CABINETS - 1.80m. ABOVE FLOOR FINISH
f ) COUNTER TOP OUTLETS - 0.15m. ABOVE COUNTER TABLE
g ) WALL FAN - 1.60m. ABOVE FLOOR FINISH
h ) CONVENIENCE OUTLET ( 2ND TO 4TH FLR ) - 0.30m. ABOVE FLOOR FINISH
12. ALL FLOURESCENT LIGHTING FIXTURES SHALL BE PROVIDED WITH RAPID START OR HIGH POWER FACTOR
BALLASTS WITH SPRING LOADED LAMP HOLDERS.
13. CONDUITS AND METAL FRAMES OF EQUIPMENT SHALL BE BONDED TOGETHER BY MEANS OF COPPER
STRAPS. CONDUITS OF SYSTEM SHALL BE PROPERLY GROUNDED TO THE WATER SUPPLY SERVICE
PIPES WHENEVER POSSIBLE OR GROUND ROD INSTALLED FOR THE PURPOSE. GROUND ROD
SHALL BE 20mm DIA x 3000mm. COPPER CLAD STEEL EMBEDDED TO THE GROUND WITH ITS
TOP ACCESSIBLE FOR INSPECTION.
14. RECEPTACLES IN GENERAL SHALL BE RATED AS 10A, 250V NATIONAL IN BRAND.
a ) CONTROL SWITCHES IN GENERAL SHALL BE RATED AS 15A, 300V NATIONAL IN BRAND.
15. LIGHT
b ) WN 5001-98 15A, 300V, NATIONAL, SINGLE POLE SWITCH "B" MODERN PLATE COVER. POWER SERVICE ENTRANCE
THREE PHASE, THREE WIRES,
c ) WN 5002-98 15A, 300V, NATIONAL, THREE WAY SWITCH "C" W/ MODERN PLATE COVER. 230VAC, 60 Hz
WN 5061-801 15A, 300V, NATIONAL APPELATION SWITCH "B" SINGLE POLE FOR SWITCHBANK.
16. LIGHTS CONTROL SWITCHES FOR SWITCHBANK SHALL BE RATED AS 15 A, 300 VAC APPELATION
SWITCH "B" SINGLE POLE WN 5061-801 NATIONAL, REFER TO PLANS FOR PLATE COVER.
17. PANELBOARDS AND BREAKERS
a ) ALL MAIN CIRCUIT BREAKERS SHALL BE MOLDED CASE INTERRUPTING
CAPACITY AS SHOWN IN THE SCHEDULE OF LOADS. M
b ) ALL BRANCH CIRCUIT BREAKERS SHALL BE BOLT-ON INTERRUPTING
CAPACITY AS SHOWN IN THE SCHEDULE OF LOADS. KWHR METER

c ) PROVIDE ACTUAL SCHEDULES OF LOADS SEE DIRECTIONS FOR EACH


INDIVIDUAL PANELBOARD. PUT NAMEPLATES (MICARTA) FOR EACH PANELS.
MDPB
d ) ALL CIRCUIT BREAKERS SHALL BE "GE" IN BRAND OR APPROVED EQUAL. 160AT 250AT 200AT 70AT 225AT
2P 2P 2P 2P 2P
18. THE CONTRACTOR SHALL CONDUCT TEST TOGETHER WITH OWNERS REPRESENTATIVE SUCH AS SPARE
INSULATION TEST, GROUND RESISTANCE TEST, PHASE SEQUENCE TEST AND OPERATING TEST.
ALL TEST RESULT SHALL BE SUBMITTED TO THE OWNERS REPRESENTATIVE. MINIMUM INSULATION PPB SPB2 SPB1 GPB CPB
TEST SHALL BE 250,000 OHMS. MINIMUM GROUND RESISTANCE TEST SHALL BE 25 OHMS.
19. ALL MATERIALS SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE IN
WHICH THEY ARE INTENDED TO BE INSTALLED.
20. THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR G
CONNECTION TO THE POWER SUPPLY, AND ALSO THE ACTUAL LOCATION OF TELEPHONE SYSTEM 50 KVA, SINGLE PHASE PHASE,
SERVICE ENTRANCE TO THE LOCAL TELEPHONE CABLE FACILITIES. EE ROOM 2 WIRES, 230 VOLTS, 60Hz

21. ANY DISCREPANCY IN LOCATION AND RATINGS OF EQUIPMENT AND APPARATUS SHALL BE VERIFIED
WITH THE OWNER OR ANY OF HIS REPRENTATIVES AND CHANGES SHALL BE MADE ACCORDINGLY.
22. FOR EACH SPARE BRANCH CIRCUIT OF PANEL BOARDS, PROVIDE 20mm(3/4") DIA. EMPTY
CONDUIT TERMINATED TO 100mm x 100mm SQUARE BOX ABOVE THE CEILING.
23. PROVIDE ENOUGH SUPPORT CONDUITS, PIPE STRAPS, WALL BRACKETS, HANGERS OR CEILING
TRAPEZE. FASTEN BY MACHINE SCREWS, WELDED THREADED STUDS, OR SPRING TENSION CLAMPS
1 RISER DIAGRAM
E-1 SCALE: 1:100 MTS.
ON STEEL WORKS.
24. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE SUPERVISION OF AN EXPERIENCED,
DULY LICENSED ELECTRICAL ENGINEER.
DESIGNER ELECTRICAL ENGINEER : PROJECT TITLE: OWNER: Designed By: REVISIONS SHEET CONTENTS SHEET NO.
NO. DESCRIPTIONS DATE
Drawn/CAD By: CADsource
PROPOSED ROSE OF SHARON UNITED 01 13Jul2017
EDGARDO H. LIGAS FileName:
PROFESSIONAL ELECTRICAL ENGINEER
METHODIST CHURCH E-1
Date:
REG. NO: 1936 PEE PTR NO.: LOCATION: ADDRESS
Checked By:
3
TIN: 190-533-271 ISSUED ON: 01-04-17
ISSUED AT: QUEZON CITY Approved By: