IS 10262 : 2009
Dr. S. RAVIRAJ
Professor of Civil Engineering
JSS Science and Technology University
S.J. College of Engineering
Mysuru – 570 006
ravirajs@sjce.ac.in
1
Introduction
Concrete – indispensable construction
material.
Economically made
2
Introduction
Concrete – Largest consumed material next
to water
3
Bentley MXROAD
A cross over in United States
A cross over in United States
BURJ KHALIFA
• Opened in 2010
• Height 828 m
• 160 + Storeys
7
BURJ KHALIFA
8
BURJ KHALIFA
9
BURJ KHALIFA
• High-performance SCC concrete with a mix
designed to provide a low-permeability and
high-durability was used in walls and columns.
12
Fly ash (Pulverised fuel ash)
Fly ash conforming to Grade I of IS 3812
may be used as part replacement of OPC,
provided uniform blending with cement is
ensured.
14
Silica fume
Silica fume (very fine non-crystalline silicon
dioxide) is a by-product of the manufacture
of silicon, ferrosilicon or the like, from
quartz and carbon in electric arc furnace.
19
Metakaoline
S.G. = 1.15
21
Other Admixtures
22
Mix design- Definition
Labour cost
• formwork, batching, mixing, transporting and
curing
25
1
Objective of Mix Proportioning
Produce Concrete – most economical and
practical combination
27
• Concrete technologist should design the
concrete taking all properties of materials,
exposure condition, field condition, standard
deviation, minimum strength and durability.
30
Requirements which form the basis for the
selection and proportioning of concrete mix:
• Minimum compressive strength
• Adequate workability
32
1
Salient feature of IS 10262 : 2009
Requirements for selection of W/C ratio,
water content and estimations of coarse
aggregate content and fine aggregate
content have been reviewed and accordingly
modified.
33
1
Data for mix proportioning
Grade designation
Type of cement
Workability
34
1
Data for mix proportioning … Contd.
Exposure conditions as per Table 4 and
Table 5 of IS: 456-2000
35
1
Data for mix proportioning … Contd.
Type of aggregate
36
1
Target strength for mix proportioning
Target strength is computed by
37
Mean and standard deviation of comp. strength
38
Example to find Mean and SD of comp. strength
39
8 45 4.8 23.04
9 37 -3.2 10.24
10 35 -5.2 27.04
11 39 -1.2 1.44
12 41 0.8 0.64
13 49 8.8 77.44
14 46
40.2 5.8 33.64
15 36 -4.2 16.64
16 38 -2.2 4.84
17 32 -8.2 67.24
18 39 -1.2 1.44
19 41 0.8 0.64
20 40 -0.2 0.04
Total 804 Total 359.20
40
Statistical values
• Average strength = 804/20 = 40.2 MPa
• Standard deviation, σ = √((359.20)/(N-1))
= √ (359.2/19)
= 4.34 MPa
• Coeff. of variation, = (S.D. / Avg. stg.)
= 4.34/40.2
= 0.108
• Target strength = Ch. comp. strength + k . s
= 30 + 1.65 x 4.34
= 37.16 MPa
Characteristic strength of concrete
1.65 S
42
Values for k
Percentage of results allowed to Value of
fall below the minimum k
0.1 3.09
0.6 2.50
1.0 2.33
2.5 1.96
5.0 1.65
6.6 1.50
16.0 1.00
f1ck = fck + k . s
f1ck = fck + 1.65 s
Standard deviation based on test strength of sample
44
Standard deviation based on test strength of sample
45
1
46
1
Value of ‘S’ correspond to the site control with
• Proper storage of cement
• Weigh batching of all materials
• Controlled addition of water
• Regular checking of all materials
• Aggregate grading
• Determination of moisture content in
aggregates
• Periodical checking of workability and
strength
47
Assumed standard deviation
49
1
Selection of mix proportions … Contd.
• Hence, relationship between strength and
free water-cement ratio should preferably be
established for the materials actually to be
used.
52
• Requirements of durability : Limiting W/C ratio
54
1
Selection of water content
Water content is influenced by a number of
factors:
• Workability requirements
• Reduction in slump
56
1
Selection of water content … Contd.
Water demand increases as
• Increase in slump
• Increase in temperature
57
1
Selection of water content … Contd.
Quantity of mixing water - Table 2
58
1
Selection of water content … Contd.
Quantity of mixing water in Table 2
• Angular aggregates
• Slump range – 25 to 50 mm
59
1
Selection of water content … Contd.
Important to test local materials
60
1
Selection of water content … Contd.
Modifications for value of water content for
different aggregates (for same workability)
61
1
Selection of water content … Contd.
62
1
Selection of water content … Contd.
Modifications for value of water content for
use chemical admixtures conforming to IS
9103 : 1999
64
1
Calculation of cementitious material content
Cementitious material
• Cement
• Cement + Supplementary cementitious
materials
Values are known for the following:
65
1
Calculation of cementitious material content
Check – 1
66
67
1
Calculation of cementitious material content
Check – 1
68
1
Calculation of cementitious material content
Check – 2
(450 kg/m3)
69
1
Estimation of coarse aggregate proportion
70
1
Estimation of coarse aggregate proportion
Volume of CA in Table 2
71
1
Estimation of coarse aggregate proportion
Volume of CA in Table 2 should be modified
for more workable mixes
• Pumping of concrete
• Congested reinforcements
Reduce CA content by up to 10 percent
72
1
Estimation of fine aggregate proportion
• Coarse Aggregate shall conform to IS 383
73
1
Combination of different C.A. fractions
The mass for the following materials are
known
• Cementitious material
• Water content
• Chemical admixture
74
1
Combination of different C.A. fractions
where
Hence,
76
1
Combination of different C.A. fractions
77
1
Trial Mixes
• Measure workability
78
1
Trial Mixes
Remedy
79
1
Trial Mixes
80
1
Trial Mixes
81
1
Trial Mixes
Trial Mixes No. 2 to 4 normally provides
sufficient information
• Workability characteristics
• Relation between compressive strength and
water-cement ratio
Based on the above results and observations,
mix proportion for field may be arrived at.
The trials shall be produced by methods of
actual concrete production.
82
1
Numerical Example – 1
Design stipulations for proportioning
Grade designation : M20
Type of cement : OPC 43
(grade confirming to IS 8112)
Maximum nominal size of aggregates : 20 mm
Minimum cement content : 320 kg/m3
Maximum water cement ratio : 0.55
Workability : 75 mm
(slump)
Exposure condition : Mild
83
1
Design stipulations for proportioning
Degree of supervision : Good
Type of aggregate : Crushed angular
aggregate
Maximum cement content : 450 kg/m3
Chemical admixture : Not recommended
84
1
Test data for materials
Cement used : OPC 43 grade
conforming to IS 8112
S. G. of cement : 3.15
S. G. of C.A. : 2.68
S. G. of F.A. : 2.65
Water absorption
Coarse aggregate : 0.6 percent
Fine aggregate : 1.0 percent
85
1
Test data for materials
Free (surface) moisture
Coarse aggregate : Nil (absorbed moisture full)
Fine aggregate : Nil
Sieve analysis
Coarse aggregate : Conforming to Table 2 of
IS: 383
Fine aggregate : Conforming to Zone I of
IS: 383
86
1
= 20 + 1.65 x 4
= 26.60 N/mm2
87
88
1
89
1
Selection of water content
From Table-2,
Maximum water content = 186 liters
(25mm – 50mm slump range, MSA = 20 mm)
90
1
91
1
Calculation of cement content
W/C ratio = 0.50
Hence, O.K.
92
1
Proportion of volume of coarse aggregate and
fine aggregate content
From Table 3,
Volume of CA/ unit vol. of TA = 0.6
(MSA = 20 mm, FA = Zone I, W/C = 0.50)
93
94
1
Proportion of volume of coarse aggregate and
fine aggregate content
From Table 3,
Volume of CA/ unit vol. of TA = 0.6
(MSA = 20 mm, FA = Zone I, W/C = 0.50)
Actual W/C = 0.50
Corrections – Nil
Hence,
Volume of FA/ unit vol. of TA = 1 – 0.6
= 0.4
95
1
Mix calculations
97
1
Slump = 90 mm
99
1
Proportions per cubic meter of concrete
100
Workability and compressive strength results
• GO GREEN
103