EXERCISE OBJECTIVE In this exercise, you will measure the level in a vessel using a wet reference leg.
DISCUSSION OUTLINE The Discussion of this exercise covers the following points:
Using the definition of static pressure and hydrostatic pressure, the total pressure
at the bottom of a closed tank is:
In most cases, the density of the gas is much less than the density of the process
liquid. Thus, the pressure due to the weight of the gas can be neglected and
Equation (4-10) becomes:
ܲ ൌ ܲ ߩ ݄݃ (4-11)
There are two types of installations to measure a level in a closed tank using a
differential-pressure transmitter. Figure 4-16 illustrates both of them.
Figure 4-16a illustrates a dry reference leg installation and Figure 4-16b
illustrates a wet reference leg installation.
Both the wet reference leg and the dry reference leg installation use the same
principle. The reference leg allows the low-pressure side of the differential-
pressure transmitter to receive the pressure of the gas above the process fluid.
The difference between a dry reference leg and a wet reference leg lies in the
filling of the reference leg. In a dry reference leg installation, the process gas fills
the reference leg while in a wet reference leg installation, the process fluid or an
inert liquid fills the reference leg. A wet reference leg installation is required if the
vapors are corrosive, if they can clog the pipe or the transmitter, or if the vapors
can condense in the reference leg.
Shut-off valve
Reference leg
Shut-off valve
Three-valve
Minimum
manifold
measurable level
Shut-off valve
Separator
Drain valve
Measurement errors
Liquid can find its way to the reference leg either if the tank is filled with liquid
above the tap connecting the reference leg to the tank or if the gas at the top of
the tank condenses into the reference leg. In both cases, the liquid in the
reference leg exerts an additional pressure on the low-pressure side of the
transmitter and the transmitter displays a level lower than the actual level.
The process fluid is usually used to fill the reference leg. If the process fluid is
corrosive and might damage the differential-pressure transmitter, an inert liquid is
used instead. Figure 4-18 shows a typical wet reference leg installation.
Shut-off
valve Condensing
chamber
Reference leg
Minimum Three-valve
measurable level manifold
Drain
valves
Measurement errors
Overflow hose
Industrial DP
transmitter
2. Make sure the reservoir of the pumping unit is filled with about 12 liters
(3.2 gallons) of water. Make sure the baffle plate is properly installed at the
bottom of the reservoir.
5. Make the pump rotate at maximum speed. Wait until the column gets full and
the excess water discharges to the reservoir through the overflow hose.
6. Bleed the high- and the low-pressure ports of the industrial DP transmitter.
7. Stop the pump. The water level drops in the column; but the reference leg
remains filled with water.
8. When the column is empty, remove the overflow hose that connects the top
of the column to the reservoir. Block the unused hose port at the top of the
column using a plug. This permits the column to be pressurized.
Transmitter calibration
10. By varying the pump speed and/or the opening of valve HV1, raise the water
level in the column from 5 cm to 29 cm by steps of 2 cm (or from 2 in to 11 in
by steps of 1 in).
After each new level setting, record the pressure differential between the wet
leg and the bottom of the column and record it in Table 4-4.
Ruler level ǻP
cm (in) kPa (psi)
5 (2)
11. Stop the pump and turn off the pumping unit.
12. From the data recorded in Table 4-4, plot the relationship between the water
level in the column and the DP transmitter output.
13. According to the curve obtained, does the pressure differential indicated by
the DP transmitter increase linearly as the level is increased? Why?
14. Disconnect the circuit. Return the components and hoses to their storage
location.
15. Wipe off any water from the floor and the training system.
CONCLUSION In this exercise, you learned how to measure the level in a pressurized column,
using a DP transmitter and a wet leg installation. Since the pressure of the air in
the pressurized column was applied equally on both sides of the transmitter, its
effect was canceled out and the transmitter responded only to the hydrostatic
pressure of the water in the column. Consequently, the transmitter output varied
in direct proportion to the level in the column, as it did when the column was
open to atmosphere.
2. When can you neglect the pressure due to the weight of the gas above the
liquid when measuring the level in a pressurized vessel using a differential-
pressure transmitter?
4. What is the difference between a wet leg and a dry leg installation?
5. What can cause an error in the level measured with a wet reference leg
installation?