Anda di halaman 1dari 5

COM.

PORT
RS232

ALARM OUTPUTS CONTROL UNIT


MK-14 CU2500

X1, TERMINAL BLOCK RK-60

ENGINE TERMINAL BOX


WITH TERMINAL BLOCK X2

+ - + -

START BATTERY AUX. BATTERY

ENGINE, SENSORS AND SWITCHES


SEE PAGE 2 & 3

Customer: Volvo Penta Brazil File Name: SEM-040223-01 Drawing no.


P832 Drawn by: LWP SEM-040223-01
Page Title: Layout Date For Last Change 2004-02-29 16:31:16
Revision: Page1 of 5
CU2500
RK60 (RK66)
X1 1 2 3 4 5 6 41 42 43 44

X2 1 2 X2 3 4 2 5 6 41 42 44

OVERSPEED
ENGINE TERMINAL BOX

START

STOP
30 30 30 30
2K33 2K31 2K24 2K21
87a 87 87a 87 87a 87 87a 87 86 2K21 86 2K24 86 2K31 86 2K33 86 2K37
30
2K37
87a 87
85 85 85 85 85

BACKUP GAC

GAC STOP
0V
3.2

0,01UF
GND
20A E- F+ SCREW

GAC
1F7
8A ELECTRONIC GOVERNOR
1F4 62 X2 2 61
A B C D G J 2 64 2 5 6
+ - + -
1,5¶
230V SUPPLY
FROM MAIN
D+
SW.BOARD
+ - + -
1,5¶ BATTERY
5k•
24VDC AUX. SUPPLY STARTER
1A2 (YARD SUPPLY)
+ -
(YARD SUPPLY)
BATTERY CHARGER

STOP SOLENOID
EMERGENCY
ACTUATOR PICKUP REMOTE SPEED PICKUP
POTENTIOMETER

1S5 (SEE MANUAL FOR SHIELDED WIRING)

(YARD SUPPLY)

+ -
BATTERY

Customer: Volvo Penta Brazil File Name: SEM-040223-01 Drawing no.


P832 Drawn by: LWP SEM-040223-01
Page Title: Engine Connection Box Date For Last Change 2004-02-29 16:31:38
Revision: Page2 of 5
CU2500
X1 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 29

X2 7 8 11 19 20 21 22 23 24

ENGINE TERMINAL BOX


0V
2.38

X2 2 7 2 8 2 11 19 20 21 22 23 24

- - -
C P L
+ + +

DIGITAL SHUT DOWN SWITCHES DIGITAL ALARM SWITCHES ANALOGUE SENDERS 4-20MA

0-200°C

0-600°C
0-10 BAR
ALARM LIMIT: 2 BAR

ALARM LIMIT:92°C

ALARM LIMIT:525 °C
SHUTDOWN SWITCH

SHUTDOWN SWITCH

ALARM SWITCH
COOL. WATER TEMP. HIGH

LUB. OIL PRESS LOW

FUEL LEAKAGE

LUB. OIL PRESS

COOL. WATER TEMP

EXHAUST TEMP
Customer: Volvo Penta Brazil File Name: SEM-040223-01 Drawing no.
P832 Drawn by: LWP SEM-040223-01
Page Title: Digital and Analogue Sensors Date For Last Change 2004-02-29 16:35:36
Revision: Page3 of 5
X1 30
REMOTE START

31
REMOTE STOP

32

P832
33
AUTOMATIC START

Revision:
(BLACKOUT)
34

KEEP CLOSEC UNTIL STARTED

DELAYED STOP
35

KEEP CLOSED UNTIL STOPPED

Customer: Volvo Penta Brazil


36

Page Title: Inputs And Outputs


REMOTE RESET
37

SHUTDOWN OVERRIDE
38
39

KEY SWITCH
40

START DISABLE
(REMOVE STRAP)
CU2500

X1 45

COMMON ALARM
46

(ALL FAULTS)
(K5)

47
48

ALARM SHUTDOWN
49
(K6)

50

Drawn by: LWP


51

READY TO TAKE LOAD


52
(K7)

53

File Name: SEM-040223-01


54

READY TO START
55
(K8)

56
57

Date For Last Change 2004-02-29 16:41:34

DISCONNECT GEN.BREAKER
58
(K9)

59

Page4

CONNECT TO GROUND
60

Drawing no.
SEM-040223-01

of 5
(>500mS)

CLOSE FOR MANUAL


(>500mS)
CLOSE FOR STANDBY
SPARE DIGITAL INPUTS

5U5 5U22
+ X0 X1 X2 X3 X4 X5 X6 X7 24+
COM. CABLE
CPU 232-IF, COM. MODULE CU2500
MODULE

- SS GND Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 24-

PE PE

5F3
3.15A PLC COM. CABLE CU2500
D-SUB D-SUB
9-PIN FEMALE 9-PIN FEMALE

PE 2 3
1 2 3 2

5 5

+ - GND GND
DO NOT
CONNECT
24VDC SPARE DIGITAL OUTPUTS
CLOSED WHEN
CLOSED WHEN CU2500

COM. ERROR
IN STANDBY

SUPPLY

Customer: Volvo Penta Brazil File Name: SEM-040223-01 Drawing no.


P832 Drawn by: LWP SEM-040223-01
Page Title: PLC For remote Stand By Date For Last Change 2004-02-29 16:43:24
Revision: Page5 of 5

Anda mungkin juga menyukai