PORT
RS232
+ - + -
X2 1 2 X2 3 4 2 5 6 41 42 44
OVERSPEED
ENGINE TERMINAL BOX
START
STOP
30 30 30 30
2K33 2K31 2K24 2K21
87a 87 87a 87 87a 87 87a 87 86 2K21 86 2K24 86 2K31 86 2K33 86 2K37
30
2K37
87a 87
85 85 85 85 85
BACKUP GAC
GAC STOP
0V
3.2
0,01UF
GND
20A E- F+ SCREW
GAC
1F7
8A ELECTRONIC GOVERNOR
1F4 62 X2 2 61
A B C D G J 2 64 2 5 6
+ - + -
1,5¶
230V SUPPLY
FROM MAIN
D+
SW.BOARD
+ - + -
1,5¶ BATTERY
5k•
24VDC AUX. SUPPLY STARTER
1A2 (YARD SUPPLY)
+ -
(YARD SUPPLY)
BATTERY CHARGER
STOP SOLENOID
EMERGENCY
ACTUATOR PICKUP REMOTE SPEED PICKUP
POTENTIOMETER
(YARD SUPPLY)
+ -
BATTERY
X2 7 8 11 19 20 21 22 23 24
X2 2 7 2 8 2 11 19 20 21 22 23 24
- - -
C P L
+ + +
DIGITAL SHUT DOWN SWITCHES DIGITAL ALARM SWITCHES ANALOGUE SENDERS 4-20MA
0-200°C
0-600°C
0-10 BAR
ALARM LIMIT: 2 BAR
ALARM LIMIT:92°C
ALARM LIMIT:525 °C
SHUTDOWN SWITCH
SHUTDOWN SWITCH
ALARM SWITCH
COOL. WATER TEMP. HIGH
FUEL LEAKAGE
EXHAUST TEMP
Customer: Volvo Penta Brazil File Name: SEM-040223-01 Drawing no.
P832 Drawn by: LWP SEM-040223-01
Page Title: Digital and Analogue Sensors Date For Last Change 2004-02-29 16:35:36
Revision: Page3 of 5
X1 30
REMOTE START
31
REMOTE STOP
32
P832
33
AUTOMATIC START
Revision:
(BLACKOUT)
34
DELAYED STOP
35
SHUTDOWN OVERRIDE
38
39
KEY SWITCH
40
START DISABLE
(REMOVE STRAP)
CU2500
X1 45
COMMON ALARM
46
(ALL FAULTS)
(K5)
47
48
ALARM SHUTDOWN
49
(K6)
50
53
READY TO START
55
(K8)
56
57
DISCONNECT GEN.BREAKER
58
(K9)
59
Page4
CONNECT TO GROUND
60
Drawing no.
SEM-040223-01
of 5
(>500mS)
5U5 5U22
+ X0 X1 X2 X3 X4 X5 X6 X7 24+
COM. CABLE
CPU 232-IF, COM. MODULE CU2500
MODULE
- SS GND Y0 Y1 Y2 Y3 Y4 Y5 Y6 Y7 24-
PE PE
5F3
3.15A PLC COM. CABLE CU2500
D-SUB D-SUB
9-PIN FEMALE 9-PIN FEMALE
PE 2 3
1 2 3 2
5 5
+ - GND GND
DO NOT
CONNECT
24VDC SPARE DIGITAL OUTPUTS
CLOSED WHEN
CLOSED WHEN CU2500
COM. ERROR
IN STANDBY
SUPPLY