Calculation for cold water Pump

Assume water supply pump for cold water in pump room at Ground Floor (GR-22)

BY FIXTURE UNITE METHOD ACCORDING TO UNIFORM PLUMING CODE TABLE (A-2)

for all building


EWC LAV SK TOTAL
Floor F.U
2.5 1 1.5
2nd.F 12 11 4
1St.F 7 6 2
GR.F 7 6 2
No. of equip.. 26 23 8 57
Fixture unite 65 23 12 100

fixture unite = 100 F.U


Assume 50% of all the fixture unit will work together
Diversety factor = 0.5
Fixture unit = 50 F.U
ACCORDING TO UNIFORM PLUMING CODE CHART (A-3)
Total Consumption =30.00 GPM
ACCORDING TO UNIFORM PLUMING CODE CHART (A-5)
If velocity = 1.5 m/s ,velocity =5 ft/s
PIPE SIZE = 1.5 "

For head of Pump


P = Pr + Pf+ Pv

Pr = Resuideal Pressure at most remote fixture


Pf= Pressure dute to friction from horizontal, vertical , fittings ,and valves on pipe line
Pv= Pressure dute to static head

Pr = 1 bar
Pf= (horizontal length +vertical length +equivelatn length from fittings) x friction factor
horizontal length = 90 m
vertical length = 13.8 m
Eqivelant length = Assume = 20% (from vertical +horizontal length) 1.2
Friction factor = 0.006 bar/m
Pv = 13.8 m
1.38 bar

P = (1) +( (90+13.8)X1.2X0.006 ) + (1.38) = 3.1274 bar


31.5 m
103 ft

Pump charqterstics = 30 GPM


103 FT