Consider a fault FC5. As defined by the zones, only CBs 4 and 5 should
trip. As CB 3 is in close proximity to CB 4, there would be no great
difference in fault current flowing through these two circuit breakers,
therefore IDMT IEDs (Inverse Definite Minimum Time protection relay)
would not be able to discriminate between them. The same situation
applies for CB 5 and CB 6.
This technical article does not go into details of exactly how this is
achieved, but it can be seen that it is possible to determine the
direction of the fault current and base a tripping decision on this
criterion.
The overcurrent IED should trip whenever the fault power flows away
from the bus but should restrain whenever the fault power flows
towards the bus. There are other situations, which do not involve dual
sources, where directional protection devices are necessary.
Parallel feeders in single-end-fed system
One example is for a single-end fed system of parallel feeders. Figure 2
shows a situation where a fault on one of the parallel lines is fed from
both the faulted line and the healthy one too.
This diagrams shows that a fault current will not only flow from the
source, through CB 4, but also from the source, through CB 1, CB 2,
Bus B and CB3. If non-directional IEDs are used, all circuit breakers will
trip, thus isolating the healthy section of line between (1) and (2).
Directional IEDs are more expensive than non- directional ones. What
is more, they necessitate the use of an additional voltage transformer.
For these reasons, they should only be used when absolutely
necessary. You can see by inspection that in this example, non-
directional IEDs will suffice for positions (1) and (4).
For fault at F1, Relay R2 is supposed to pick-up and operate the circuit
breaker.
Similarly, for fault at F2, Relay R1 shall operate to isolate the faulty
section from the healthy section. Now suppose fault occurs at F2, it
may happen so that Relay R2 operate before the operation of Relay R1
as the set pick-up value for both the Relay is same and both Relay see
the same fault current. As Relay R2 is operating here hence the power
supply to the load from Source B is interrupted even when there is no
fault in that section. To avoid such scenario what can be done?
So, what could be the solution? We may arrange something such that
Relay R1 only operate if the fault is at F2 or toward Source A and
likewise Relay R2 operates if the fault is at F1 or toward source B.
This provision is Directional Feature as we are assigning a direction in
which the Relay has to operate.
But how can we provide this directional feature to a Relay? Which
electrical quantities need to be used for this?
For answering this, suppose a system as shown below.
Suppose a fault occurs at F1. The fault current is flowing in the direction
of I1. The bus voltage is measured using a PT which is Vp here. The CT
secondary and PT secondary is connected to the Relay R2 Operating
and Polarizing Coil respectively. Will explain Polarizing Coil latter in this
section, be patient till then.
As the fault is at F1, the fault current I 1will lag behind the reference
voltage Vp. Now if the fault is at F2, the direction of fault current
through the CT will change by 180 degree and therefore the CT
secondary current will also change its direction by 180 degree and
hence the fault current in this case will lead the reference voltage Vp
(saying reference voltage assuming that Vp remain unchanged).
Carefully observe the zone where the Relay operates and the zone
where it is not operating. Therefore, it is clear that the Relay operates
in between the Zero Torque Line on both side of Maximum Torque Line.
Observe that Maximum Torque Line and Zero Torque Line are
perpendicular to each other.
Now, how to select reference Voltage Phasor?
Now consider a line fault involving phase ‘a’ and ‘b’. Then, using 3-
phase line model we get,
Va – Vf = ZsIa + Zm(-Ia) = (Zs – Zm) Ia = Z1Ia
Similarly,
Vb- Vf = ZsIb + ZmIa = – (Zs – Zm) Ia = – Z1Ia
So, Va- Vb = 2Z1 Ia
Ia = (Va- Vb)/ 2Z1
If for simplicity we assume Z to be purely reactive, then from below
figure we get that If abwill be at an angle of 60 degrees lagging to Van.
Thus, unit with Vbc as reference phasor will pick-up on both 3-phase
fault and L-L fault.
For a L-L fault involving phases ‘a’ and ‘c’ , Vac lags Van by . Assuming
purely reactive circuit, the phase current Ia will lag Vbc by . As seen in
the figure, Iac will be again in the operate region and the directional
unit will pickup. Thus, this unit (lead with Vbc as reference phasor) will
pickup for all phase faults involving phase ‘a’. In contrast, for L-L fault
involving phases ‘b’ and ‘c’, Ibc will lag Vbc by . Hence, it will lie outside
the tripping region of the directional unit. Therefore, directional unit
will not pick up.
Generally, earth faults are Single Line to Ground (SLG) and Line-Line to
Ground (LLG) faults. Earth faults are characterized by the presence of
Zero Sequence Curren I0. Since, except for unbalance, normal system
operation is not having Zero Sequence Current I0, much more sensitive
pick-up is possible for earth fault by using zero sequence current
component I0 = (Ia + Ib + Ic) / 3 and declaring a fault if I0 exceeds a
threshold.
Voltage Polarization:
Let the system be initially unloaded and a ground fault occur on phase
A.
Now we will find the Zero Sequence Voltage under the fault.
In normal power system V0is not present but available only during the
fault. Let the maximum torque be drawn at 60 degrees lag with respect
to -3V0 phasor as shown in figure below.
As we know that Zero Torque Line is perpendicular to the Maximum
Torque Line, therefore we draw Zero Torque Line as shown in figure
above.
It is then clear that zero Torque Line which separates the plane into
Operate and Do Not Operate zone leads -3V0by 30 degrees. Thus, for
fault in the correct region, 3I0 lags -3V0 hence falls in operate region. If
fault is behind the relay, 3I0 will lead -3V0 by about 45 to 60 degrees
and hence will lie in do not operate region. Hence, earth fault
directional unit will not pick-up.
Current Polarization:
For providing direction feature in earth fault relay we can also use
current as refrenec phasor which is called current polarization. It is an
alternative for voltage polarization. It does not require an additional
Potential Transformer (PT).
During ground fault say at phase A, 3I0 flows from ground to neutral of
a Wye connection of Transformer. If we assume for simplicity that Ib =
Ic = 0, then 3I0 and Ia are in phase. This indicates that directional unit
for ground relay should pick-up as Ia is in phase with 3I0. Thus we place
maximum torque line at zero degrees with respect to I 0 phasor. The
correspondingOperate and Do Not Operate zones are marked in figure
below.
If fault is behind the relay, then the Ia will fall in Do Not Operate region
and hence relay will not pick up as Zero sequence Current through the
neutral of Wye connection and Relay will be in phase opposition.
V = VmSinωt
If we see this voltage on Voltage and Time axis, we find that magnitude
of voltage varies from –Vm to +Vm with respect to time. Now consider
the figure below.
In the figure a vector is drawn from the origin making an angle of wt
with the time axis and rotating in anti clockwise direction. Mind that
this vector is rotating with some frequency, that is why it is Phasor.
Normal Vector do not rotate. If we take the projection of the vector on
Voltage axis, we observe that we get the instantaneous value of the
Voltage V = VmSinwt. It is normal practice to take the length of Phasor
as the R.M.S value of the Voltage / Current while in vector, length is
directly proportional to magnitude of the vector.