Generator and
Transformer Protection
Lecture
Ó 1997 ABB Network Partner AG / Baden / Switzerland
ABB Kraftwerke AG / Baden / Switzerland
ABB Kraftwerke AG / Mannheim / Germany
3rd Edition
All rights with respect to this document, including applications for patent and
registration of other industrial property rights, are reserved. Unauthorised use, in
particular reproduction or making available to third parties, is prohibited.
This document has been carefully prepared and reviewed. Should in spite of this the
reader find an error, he is requested to inform us at his earliest convenience.
The data contained herein purport solely to describe the product and are not a
warranty of performance or characteristic. It is with the best interest of our
customers in mind that we constantly strive to improve our products and keep them
abreast of advances in technology. This may, however, lead to discrepancies
between a product and its Lecture Notes.
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Contents
1. Introduction ............................................................................................. 2
1.1. Fault Conditions...................................................................................... 2
1.2. Abnormal Operating Conditions.............................................................. 2
1.3. Basic Requirements................................................................................ 3
1.4. Basic Conditions ..................................................................................... 4
1.5. Additional Requirements......................................................................... 4
1.6. Overall Protection of a Generator-Transformer Unit ............................... 4
1
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
1. INTRODUCTION
On electrical machines the following kinds of faults can occur and cause
damage:
- Short-circuits
- Interturn faults
- Ground faults
Most of the fault currents are of a higher level, usually higher than two-times
the rated value (refer to the Tables); the damage is therefore great and con-
tinuing operation may not be possible. Because the damage rises with time, it
is necessary to interrupt operation as soon as possible by a trip of:
- circuit breaker(s)
- excitation circuit breaker
- turbine shut down.
During stator ground faults the circulating fault currents are small; they are
limited to a level of 20 A by a grounding resistor. An arc between the faulted
slot bar and the laminated stator iron causes damage to the generator and
long and expensive repair work. Therefore operation must also be interrupted
by a trip. An exception are faults on ungrounded and impedance-grounded
systems having a low level of circulating currents. This is the case for:
- rotor ground faults
- M.V. system ground faults.
With respect to restricted damage, the protection device often emits only an
alarm and operation is not interrupted usually.
2
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
- overcurrent
- unbalanced load
- overtemperature
- overvoltage
- over- and underexcitation
- over- and underfrequency
- asynchronous running
- generator motoring.
The protected machines are still sound, but their life can be influenced.
The abnormal operating conditions could cause a fault later, if they are not
detected by a protection system in time.
measuring methods and having a different sensitivity. They are called main
and back-up protection devices.
Basic conditions for the correct operation of the protection system are:
- suitable settings
- a suitable location and specification of voltage and current transformers.
The selectivity enables the detection of individual failures and faults. The cor-
responding zone is cleared and the other system stays in operation.
The protection system must also be able to operate under worst conditions
(e.g. at a reduced level of the DC voltage, failure on AVR, etc.).
4
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
C.B.
- Although the breaker failure protection can be provided for each circuit
breaker, it is applied mainly for units with a generator C.B.
The scheme using two 52 G and 52 T circuit breakers enables the supply of
the station transformer at an open H.V. or generator C.B. and is often
preferred for gas turbine generators. For steam turbine and water-wheel
generators the 52 G circuit breaker is usually omitted.
For the REG216/316 and RET316 systems the frequency range of the
measured voltages and currents is considerably restricted by filtering for most
protection devices. Therefore the DC component and the higher harmonics
need not be considered during selection of the setting values.
5
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The current and voltage values required for the dimensioning of the current
and voltage transformers, for various protection components as well as for
the determination of protection setting values can be calculated according to
the following figures and tables.
The characteristic of short-circuit currents of transformers and generators are
quite different (refer to Fig. 2-1 and 2-2).
With the help of the discharging resistor the time constant T'd of the field
current can be reduced by approx. one half and the suppression of the field
current can thus be accelerated.
For formulas required for the calculation of currents and voltages during sym-
metrical short-circuits on generators, transformers and generator-transformer
units refer to Tables 2-I to 2-VI.
6
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The task of this protection device connected to CT's located at the gener-
ator neutral point is to protect:
a) the zone between the generator neutral point and the H.V. circuit
breaker against service overcurrents
b) the zone from the generator neutral point up to the H.V. power system
as a back-up protection during faults (If a M.V. bus is applied, it is also
involved in the protected zone).
7
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The minimum through-fault current is therefore equal to 2.0 p.u. and cir-
culates through the generator CT's during an H.V. line-to-line short-circuit.
The value of the applied delay depends on the grading with overcurrent
devices of the power system and of the auxiliaries. The setting value of
the delay is usually in the range between 2 and 5 s. At its selection the
permitted maximum through-fault current duration of 2 s for many trans-
formers is to be considered.
we get
8
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
0.9 3 0.9 3
i= "
= = 5.2
xd + x2 0.15 + 0.15
for the maximum through-fault current during an H.V. three-phase fault (at
a voltage of 110%)
For large machines the difference between the minimum fault current and
the external maximum fault current is smaller due to a higher value of xd''.
It is then even more difficult to find a suitable setting level.
The task of the definite time device is a selective detection of short circuits
on the transformer and on its M.V. side supplied by the H.V. power
system. This device must be graded with the overcurrent devices of the
M.V. side of auxiliary transformers. Naturally this device must not operate
during continuous operation current as well as during short-time
9
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The instantaneous device must operate during H.V. faults between the
H.V. current transformers and the transformer H.V. winding. It must not
operate during M.V. faults and transformer inrush currents. The
application of an instantaneous device is especially important at long
distances between the H.V. current transformers and the transformer
H.V. winding, threatened by a very high fault current level. E.g. if the H.V.
current transformers are located close to the H.V. circuit breaker at the
begin of a line supplying this transformer.The current setting must be
selected between
- minimum fault current of the H.V. side
and
- maximum through-fault current.
Designating the H.V. power system reactance xS and the transformer
reactance xT, the minimum H.V. fault current is
3
iF =
2x S
1
i=
xT
3 1
iF = = 43 i= = 10
2 x0. 02 0.1
In the case that an inrush current is higher than the through-fault current,
the bottom limit of the instantaneous stage setting range is to be specified
by the inrush current level instead of the through-fault current level. Very
10
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
For the REG216/316 and RET systems the instantaneous stage can be
blocked if the circulating overcurrent has a 2nd harmonic component
which is higher than 10 % of the current setting level.
3.2.1. Introduction
The differential protection is used for the detection of internal faults within
a zone defined by the location of the supplying current transformers. It
operates with a comparison of the currents before and behind the
protected machine (Fig.3.2-1). The differential protection must be
sensitive and fast (Fig. 3.1-2). Otherwise the damage caused by high fault
currents, rising with time, would be too high. The high sensitivity is
demanded in order to detect most of the faults; this is important especially
during transformer ground faults. It is usually accepted that the differential
protection detects failures of the secondary CT circuits (interturn faults,
short-circuits as well as interruptions) and trips. During external faults the
differential protection must not trip (Fig. 3.2-1).
11
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
3.2.2.1. Application
Using the protection class 5P20 for CT's the differential current caused
by the current error of CT's is usually considered to be 10 %.
The differential current caused by the tap changer depends on its range,
which can be e.g. +/- 5 % or +/- 10 %.
12
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The stability of the differential protection depends on the slope of the ope-
rating characteristic given by the factor "v" (sometimes called "pic-up
ratio"). The value "v" is given by the ratio of the pick-up differential current
, I to the through current IH (Fig. 3.2-4).
At the REG and RET protection systems the steep slope is activated only
during CT secondary currents I > b IN, where "b" is a certain through
current in p.u. By setting the value "b" the point of intersection of both
slopes is selected. The steepness of the steep slope is infinite (Fig. 3.2-4).
The usual setting value is b = 1.5. In the case of danger of a false
tripping at low through currents the value b = 1.25 can be applied.
Very often rated currents of the protected transformer and of the CT's are
different.
The difference between the ratio of the transformer rated currents and the
ratio of CT's rated currents must be matched. Otherwise this difference
would produce a spurious differential current. This matching is possible for
the REG216/316 and RET316 systems with the help of "reference
values".
It is an advantage if the setting value "g" (p.u.) can be based on the rated
currents of the transformer and not of the CT's. The phase shift between
the currents of the primary and secondary transformer side is given by the
connection group and must also be matched.
13
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The REG and RET systems offer the possibility to reduce the sensitivity
by increasing the value "g" ,if it is required, with respect to
- increased transformer no-load currents
(due to a short time overvoltage)
- differential currents caused by a tap changer
- various other purposes.
The inrush current detection operates with the detection of the 2nd
harmonic. During normal operation this detection is not activated. It can be
activated by the:
- energizing detector
- external signal "InrushInp".
The energizing detector operates when the setting value of the "inrush
ratio" is exceeded, i.e. when the content of the 2nd harmonic exceeds the
setting value.
14
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The inrush current detection is only active during the "InrushTime", which
must be set.
3.2.3.1. Application
3.2.3.2. Settings
The factor "v" is usually set to the value 0.25 with respect to not especially
high through-currents during external faults. If necessary the higher value
of 0.5 can be applied.
The factor "b" cannot be set at the differential device of the REG216/316
systems for generators. Its value 1.5 is fixed.
3.2.4.1. Application
The units for gas turbines have a generator circuit breaker which en-
15
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The CT's designed for conditions of external faults mostly enable correct
protection operation during internal faults too. Therefore the CT's are
usually specified with respect to the protection stability during external
faults. This stability depends on the behaviour of the protection device and
of the CT's. The differential protection device has a suitable operating
curve as a means for device stability. Therefore it is not necessary to
demand that CT's do not saturate. Such a requirement would cause big
CT's with a high magnetic core cross section.
The overcurrent factor "n" desired for a faulted circuit and non-saturating
CT's is defined by a continuous AC overcurrent without any DC
component.
This factor "n" may also be used for offset overcurrents having an AC
current component "i" and a DC component. The influence of the DC
component is specified by a factor "k" :
16
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
n = k i
i1
= sin wt
I1N 2
k=2
Short-circuit at v = 0:
The short-circuit current has a DC and an AC component.
t
i1 -
J2
=e - cos w t
I1N 2
J2 æ - Jt - ö
t
k = MJ çç e 2 - e J ÷÷ + 1
J2 -J è ø
17
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
J J2 æJ ö
tm = ln ç ÷
J -J2 èJ2 ø
J
æ J ö J 2 -J
k m = MJ ç ÷ +1
èJ2 ø
Current transformers with a magnetic ring core have a high time constant
J 2 . If the " J 2 " is much higher than " J "
t 2 >> t
18
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
E2 = 20 ( V2N + R2 I2N )
E2 = n ( V2 + R2 I2N )
V2N + R2 I2N
n = 20
V2 + R2 I2N
SN + DPCu2
n = 20
S + DPCu2
This equation shows that an overcurrent factor "n" higher than 20 can be
reached if the actual burden is smaller than the rated burden at SN. The
above formula is to be used if a certain CT is to be applied for a required
higher factor "n" . In opposition if the desired overcurrent factor "n" was
calculated, the actual burden is known and the CT copper losses can be
estimated, the CT is to be specified for class 5P20 by the calculated
rated output
n
SN =
20
S + DPCu2 -DPCu2
such as e.g. class 5P20 and rated output SN = 90 VA.
Example:
Required value n = 40
Actual output S = 5 VA
Secondary copper losses , PCu2 = 35 W = 35 VA
n 40
SN =
20
S + DPCu2 - DPCu2 =
20
5 + 35 - 35
SN = 45 VA
19
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
E.g. the class C 400 means a ring CT with an output voltage of 400 V at
20 I2N and of 20 V at I2N . If the rated output current is 5 A, the rated
output would be
SN = 20 x 5 = 100 VA.
The CT's specified acc. to ANSI or IEEE standard are designed for an
inner voltage E2 given by the output voltage and by the voltage drop
across the resistor R2. The allowed maximum current error is 10 % at 20
I2N .These CT's may also be applied for a higher overcurrent factor if the
actual burden is smaller than the rated burden.
3.2.4.5. Requirements on CT's Applied for the REG and RET Systems
The above results for transformers with 2 windings can also be used for
generators. Thanks to the similar design all above results can also be
used for the REG216 and 316 systems.
Conclusion:
- CT's of the class 5P20 may be used for the differential protection
devices for generators and 2-winding transformers
- CT's of the class 5P20 may also be used for the differential protection
of 3-winding transformers if the rated output SN is calculated with
respect to the required factor "n" and to the actual required output S;
20
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
i.e. if the rated output SN is higher enough than the required output
S in order to enable the required value "n".
21
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
22
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
All above methods use the decreased magnetic flux of the faulted phase
for the detection. A large current circulating in the shorted turn or turns
produces a magnetic flux of the opposite polarity in contrast to the polarity
of the original flux. The total magnetic flux is then much smaller and the
phase voltage too.
The differential method is the sole one enabling the detection of the faulted
phase.
23
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
This protection should be fast to restrict the damage caused by high fault
currents. Nevertheless sometimes a short delay between 0.1 and 0.5 s may
be necessary to avoid any maloperation. This especially holds true for the
method using the voltage measurement.
Interturn faults across a smaller number of winding turns may cause small
and not well measurable circulating currents. Such interturn faults should
be detected by a gas protection device like the Buchholz relay or the SPR
device. Nevertheless, in the range of interturn faults with more shorted
turns the currents are high enough to be detected by a differential or an
overcurrent protection.
24
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
In an extreme case the total length of a stator phase winding is shorted; i.e.
all turns of a phase winding are shorted and the voltage on this faulted
phase fully disappears. The two different service kinds are:
- generator disconnected from the power system (running at no-load)
- generator directly connected to a large power system
At no-load the potential of the terminal of the faulted phase moves to the
neutral point. The line-to-line voltage between the sound phases is fixed,
non influenced. The line-to-line voltages between the faulted phase and 2
sound phases drop to the phase voltage value. Using the measurement of
the neutral point voltage displacement by the broken delta side of three
VT's connected in parallel with the generator phase windings the voltage
measured during an interturn fault along the total phase winding length is
1/3 of the maximum value e.g. of 100 V (Fig. 3.4-5a).
n3 1 - s 2 N2 N3
i1 =
n 2 x n N2 + n N2 - 2 N N - 1
N22
1 1 3 3 1 3
n2
n 3 N3 1 -1
i2 =
n 2 N2 x s2 N22
1 +
n 2 n1 N12 + n 3 N32 - 2 N1 N3 - N22
1
U1s 2 N1
é
ê
N2 n1 N1 - N3 +
n2
N22
ù
ú
u1 = = ê1 + ú
E n 3 N3 ê 2 2 1 2ú
ê n1 N1 + n3 N3 - 2 N1 N3 - N
ë n 2 2 úû
, u1 = 1 - u1
Used symbols:
E E.M.F. per phase, induced from the rotor
U1 , u1 phase voltage during an interturn fault
Du1 phase voltage change caused by an interturn fault
i1 current of the sound section in p.u.
i2 current of the section with the interturn fault in p.u.
N1, N2, N3 number of turns of section 1, 2 and 3
n1, n2, n3 Blondel's factors (ratio of the total flux to the excitation flux,
defined by the leakage)
s1 , s2 , s3 leakage factors
x subtransient reactance.
From the diagram im Fig. 3.4-8 it is evident that the minimum number of
shorted turns, which can be registered, depends on the ratio of faulted and
total turns per phase and naturally on the protection voltage setting.
Therefore a better detection sensitivity is reached at turbogenerators which
have a smaller number of turns per phase as e.g. N3 =10, in comparison
with salient pole generators having e.g. N3 = 40.
In the absence of parallel branches we get the simple formulas from the
above modified equations:
26
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
i1 = 0
n 3 N3 1
i2 =
n 2 N2 x
s 2 N1
u1 =
n 2 N3
The last formula shows that the reduction of the phase voltage depends on
the leakage factor s2. Without this leakage the voltage u1 would sink to
zero.
In this case the currents circulating in the faulted winding are overlapped
with currents circulating from the power system.
The current curves for the following diagrams were calculated under the
assumption of a certain variability of the leakage reactance.
1 1
i1 =
3 2
é æ N ö2ù
2
é 2 æ N2sc ö ù
+ êr ç ÷ ú
2
ê x s + x T çç 5 - 4 ÷ú
÷
êë 3 è N2 øú ê è N2sc ø ú
û ë û
27
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
N2
i 2sc = i1 3
N2sc
Used symbols:
i1 primary current in p.u. of the transformer rated current
i2sc current in the interturn faulted winding section in p.u.
xs reactance of the supplying power system in p.u. of the transformer
rating
xT transformer reactance (impedance voltage) in p.u.
r resistance of the faulted circuit in p.u.
N2 number of secondary winding turns (per phase)
N2sc number of shorted turns of the secondary winding.
With respect to the protection sensitivity desired for the fault detection, the
currents circulating during interturn faults were calculated considering the
severe conditions given by the great variability of the transformer leakage
reactance being between 10 and 50% and by the circuit resistance.
Fig. 3.4-9 shows that during interturn faults on a secondary winding with a
constant leakage reactance and without any resistance, the primary as well
as the secondary currents are high enough for the detection at each
interturn faulted winding length "x". The leakage reactance variability
causes the circulating currents to be smaller. For the influence of the circuit
resistance refer to the (Fig. 3.4-10). It is shown there that especially the
range of short faulted winding lengths is influenced by the circuit
resistance. Nevertheless in the range of the longer faulted winding lengths
(above 20% of the total winding length), the measured primary currents are
high enough to be detected also by a simple overcurrent protection
scheme.
Conclusion:
In the range of the faulted secondary winding lengths between 20 and
100% the currents are influenced especially by the variability of the
secondary winding leakage. In the range between 0 and 20% the currents
are restricted especially by the circuit resistance.
1
i1 =
2
é æ N1 - N1sc ö 2 æ N1sc öù
2
3r + ê2 x s + 3 çç ÷ x ç5 - 4 ÷ú
÷ 1l ç ÷ú
ê è N1 ø è N1 øû
ë
28
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
N1
i1sc = i1
N1sc
Used symbols:
i1 primary current in p.u. of the transformer rated current
i1sc current in the interturn faulted winding section in p.u.
xs reactance of the supplying power system in p.u. of the transformer
rating
x1l primary leakage reactance of the transformer in p.u.
r resistance of the faulted circuit in p.u.
N1 number of primary winding turns
N1sc number of shorted turns of the primary winding
For interturn faults on the transformer primary winding the critical range for
the detection is again at the short interturn faulted winding lengths
(Fig. 3.4-11,12), especially due to the circuit resistance. Nevertheless the
measured primary current value is often sufficient for the detection also in
this range.
The Buchholz relay supervises gas emissions and is built into the oil pipe
connecting the transformer tank with the expansion chamber. The relay
consists of a small reservoir to accumulate the incoming gas, and of two
swimmers to monitor the oil level located one above the other.
The relay has two stages for an alarm and a trip. The upper swimmer
operates the very sensitive 1st stage protection and is able to detect small
oil level differences caused by small gas emissions or by a small oil
leakage.
The lower swimmer operates the 2nd stage protection; it detects greater oil
level differences and oil stream surges caused by sudden insulation
faults.
The second stage detecting the fast oil streams caused by insulation
faults trips in approximately the same time as the differential protection.
by the Buchholz relay is limited to the transformer tank, whilst the zone of
the differential protection is given by the location of current transformers
installed inside or outside of the tank.
The Buchholz relay is usually used for transformers with ratings above
1000 kVA and in some exceptional cases between 100 and 1000 kVA.
For larger transformers, the Buchholz relay is used together with the
differential relay as an important protection against faults. The first stage
of the Buchholz relay is very sensitive and detects very small gas
emissions, which cannot be detected by the differential relay responding
to higher measurable currents, e.g. above 20 % of the rated current. On
the other hand, high fault currents are detected by the differential relay
and by the Buchholz relay which both initiate a trip and interruption within
approximately the same time.
Both types are sensitive to low-and high-energy arcs and have inverse-
time characteristics. Generally the SPR devices are used to trip. They are
free from false operation.
The stator ground fault protection protects the generator stator against
damage caused by ground faults.
The following stator ground fault protection devices are applied for
generators with an impedance-grounded or an ungrounded neutral point.
For the detection of a stator ground fault either the generator voltage or an
auxiliary voltage can be used. Using the generator voltage, approximately
30
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
During a ground fault of the neutral point the component "a" is equal to
zero. This voltage increases with the rising distance from the neutral point
and reaches the value of the full phase voltage at a fixed ground fault on
the generator terminals.
The measured voltage may be higher than the phase voltage value during
an arcing ground fault due to oscillations produced between the stator
circuit and the ground. The neutral point voltage transformer should never
become saturated with respect to a danger of ferro-resonance. Therefore
it is to be designed for a higher voltage than the phase voltage. The best
method is to specify the VT for the voltage factor 1.9 (acc. to IEC
standard) or for the line-to-line voltage (acc. to ANSI standard).
Also the three VT's of the variant with the VT's located at the generator
31
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
terminal side should be specified by the voltage factor 1.9 or by the line-
to-line voltage value.
ABB prefers the method using a grounding resistor and a voltage trans-
former connected in parallel between the generator neutral point and the
ground for the following reasons.
In both cases (Fig. 3.6-1 and 3.6-2) the grounding resistor reduces the
transferred voltage of the component "b" and enables a selective
detection of ground faults on the generator side. If this resistor fails or is
interrupted, the selectivity of the protection may be lost, but the generator
side remains protected.
The voltage transformer located at the neutral point is without any voltage
under normal operating conditions. It is energized only during a ground
fault and is then slightly loaded by the very small power consumption of
the protection device.
Grounding Resistor
- Maximum ground fault current IE < admitted value IEmax < 20A
- Spurious voltage Vs < 0.5 of the setting value Vset
Used symbols:
RE grounding resistance
Co generator capacitance
33
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
M angular velocity
The capacitance
C = 3 (Co + Ce + C1)
The second condition is used for the determination of the maximum value
of the grounding resistance with respect to spurious voltages. A spurious
voltage consists of three components. The equation for these three com-
ponents expressed in p.u. values:
vs = vb + vc + vd
RE
ZE =
w 2LC - 1
1 + jwCRE
w 2LC
34
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
RE
ZE @
1 + jw CRE
or
ZE
RE @
1 - jw CZE
Vph
We put Z E ³
IE max
24000
Vph = V IEmax = 10 A
3
24000
ZE ³ = 1385 ohms
3 10
2 2
æ 1ö æ 1ö Z E2
ç ÷ = ç ÷ + w C
2 2
R =
1 - w CZ E
E 2
è ZE ø è RE ø
1385 2
REmin ³ for M = 314 1/s
1 - 314x0.6x10 -6 x1385
2
The ABB static devices applied for monitoring the neutral point voltage
displacement are less sensitive to higher harmonics and therefore
vc = 0
Using the value vd = 2 % and keeping the value vb < 2.5 % a setting value
vset = 5 % is not exceeded by spurious voltages.
IC ( 3M C12 V2ph
DV = ZEIC
0. 025 Vph
ZE £
IC
2
Z E2
R £
1 - w CZ E
Emax 2
24000
Vph = = 13856 V
3
w = 314 1/ s
C12 = 3 x10 -9 F
110000
V2ph = = 63500 V
3
C = 0. 6 x10 -6 F
we get
0. 025 x13856
ZE = = 1924 ohms
0.18
1924 2
REmax £
1 - ( 314 x0. 6 x10 -6 x1924)2
36
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Vph 13850
IR = = = 9. 23 A
RE 1500
ZE = 1443 ohms
13850
IE = = 9. 60 A
1443
IC = 0. 5w C12 V2ph
0. 025 x13856
ZE = = 11547 ohms
0. 03
1 10 6
XC = = = 5308 ohms
w C 314 x0. 6
we see that the capacitance C allone is able to keep the voltage drop
produced by a current transferred from the H.V. side, below the level of
the ground fault protection pick-up value. The resistor RE is thus not
desired to stabilize the protection device at H.V. ground faults; it is to be
37
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
used only to damp transient voltage oscillations. Its value should thus be
equal or smaller than the capacitive reactance Xc.
The final resistance value can be chosen between 1435 and 5308 ohms.
Taking the value of e.g. 3000 ohms we get:
13850
IR = = 4. 62 A
3000
3000
ZE =
1 + j314 x0. 6 x10 -6 x3000
ZE = 2612 ohms
13850
IE = = 5. 3 A
2612
The voltages V1N and V2N are rated voltages of this voltage transformer.
The value of a resistor connected to a tertiary side in delta of 3 voltage
transformers situated at generator terminals is:
2
æ 3V3N ö
Re = RE ç ÷
è V1N ø
where:
38
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The task of the 100 % stator ground fault protection is the detection of all
stator ground faults.
The advantage of the low frequency for the injection voltage is the:
- possibility to distinguish between a service and a ground fault current
- low capacitive currents during normal operation.
Typical settings:
Remark: a similar injection scheme can also be applied for the rotor
ground fault protection.
39
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
For a ground fault on the generator side of the current transformers the
directional overcurrent device picks up and the faulted generator is tripped
after 0.5 s.
Summary:
- The voltage device detects any ground fault
40
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
- If only the voltage device picks- up, it means that the bus or some
transformer feeder is faulted to ground
- The directional current device detects ground faults on its generator
feeder.
The rotor ground fault protection is the protection of the field circuit
against ground faults.
The rotor ground faults are less dangerous, because the fault current is
small due to the low voltage. More dangerous is the double rotor ground
fault causing heavy rotor vibrations due to the magnetic unsymmetry.
The applied rotor ground fault protection device is not able to differentiate
between single- and double-ground faults. Depending on the kind of the
excitation system, the ground faults of the excitation machine, rectifier and
excitation transformer are also detected.
The rotor circuit is ungrounded under normal operating conditions and the
excitation voltage is divided into two voltages of the + and -pole to ground.
At the occurrence of a ground fault this voltage distribution is changed and
results in a small ground fault current.
The simple rotor ground fault protection system monitoring the current of
the supplying voltage transformer is suitable for generators with excitation
systems having a voltage with only few harmonics, such as e.g. excitation
41
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Also the device operating with the neutral point current of an impedance-
grounded system (Fig. 3.6-3) is an unselective protection detecting ground
faults not only on the transformer winding but also on the connected
system. The maximum ground fault current circulates during ground faults
on the terminals or on the connected lines. Evaluating the maximum
42
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
For internal faults the fault current causes high overvoltages across the
high-impedance of the differential circuit. These overvoltages must be
limited by one or more nonlinear resistors connected in parallel to the
differential circuit. Sometimes the differential circuit is to be shorted after
the protection device has tripped.
Only current transformers with the same current ratio can be used. They
are to be specified by the knee-point voltage and by the maximum allowed
secondary winding resistance.
43
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The ground fault current circulates from the tank to the ground during an
internal fault and is monitored by the current device.
The BF protection can be arranged with one stage only to trip the remote
C.B.'s or with two stages. In the second case the first stage is provided to
repeat the trip of the local C.B. and the second stage to trip the remote
C.B.'s.
The scheme with the overcurrent device and the trip command is mostly
used.
44
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
It uses a trip signal and a current still circulating and not yet interrupted as
a criterion of a C.B. failure. At a false trip signal a maloperation of the B.F.
failure device is prohibited with the help of the current supervision.
During correct operation of the C.B. the fault is cleared after a time given
by:
- the operating time of the fault detecting device
- the C.B. operating time.
After the fault has been cleared, the overcurrent device drops out after the
reset time. If the overcurrent device does not drop out, this means that the
current still circulates due to a C.B. failure. In this case the fault current
must be interrupted by a next C.B. or by next C.B's tripped by the C.B.
failure protection after a delay set on the timer 62.
In order to keep a short operating time the reset time of the overcurrent
device must be as short as possible.
The CT's applied to supply the current device of the B.F. protection should
be located close to the protected C.B. The B.F. protection is provided for
the detection of currents circulating trough the failed circuit breaker. If the
applied CT's are located too far from the C.B., only the current supplied by
the generator is monitored during faults between the CT's and the C.B.
and can cause a B.F. device maloperation although the C.B. is already
open (Fig. 3.9-2).
The modified B.F. device has a minimum operating time given by the ope-
rating time of the failed C.B. only.
The current setting must be selected such that the overcurrent device
does not drop out due to the damping of the fault current during the
operating time of the B.F. device.
A typical current setting is above the rated current value. Applying a value
below IN the range of the current supervision is extended down to the
service current values, but the risk of a maloperation is higher.
If the reset time of the overcurrent device is too long a modified B.F.
45
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The protection scheme uses a trip signal and an auxiliary contact of the
C.B. for the detection of a C.B. failure (Fig. 3.9-1,4).
46
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
4.1.1 Introduction
The spot temperature the of insulation surface, the cooling gas or the oil is
monitored.
47
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
level.
- Delay of the temperature detection
Thermal devices are provided for the supervision of the average tem-
perature rise or of the average winding temperature. Because the direct
measurement of the winding temperature for high-voltage machines is not
possible, a thermal image of the winding temperature is used.
The thermal image usually operates with the assumption that the
temperature rise depends only on the winding current. If the current
suddenly changes, the winding temperature rise follows according to
several exponential functions for the temperature rise of the
- cooling medium against the ambient air
- winding against the cooling medium.
é -
t
J oil
-
t
Jw
ù
J w (t ) = J 0 + êDJ Noil (1 - e ) + ( DJ Nw - DJ Noil )(1 - e ) ú(i 2 - 1)
êë úû
Equation 1.1
48
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
I
where i=
IN
Used symbols:
t - time
æ -
t
ö
J oil = J 0 + DJ Noil çç 1 - e J oil ÷÷ Equation 1.2
è ø
æ -
t
ö
J w (t ) = J oil + ( DJ Nw - DJ Noil )ç 1 - e ÷ (i 2 - 1)
Jw
Equation 1.3
è ø
For a gas or water cooled generator or motor similar equations are valid.
æ - ö
t
DJ w = DJ Nw ç 1 - e ÷ (i 2 - 1)
J
Equation 1.4
è ø
49
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
For an optimum value of " J " refer to Fig. 4.1-2. Often a suitable value is
J = 0.7 t oil .
Used symbols:
IN rated current
I current at overload
J0 temperature at I = 0
JN steady-state temperature at IN
J steady-state temperature at I
Jm maximum temperature
ti instantaneous time
K multiplying factor
The end value of the temperature rise is given by the current (Fig. 4.1-3):
50
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
DJ I2
=
DJ N IN2
æ - i ö
t
J i = J N + (J - J N )ç 1 - e J ÷
è ø
or
æ - i ö
t
J 1 = J N + ( DJ - D J N ) ç 1 - e J ÷ Equation 1.7
è ø
éæ I ö 2 ùæ - i ö
t
Ji = Jm t i = tm
éæ I ö 2 ù æ - mö
t
J m - J N = DJ N êç ÷ - 1úç 1 - e J ÷ Equation 1.9
êëè I N ø úûè ø
DJ m = J m - J N
According to the last and following equations the allowed maximum tem-
perature rise DJ m can be reached at various currents I during different
times tm:
Jm - J N 1 -
tm
= 1 - e J
DJ N æ I ö 2
ç ÷ -1
è IN ø
é ù
ê ú
tm ê Jm - J N 1 ú
- ln e = ln ê1 - 2 ú
t DJ N æ I ö
ê ç ÷ - 1ú
êë è IN ø úû
51
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
é ù
ê ú
ê ú
ê 1 ú
t m = t ln ê ú
ê1 - J m - J N 1 ú
ê DJ N æ I ö 2 ú
ê ç ÷ - 1ú
êë è IN ø ûú
Equation 1.10
I
= ¥: t m = t ln1 = 0
IN
I = Im : tm = ¥
é ù
ê ú
ê ú
ê 1 ú
ln ê ú=¥
ê1 - J m - J N 1 ú
ê DJ N æ I ö 2 ú
ê ç ÷ - 1ú
êë è IN ø úû
Im J - JN
= 1+ m
IN DJ N
For the overload capability of the machine according to the equation 1.10
refer to Fig. 4.1-4.
hG
t= [s; J/kg; W/cm2; cm2]
J cS
Equation 1.11
where:
52
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The tripping characteristic of this ABB device consists of two sections. For
small overcurrents a definite time curve and for high overcurrents an
inverse time characteristic is provided. The characteristic of the second
section is specified according to the overload requirement by the
American Standard ANSI C 50.13 for turbogenerators. The applied
characteristic is given by an approximate equation, which is suitable at
fast short time current changes. Using a series development of the
exponential function we obtain:
1 1 1
e- x = 1 - x + x2 - x3 +...
1! 2! 3!
1 1 2 1 3
1 - e- x = x - x + x -...
1! 2! 3!
Ji = Jm ti = tm
Jm - J N 1
tm = t
DJ N æ I ö 2
ç ÷ -1
è IN ø
ti
This approximate equation is correct for small ratios << 1; it results in
t
shorter tripping times for overcurrents of longer duration than the exact
solution.
Jm - JN
t = 41. 4
DJ N
53
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
The bottom of the definite time curve for stators is at 1.16 In and 120 s
(Fig. 4.1-5). A similar characteristic can be applied for turbogenerator
rotors.
temperature rise 80 K
absolute temperature 120°C
Transformers:
54
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
In order not to exceed the value of 250°C the duration of the through fault
current is to be limited to 2 s according to VDE and ANSI / IEEE.
The setting depends on the winding insulation class and on the winding
temperature at full load.
E.g. oil cooled transformers are often designed for the following tem-
peratures at rated current and at an ambient temperature of 40°C:
oil 95°C
winding 100°C
oil 55 K
winding 60 K
55
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Generally the values of thermal time constants for generators and trans-
formers vary in a wide range depending on the machine design. Also the
values of the maximum temperature of the cooling medium and of the
winding can be different depending on the insulation class. Therefore it is
recommended to get those values from the machine manufacturer.
If the values of the individual thermal time constants are not known, the
approximate equivalent value can be determined from the measured
winding temperature rise curve. For this purpose the low-voltage
transformer side is usually shorted and the high-voltage side is supplied
by a voltage reduced approximately to the value of the impedance
voltage.
If the transmission lines between the circuit breaker and the transformer
should also be protected, then it may be necessary to take their thermal
time constants into account.
56
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The accuracy of the NPS current detection must be sufficient to avoid any
maloperation at symmetrical three-phase fault currents.
57
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
4.2.1.3. Application
ABB use two different NPS current devices. They operate either with a
definite-time characteristic or with an inverse-time characteristic.
58
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The task of the inverse-time NPS device is the protection during un-
balanced load as well as during asymmetrical faults.
The negative phase sequence current devices (NPS current devices) eva-
luate the current I2 from the measurement of individual phase currents.
For selection of setting values the thermal rotor capability must be known,
specified by the machine manufacturer with the help of
- permitted continuous negative-sequence current i2 ¥(p.u.)
- permitted product (i2)2 t (p.u.;s)
The allowed product value (i2)2 t is usualy in the range between 5 and
30 s.
ABB use the NPS definite-time devices in two stages for an alarm and a
trip (Fig. 4.2-2). The current setting of both stages is selected according to
the value i2 ; the delay of the alarm stage is usually approximately one half
of the trip stage delay. The alarm delay should avoid any false alarm at
short-time unbalanced currents. The trip delay should avoid any trip during
local and remote faults before they are cleared by a fault protection.
The NPS device with a definite time characteristic usually has to protect
the generator only at unbalanced load. The expected values of the current
i2 are between 0 and 57.7 %. The typical current setting is 0.1 IN for
medium rating machines. The delay for the trip stage must be
- longer than the operating time of all fast fault protection devices
detecting the same current level; e.g.
59
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
t >1s
- shorter than the allowed time tm. This time is given by the allowed
product
(i2)2 t and by the expected maximum current i2 = 0.577 IN .E.g. for
(i2)2 t = 10 s the delay is
i
2
2
t 10
tm £ = = 30s
i 2
2 0.577 2
A typical setting value for the alarm and the trip is 5 and 10 s.
JO inital temperature
J end temperature I2
Ji instantaneous temperature
Jm steady-state temperature at I2
IN rated current
60
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
æ - i ö
t
2
J i = J O + KI ç 1 - e J ÷
2 Equation 2.3
è ø
According to the condition that the same maximum temperature J m is
permitted for short time unbalanced loading as well as for steady-state un-
balanced loading, we calculate the time tm, at which the temperature is
exceeded:
ti = tm and Ji = Jm
æ -
tm
ö
J m = J o + KI22 ç 1 - e t ÷ Equation 2.4
è ø
and
é ti 1 æ ti ö 2 1 æ ti ö 3 ù
2
J i = J 0 + KI ê - ç ÷ + ç ÷ -...ú
ët 2 è t ø 6èt ø
2
û
61
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
ti
For small ratios an approximate solution using only the two first terms of
J
the series can be used:
é ti 1 æ ti ö 2 ù
2
J i @ J 0 + KI ê - ç ÷ ú Equation 2.7
ët 2 è t ø û
2
Jm = Ji tm = ti
we get
é tm 1 æ tm ö 2 ù
2
J m @ J 0 + KI ê - ç ÷ ú Equation 2.8
ët 2è t ø û
2
Now we compare:
étm 1 æ tm ö 2 ù
KI ê - ç ÷ ú @ KI 22¥
2
Equation 2.9
êë t 2 è t ø úû
2
1
I 22 @ I 22¥ Equation 2.10
tm æ 1 tm ö
ç1 - ÷
J è 2 J ø
tm
For << 1 can be written approximately
J
t 12
I22 @ I22¥ + I2¥ Equation 2.11
tm 2
or
i22¥ t K
tm = = 2 1 2 Equation 2.13
1
i22 - i22¥ i2 - K 2
2
62
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
where
I2 I2¥
i2 = i2 ¥ =
IN IN
1
K 1 = i22¥ t K2 = i2 ¥ Equation 2.14
2
The REG system device "NPS-Invers" of ABB operates with curves given
by the equation 2.13; for one of its curves refer to Fig. 4.2-3.
i
2
2
t
tmax = 2
i 2¥
(i2)2 t = 10 s
i2 = 0.1
10
tmax = = 1000 s
0,1 2
The time "tmin" must be:
- longer than the operating time of all fast fault protection devices
detecting the same current level; e.g.
tmin > 1 s
If the device has to protect the generator only at unbalanced load, the
maximum value of i2 which should be considered is 0.577. From the value
(i2)2 t = 10 the time tmin is
63
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
10
t min £ = 30s
0.577 2
10
t min £ = 0.90s
3.33 2
The possible setting which can be realized with respect to both conditions
is
tm
At high currents I2 the second term in the bracket of the equation
2J
t
2.10 is quite small and may be neglected because m << 1; then we get a
2t
second approximate solution:
t
I22 = I22¥ Equation 2.15
tm
I J i J
2¥
2
2¥
2
K1
tm = 2 = 2 = Equation 2.16
I 2 i 2 i 22
i
2
2
t m = i 2 ¥ J
2
Equation 2.17
Some NPS current devices (not involved in the REG216/316 system) ope-
rate according to this simple equation.
The value of the thermal time constant J depends on the rotor surface
and is much larger than the thermal time constant of the winding.
For instance at
K1 = 30 s , i2 = 0.1
64
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
K1 30
J = = = 3000 s or 50 min
i
2¥
2
0.01
1
I1 = ( IA + a IB + a2IC )
3
1
I2 = ( IA + a2IB + a IC )
3
1
I0 = ( IA + IB + IC )
3
IB = a 2 IA I C = a IA
and
1
I1 = ( IA + a 3 I A + a 3 I A ) = IA
3
1
I2 = ( IA + a 4 IA + a 2 IA ) = 0
3
1
I0 = ( IA + a2 IA + a IA) = 0
3
because
1 + a + a2 = 0
a3 = 1 a4 = a
2. Interruption of 1 Phase
65
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
For IB = 0 : IC = -IA
1
I1 = (IA + 0 - a2 IA)
3
1
I2 = (IA + 0 - a IA)
3
1
I0 = (IA + 0 - IA)
3
Because 1 - a2 = 3 and 1- a = 3
we get
1
I1 = IA
3
1
I2 = IA
3
I0 = 0
IB = a IA IC = a 2 IA
and
1
I1 = (IA + a2 IA + a4 IA) = 0
3
1
I2 = (IA + a3 IA + a3 IA) = IA
3
1
I0 = (IA + a IA + a2 IA) = 0
3
66
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
IA + IB + IC = 0
I B = - IA IC = - IA
and
1 1 1 1
I1 = (IA - a IA - a2 IA) = IA
3 2 2 2
1 1 1 1
I2 = (IA - a2 IA - a IA) = IA
3 2 2 2
1 1 1
I0 = (IA - IA - IA) = 0
3 2 2
IB = 0 IC = - IA
and
1 1
I1 = (IA - a2 IA) = IA
3 3
1 1
I2 = (IA - a IA) = IA
3 3
1
I0 = (IA - IA) = 0
3
IB = IC = 0
1 1 1
I1 = IA I2 =IA I0 = IA
3 3 3
With respect to the equation for I2 the pick-up value is three times higher
than the setting value.
4.2.2. NPS Protection for Motors
The NPS current protection is also required for induction motors. The
67
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
For the test a generator operating into a symmetrical short circuit arranged
by a link or by a grounding isolator can also be used. After shorting 1 or 2
current inputs the NPS current device operates, if the current value is
sufficient. Never should an asymmetrical short-circuit of the generator be
used for the tests because the danger for the rotor would be too high.
68
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
69
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
1.10 VN/fN 5s
70
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
lost. The protection device operates by monitoring the angle between two
phasors V and E being the load angle @ (Fig. 4.6-3).
Stability Conditions
VE
P= sin @ (Fig. 4.6-5)
Xd
The equation for the power P shows that the load angle @ rises if at the
constant value of P the phasor V or E sinks. However the active power
P is zero if:
- the phasor V is zero (short-circuit)
- the phasor E is zero (loss-of-excitation)
- the load angle @ is zero (no-load condition)
72
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The active power can be changed by the power of the prime-mover and
the reactive power by the field current (Fig. 4.6-1, 4.6-2). After the
synchronous machine has been synchronized and connected to the power
system the stator current is still zero at a field current if = 1.
Increasing the field current the stator inductive current rises together
with the reactive power. Decreasing the field current the stator
capacitive current rises. At the field current if = 0 the stator capacitive
current for a turbogenerator, directly connected to a power system
according to the phasor diagram on Fig. 4.6-1, is:
V
Xd I = V or I=
Xd
1
In the p.u. system i =
xd
1
At the usual value xd = 2 the current is i = = 0.5
2
Increasing the power of the prime mover the active power rises (ge-
nerator mode). Decreasing the power of the prime mover the active
power sinks (motor mode). At an increased active power the load angle
rises; the stator current is getting capacitive if the field current is not
increased too. Under stable conditions the load angle can rise up to a
value of 90° (Fig. 4.6-4,5.6). At a load angle @ > 90° the active power
of the generator starts to sink and the operation is getting unstable and
the synchronism is lost.The limit of 90° can be reached only at a
capacitive current (Fig. 4.6-2).
For setting values for turbogenerators the reactance values Xd and Xd'
must be known. For salient-pole generators the point with the maximum
active power is not identical with the point at @ = 90°; nevertheless the
device is often set for the detection of 90° and the reactances Xq and
Xd' are used for settings acc. to Fig. 4.6-3.
The REG216/316 system enables the shifting of the axis of the circles and
thus to set another load angle limit, e.g. 70° (Fig. 4.6-14).
74
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Pole slipping protection has been developed to protect the generator rotor
from disturbances causing dynamic instability. Such abnormal operating
conditions are intiated by sudden load changes which cause a loss of
synchronisms (unstable swings).
VE
P = VI cos j = = sin @ (per phase)
Xd
In accordance with that the load angle @ must rise if the voltage drops at a
constant power P. Whilst fast changes of E.M.S. "E" are restricted by the
time constant of eddy currents circulating in the rotor body, the voltage
can be changed suddenly by a short-circuit. Under steady-state stability
conditions the load angle can rise only up to 90°.
When the value 90° is exceeded, the synchronism is lost and the machine
begins to slip.
The load angle rise depends on the actual turbine power, on the time
constant J A and on the operating time of the line C.B.
75
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
180 w N P 2
J = JN + t [° ; 1/s ; s ; MW ; MVA ; s]
p 2t A PN
Example:
P
M N = 314 1/s ; J A = 10 s ; = 0.8 ; @ N = 36°
PN
t - fault duration @ N - rated load angle
After "out-of-step" the stator reactance is reduced to the value of the tran-
sient reactance X'd due to the currents induced into the rotor. The current
then varies between a minimum and a maximum value depending on the
voltage varying between the difference and the sum of voltage phasors of
the protected generator and of the power system. The impedance given
by the generator voltage and current varies between a minimum and a
maximum value too (Fig. 4.7-3, 4.7-4). If the load angle of a generator
rises the service point given by the impedance phasor moves from the
right side (generator mode) to the left side (motor mode) crossing the X-
axis close to the origin. This crossing is considered as a slip. The number
of permitted slips must be specified by the generator manufacturer.
After a longer fault clearing time when the load angle is greater than 90° it
may happen that the load angle rises more and more when the recovery
voltage again enables a power transfer through the healthy line.
If the load angle @ > 90° the loss of the stability is to be expected; if the
rating of the generator is equal or higher than 500 MW or if it is especially
required by the generator manufacturer, a "pole slipping protection" is to
be applied.
duration of unstable rotor swings in the range up to 1s, the generator can
be represented under these conditions by the transient reactance.
EG - ES EG + ES
Imin = Imax =
Xt Xt
V V
Zmax = Zmin =
Imin Imax
If the E.M.F.'s EG and ES are not equal (EG ¹ ES), the impedance
locus is a circle. The current varies between a minimum and a maximum
value as well as the impedance given by the terminal voltage and the
current.
EG
a) =1
ES
77
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
c) ES = 0
full loss of system excitation, the impedance locus is a point; its location is
given by XT + XS .
On the R-X diagram (Fig. 4.7-3) the generator mode is drawn on the right
side of the X-axis and the motor mode on the left side. The upper
quadrants are used for the overexcited mode with the ratio
EG
>1
ES
and the lower quadrants for the underexcited mode with the ratio
EG
<1
ES
EG
=1
ES
with the rising active power of a generator the measured impedance point
moves to the X-axis and the load angle @ also rises. Crossing the X-axis,
the angle @ = 180°.
EG
<1
ES
the upper point on the X-axis corresponds with the highest voltage dif-
ference of EG and ES out of phase and to the highest current at @ =
180°. The lowest point corresponds with the smallest voltage difference of
EG and ES in phase and to the smallest current at @ = 0.
If, for unstable swings of a generator the load angle rises, then the X-axis
78
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
If, for an out-of-step motor, the impedance point crosses the X-axis from
left to right near to the origin, the nM < nS and the locus path is clockwise.
From the maximum and minimum values of the measured impedance the
diameter D of the impedance locus circle can be calculated:
X d' + X T + X S
D=
é ES ùé EG ù
ê + 1ú ê - 1ú
ë EG ûë E S û
and for
EG = 0 : D = 0
ES = 0 : D=0
EG = ES : D = ¥
79
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
4.8.1. Motoring
That pick-up value is very low for steam turbines, e.g. 1 %. In order to
guarantee a trip, the power setting value is usually selected according to
one half of the pick-up value at closed input valves (Fig. 4.8-1).
The motoring conditions cause a danger coming not suddenly but rising
slowly with time. E.g. the temperature of a steam turbine running at no-
load rises according to a relatively long time constant. Therefore the
reverse power device operates with a delay of e.g. 20 s for steam
turbines. This delay is necessary to avoid any maloperation at sudden
load swings, especially after just synchronizing a generator or if it operates
with a small load.
During repeated power swings the applied delay disables the tripping of
80
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
the circuit breaker, because the protection device picks-up and drops-out
again before a trip can be released by the timer. In this case an additional
integrating timer is to be used (Fig.4.8-2). Due to its longer reset time the
trip is guaranteed also during swings. The integrator is used especially for
steam turbines, because their motoring power is small.
For ABB gas turbines two different power setting values are specified, e.g.
1.5 % and 8 %.
4.8.2. Overspeed
Most steam turbines have such small losses that the power device
sensitivity is required to be very high. The measurement of such very low
power values may be affected by phase-angle displacements of the
supplying voltage and current transformers, specially at lower power
factors. It is therefore recommended to connect the reverse power device
only to protective or measuring transformers of a sufficient accuracy and
of a very small phase-angle displacement.
81
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
82
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
83
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Current transformers applied for the protection must be able to transfer the
primary current to the secondary side also at high fault currents with a
sufficient accuracy.
The current transformers, which must not saturate under given fault
conditions, are to be designed such that a certain maximum flux density,
allowed with respect to the maximum permitted current error, usually being
1.8 Vs/m2, will be not exceeded. The CT's are to be designed according to
the overcurrent factor n, given by the ratio of the maximum magnetic flux to
the flux at the rated current. This factor n is calculated by the ac fault
current component i (p.u.) and by the factor k corresponding to the dc fault
current component:
n=ki
- the frequency
- the AC fault current component i (p.u.)
- the time constants of the faulted ciircuit t and of the CT secondary side
circuit t2
- the time t.
diF
V 2 sin ( M t + = ) = R iF + L
dt
where
84
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
The fault current given by the solution of the above equation is:
-t
V 2
iF = K e J + sin ( w t + a - j
Z
where Z is the impedance given by R and L and t is the time constant of the
faulted unit (generator, transformer or both). The factor K is to be
determined for the current iF at the time zero. If the current iF is zero at the
instant of the fault we get
V 2
iF (t=0) = K + sin ( a - j = 0
Z
-V 2
K = sin ( a- j
Z
-t
V 2
iF = ( sin ( w t + a - j - e J sin ( a- j )
Z
V 2
iF = sin M t
Z
V
IF =
Z
iF = IF 2 sin M t
The full dc component is developed at the angle (a-j) = -90°. It may be e.g.
at a = 0 and j = 90°. In this case the fault current is:
85
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
-t
V 2
iF = ( sin ( M t - 90 ° ) - e J sin (-90 ° ) )
Z
-t
V 2
iF = ( eJ
- cos w t )
Z
or using the RMS value of the ac component of the fault current
-t
iF = IF 2 ( e J - cos M t )
i1 = iF
i1 = IF 2 sin ( M t)
di 2 di1
0 = (R2 + RB ) i 2 + L 2 -M
dt dt
where
M CT mutual inductance
L2
J2 =
R2 + R B
86
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
di1
= IF 2 M cos M t
dt
di 2 1 M
0 = + i2 - IF 2 M cos M t
dt J2 L2
-t t
i2 J MM J J22 1
= e 2 (K + e 2 ( cos M t + M sin M t) )
IF 2 L2 1+ ( MJ )
2
2
J2
i1exc 1 N2
= (i1 - i2 )
IF 2 IF 2 N1
L2 N2
=
M N1
87
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
-t
i1exc 1 J
= ( sin M t + MJ (e 2 - cos M t ) )
IF 2 1+ ( MJ 2 2
2
-t
i1exc 1 J 1
( e 2 - cos M t) = k
IF 2 MJ MJ
2 2
N1 N2
E2N ( ) (R 2 + RB )I2N ( )
E1N N2 N1 1
I1excN = = = @ I1N
X 1exc N1 2 M L 2exc MJ
X 2exc ) 2
N2
For the p.u. value of the magnetizing current at rated load (refer to
Fig.3.2-7)
I 1
i excN = 1excN (
I1N MJ
2
is also the CT current error of the CT primary rated current I1N under the
assumption that the CT turn-ratio is correct. According to this formula the
time constant of the secondary circuit J2 must be equal or higher than 318
ms at magnetizing currents up to 1% and at 50 Hz. It means that in this
case the product MJ2 >> 100. According to the class 5P20 the allowed
magnetizing current is 1% at the rated current and at the rated load.
88
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
i1exc
n = = ki
I1excN 2
According to the equation with factor k as a function of the time, the factor k
reaches values up to 2 in the worst case with a large time constant
J2 . Therefore the CT's are to be specified at least with the factor k = 2 ,
also in cases with no dc component of the fault current. This is e.g. the case
of ground fault currents on a resistance grounded power system.
-t -t
i2 -M t2 -t
t2 M (wt )2 t2
=
t - t2
( et - e ) + 2
)e +
IF 2 L2 L2 1 + (wt )2
2
2
M (wt )
+ 2
L 2 1 + (wt )2
( w1t sin w t - cos w t )
2 2
and for MJ2 >> 1:
-t
i2 -M J -t
J J 1
( ( 2 eJ - e 2 + cos M t - sin M t )
IF 2 L2 J - J J - J MJ
2 2 2
89
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
-t -t
i1exc J -t J J ( MJ ) 2 J
= eJ - 2
e 2 - 2
e 2 -
IF 2 J- J J- J 1+ ( MJ ) 2
2 2 2
( MJ 2
1
- 2
( sin M t - cos M t ) - cos M t
1+ ( MJ ) 2 MJ
2 2
For the factor k of CT's with a large time constant J2 >> J we get a
simplified formula
-t
k ( wJ (1 - e J ) + 1
k ( wJ + 1
90
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
For the comparison of the curves for the factor k according to above three
formulas see Fig. 5.1-1.
For curves of the desired factor k as a function of time t refer to Fig. 5.1-2.
These curves have a peak value
t
J 2 -t
t
km = M J ( ) + 1
J
2
at the time
J J2 J
tm = ln ( )
J -J J
2 2
For the curves of the factor km as a function of the time constant J2 at given
time constants J see Fig.5.2-3.
Often very large and expensive CT's are specified as a result of above
equations. Therefore often a certain saturation is allowed or the time
without saturation reduced in order to reduce the factor n (refer to
Fig. 5.1-1).
For the development of the desired formulas for the factor n the following
equations can be used. The electromotive force E2 desired for the cal-
culation of the CT
91
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
or
R2 g s
A = a2 = ( wire length )2 = ( )2 cm 2 ; m ; W; Sm / mm 2 ; mm 2
4 x1,25 xN2 5 N2
The factor 1.25 is a safety margin, because the actual length of one turn is
longer than the size of the magnetic core. The value s is the wire cross
section.
A = 10 6 ( R 2 s )2
N2
and using the typical values of the wire cross section we get
and we get
s2
(R 2 2 f - R 2 (n I2N - n V2N = 0
N2
800 f s 2 n V2N
n I1N
+ n I1N )2 +
2 2 N2
R2 =
800 f
s2
N2
1. Equations for f = 50 Hz
n = optional value :
n
+ n) 2
+
14400
n V2N
2 2 N2
R2 =
14400
N2
A = 0.36 x10 6 ( R 2 )2
N2
n = 20 :
288
10 + 100 + 103 V2N
N2
R2 = A = as above
360
103
N2
n = optional value :
360
2.5 n + 6.25 n 2 + 10 3 n V2N
N2
R2 = A = 9 x10 6 ( R 2 )2
360 N2
10 3
N2
n = 20 :
7200
50 + 2500 + V2N
N2
R2 = A = as above
360 3
10
N2
2. Equations for f = 60 Hz
93
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
n = optional value :
n
+ ( n )2 +
17.28
10 3 n V2N
2 2 N2
R2 = A = 0.36 x10 6 ( R 2 )2
17280 N2
N2
n = 20 :
345.6
10 + 100 + 103 V2N
N2
R2 = A = as above
17280
N2
2.2 Secondary rated current I2N = 5 A and s = 3 mm2
n = optional value :
432
2.5 n + 6.25 n 2 + 10 3 n V2N
N2 R
R2 = A = 9 x10 6 2 2
432 N
10 3 2
N2
n = 20 :
8640
50 + 2500 + 10 3 V2N
N2
R2 = A = as above
432
10 3
N2
With the help of the above formulas the secondary winding resistance,
losses and the magnetic core cross section were calculated as example for
the following CT's with four various current ratioes.
CT ......../5 A 50 Hz 5P20 30 VA
window, bar or bushing-type with only one primary turn (N1 = 1).
Remarks to
94
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
According to the above table a large magnetic core would be necessary for
ratings 60 and 100 VA. Using a higher number of ampere turns the core
cross section would be smaller. For the influence of several primary winding
turns refer to the next table.
CT's with the ratio 1000/5 A , at various numbers of primary turns N1 . The
rated output is 100 VA, the rated output voltage V2N = 20 V, 20 V2N = 400
V.
95
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Note
The calculation of the resistance R2 and of the magnetic core cross section
A described above is to be applied for preliminary values only, desired at
the begin of the project. The final values are to be asked from the CT
manufacturer.
The features:
For linear CT's the same basic equations as those developed for CT's with
closed magnetic core may be used, only the leakage inductance of the
secondary winding is not negligable.
96
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
inductance the core cross section sinks. Naturally the reduced magnetizing
inductance causes an increased magnetizing current. Depending on the
reduction of the magnetizing inductance the cross section of a linear
magnetic core may be e.g. 3 up to 5 times smaller than the cross section of
a closed magnetic core.
With the help of the selected current error, given by the magnetizing current
I1excN according to Fig. 3.2-5, the CT secondary circuit time constant t2
can be calculated:
1 I1N 1 N1 I1N 1
J ( or J ( or J (
2 M I1excN 2 M N1 I1excN 2 M i excN
E.g. at a selected current error of 0.01 (iexcN = 0.01 or 1%) and w = 314 1/s
the time constant t2 = 0.318 s or 318 ms. For several examples refer to the
following table.
Magnetizing currents at various values of the time constant t2 (at 50Hz):
97
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
n N1 I1excN 2 n N1 I1excN 2
g = = 10 -6 m; A; Vs / m 2
H 0.8 B
or
n N1 I1excN 2
g = 10 -3 mm; A; Vs / m 2
0.8 B
It is evident, that short air-gaps are difficult to be adjusted. The applied air-
gap or gaps cause an irregular distribution of the magnetic in the magnetic
core. The result is a magnetic flux leakage and the value of the secondary
leakage inductance L2L is not longer negligible. In order to keep the
magnetic flux leakage as low as possible, the length of the air gap must be
much smaller than the size of the magnetic core cross section. Therefore it
is sometimes necessary to split the calculated value of the gap into several
short air-gaps. This is especially the case for CT's for very high currents, as
the above table shows.
Specification
The formulas developed for CT's with a closed magnetic core and
negligeable secondary winding leakage inductance cannot be used for
linear CT's. Due to the applied air-gap the secondary leakage inductance is
not negligible. The formula for the calculation of the inner E.M.F. E2 as the
sum of V2N and R2 I2N is not longer correct. The calculation of the
secondary winding leakage inductance L2L is not simple and should be
made by the CT manufacturer. Therefore the cross section of the magnetic
core cannot be calculated and consequently the value of the secondary
winding resistance cannot be estimated.
Conclusion
99
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
100
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
101
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
3 Unbalanced load 46
6 Frequency 81
7 Loss-of-excitation 40
8 Pole slipping 78
9 Standstill 67
10 Reverse power 32
11 Differential 87
12 Buchholz or SPR*) 63
13 Minimum impedance 21
14 Interturn fault -
102
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
103
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I>/U< 51V x x x x x x
Z< 21 (x) x x
Interturn fault - x x
U< 27 x
-P> 32 x x x x
104
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
105
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
i 10
9
8
7
6
5
i sc
4
3
2
i
N 1
t
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10
106
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
107
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
108
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
di
U = Uarc + Ri + = L
dt
current suppression:
di U - U + Ri
= arc
dt L
U
at the instant t = 0 is i0 = and
R
di U
- = arc or by the time constant T
dt L
di U
- = arc
dt RT
Uarc - Tt Uarc - U
I= e -
R R
Uarc
t arc = T ln
Uarc - U
109
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Ea Ua2
Ea Ic Ua1 Ua2
Ua1
Uc1 Uc Ub Ub1
Uc1 Ub1 Ub2 Uc2
Uc2 Ub2
Uc Ub I
b
Ic2
a Ic1 Ic2 Ic
Ic1
Ia1 Ia2
c b Ib1
Ib
Ib1 Ib2
Ib2
110
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Ua1
Uc2 Ub2
Ua = 0 Ib = Ic = 0
Ia
Ua1 Ua2
Ua0
Uc0
Uc Ub Ub0
a Ic1 Ib2
Ia0
Ia1 Ia2 Ib0
c b Ic0
Ib1 Ic2
Ic2 Ic1
Ic0 Ia
111
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Ua1
Uc2 Ub2
Uc Ua = 0 Ub
Ib = Ic = 0 Ia
Uc1 Ub1 Ua2
Ua1 Ua2
Uc Ub
Uc2 Ub2
Uc1 Ub1
a Ic1 Ib2
Ia0
Ia1 Ia2 Ib0
c b Ic0
Ib1 Ic2
Ic2 Ic1
Ic0 Ia
112
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
T
1 2
input output
T
1 2
input output
113
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
T1
input
output
T2
114
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
115
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
a Ia = I b = Ic E
X1
c b
a Ö3E
Ib = Ic
X1 + X2
X2
Ub = Uc E
c b X1 + X2
2X2
Ea E
X1 + X2
3E
Ia
a X1 + X2 + X0
Eb = Ec Ö3E
X1 + X2 + X0
2X2 + X0
c b Ebc Ö3E
X1 + X2 + X0
a Ib = Ic Ö3E
X1(X2 + X0)+ X2X0
3X2
E
I0 X1(X2 + X0)+ X2X0
c b
3X2 X0
Ea E
X1(X2 + X0)+ X2X0
116
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
I1 I2 I0 E1 E2 E0
E
0 0 E 0 0
X1
E -E X2 X2
0 E E 0
X1 + X2 X1 + X2 X1 + X2 X1 + X2
E E E X2 + X0 -X2 - X0
E E E
X1 + X2 + X0 X1 + X2 + X0 X1 + X2 + X0 X1 + X2 + X0 X1 + X2 + X0 X1 + X2 + X0
X2 + X0 - X0 - X2 X2 X0 X2 X0 X2 X0
E E E E E E
X1(X2 + X0)+ X2X0 X1(X2 + X0)+ X2X0 X1(X2 + X0)+ X2X0 X1(X2 + X0)+ X2X0 X1(X2 + X0)+ X2X0 X1(X2 + X0)+ X2X0
117
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
i
fmax = 2.5
i
fo
118
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
1 Ö3 3 Ö x2T+ xT xT0+x2T0
xT0 Ö3
xT 2 xT 2 xT + xT0 x2T+2 xT xT0
0.1 10 8.66 10 10
119
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
1 Ö3
xT 2 xT
10 8.66
10 8.66
120
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
1 2.5
x''d + xT 4.0 4.0 1.19 1.19
xd + xT
Ö3 4.0 2.5 x Ö 3
3.46 2.13 1.84
x''d + x2 + 2xT xd + x2 + 2xT
2.0 *
3 2.5 x 3
2.89 5.0 1.77 3.06
x''d + x2 + 3xT xd + x2 + 3xT
121
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
2.0
2
I Possible current
IN setting range
1.5
1.3
Max service
1 IN current
0 t
Fig 3.1-1 Generator overcurrent protection
122
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
0 t
0 t
Start
signal
0 t
Delay Trip
0 t
Fig. 3.1-2 Generator current, voltage and signals of the protection device 51 V.
123
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
50 43
Min. HV fault current
I
15 Possible setting range of
IN
the instantaneous stage
1 IN
0 t
124
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
sN (MVA) 0.5 1 5 10 50
I0 peak
16 14 10 10 9
IN
125
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I
IN Ö2
1.5 IN Ö2
IN Ö2
0 ts t
126
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
G
Power system T AT
1000 MVA 100 MVA 10 MVA
10 % 10 % 10 %
~
50T 50.1 51.2
51T 51.1
150 50T
150 IATN º 15 ITN 83 83 IATN
100 IATN º 8.3 ITN
º 10 ITN
15 51T 50.1
15 IATN
º 1.5 ITN
10
ITN
º 10 IATN
7.8
7.8 IATN
127
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I>> I>
50 T 51 T
t
I>> I>
50 51.1
t1
AT
G ~ I>
51.2
t2
50 T
150 IATN
I
IATN 51 T
50.1
15 IATN
51.1
2 IATN 51.2
IATN
t (s)
128
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
G G
, I>
, I>
129
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
is
1.5
1 iN
0.5
ts
0 t
1 iN
is
0 t
130
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
U
1.3
U
1.2
1.1
iexc
131
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I,
IN
0,75
0,5
0,25
g b
IH
0 0,5 1 1,5 IN
132
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
R1 L1L L2L = 0 R2
input L1 exc
E1=E2 U2 Z
I1 Iexc I2
E1 = E2
R2I2
U2=R I2
Iexc
.
Used symbols:
133
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
H.V. FAULT
87T 87T
FAULT IN THE
GENERATOR ZONE
87G
G 87G
G
0,4kV
134
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
135
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I1 = 0
I 20
R V V 220 V
2 2
U = 20 x U2N + 20 x R2I2N
U
2
E2 (at I 2 = 20 I 2N )
E2 (at I 2 = I 2N )
I 20 £ 0,05 x 20 I 2N = I 2N
0 I 20 £ 0,01 x I 2N I2
HEST 905 048 FL
136
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Generator
Motor 10% -- 15% or
-- 10%
20%
Reactor
137
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
GT
Protection zone
I>
Z<
138
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
x
+0.07
0 r
Z-setting
-0.07
HEST 905 027 FL
139
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
R S T
Voltage
transformer
Generator Voltage
relay
R S T
Current
Neutral points relay
Current
transformer
140
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
R S T
Current
Neutral points Relay
ct 1 ct 2
Earthing resistor
141
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
R S T
R1 S1 T1 R2 S2 T2
ct 4 ct 5 ct 6
ct 1 ct 2 ct 3
R1 0 R2 S1 0 S2 T1 0 T2
R S T
Differential relay
142
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
143
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
N = N1 + N2
N N N1 I1 = 0
N2 I2 X
N N N N N = N3 N1 I1
N2 I2 X
I1
1
I1 I>
144
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
I1 E1 X1
N1
X31
E X13
I1
N3 = N
X
X32 X12
I2 X
X23 X21 X2
N2
E2
145
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
146
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
T
xs i1
1 2
w1 r
N2 - N2K
Feeder
N2K i2K
i1
xs i1
xs
147
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
148
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
xs i1
1 T 2
A
i1 N1-N1K
i1K N1K
xs i1 B
xs
C
149
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
150
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
UA
UE;IE
UE º Uph; IEmax
UC UB
C RE UE L
IC IL
IR IE
G
(ground)
G
UE = UA
UAG = 0
IE IR UA
UCG UBG
IL
UC UB
IC
151
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
UA
I3
Re
UC UB
U3
C L
IC IL IE
G
(ground)
UC3
UA3 = 0
U3
G G
UA IE IR
UCG UBG UC3 UB3 I3
IL
UC UB
IC
152
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
IEmax
C RE
B
IE >
Ground
153
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Ic
vt
R
E UE>
3C12 Ic
U2ph
Ic RE C Ic
Fig. 3.6-4 Influence of the H.V. ground fault on stator ground fault protection
for generators operating with generator transformers.
154
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
3~
RPS RES
G
UiP N12
Ugen/Ö3
100V
REr RPr
N11
2*2 mF
US
Ur Uir
+ -
Uis Uir Ui
[V]
110
-110 A
Injection Test
D
[ms]
Coded 12.5Hz injection Signal
Voltage
(95%) StEF Stator-EFP Rotor-EFP
155
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
G1
T1
G2
T2
G3
T3
G4
156
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Transformer
3 C 12
Voltage transformer
UE> Re
Rp
voltage transformer
Interposing VT
IE> UE>
Fig. 3.6-7 Stator ground fault protection for generators directly connected to
busbars
157
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Rotor C
Rotor shaft
C1 50 V 100 V C2
R R
R R
100 V 50 V
C1
C2
C
158
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
50% of Uph
UE
UE >
159
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
,I>
i1
l
x
i2
output
input
i1
ZE i2
IIEE >>
E >
1,0
0,6 1
3
80%
0,4 42%
i1
is
0,2
0 20 40 60 80 100
x [%]
160
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
1 T 2
RE CT's
CT
RS
IE >
161
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
IE >
162
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
I>
current I 50 BF
timer
62 remote trip
trip signals
I>
current I 50 BF
release
remote trip
timer
trip signals 62
C.B.
+
remote trip
timer
trip signals 62
163
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
~ ~
164
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
local
C.B. closed open
fault
fault clearing
current
time
setting level
50 BF
reset time
local
C.B. operating
trip signal time
margin
remote delay by 62
trip signal
0 t
local
closed
C.B.
fault
fault clearing
current
time
setting level
50 BF
local
trip signal
remote C.B.
remote delay by 62 operating time
trip signal
remote
closed open
C.B.
0 t
Fig. 3.9-3 Time chart of the device 50/62 BF.
165
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
local
C.B. closed open
fault
fault clearing
current
time
reset time
local
C.B. operating
trip signal time
margin
delay by 62
0 t
local
closed
C.B.
fault
fault clearing
current
time
local
trip signal
remote C.B.
remote operating time
trip signal
remote
closed open
C.B.
0 t
166
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
i
1.5
0 t
Jw (t = ¥)
Joil(t = ¥)
J (°C)160
J
140 w
120
Joil
JNw 100
JNoil
80 toil
60
40
D Joil
tw
20
D Jw- D Joil
0 20 40 60 80 100 120 140
t (min)
167
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
J = 126.4° C
140
winding temperature
120 simulated temperature rise
130
J (°C) DJ (%)
overload i = 1.2
temperature rise at DJNw - DJNoil = 10 K tw = 10 min
120 rated current DJNoil = 50 K t oil = 120 min
relay setting of the thermal time constant t = 90 min
110
110
10 100
0 100 200 300 400 500
t (min)
168
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
169
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
170
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
171
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
172
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
I2
IN
I2 Tripping stage
IN
Alarm stage
Fig. 4.2-2 Operating characteristics of the definite time NPS protection device.
173
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
174
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
A B C
IA IB IC
a2 IC
IA
a IB
3 I1 IB
a2 IB
IA IA
IA a IC IC
IC IB
3 I1 = 3 IA 3 I2 = 0 3 I0 = 0
I1 = IA I2 = 0 I0 = 0
175
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
A B C
IA IC
a2 IC
a IC
IA 3 I1
IA IA
IC
IA
3 I2
IC
3 I1 = Ö 3 IA 3 I2 = Ö 3 IA 3 I0 = 0
I1 = Ö 33 IA I2 = Ö 33 IA I0 = 0
176
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
A B C
IA IB IC
a IC
I2 a2 IB
IA
aIB
IB
IA IA
IA
a2 IC IC
IB IC
3 I1 = 0 3 I2 = 3 IA 3 I0 = 0
I1 = 0 I2 = IA I0 = 0
177
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I2
100 (%) 1 ... 57.7 333 200 167
IN
X X
I2
100 (%) 57.7 33.3
IN
178
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
179
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
180
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
U set 2
U set 1 Stage 2
Stage 1
UN
Delay 2 Delay 1
0 t
181
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
E
Xd I
G Us
If
U
Ss = ¥
Us = constant
jXdI
E U Us
jXdI U
E U
E
j I I j
I=0 If If If
Fig. 4.6-1 Synchronous machine operating in parallel with a large power system.
Reactive and capacitive power loading.
182
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
183
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
E jXdI
a) Turbo-
U
generator
I
j
d
jXqI
jXdI
b) Salient-pole
U
generator
I
j
d
184
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Xd I XdI
U U
E E
@ @
P
P
185
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Xd Icos j
j P = U I cos j
E j
sin d = Xd Icos
jXdI E
UE sin d
P =
Xd
U
If
I
d j
jXdI
U
I
E d
I U jXdI U
jXdI I
jXdI
d I
E E E=0
186
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
E
Xd I
G Us
U
XdI U Xd U
I
E E
I
U
X
I E
@ I
R
0
Xd
187
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Iactive max.
E
Xd I
j
d Ireactive
U 0
Xd
Qcmax P
U = const
P max.
EU
Xd S=UI
j
d Q
U2 0
Qexc= X
d
188
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
I GT
E G Us
Xd U XT
jXdI
jXTI jXTI
E
U Us jXdI U Us
@ @
E
X Us
I
@ E
XT I
R
0
Xd
189
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
I GT
E G Us
Xd V XT
Steady-state
X U
Z= stability curve
I
XT
0
R
X'd
2
Xd
Loss-of-
excitation
device curve
190
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
protection
device
start signal
reset t
delay
extended
signal
t
protection
device
start signal
t
extended
signal
reset t
delay
191
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
G U = Us = const
Xd
I
X j
U d
B
0 j R
V
Z=
I E
Z jXdI
Xd
Point A, A': 90° Point B:
E=0 U=0
U E
I= A I=
Xd Xd
j = 90°cap j = 0°
jXdI U E jXdI
j B' P
I U = const I
EU
Xd
E
S=UI
A'
j j jXdI
d d
U2 0 Q U
Xd I
B'
192
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
E U
G T Us
Xd XT
X'd
X
R
I
X'd 0 j US
2 B j
@
jXTI
U
Z
jXdI E
U
Z= Xd
I
Us=U=const
P EU
Point B': (XT=0) Xd Point A':
U jXdI U
j UI= S
j j
I I
A'
E B' @
Q
U2 0
jX'dI
Xd
-E = U E=0
2U U
I= U2 I=
X'd 2 X’ Xd
d
j = 90°cap j = 90°cap
@ = 180° @ = 90°
193
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
E U
G T Us
Xd XT
X U I
Z= US
B I
j
d @G
0 jXTI
XT j U
R
d dG
jXdI E
Xd
A
P
194
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
D3
B3
No.3
B2 D2 E2 E3
F3
R
@ No.2
0
B1
No.1
D1
C1
C2
A1=A2=A3
C3
P B'2
No.1 U=const
B'1 E'2
E'3
No.3
A'1=A'2=A'3
C'1 0 D'3
Q
D'1 C'3 U 2
U2
Xd XT
B'3
@
No.2 F'3
D'2
195
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
j Xq Iq
j Xd Id
E U
I
Id
j
Iq
d
X
j X q IL
d
j Iq
j Id
E
Xd
jI
U
Xd
I
E Id
Xd j
Iq
d
Xd - Xq
Xd Xq U
d
196
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
j U Iq
jU Id
j UI U2
Xd
EU
Xd I
EU j Id
Xd Iq
d
Xd - Xq 2
U
d Xd Xq
EU
Xd EU sin
P 1= d
S = UI Xd
j
U2 Xd - Xq sin2d
P 2=
d 2 Xd Xq
U2 0 Q
U2 Xd
Xq P = P1+P2
197
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
198
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
Fig. 4.6-18 Steady-state stability limit for salient-pole generator and generator-
transformer units.
———— salient-pole generator
------------ turbogenerator (for comparison)
199
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
200
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
201
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Fig. 4.6-21 Stator voltage, current and speed after loss of excitation.
202
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
GT
network
EG G system
Xd XT XS
EG G G ES
U US
XdI
EG (XT + XS)I ES
XSI ES
I
U XT + XS
U
ES XTI @ I
@
U
@
XdI EG Xd EG
I
203
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
,E EG
,E
EG EG
ES ES ,E
ES
204
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
EG > ES
XS
XT @ @ EG = ES
@ R
0
X'd
EG < ES
205
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Fig. 4.7-4 Locus of the impedance measured at the generator terminals during
pole slipping in relation to the power system A.
206
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
3.0
EG=1.2
2.0
EG=1.3
EG=1.4
EG=1.6
EG=1.8
1.0
EG=3.0
ES=0
xS
xT R
0
x'd
Fig. 4.7-5 Impedance locus on the R-X diagram at ES = 1.0 and different
voltages EG > ES.
x'd = xT = xS = 0.2 (non-typical values).
207
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
xS
EG=ES=1.0
xT R
x'd
ES=0.2
EG=0.4
1.0
EG=1.8
EG=1.6
EG=0.7
2.0
EG=0.8
3.0
EG=0.85
X'D = XT = XS = 0.2
Fig. 4.7-6 Impedance locus at ES = 1.0 and different voltages. EG < ES.
- × - × - × - operating curve of 'loss-of-excitation' relay.
208
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
PG
Qcap 0 Qind
reverse
power device
setting
generator and
turbine no-load
losses
PM
209
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
Block
U t 1>
P>
I t 2>
TRIP
t 3>
Integrator
210
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
t = 300 ms
t2 = 0.63662 (i.e. i0 = 0.5%)
w = 314.16 1/1
211
Generator and Transformer Protection 1MRB520046-Len ABB Network Partner AG
___________________________________________________________________
212
ABB Network Partner AG 1MRB520046-Len Generator and Transformer Protection
___________________________________________________________________
213
IMPORTANT NOTICE!