General conditions and function limitations, notes for configuration and operation

These notes take precedence over statements contained in other documents.


Because these notes contain important information for the installation and use of the software, please read them carefully.

SINAMICS MV V4.7 SP5


ARTS-Plus Brief Description Circumstances Possible work-around Affected DO Dri new since
RQ ve
Fa
mil
y

GH150

GL150
SINAMICS_MV_SW - General
TFS345276 Hold-off time measurement The hold-off time measurement does not work for 3PSA and RSZ1. None - X V4.7
SINAMICS_MV_SW - General communication
TFS456376 Interruption of the SINAMICS Link The interruption of the SINAMICS Link connection between two CUs causes both Alarm A50005 must be re-parameterized as a fault X - V4.7
CUs to issue alarm A50005. However, the units do not shut down. with unit shutdown.