SUBJECT : UPS PERFORMANCES TYPE TEST REPORT

R.P.S.
UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

INDEX
Pag.
UPS input tests

1) Steady-state input voltage tolerance 2

UPS input/output characteristics - static conditions

3) Efficiency 3-4-5-6
4) Harmonic current 7-8
5) Unbalance test 9
6) non linear load 10
7) Discharge energy mode 11
8) Output - Normal mode - Overload 12
9) Output - Normal mode - Short circuit 13

UPS output dynamic tests

10) UPS output dynamic - Output linear-load steps 14 - 15- 16


11) Change of operating mode - Normal to bypass mode 17
12) UPS dynamic characteristics - Battery operation 18

Testing of UPS

13) Acoustical noise 19

Instruments
14) List of instruments 20

1/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: INPUT VOLTAGE TOLERANCE TEST

EN 62040 ref. 6.3.2.1

Purpose: The imput voltage shall be adjusted to the minimum and maximum values of the tollerance range, output and input current charatteristics shall be verified

OUTPUT CHARACTERISTICS WITH INPUT VOLTAGE VARIATION


N.Volt. Load INPUT OUTPUT
V/Vn V Freq. I A THD I P.F. V1 V2 V3 THD V1 THD V2 THD V3 I P V o/p batt
[%] [%] [V a.c.] [Hz] [A] [kVA] [%] [V a.c.] [V a.c.] [V a.c.] [%] [%] [%] [A] [kW]
113% 99% 450,7 50 543,7 424,39 2,9 0,996 230,8 230,8 230,6 0,4 0,4 0,5 571,5 395,6 540
110% 99% 438,0 50 560,5 425,26 1,7 0,997 230,9 230,8 230,6 0,4 0,4 0,5 572,0 396,0 540
100% 99% 398,0 50 616,0 424,68 1,2 0,997 230,9 230,8 230,7 0,7 0,8 0,9 572,9 396,7 540
89% 99% 356,8 50 683,3 422,3 1,6 0,996 230,9 230,8 230,7 0,8 0,9 1 571,0 395,5 540
79% 82% 317,3 50 644,5 354,2 1,2 0,995 230,6 230,9 230,6 0,8 0,8 1 474,4 328,3 540
61% 62% 244,0 50 652,0 275,62 1,4 0,998 230,9 230,6 230,7 0,4 0,4 0,5 358,5 248,2 540

2/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR:
Doc.:
400
F.Amodeo Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

UPS input/output characteristics - static conditions


Test type: Input - Output characteristics, losses, efficiency (EN 62040-3)

Purpose: measurament of the input and output UPS parameter at different load percentage (0-25%-50%-75%-100%) in order to verify:
1. Efficiency and losses
2. Total Harmonic Distortion of output voltage (THD V)
3. Static stability of output voltage
4. Total Harmonic Distortion of input current and input Power Factor

Input - Output characteristics, losses, efficiency - resistive load


LOAD INPUT OUTPUT SYSTEM
% V I A P THD I P.F. V I A P THD V1 THD V2 THD V3 P.F. Losses η
[Va.c.] [A] [kVA] [kW] [%] [Va.c.] [A] [kVA] [kW] [%] [%] [%] [kW] [%]
0,0% 400,8 22,4 15,53 3,6 230,3 3,6
13,3% 399,6 86,7 60,04 57,74 8,1 0,962 230,5 77,0 53,3 53,3 1 0,8 0,9 1 4,5 92,24%
25,5% 399,1 157,1 108,62 107,6 4 0,991 230,5 147,2 101,8 101,8 1,2 1 1 1 5,8 94,63%
38,6% 398,9 235,4 162,67 162,08 2,7 0,996 230,6 223,3 154,5 154,5 1,4 1,3 1,3 1 7,6 95,32%
50,2% 398,7 304,9 210,57 210,17 2,2 0,998 230,6 290,2 200,8 200,8 1,2 1,2 1,3 1 9,4 95,52%
63,3% 398,5 385,0 265,78 265,45 1,5 0,999 230,7 365,7 253,1 253,1 0,9 1 1,1 1 12,3 95,36%
75,1% 398,4 457,9 315,95 315,65 1,3 0,999 230,8 433,8 300,4 300,4 0,8 0,8 0,9 1 15,3 95,16%
87,7% 398,0 536,7 370,05 369,81 1,1 0,999 230,8 506,6 350,8 350,8 0,6 0,7 0,8 1 19,0 94,86%
99,1% 397,7 609,1 419,61 419,31 1,2 0,999 230,7 572,6 396,3 396,3 0,7 0,7 0,9 1 23,0 94,51%

400kVA Power Losses 400kVA Efficiency


24
96,0%
20 94,0% 20
% Efficiency

Transformer manufacturer:
Losses [kW]

16 92,0%
90,0% TAMURA
12
88,0%
8 86,0%
4 resistive load 84,0% resistive load
0 82,0%
0% 20% 40% 60% 80% 100% 80,0%
0% 25% 50% 75% 100%
Load
Load

3/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

UPS input/output characteristics - static conditions


Test type: Input - Output characteristics, losses, efficiency (EN 62040-3)

Purpose: measurament of the input and output UPS parameter at different load percentage (0-25%-50%-75%-100%) in order to verify:
1. Efficiency and losses
2. Total Harmonic Distortion of output voltage (THD V)
3. Static stability of output voltage
4. Total Harmonic Distortion of input current and input Power Factor

Input - Output characteristics, losses, efficiency resistive - inductive load


LOAD INPUT OUTPUT SYSTEM
% V I A P THD I P.F. V I A P THD V1 THD V2 THD V3 P.F. Losses η
[Va.c.] [A] [kVA] [kW] [%] [Va.c.] [A] [kVA] [kW] [%] [%] [%] [lagging] [kW] [%]
0,0% 400,8 22,4 15,5 3,6 230,3 3,6
27,3% 399,2 151,9 105,1 104,0 4,2 0,990 230,5 156,7 108,4 98,4 1 0,8 0,8 0,908 5,6 94,59%
50,3% 398,9 276,0 190,7 190,3 2,5 0,998 230,5 290,0 200,6 181,1 0,8 0,6 0,6 0,903 9,2 95,18%
73,3% 398,5 403,1 278,3 278,0 1,3 0,999 230,4 422,3 291,9 263,8 0,7 0,6 0,7 0,904 14,2 94,91%
100,0% 398,0 554,9 382,6 382,4 1,3 0,999 230,3 575,4 397,5 359,9 0,8 0,7 0,7 0,905 22,5 94,11%

400kVA Power Losses 400kVA Efficiency


96,0%
24
94,0%
20 92,0%
Transformer manufacturer:
% Efficiency
Losses [kW]

16 90,0%
TAMURA
12 88,0%
86,0%
8
84,0%
4 resistive-inductive load resistive -inductive load
82,0%
0 80,0%
0% 20% 40% 60% 80% 100% 0% 25% 50% 75% 100%

Load Load

4/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

UPS input/output characteristics - static conditions


Test type: Input - Output characteristics, losses, efficiency (EN 62040-3)

Purpose: measurament of the input and output UPS parameter at different load percentage (0-25%-50%-75%-100%) in order to verify:
1. Efficiency and losses
2. Total Harmonic Distortion of output voltage (THD V)
3. Static stability of output voltage
4. Total Harmonic Distortion of input current and input Power Factor

Input - Output characteristics, losses, efficiency resistive - capacitive load


LOAD INPUT OUTPUT SYSTEM
% V I A P THD I P.F. V I A P THD V1 THD V2 THD V3 P.F. Losses η
[Va.c.] [A] [kVA] [kW] [%] [Va.c.] [A] [kVA] [kW] [%] [%] [%] [Leading] [kW] [%]
0,0% 399,2 22,4 15,5 3,6 3,6 0,00%
25,6% 399,2 143,7 99,4 98,1 5,1 0,987 230,5 147,1 101,7 92,1 0,8 0,7 0,8 0,905 6,1 93,83%
50,2% 398,9 276,8 191,2 190,8 3 0,997 230,3 289,0 199,7 180,7 1 0,8 0,8 0,905 10,1 94,72%
72,8% 398,5 402,5 277,8 277,5 2 0,999 230,3 419,7 290,0 262,1 0,9 0,8 0,8 0,904 15,4 94,46%
99,4% 398,0 554,6 382,4 382,1 1,5 0,999 230,3 574,7 397,1 357,9 0,8 0,7 0,7 0,901 24,2 93,66%

400kVA Power Losses 400kVA Efficiency


96,0%
24 94,0%
20 92,0% Transformer manufacturer:
Losses [kW]

% Efficiency

16 90,0% TAMURA
88,0%
12
86,0%
8
84,0% resistive-capacitive load
4 resistive-capacitive load 82,0%
0 80,0%
0% 20% 40% 60% 80% 100% 0% 25% 50% 75% 100% 125%

Load Load

5/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

UPS input/output characteristics - static conditions


Test type: Input - Output characteristics, losses, efficiency (EN 62040-3)

Purpose: measurament of the input and output UPS parameter at different load percentage (0-25%-50%-75%-100%) in order to verify:
1. Efficiency and losses
2. Total Harmonic Distortion of output voltage (THD V)
3. Static stability of output voltage
4. Total Harmonic Distortion of input current and input Power Factor

Test conducted applying 100kVa of reference non liner load + linear load to reach rated power (EN 62040-3 annex E)
Input - Output characteristics, losses, efficiency no linear load
LOAD INPUT OUTPUT SYSTEM
% V I A P THD I P.F. V I A P THD V1 THD V2 THD V3 P.F. Losses η
[Va.c.] [A] [kVA] [kW] [%] [Va.c.] [A] [kVA] [kW] [%] [%] [%] [kW] [%]
0,0% 399,5 22,4 15,5 3,6 3,6
26,1% 399,6 115,2 79,7 78,2 5,6 0,982 230,8 143,3 99,2 73,1 1,5 1,5 2 0,736 5,2 93,39%
51,5% 398,9 282,6 195,2 194,8 2,7 0,998 231,1 284,2 197,0 185,4 1,7 1,9 2,1 0,941 9,4 95,16%
74,0% 398,5 433,8 299,5 299,2 1,4 0,999 231,6 420,0 291,2 284,0 2 2,4 2,5 0,975 15,2 94,93%
99,2% 398,0 599,9 413,6 413,3 1,3 0,999 231,3 567,5 393,8 388,9 2,4 2,7 2,6 0,988 24,4 94,11%

400kVA Power Losses 400kVA Efficiency


96,0%
24 94,0%
20 92,0% Transformer manufacturer:
% Efficiency
Losses [kW]

90,0% TAMURA
16
88,0%
12 86,0%
8 84,0% non linear load
4 non linear load 82,0%
0 80,0%
0% 25% 50% 75% 100% 125%
0% 20% 40% 60% 80% 100%
Load % Load

6/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR:
Doc.:
400
F.Amodeo Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: Input harmonic current (EN 62040-3)

Purpose: input current harmonic current levels measured at rated input current with nominal load ref. 5.2.2.i

LOAD 100% 75% 50% 25%


Harm. Irms Irms Irms Irms
n° [A] [%] [A] [%] [A] [%] [A] [%]
1 609,1 100 457,9 100 304,9 100 157,00 100
2 5,48 0,9 4,12 0,9 4,57 1,5 5,02 3,2
3 1,22 0,2 0,92 0,2 1,22 0,4 0,94 0,6
4 2,44 0,4 2,29 0,5 3,35 1,1 2,36 1,5
5 3,65 0,6 2,75 0,6 1,83 0,6 2,04 1,3
7 1,83 0,3 1,83 0,4 2,44 0,8 1,57 1
9 0,61 0,1 0,00 0 0,30 0,1 0,16 0,1
11 0,61 0,1 0,46 0,1 0,30 0,1 0,16 0,1
13 0,00 0,0 0,00 0,0 0,00 0 0,31 0,2
15 0,00 0,0 0,00 0,0 0,00 0 0,00 0,0
17 0,00 0,0 0,00 0,0 0,00 0 0,16 0,1
19 0,00 0,0 0,00 0,0 0,00 0 0,16 0,1
21 0,00 0,0 0,00 0,0 0,00 0 0,00 0,0
23 0,00 0,0 0,00 0,0 0,00 0 0,00 0,0
25 0,00 0,0 0,00 0,0 0,00 0 0,00 0,0

Tot. 609,15 1,22 457,89 1,28 304,92 2,15 157,12 3,95

7/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: Input harmonic current (EN 62040-3)

Purpose: input current harmonic current levels measured at rated input current with nominal load ref. 5.2.2.i

120

input harmonics level at different load

100

80
%Current

100% load
60

75%load

50%load
40

25% load

20

0
1

%THD

8/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: Output voltage unbalance test (EN 62040-3)


ref. 6.3.4.5

Purpose: measurement of the output voltage in condition of balance load and unbalance load in order to verify:
1) output unbalance voltages
2) angle phases deviation

OUTPUT VOLTAGE UNBALANCE-PHASE ANGLE DEVIATION


Load % V L1-N V L2-N V L3-N V L1-L2 V L2-L3 V L3-L1 Unbal. S°el.
L1 L2 L3 Vrms Vrms Vrms Vrms cosj °el Vrms cosj °el Vrms cosj °el % °el
0 0 0 230,5 230,3 230,1 399,2 -0,501 120,1 398,9 -0,5014 120,1 398,5 -0,4971 119,8 0,17 360,0
100 100 100 230,9 230,8 230,7 399,9 -0,5004 120,0 399,7 -0,5002 120,0 399,6 -0,4988 119,9 0,09 360,0
100 100 0 230,6 229,3 231,6 399,4 -0,5084 120,6 397,2 -0,4854 119,0 401 -0,5054 120,4 1,00 360,0
100 0 0 230,4 230,6 231,5 399 -0,4982 119,9 399,4 -0,4941 119,6 401,2 -0,5089 120,6 0,48 360,1

9/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: UPS OUTPUT CHARACTERISTICS - STATIC CONDITIONS WITH NON LINEAR LOAD

EN 62040-3 ref. 6.3.8.1

Purpose: Measurament of the output rms and THD voltage in order to verify the output characteristics under conditions of reference non linear load

Test conducted applying 100kVa of reference non liner load + linear load to reach rated power (EN 62040-3 annex E)

NON LINEAR LOAD - OUTPUT CHARACTERISTICS


OUTPUT CURRENT OUTPUT VOLTAGE Ph-N OUTPUT VOLTAGE Ph-Ph OUTPUT POWER
load L1 L2 L3 C.F. VL1-N VL2-N VL3-N THD max VL1-L2 VL2-L3 VL3-3 THD max A P
P.F.
[A rms] [A rms] [A rms] [aver.] [V rms] [V rms] [V rms] [%] [V rms] [V rms] [V rms] [%] [kVA] [kW]
24,8% 123,7 154 152,2 2,5 231,1 230,8 230,6 2 400 399,2 399,5 1,9 99,2 73,1 0,736
49,2% 273 289,4 290,1 2,1 231,7 230,7 230,8 2,1 400,2 398,7 400,5 2 197,0 185,4 0,941
72,8% 413,8 424,5 421,7 1,9 231,6 231 230,6 2,5 400,6 399 399,7 2,4 291,1 284,0 0,976
98,5% 562,8 569,4 570,3 1,7 231,7 231,2 231,1 2,7 401,1 399,6 400,5 2,5 393,8 388,9 0,988

10/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: Output discharge energy mode (EN 62040-3)

ref. 6.3.4.3 & 6.3.4.4

Purpose: verification of output characteristics during the discharge of battery

Table 8 OUTPUT VOLTAGES CHARACTERSTICS


Vdc V L1-N V L2-N V L3-N V L1-L2 V L2-L3 V L3-L1 Sout mis Pout mis Thdmis P.F.
V Veff D% Veff D% Veff D% Veff D% Veff D% Veff D% kVA kW /
445 230,5 -0,19 230,3 -0,28 230,4 -0,23 399,1 -0,22 399,0 -0,25 399,3 -0,17 321,0 321 0,5 1
420 230,6 -0,15 230,5 -0,19 230,4 -0,23 399,3 -0,17 399,2 -0,20 399,3 -0,17 321,0 321 0,6 1
405 230,5 -0,19 230,5 -0,19 230,4 -0,23 399,3 -0,17 399,2 -0,20 399,2 -0,20 321,0 321 0,5 1
395 230,6 -0,15 230,4 -0,23 230,4 -0,23 399,3 -0,17 399,1 -0,22 399,4 -0,15 321,0 321 0,6 1
387 230,7 -0,10 230,4 -0,23 230,4 -0,23 399,4 -0,15 399,1 -0,22 399,4 -0,15 321,0 321 0,6 1

11/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: UPS DYNAMIC CHARACTERISTIC - OVERLOAD

Purpose: UPS otput caratteristics during overload

EN 62040-3 ref. 6.3.5.1

Table 9
OUTPUT CARATTERISTICS WITH OVERLOAD
TIME LOAD INPUT OUTPUT A.C.
Δt % V I A P V I A P THD V P.F.
[s] [V a.c.] [A] [kVA] [kW] [V a.c.] [A] [kVA] [kW] [%]
3 phases
0 110% 390,6 680,1 460,1 459,7 230,6 636,2 440,1 440,1 0,9 1
3600 110% 390,6 680,3 460,2 459,7 230,6 629,5 435,5 435,5 0,8 1
0 125% 383,0 681,5 452,0 450,7 230,8 723,4 500,9 500,9 0,5 1
600 125% 382,3 681,4 451,2 450,8 230,6 723,3 500,4 500,4 0,5 1
0 150% 384,7 681,2 453,9 453,5 230,6 856,2 592,3 592,3 0,7 1
60 150% 384,7 681,2 453,9 453,5 230,6 853,3 590,3 590,3 0,8 1

Note: Whith the load ≥ 125%, part of the power is supplied from battery.

12/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: UPS DYNAMIC CHARACTERISTIC - SHORT CIRCUIT

Purpose: Normal mode - Short circuit test

EN62040-3 ref. 6.3.5.3


Table 10
SHORT CIRCUIT TEST (input bypass C.B. open)
t duration I/Irated
ref. fig transient description scope sign ref.
[ms] [rms]
Fig. 1 Short circuit - three-phase 1000 1,9 CH1 Voltage L1-N
Fig. 2 Short circuit - phase-neutral 1000 3,0 CH2 Current L1

Figure 1 Figure 2

13/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR:
Doc.:
400
F.Amodeo Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

UPS output dynamic tests


Test type: UPS OUTPUT DYNAMIC LOAD TESTS

Purpose: Verification of the UPS dynamic behaviour due to the mains transient:

Load variation EN 62040-3 ref. 6.3.7.1 & 5.3.1

LOAD VARIATION: OUTPUT LOAD STEP LINEAR LOAD


ref. fig. transient description ΔV Δt scope sign ref.
Va Vb
[%] [ms]
Fig.3a/b load variation 20-100% 228 223 -2,2 ≤ 10 CH1 Voltage phase 1
Fig.4a/b load variation 100-20% 225 230 2,2 ≤ 10 CH2 Voltage phase 2
Fig.5a/b load variation 0-100% 230 221 -3,9 ≤ 10 CH3 Voltage phase 3
Fig.6a/b load variation 100%-0 230 234 1,7 ≤ 10 CH4 Current phase 1

Figure 3a Figure 3b

14/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

UPS output dynamic tests


Test type: UPS OUTPUT DYNAMIC LOAD TESTS

Figure 4a Figure 4b

Figure 5a Figure 5b
Figure 5b

15/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: UPS OUTPUT DYNAMIC LOAD TESTS

Figure 6a Figure 6b

16/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: UPS DYNAMIC CHARACTERISTIC - CHANGE OF OPERATING MODE - NORMAL TO BYPASS MODE

Purpose: Transfer of load from inverter to bypass line and vieceversa

EN 62040-3 ref. 6.3.6.4


Ttable 14
TRANSFER OF LOAD FROM INVERTER TO BYPASS LINE AND VIECEVERSA
ref. fig transient description Scope sign ref.
Transfer of load from inverter to bypass due CH1 output voltage L1-N
Fig.9
to inv. Fault CH2 bypass current L1
CH3 inverter current L1
Fig.10 Retransfer of load from bypass to inverter

Figure 9 Figure 10

17/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: UPS DYNAMIC CHARACTERISTIC - BATTERY OPERATION

Purpose: Battery operation and restart of input mains

EN 62040-3 ref. 6.3.6.1 & 6.3.6.2 & 6.3.6.3 & 6.3.6.4


table 15
ΔV output f
ref. fig. transient description scope sign ref.
[%] [Hz]
CH1 input voltage
Fig. 11 Battery operation opening ext. Mains circuit breaker 0 50
CH2 output voltage
return at normal operation (restarting mains) power walk CH4 Battery current
Fig.12 0 50
in programmed
CH2 output voltage
return at normal operation (restarting mains) power walk
Fig.13 0 50 CH3 input current
in programmed
CH4 battery current

Fig. 11 Fig. 12 Fig. 13

18/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

Test type: ACOUSTICAL NOISE

Purpose: Measurament of the acoutical noise level emitted by the equipment

EN 62040-3 ref. 7.3

FRONT RIGHT SIDE LEFT SIDE BACK AVERAGE


% LOAD
[dBA] [dBA] [dBA] [dBA] [dBA]
0 69,5 69,5 69,5 69,5 69,5

50 70,5 71 71 71 70,9

100 71,5 71,5 72 72 71,8

19/20
SUBJECT : UPS PERFORMANCES TYPE TEST REPORT
R.P.S. UPS SIZE (kVA):
EDITOR: F.Amodeo
Doc.:
400
Date: 31/03/2014

Type:
Approved
TR - MASTER HE 400
MASTER HE / MHE
F.Amodeo

Code Nr: FMHEM40ANB00 Serial Nr: T77357 (w.o.)


Conducted by: S.Mannino Date: 31/03/2014 Pag. 20

list of instruments invent.


notes/characteristics
Nr.
type/position model
Input three phases Power analyzer YOKOGAWA WT1806-60-F-HE/G5/EC serial no. connetion 3phases 4 wires
6634
Output three phases Power analyzer 91NA15618 connetion 3phases 4 wires
Input current transformer phase L1 LEM IT 1000-S/SP1 s.no. 9102810009 6634/1 trans.ratio 1000A/1A
Input current transformer phase L2 LEM IT 1000-S/SP1 s.no. 9102810010 6634/2 trans.ratio 1000A/1A
Input current transformer phase L3 LEM IT 1000-S/SP1 s.no. 1132810036 6634/3 connection 1000A/1A
Output current transformer phase L1 LEM IT 1000-S/SP1 s.no. 1132810035 6634/4 trans.ratio 1000A/1A
Output current transformer phase L2 LEM IT 1000-S/SP1 s.no. 1132810065 6634/5 trans.ratio 1000A/1A
Output current transformer phase L3 LEM IT 1000-S/SP1 s.no. 1132810083 6634/6 trans.ratio 1000A/1A
D.C voltage multimeter FLUKE 87 6550
scope TEKTRONIX TDS 3014B 6134
insulated voltage probe L1-N TEKTRONIX P205 6272 signal ratio 1000V/2V
insulated voltage probe L2-N TEKTRONIX P205 6380 signal ratio 1000V/2V
insulated voltage probe L3-N CHAUVIN ARNOUX DP25 6033 signal ratio 1000V/5V
current transformer CHAUVIN ARNOUX PAC 22 6027 trans.ratio 1000A/1V
current transformer CHAUVIN ARNOUX PAC 22 6420 trans.ratio 1000A/1V
Sound Level Meter ASITA AS8000 6277

20/20