Staff:
序号 巡检项目名称 Inspection project name 0:00
Room temperature between 23 - 30
机房温度(23--30℃)正常,高或低 ℃ is normal, if higher or lower than
1 于设定值故障,通知相关人员处理 is fails, contact relevant person to
deal it.
Room humidity between 30-90% is
机房湿度(30--90%)正常,高或低于 normal, if higher or lower than is
2 设定值故障,通知相关人员处理 fails, please contact relevant person
to deal it.
3 机房卫生、清洁情况(自定义) Room hygiene, cleanliness (Custom)
有无漏水、渗水,有通知相关人员处 Whether leakage, seepage, contact
4 理 relevant person to deal it.
5 天花板、地板有无裂痕(自定义) Ceiling, floor for cracks (Custom)
Doors and windows are in good
6 门窗是否完好(自定义)
condition (Custom)
消防设备面板有灯亮正常,发出鸣叫 Fire equipment panel lights properly,
7 声为故障。 beeps sound of failure.
UPS # 1 mains power indicator lights
UPS#1市电显示灯亮绿灯正常,灭故障 green normal, off failure, contact
8 ,立即通知相关人员处理 relevant person to deal it
immediately.
UPS # 1 normal load indicator lights
UPS#1负载显示灯亮绿灯正常,灭故障
9 ,立即通知相关人员处理 green, off failure, contact relevant
person to deal it immediately.
UPS # 2 mains indicator lights green
UPS#2市电显示灯亮绿灯正常,灭故障
10 ,立即通知相关人员处理 normal, off failure, contact relevant
person to deal it immediately.
UPS # 2 normal load indicator lights
UPS#2负载显示灯亮绿灯正常,灭故障
11 ,立即通知相关人员处理 green, off failure, contact relevant
person to deal it immediately.
UPS # 3 mains indicator lights green
UPS#3市电显示灯亮绿灯正常,灭故障
12 ,立即通知相关人员处理 normal, off failure, contact relevant
person to deal it immediately.
UPS # 3 normal load indicator lights
UPS#3负载显示灯亮绿灯正常,灭故障
13 ,立即通知相关人员处理 green, off failure, contact relevant
person to deal it immediately.
Precision air-conditioning fault light
精密空调故障灯灭正常,亮红灯故障 off normal, red fault, start the
14 ,启动备用机使用,并通知相关人员
处理 standby machine to use, and contact
relevant person to deal it.
High-frequency switching power
高频开关电源故障灯亮橙灯次要告警 supply failure minor alarm lamp
15 ,亮红灯通知相关人员处理 lights orange, red notify the relevant
person to deal it.
High-frequency switching power float
voltage (V) at 52V to 56.3V (A / B
高频开关电源浮充电压(V)在52V到 channel) is normal, higher or lower
16 56.3V(A/B路)正常,高或低于设定
值故障,立即通知相关人员处理 than the set value fault, contact
relevant person to deal it
immediately.
High-frequency switching power
高频开关电源整流模块亮绿灯和橙灯 rectifier module bright green and
17 正常,亮红灯或全灭灯故障,通知相 orange lights normally, red or
关人员处理 Quanmie lamp failure, contact
relevant person to deal it.
AC input switch on the column
交流列头机柜输入合闸开灯亮红灯 header cabinet lights red (A, B
18 (A、B路)正常,不亮或亮绿灯故障 channel) is normal, not light or green
,通知相关人员处理。 light failure, notify the relevant
person.
DC input switch cabinet column
直流列头机柜输入开关负载电压在51V header load voltage 51V to 56.3V
19 到56.3V(A/B路)正常,高或低于设 (A / B channel) is normal, higher or
定值故障,通知相关人员处理 lower than the set value fails, notify
the relevant person to deal it.
AST AC low voltage distribution
低压配电AST柜AC灯亮正常,灭故障,
20 通知相关人员处理 cabinet lights normal, off failure,
notify the relevant person to deal it.
Fixed Generators not installed,
21 固定发电机没装好,注意事项代定
precautions to be confirmed.
1、注意所有设备机柜,如有异常的响声、冒烟、冒火,请通知动力维护人员。
1. Be carefull of all equipment cabinet, if unusual sound, smoke, sparks, please notify motivation maintenance staff.

2、机房温度高于32℃,请通知动力维护人员。
2. If oom temperature higher than 32 ℃, please notify to maintenance staff.
3、机房停市电要立即通知动力维护人员。
3. When engine room stopped the mains power, notify to maintenance staff immediately.
4、机房UPS设备的AC、的input和output灯灭立即通知动力维护人员。
4. Room UPS devices AC, the input and output power light off notify to maintenance staff immediately.
Notice:
5、开关电源电压低于52.8V,或传输有任何一个列头柜电压低于51.0V,立即通知动力维护人员。
5. Switching power supply voltage drops below 52.8V, or transmit any voltage below a column header cabinet 51.0V,
notify to motivation maintenance staff immediately.
6、如各巡检设备出现告警、空气开关非闭合状态、油机启动或其他异常情况,请立即通知动力维护人员及苏通服(099295588)
6. Such inspection of equipment alarm has occurred, the air switch not closed, oil machine startup
or other unusual circumstances, please immediately notify maintenance staff
and Su Tong power services (099 295 588).
7、动力维护人员联系方式:胡业绘(0383001027)
7. For power maintenance staff Contact: Hu Ye Hui (Mr. Hu) 038-3001027
机房值班巡检记录表
Machine room record sheet

4:00 8:00 12:00 16:00 20:00


ce staff.

et 51.0V,

护人员及苏通服(099295588)。
COREROOM POWER LOG SHEET
Date: / /2013 On duty staff: M: , E: , N:
Nº Cabinet Name Name Status
1 Airconditioner 1 □ □ □ ON □ □ □ OFF □ □ □ ALARM
2 Airconditioner 2 □ □ □ ON □ □ □ OFF □ □ □ ALARM
3 Airconditioner 3 □ □ □ ON □ □ □ OFF □ □ □ ALARM
□ A Voltage: v; □ B Voltage: v
4 XW0-F01-R05-N01 DC Voltage □ A Voltage: v; □ B Voltage: v
□ A Voltage: v; □ B Voltage: v
□ A Voltage: v; □ B Voltage: v
5 XW0-F01-R06-N01 DC Voltage □ A Voltage: v; □ B Voltage: v
□ A Voltage: v; □ B Voltage: v
□ A Voltage: v; □ B Voltage: v
6 XW0-F01-R07-N01 DC Voltage □ A Voltage: v; □ B Voltage: v
□ A Voltage: v; □ B Voltage: v
7 Z13 DC Cabinet □ □ □ Normal □ □ □ Abnormal
DC Cabinet Rectifier
8 Z12
(From top to buttom)
9 Z12 Module 01 □ □ □ Normal □ □ □ Abnormal □ □ □ Off
10 Z12 Module 02 □ □ □ Normal □ □ □ Abnormal □ □ □ Off
11 Z12 Module 03 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
12 Z12 Module 04 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
13 Z12 Module 05 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
14 Z12 Module 06 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
15 Z12 Module 07 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
16 Z12 Module 08 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
17 Z12 Module 09 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
18 Z12 Module 10 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
19 Z12 Module 11 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
20 Z12 Module 12 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
21 Z12 Module 13 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
22 Z12 Module 14 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
23 Z12 Module 15 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
24 Z11 AC Cabinet □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
25 1-1#UPS/U11 UPS □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
26 U12 U12 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
27 U13 U13 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
28 U114 U14 □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
29 12-1#UPS/U15 UPS □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
Left side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
30 XW01-F01-R04-N13
Right side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
Left side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
31 XW01-F01-R03-N12
Right side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
Left side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
32 XW01-F01-R02-N13
Right side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
Left side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
33 XW01-F01-R01-N13
Right side □ □ □ Normal □ □ □ Abnormal □ □ □ Overload
34 Battery Room
35 Airconditioner 1 □ □ □ ON □ □ □ OFF
36 Airconditioner 2 □ □ □ ON □ □ □ OFF
37 Breaker 1 □ □ □ ON □ □ □ OFF
38 Breaker 2 □ □ □ ON □ □ □ OFF
39 Breaker 3 □ □ □ ON □ □ □ OFF
40 Breaker 4 □ □ □ ON □ □ □ OFF
41 Breaker 5 □ □ □ ON □ □ □ OFF
42 Breaker 6 □ □ □ ON □ □ □ OFF
43 AC Power Room D1.4 □ □ □ Normal □ □ □ Abnormal
44 D1.5 □ □ □ Normal □ □ □ Abnormal

1. Be carefull of all equipment cabinet, if unusual sound, smoke, sparks, please notify
motivation maintenance staff.
2. If oom temperature higher than 32 ℃, please notify to maintenance staff.
3. When engine room stopped the mains power, notify to maintenance staff immediately.
4. UPS Room AC devices, if input and output power light off, notify maintenance staff immediately.
5. Switching power supply voltage drops below 52.8V, or transmit any voltage below
a column header cabinet 51.0V, notify to motivation maintenance staff immediately.
6. Such inspection of equipment alarm has occurred, the air switch not closed, oil machine startup
or other unusual circumstances, please immediately notify maintenance staff
and Su Tong power services (099 295 588).
7. For power maintenance staff Contact: Hu Ye Hui (Mr. Hu) 038-3001027
mmediately.

ne startup
Date Power Check Status Person M E N
16/08/2013
15/08/2013 2 times power cut off ok Hing