Fundamentals of Harmonics
3
Distribution Factors
where
• Ih is the harmonic current at harmonic frequency “h” in rms
• I1 is the rated fundamental current in rms
4
The rms voltage and current
5
Total Demand Distortion (TDD)
• The current THD definition causes some confusion because there is a nonlinear
relationship between the magnitude of the harmonic components and percent THD.
• a waveform with 120% does not contain twice the harmonic components of a
waveform with 60% distortion.
• a small current may have a high THD but not be a significant threat to the system.
• This difficulty may be avoided by referring THD to the fundamental of the peak
demand current rather than the fundamental of the present sample.
• This is called total demand distortion (TDD) and serves as the basis for the guidelines
in IEEE Std. 519-1992. Therefore,
where
IL is the maximum demand
load current in rms amps. 6
Active (Real) and Reactive Power
7
Apparent Power
• For purely sinusoidal voltage and current, the average power (or
true average active power)
9
Power Factor
For the nonsinusoidal case
Note that here, the Vh and Ih quantities are the peak quantities:
11
True Power Factor (TPF)
where
DF = P/S1 is the displacement power factor
DPF is the distortion power factor
12
True Power Factor (TPF)
• The unity PF is attainable only with pure sinusoids. What is actually provided is the
displacement PF.
• Power quality monitoring instruments now commonly report both the displacement
factors as well as the TPFs.
• The displacement factor is typically used in determining PF adjustments on a utility
bill since it is related to the displacement of the fundamental voltage and current.
• sizing capacitors for PF correction is no longer simple. It is not possible to get unity
PF due to the distortion power presence.
• Capacitors basically compensate only for the fundamental frequency reactive power
and cannot completely correct the TPF to unity when there are harmonics present.
• In fact, capacitors can make the PF worse by creating resonance conditions that
magnify the harmonic distortion.
13
Example
14
Example Cont’d
b.
Or
15
IEEE Std. 519
16
Example
A 4.16 kV three-phase feeder is supplying a purely resistive load of 5400 kVA. It has
been determined that there are 175 V of zero-sequence third harmonic and 75 V of
negative-sequence fifth harmonic.
Determine the following:
a. The total voltage distortion.
b. Is the THD below the IEEE Std. 519-1992 for the 4.16 kV distribution system?
Solution
(a)
(b)
the THDV limit for 4.16 kV is 5%. Since the THD calculated is 4.58%, it is less than the
limit of 5% recommended by IEEE Std. 519-1992 for 4.16 kV distribution systems.
17
Power in Passive Elements
, where
18
A. Power in a Pure Resistance Cont’d
, where
where
P is the total power loss in the resistance
P1 is the power loss in the resistance at the fundamental frequency
• For a purely resistive element, it can be observed from
𝑝 = 𝑝1 1 + 𝑇𝐻𝐷𝐼2 = 𝑝1 1 + 𝑇𝐻𝐷𝑉2
That
19
B. Power in a Pure Inductance
• Where
𝑓1 is the fundamental frequency
𝑉ℎ = 𝑗2𝜋 ℎ𝑓1 𝐿 𝐼ℎ
• Thus
• So that
20
C. Power in a Pure Capacitance
• The negative sign indicates that the reactive power is delivered to the load
• Thus
• Hence
21
Harmonic Distortion Limits
• IEEE Std. 519-1992 is entitled Recommended Practices and Requirements
for Harmonic Control in Electric Power Systems.
– gives the recommended practice for electric power system designers to control the
harmonic distortion that might otherwise determine electric power quality.
– a guideline in the design of power system with nonlinear loads.
– The limits set are for steady-state operation and are recommended for “worse-
case” conditions.
– The underlying philosophy is that the customer should limit harmonic currents and
the electric utility should limit harmonic voltages.
– It does not specify the highest-order harmonics to be limited.
– it does not differentiate between single-phase and three-phase systems. Thus, the
recommended harmonic limits equally apply to both.
– It does also address direct current that is not a harmonic. 22
Voltage Distortion Limits
24
Current Distortion Limits
25
Current Distortion Limits
• The harmonic currents from an individual customer are evaluated at the PCC
where the utility can supply other customers.
• The limits are dependent on the customer load in relation to the system short-
circuit capacity at the PCC.
• Note that all current limits are expressed as a percentage of the customer’s
average maximum demand load current.
• The current distortion limits vary by the size of the user relative to the utility
system capacity.
26
A procedure to determine the short-circuit ratio: Isc/IL
• Find the load average kilowatt demand PD over the most recent 12
months. This can be found from billing information.
• Convert the average kilowatt demand to the average demand current in
amperes using the following expression:
27
Harmonics Evaluation at PCC
• The harmonic characteristics of the utility circuit seen from the PCC are often
not known accurately.
• Therefore, good engineering judgment often dictated to review a case-by-case
basis.
• However, through a judicious application of the recommended practice, the
interferences between different loads and the system can be minimized.
28
According to IEEE 519-1992, the evaluation procedure for newly installed
nonlinear loads includes the following:
29
Harmonic controls
2) Electric utilities should limit harmonic voltages, since they have control over the
system impedances;
3) Both parties share the responsibility for holding harmonic levels in check.
30
Representation of a nonlinear load
• In power systems, the nonlinear load can be modeled as a load for the
fundamental current and as a current source for the harmonic currents.
• The harmonic currents flow from the nonlinear load toward the power source,
following the paths of least impedance
31
General flow of harmonic currents in a radial power system
32
Derating Transformers
• Transformers serving nonlinear loads exhibit increased eddy current losses due
to harmonic currents generated by those loads.
• Because of this, the transformer rating is derated using a K-factor.
33
K-Factor
• K-factor is an indication to transformer’s suitability for nonsinusoidal load
currents.
• K-factor relates transformer capability to serve varying degrees of nonlinear load
without exceeding the rated temperature rise limits.
• It is based on the predicted losses of a transformer.
• In per unit, the K-factor is
where Ih is the rms current at harmonic h, in per unit of rated rms load current
34
K-Factor
35
Transformer Derating
where
• Pec-r is the maximum transformer per unit
eddy current loss factor (typically, between
0.05 and 0.10 per units for dry-type
transformers).
• Ih is the harmonic current, normalized by
dividing it by the fundamental current.
• h is the harmonic order.
36
Typical Values Of Eddy Current Loss Factor (Pec-r )
37
Example
Assume that the per unit harmonic currents are 1.000, 0.016, 0.261, 0.050, 0.003,
0.089, 0.031, 0.002, 0.048, 0.026, 0.001, 0.033, and 0.021 pu A for the harmonic
order of 1, 3, 5, 7, 9, 11, 13, 15, 17, 19, 21, 23, and 25, respectively. Also assume
that the eddy current loss factor is 8%. Based on ANSI/IEEE Std. C75.110,
determine the following:
a. The K-factor of the transformer
b. The transformer derating based on the standard
38
39