EX##-OMO0030-A

PRODUCT NAME

SI unit for PROFINET

MODEL / Series / Product Number

EX260 Series
Table of Contents

Safety Instructions 2
Model Indication and How to Order 8
Summary of Product elements 9
Installation and Wiring 10
Installation 10
Wiring 11
LED Indication and Settings 14
Configuration 15
Troubleshooting and Maintenance 25
Specifications 29
Specifications 29
Dimensions 30
Accessories 31

-1-

No.EX##-OMO0030-A
Safety Instructions
These safety instructions are intended to prevent hazardous situations and/or equipment damage.
These instructions indicate the level of potential hazard with the labels of "Caution", "Warning" or
"Danger". They are all important notes for safety and must be followed in addition to International
standards (ISO/IEC) ∗1) and other safety regulations.
∗1) ISO 4414: Pneumatic fluid power -- General rules relating to systems
ISO 4413: Hydraulic fluid power -- General rules relating to systems
IEC 60204-1: Safety of machinery -- Electrical equipment of machines (Part 1: General requirements)
ISO 10218-1992: Manipulating industrial robots -Safety.
etc.

CAUTION indicates a hazard with a low level of risk which, if not avoided,
Caution : could result in minor or moderate injury.
WARNING indicates a hazard with a medium level of risk which, if not
Warning : avoided, could result in death or serious injury.
DANGER indicates a hazard with a high level of risk which, if not avoided,
Danger : will result in death or serious injury.

Warning
1. The compatibility of the product is the responsibility of the person who designs the
equipment or decides its specifications.
Since the product specified here is used under various operating conditions, its compatibility with
specific equipment must be decided by the person who designs the equipment or decides its
specifications based on necessary analysis and test results. The expected performance and safety
assurance of the equipment will be the responsibility of the person who has determined its
compatibility with the product. This person should also continuously review all specifications of the
product referring to its latest catalog information, with a view to giving due consideration to any
possibility of equipment failure when configuring the equipment.
2. Only personnel with appropriate training should operate machinery and equipment.
The product specified here may become unsafe if handled incorrectly. The assembly, operation and
maintenance of machines or equipment including our products must be performed by an operator
who is appropriately trained and experienced.
3. Do not service or attempt to remove product and machinery/equipment until safety is confirmed.
1. The inspection and maintenance of machinery/equipment should only be performed after measures
to prevent falling or runaway of the driven objects have been confirmed.
2. When the product is to be removed, confirm that the safety measures as mentioned above are
implemented and the power from any appropriate source is cut, and read and understand the
specific product precautions of all relevant products carefully.
3. Before machinery/equipment is restarted, take measures to prevent unexpected operation and
malfunction.
4. Contact SMC beforehand and take special consideration of safety measures if the product is
to be used in any of the following conditions.
1. Conditions and environments outside of the given specifications, or use outdoors or in a place exposed
to direct sunlight.
2. Installation on equipment in conjunction with atomic energy, railways, air navigation, space, shipping,
vehicles, military, medical treatment, combustion and recreation, or equipment in contact with food and
beverages, emergency stop circuits, clutch and brake circuits in press applications, safety equipment or
other applications unsuitable for the standard specifications described in the product catalog.
3. An application which could have negative effects on people, property, or animals requiring special
safety analysis.
4. Use in an interlock circuit, which requires the provision of double interlock for possible failure by
using a mechanical protective function, and periodical checks to confirm proper operation.

-2-

No.EX##-OMO0030-A
Caution
The product is provided for use in manufacturing industries.
The product herein described is basically provided for peaceful use in manufacturing industries.
If considering using the product in other industries, consult SMC beforehand and exchange
specifications or a contract if necessary.
If anything is unclear, contact your nearest sales branch.

Limited warranty and Disclaimer/Compliance Requirements


The product used is subject to the following "Limited warranty and Disclaimer" and "Compliance
Requirements".
Read and accept them before using the product.

Limited warranty and Disclaimer


1. The warranty period of the product is 1 year in service or 1.5 years after the product is delivered.*2)
Also, the product may have specified durability, running distance or replacement parts. Please
consult your nearest sales branch.
2. For any failure or damage reported within the warranty period which is clearly our responsibility, a
replacement product or necessary parts will be provided.
This limited warranty applies only to our product independently, and not to any other damage
incurred due to the failure of the product.
3. Prior to using SMC products, please read and understand the warranty terms and disclaimers noted
in the specified catalog for the particular products.
∗2) Vacuum pads are excluded from this 1 year warranty.
A vacuum pad is a consumable part, so it is warranted for a year after it is delivered.
Also, even within the warranty period, the wear of a product due to the use of the vacuum pad or failure due to
the deterioration of rubber material are not covered by the limited warranty.

Compliance Requirements
1. The use of SMC products with production equipment for the manufacture of weapons of mass
destruction (WMD) or any other weapon is strictly prohibited.
2. The exports of SMC products or technology from one country to another are governed by the
relevant security laws and regulation of the countries involved in the transaction. Prior to the
shipment of a SMC product to another country, assure that all local rules governing that export are
known and followed.

-3-

No.EX##-OMO0030-A
Operator
♦This operation manual is intended for those who have knowledge of machinery using pneumatic
equipment, and have sufficient knowledge of assembly, operation and maintenance of such
equipment. Only those persons are allowed to perform assembly, operation and maintenance.
♦Read and understand this operation manual carefully before assembling, operating or providing
maintenance to the product.

■Safety Instructions
Warning
■Do not disassemble, modify (including changing the printed circuit board) or repair.
An injury or failure can result.
■Do not operate the product outside of the specifications.
Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.
■Do not operate in an atmosphere containing flammable or explosive gases.
Fire or an explosion can result.
This product is not designed to be explosion proof.
■If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system.
•Check the product regularly for proper operation.
Otherwise malfunction can result, causing an accident.
■The following instructions must be followed during maintenance:
•Turn off the power supply.
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing
maintenance.
Otherwise an injury can result.

Caution
■After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly.
Safety cannot be assured in the case of unexpected malfunction.
■Provide grounding to assure the safety and noise resistance of the Serial System.
Individual grounding should be provided close to the product with a short cable.

-4-

No.EX##-OMO0030-A
■NOTE
○Follow the instructions given below when designing, selecting and handling the product.
•The instructions on design and selection (installation, wiring, environment, adjustment, operation,
maintenance, etc.) described below must also be followed.
∗Product specifications
•When conformity to UL is required, the SI unit should be used with a UL1310 Class 2 power supply.
•The SI unit is a approved product only if they have a mark on the body.
•Use the specified voltage.
Otherwise failure or malfunction can result.
•Reserve a space for maintenance.
Allow sufficient space for maintenance when designing the system.
•Do not remove any nameplates or labels.
This can lead to incorrect maintenance, or misreading of the operation manual, which could cause damage or
malfunction to the product.
It may also result in non-conformity to safety standards.

-5-

No.EX##-OMO0030-A
•Product handling
∗Installation
•Do not drop, hit or apply excessive shock to the fieldbus system.
Otherwise damage to the product can result, causing malfunction.
•Tighten to the specified tightening torque.
If the tightening torque is exceeded the mounting screws may be broken.
IP67 protection cannot be guaranteed if the screws are not tightened to the specified torque.
•Never mount a product in a location that will be used as a foothold.
The product may be damaged if excessive force is applied by stepping or climbing onto it.

∗Wiring
•Avoid repeatedly bending or stretching the cables, or placing heavy load on them.
Repetitive bending stress or tensile stress can cause breakage of the cable.
•Wire correctly.
Incorrect wiring can break the product.
•Do not perform wiring while the power is on.
Otherwise damage to the fieldbus system and/or I/O device can result, causing malfunction.
•Do not route wires and cables together with power or high voltage cables.
Otherwise the fieldbus system and/or I/O device can malfunction due to interference of noise and surge voltage
from power and high voltage cables to the signal line.
Route the wires (piping) of the fieldbus system and/or I/O device separately from power or high voltage cables.
•Confirm proper insulation of wiring.
Poor insulation (interference from another circuit, poor insulation between terminals, etc.) can lead to excess
voltage or current being applied to the product, causing damage.
•Take appropriate measures against noise, such as using a noise filter, when the fieldbus system is
incorporated into equipment.
Otherwise noise can cause malfunction.
•Separate the power line for output devices from the power line for control.
Otherwise noise or induced surge voltage can cause malfunction.

∗Environment
•Select the proper type of protection according to the environment of operation.
IP67 protection is achieved when the following conditions are met.
(1) The units are connected properly with fieldbus cable with M12 connector and power cable with M12 (M8)
connector.
(2) Suitable mounting of each unit and manifold valve.
If using in an environment that is exposed to water splashes, please take measures such as using a cover.
•Do not use in a place where the product could be splashed by oil or chemicals.
If the product is to be used in an environment containing oils or chemicals such as coolant or cleaning solvent, even
for a short time, it may be adversely affected (damage, malfunction etc.).
•Do not use the product in an environment where corrosive gases or fluids could be splashed.
Otherwise damage to the product and malfunction can result.
•Do not use in an area where surges are generated.
If there is equipment which generates a large amount of surge (solenoid type lifter, high frequency induction furnace,
motor, etc.) close to the fieldbus system, this may cause deterioration or breakage of the internal circuit of the
fieldbus system. Avoid sources of surge generation and crossed lines.
•When a surge-generating load such as a relay or solenoid is driven directly, use an fieldbus system with
a built-in surge absorbing element.
Direct drive of a load generating surge voltage can damage the fieldbus system.
•The product is CE marked, but not immune to lightning strikes. Take measures against lightning strikes
in the system.
•Prevent foreign matter such as remnant of wires from entering the fieldbus system to avoid failure and
malfunction.

-6-

No.EX##-OMO0030-A
•Mount the product in a place that is not exposed to vibration or impact.
Otherwise failure or malfunction can result.
•Do not use the product in an environment that is exposed to temperature cycle.
Heat cycles other than ordinary changes in temperature can adversely affect the inside of the product.
•Do not expose the product to direct sunlight.
If using in a location directly exposed to sunlight, shade the product from the sunlight.
Otherwise failure or malfunction can result.
•Keep within the specified ambient temperature range.
Otherwise malfunction can result.
•Do not operate close to a heat source, or in a location exposed to radiant heat.
Otherwise malfunction can result.

∗Adjustment and Operation


•Perform settings suitable for the operating conditions.
Incorrect setting can cause operation failure.
•Please refer to the PLC manufacturer's manual etc. for details of programming and addresses.
For the PLC protocol and programming refer to the relevant manufacturer's documentation.
•The surface on the product may be hot.

∗Maintenance
•Turn off the power supply, stop the supplied air, exhaust the residual pressure and verify the release of
air before performing maintenance.
There is a risk of unexpected malfunction.
•Perform regular maintenance and inspections.
There is a risk of unexpected malfunction.
•After maintenance is complete, perform appropriate functional inspections.
Stop operation if the equipment does not function properly.
Otherwise safety is not assured due to an unexpected malfunction or incorrect operation.
•Do not use solvents such as benzene, thinner etc. to clean the each unit.
They could damage the surface of the body and erase the markings on the body.
Use a soft cloth to remove stains.
For heavy stains, use a cloth soaked with diluted neutral detergent and fully squeezed, then wipe up the stains
again with a dry cloth.

-7-

No.EX##-OMO0030-A
Model Indication and How to Order

EX260-SPN 1

Connector type, output specification


1 M12 connector, 32 outputs, PNP (negative common) / source
2 M12 connector, 32 outputs, NPN (positive common) / sink
3 M12 connector, 16 outputs, PNP (negative common) / source
4 M12 connector, 16 outputs, NPN (positive common) / sink

Fieldbus
PN PROFINET

-8-

No.EX##-OMO0030-A
Summary of Product elements
<EX260-SPN1/-SPN2/-SPN3/-SPN4>

No. Element Description


Fieldbus interface connector PROFINET connection PORT 2. ∗1
1
(BUS OUT) (M12 4-pin socket, D-coded)
Fieldbus interface connector PROFINET connection PORT 1. ∗1
2
(BUS IN) (M12 4-pin socket, D-coded)

Power supply with load voltage for valves and operating voltage for SI unit. ∗1
3 Power supply connector
(M12 5-pin plug, A-coded)
4 Ground terminal Functional earth. (M3 screw)
5 Output connector Output signal interface for valve manifold.
6 LED display LED display to indicate the status of the SI unit. ∗2
7 Mounting hole Mounting hole for connection to the valve manifold.

Accessories
Hexagon socket head cap screw 2 pcs. M3 x 30 screw for connection to the valve manifold.
Seal cap 1 pc. seal cap for unused fieldbus interface connector (BUS OUT).
∗1: For details of suitable cables refer to the Accessories section on page 31.
∗2: Refer to page 14 for the LED Indication and Settings.

-9-

No.EX##-OMO0030-A
Installation and Wiring
■Installation
Connect valve manifold to the SI unit.

•Dimensions for installation

n: number of valve stations


L n 1 2 3 4 5 6 7 8
L1 120.7 136.7 152.7 168.7 184.7 200.7 216.7
L2 80 96 112 128 144 160 176
L n 9 10 11 12 13 14 15 16
L1 232.7 248.7 264.7 280.7 296.7 312.7 328.7 344.7
L2 192 208 224 240 256 272 288 304
(mm)

The above table shows dimensions as an example for the SY5000 series valve manifold.
Connectable valve manifolds are the same as for EX250 series SI unit.
Refer to the EX250 series valve manifold section in the valve catalogue for valve manifold dimensions.

-10-

No.EX##-OMO0030-A
■Wiring
Select the appropriate cables to mate with the connectors mounted on the SI unit.

○Fieldbus interface connector layout

BUS OUT: M12 4-pin socket, D-coded


No. Designation Description
1 TD+ Transmit Data +
2 RD+ Receive Data +
3 TD- Transmit Data -
4 RD- Receive Data -

BUS IN: M12 4-pin socket, D-coded


No. Designation Description
1 TD+ Transmit Data +
2 RD+ Receive Data +
3 TD- Transmit Data -
4 RD- Receive Data -

Connect the "BUS IN" connector to the upstream device (PLC etc.) and connect the "BUS OUT" connector
to the downstream device.

Note
•Be sure to fit a seal cap on any unused connectors.
Proper use of the seal cap enables the enclosure to achieve IP67 specification.
∗: Refer to page 31 for the seal cap.

-11-

No.EX##-OMO0030-A
○Power supply connector layout

PWR: M12 5-pin plug, A-coded


No. Designation Description
1 SV24 V +24 V for solenoid valve
2 SV0 V 0 V for solenoid valve
3 SI24 V +24 V for SI unit operation
4 SI0 V 0 V for SI unit operation
5 - Unused

Power-supply line for solenoid valve and power-supply line for SI unit operation are isolated.
Be sure to supply power, respectively.
Either single-source power or two different power supplies can be used.

∗: Pay attention not to exceed the tolerance range of power supply voltage.

-12-

No.EX##-OMO0030-A
○Ground terminal
Connect the ground terminal to ground.
Resistance to ground should be 100 ohms or less.

-13-

No.EX##-OMO0030-A
LED Indication and Settings

○LED indication

LED LED Status Description


OFF Operating normally
SF SI unit-related diagnostic error is detected
Red ON
(load power for the valve is not supplied or outside tolerance range)

•SI unit cannot detect a transmission rate and the connection to the PN
master has failed
BF Red ON •The configuration data sent from the PN master to the SI unit does not
agree with the SI unit configuration
•IP address/device name duplicated

Green ON BUS IN side: Link


Green OFF BUS IN side: No Link
L/A1
Yellow flashing BUS IN side: Activity
Yellow OFF BUS IN side: No Activity
Green ON BUS OUT side: Link
Green OFF BUS OUT side: No Link
L/A2
Yellow flashing BUS OUT side: Activity
Yellow OFF BUS OUT side: No Activity
Green ON SI unit operating voltage is supplied
PWR
OFF SI unit operating voltage is not supplied
Green ON Load voltage for the valve is supplied
PWR(V) Load voltage for the valve is not supplied or is outside the tolerance range
OFF
(19 V or less)

-14-

No.EX##-OMO0030-A
■Configuration
An applicable GSD file is required to configure the SI unit in the PROFINET network.
Please download the latest GSD file from the SMC website (URL http://www.smcworld.com).

GSD file
Model No. GSD file
1 EX260-SPN1/-SPN2
GSDML-V2.2-SMC-EX260-∗∗∗∗∗∗∗∗.xml
2 EX260-SPN3/-SPN4

The network configuration procedure using the SIEMENS STEP7 version V5.5 master software is described
below.

○GSD file installation


The GSD file must be installed into the STEP7 system.
Execute "Options" – "Install GSD File" from the HW Configuration window.

STEP7 software is manufactured by and a registered trademark of Siemens AG.

-15-

No.EX##-OMO0030-A
Browse and select the GSD file stored on the PC.

○Device name assignment


Connect the SI unit and execute "PLC" – "Edit Ethernet Node" from the HW Configuration window.

-16-

No.EX##-OMO0030-A
Enter the MAC address if it is known, or execute "Browse" and select the MAC address of the connected SI
unit.
After entering the MAC address, assign the Device name.

-17-

No.EX##-OMO0030-A
○Remote I/O configuration
Drag and drop the folder for the "EX260-SPN1/2" or "EX260-SPN3/4" from the HW catalogue, and place it
on the PROFINET line on the PN master.
EX260-SPN1/2: SI unit with 32 outputs, EX260-SPN1 or EX260-SPN2
EX260-SPN3/4: SI unit with 16 outputs, EX260-SPN3 or EX260-SPN4
Select either of the above.
If the connected SI unit and the selected folder EX260-SPN1/2 or EX260-SPN3/4 do not match, an error
will occur due to a mismatch in the number of outputs for slot 1.

-18-

No.EX##-OMO0030-A
Double click the EX260 icon or right click on the icon and execute "Object property".
Edit the Device name.
"EX260-SPN (EX260-SPN-1, EX260-SPN-2, and so on)" should be entered in the Device name box for
each EX260-SPN1/2 or EX260-SPN3/4 set with the hardware configuration.
The same name must be used for the connected SI unit device name (page 17) and the device name set in
the hardware configuration. If the device names do not match, the connected SI unit will have a
communication failure.

-19-

No.EX##-OMO0030-A
○Diagnostic parameters
The diagnostic parameters of the EX260-SPN1/2 (32 outputs) are as follows:
Name Range of values Default Description
If the solenoid valve supply voltage is 19 V
Enable
Valve Power Disable or less, it is possible to send an error state
Disable
to the master.

Hold
Output 0 Force to ON Force to OFF
Force to OFF
When a bus fault occurs, the output state
Hold can be set to either:
Output 1 Force to ON Force to OFF •Maintain the output state immediately
Force to OFF before the bus fault was generated.
: : : •Force the output ON
•Force the output OFF
Hold
Output31 Force to ON Force to OFF
Force to OFF

The diagnostic parameters of the EX260-SPN3/4 (16 outputs) are as follows:


Name Range of values Default Description
If the solenoid valve supply voltage is 19 V
Enable
Valve Power Disable or less, it is possible to send an error state
Disable
to the master.

Hold
Output 0 Force to ON Force to OFF
Force to OFF
When a bus fault occurs, the output state
Hold can be set to either:
Output 1 Force to ON Force to OFF •Maintain the output state immediately
Force to OFF before the bus fault was generated.
: : : •Force the output ON
•Force the output OFF
Hold
Output15 Force to ON Force to OFF
Force to OFF

○Diagnostics information
Channel Error Type
Value (hexadecimal) Description Error message
Vendor-specific
W#16#0011 Power supply failure
Power supply failure

-20-

No.EX##-OMO0030-A
○Setting of diagnostic parameters
Select the EX260-SPN icon from the dialogue of the HW configuration window.
Double click the slot 0 and set the diagnostic parameters in the "Properties" window.

-21-

No.EX##-OMO0030-A
○FSU (Fast Start Up) function
The EX260-SPN supports the FSU function.
The connected master controller must also support the FSU function in order to enable the EX260-SPN
FSU function.

•Configuration of the controller to enable the FSU function


Double click the PROFINET port of the controller which is connected to the EX260-SPN to enable the FSU
function.
Select "Options" – "TP/ITP 100 Mbps full duplex"and check "Disable autonegotiation".

-22-

No.EX##-OMO0030-A
•Configuration of the EX260-SPN to enable the FSU function
Select the EX260-SPN icon from the dialogue of the HW configuration window.
Double click the Slot X1 Interface and in the "General" window check "Prioritized startup".

Double click the port (P1 or P2) which enables the EX260-SPN FSU function.
Select "Options" – "TP/ITP 100 Mbps full duplex" and check "Disable autonegotiation".

-23-

No.EX##-OMO0030-A
○Output number assignment
Output data

∗: The output numbering refers to the solenoid position on the manifold and starts at zero.
∗: Standard wiring of the manifold is for double-solenoid valves and the output number starts at the A side and then B side in that
order as shown in the figure a.
If a single-solenoid valve is mounted on the standard wiring manifold, the output number for the B side valve is skipped.
∗: Custom wiring for mixed mounting single-solenoid valves and double-solenoid-valves can be specified with a Wiring Specification
Sheet. Example wiring is shown in the figure b.
∗: Bit status “0” and ”1” in the data corresponds to solenoid valve status OFF and ON (0: OFF, 1: ON), and the output number starts
at zero from LSB (least significant bit).

-24-

No.EX##-OMO0030-A
Troubleshooting and Maintenance
○Troubleshooting chart
When any malfunction is observed, it is recommended to perform the following troubleshooting.

SI unit SI unit Refer to fault


malfunction PWR LED is OFF No.1

SI unit Refer to fault


PWR (V) LED is OFF No.2
Yes
No
SI unit Refer to fault
L/A LED is OFF No.3

SI unit Refer to fault


BF LED is ON No.4

SI unit Refer to fault


SF LED is ON No.5

Group of valves Refer to fault


not working No.6

All valves and


Refer to fault
valve LEDs are not
operating No.7

Valves do not
Refer to fault
work but valve LEDs
are operating No.8

-25-

No.EX##-OMO0030-A
Troubleshooting table
Fault No.1
Fault Probable cause Recommended error handling Recommended action
Re-tighten the power cable.
Defective power (Replace the cable if it is broken)
Check the condition of the power cable
cable wiring for SI
SI unit wiring to the SI unit. Correct the power cable wiring
unit operation
PWR LED is layout.
OFF
SI unit operating
Check the condition of the supply voltage to Supply 24 VDC ±10% to the SI
voltage is not
the SI unit. unit.
supplied

Fault No.2
Fault Probable cause Recommended error handling Recommended action
Re-tighten the power cable.
Defective power (Replace the cable if it is broken)
Check the condition of the power cable
cable wiring for the
SI unit wiring for the valve. Correct the power cable wiring
solenoid valve
PWR (V) layout.
LED is OFF
Load voltage for the
Check the condition of the supply voltage Supply 24 VDC +10%/-5% to
valve is not
for the valve. the valves.
supplied

Fault No.3
Fault Probable cause Recommended error handling Recommended action
Check the condition of the upstream Supply power to the upstream
PROFINET device. PROFINET device.
PROFINET
communication Check the BUS IN side communication Tighten the communication
SI unit L/A error between the cable connections and check for broken cable connection.
LED is OFF SI unit and the wires. (Replace the cable if it is broken)
upstream
Check that there are no high voltage cables Take measures to keep the
PROFINET device.
or equipment that generates noise around communication cable and SI unit
the communication cable and SI unit. away from noise sources.

Fault No.4
Fault Probable cause Recommended error handling Recommended action
Tighten the communication
Check the communication cable
cable connection.
connections and check for broken wires.
(Replace the cable if it is broken)

Check that the configuration information


PROFINET Configure the SI unit in the PN
registered in the PN master matches the
SI unit BF communication is master software.
profile of the SI unit.
LED is ON abnormal
(Bus Fault). Check that the IP address and Device Configure the SI unit in the PN
name of the SI unit are not duplicated. master software.
Check that there is no high voltage cable or Take measures to keep the
equipment that generates noise around the communication cable and SI unit
communication cable and SI unit. away from noise sources.

-26-

No.EX##-OMO0030-A
Fault No.5
Fault Probable cause Recommended error handling Recommended action
Check that the diagnostic parameter for
SI unit SF Supply 24 VDC +10%/-5% to
Diagnostic error Valve Power is "Enabled" and that the
LED is ON the valves.
solenoid valve power is supplied.

Fault No.6
Fault Probable cause Recommended error handling Recommended action

Check if solenoid count does not exceed


the allowable number.
This depends on the SI unit model and
Group of Keep the number of mounted
valve series.
valves not Too many valves solenoid valves within
working specification.
Allowable solenoid number by valve series:
SY/SV/S0700 series: 32 points
VQC series: 24 points

Fault No.7
Fault Probable cause Recommended error handling Recommended action

Tighten the screws with the


Poor connection Check if there are any loose screws making specified tightening torque
between SI unit and the connection between the SI unit and the (i.e. 0.6 Nm) and make sure
valve manifold valve manifold. there is no gap between the SI
All valves unit and the valve manifold.
and valve
LEDs are not Mismatch polarity
Check if the solenoid valve common
operating between solenoid Match polarity between solenoid
specification matches the output polarity of
valve and SI unit valve and SI unit output.
the SI unit.
output

Defective solenoid Follow the troubleshooting for the solenoid


Same as left.
valve valve.

Fault No.8
Fault Probable cause Recommended error handling Recommended action

Valves do not Mismatch polarity


Check if the solenoid valve common
work but between solenoid Match polarity between solenoid
specification matches the output polarity of
valve LEDs valve and SI unit valve and SI unit output.
the SI unit.
are operating output

-27-

No.EX##-OMO0030-A
○Maintenance
Replacement of the SI unit
•Remove the M3 hexagon screws from the SI unit and release the SI unit from the valve manifold.
•Replace the SI unit.
•Tighten the screws with the specified tightening torque. (0.6 Nm)

Precautions for maintenance


(1) Be sure to switch off the power.
(2) Check there is no foreign matter inside the SI unit.
(3) Check there is no damage and no foreign matter on the gasket.
(4) Be sure to tighten the screws with the specified torque.
If the SI unit is not assembled properly, inside PCBs may be damaged or liquid and/or dust may enter
into the unit.

○Assembly and disassembly of the SI unit

-28-

No.EX##-OMO0030-A
Specifications
■Specifications
General specifications
Item Specifications
o
Ambient temperature -10 to +50 C
Ambient humidity 35 to 85%RH (No condensate)
Ambient temperature for storage -20 to +60 oC
Withstand voltage 500 VAC applied for 1 minute
Insulation resistance 500 VDC, 10 MΩ or more
Operating atmosphere No corrosive gas
Pollution degree Pollution degree 3
Enclosure IP67
Weight 200 g or less

Electrical specifications
Item Specifications
Current consumption of controller 21.6 to 26.4 VDC
Current power supply 0.1 A max.
consumption in
power supply 22.8 to 26.4 VDC
voltage range Solenoid valve power supply 2.0 A or less, according to the solenoid valve station
specification
EX260-SPN1/-SPN3 PNP (negative common) / source
Output type
EX260-SPN2/-SPN4 NPN (positive common) / sink
Output condition at the time of
Solenoid valve Output clear
communication error
connecting
specification Solenoid valve with surge voltage suppressor of
Connected load
24 VDC and 1.0 W or less (manufactured by SMC)
Insulation type Photo coupler insulation type
Residual voltage 0.4 VDC or less

Network communication specifications


Item Specifications
Protocol PROFINET (Specification Version 2.2)
Standard Ethernet cable (CAT5)
Transmission medium
(100BASE-TX)
Transmission speed 100 Mbps
EX260-SPN1/-SPN2 32 outputs
Number of outputs
EX260-SPN3/-SPN4 16 outputs
Vendor ID 0083 hex
Device ID 0001 hex

Connectable valve series


Valve Series
SY series SY3000, SY5000
VQC series VQC1000, VQC2000, VQC4000
SV series SV1000, SV2000, SV3000 (10 type tie-rod base)
S0700 series S0700
∗: The valve manifolds that can be connected are the same as those connectable to EX250 series.
-29-

No.EX##-OMO0030-A
■Dimensions

•If a fieldwireable connector is used for the power supply connection, and the SI unit is installed directly to a
valve manifold, the connector should be φ16 mm or less.
If the connector is a larger diameter it will interfere with the clamping face.
Recommended cables are specified in the accessories section, on page 31.

-30-

No.EX##-OMO0030-A
Accessories
○Connector cable
SI unit Compatible connector
connector Description Part number Specifications Manufacturer
Connector: M12 straight at one
end and RJ45 at the
Cable with EX9-AC020EN-PSRJ
other end
Fieldbus communication Cable: 2 m
1 interface connector
connector Connector: M12 straight
PCA-1446566
Cable: 5 m
Fieldwireable Connector: M12 straight
PCA-1446553
connector plug
SMC
Connector: M12 straight
EX500-AP010-S
Cable: 1 m
Connector: M12 straight
Power EX500-AP050-S
Cable with power Cable: 5 m
2 supply
supply connector Connector: M12 angle
connector EX500-AP010-A
Cable: 1 m
Connector: M12 angle
EX500-AP050-A
Cable: 5 m

○Seal cap
This cap is used to protect the M12 connector opening when the connector is not used.
When the "BUS OUT" connector is not used, the seal cap can keep the SI unit under IP67 rated protection.
(One seal cap will be attached to the SI unit when shipped from factory.)

Description Part No. Specification


Seal cap EX9-AWTS For M12 connector socket: 10 pcs.

-31-

No.EX##-OMO0030-A
Revision history
A: Revision

Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011-2012 SMC Corporation All Rights Reserved