Anda di halaman 1dari 172

DISTRICT

COOLING
BEST
PRACTICE
GUIDE
FIRST EDITION

Published to inform, connect


and advance the global
district cooling industry

INTERNATIONAL
DISTRICT ENERGY
• ASSOCIATION
Westborough, Massachusetts, USA
Dedicated to the growth and utilization of warranty or guaranty by IDEA of any product, service,
district cooling as a means to enhance energy process, procedure, design or the like. IDEA does not
efficiency, provide more sustainable and make any representation or warranties about the suit-
reliable energy infrastructure, and contribute ability or accuracyof the Information in this publication
to improving the global environment. or that the Information in this publication is error-free.
All Information presented in this work is provided "as
Proprietary Notice is" without warranty of any kind. IDEA disclaims all
warranties and conditions of any kind, express or
Copyright©2008lnternational District Energy Association. implied, including all implied warranties and conditions
ALL RIGHTS RESERVED. This publication contains of merchantability, fitness for a particular purpose, title
proprietary content of International District Energy and non-infringement. The Information contained in
Association (IDEA) which is protected by copyright, this publication may be superseded, may contain
trademark and other intellectual property rights. errors, and/or may include inaccuracies.

No part of this publication or any "Information" (as Disclaimer of Liability


defined below) contained herein may be reproduced (by
photocopying or otherwise), transmitted, stored (in a IDEA shall not be liable for any special, indirect,
database, retrieval system, or otherwise), or otherwise incidental, consequential or any damages whatsoever
used through any meanswithoutthe express prior written resulting from inconvenience. or loss of use, resources,
permission of IDEA. "Information" means any and all or profits, whether in an action of contract, negligence
information, data, specific products, services, processes, orother tortious action, arising out of or in connection
procedures, designs, techniques, technical data, editorial with the use or performance of any of the Information
material, advice, instructions, opinions or any other available in this publication even if IDEA has been
content appearing or referenced in this publication. advised of the possibility of such damages or losses.
IDEA invites comments. criticisms and suggestions
No Professional Advice regarding the subject matter in this publication,
including notice of errors or omissions.
IDEA has prepared this publication for informational
purposes only. This publication is not intended to
provide anyprofessional advice, instruction or opinions INTERNATIONAL
regarding any topic that appears in this publication and
DISTRICf ENERGY
• ASSOCIATION
should not be relied upon as such. The Information
contained in this publication is general in nature and 24 Lyman Street, Suite 230
may not apply to your particular circumstances or Westborough, MA 01581 USA
508-366-9339 phone
needs. Consult an appropriate professional for advice 508-366-0019 fax
tailored to your particular circumstances and needs. www.districtenergy.org

Disclaimer of All Warranties


ISBN 978-0-615-25071-7
Library of Congress Control Number: 2008937624
IDEA has exercised reasonable care in producing the
Information contained in this publication. IDEAhas not ISBN 978-0-615-25071-7
investigated, and IDEA expressly disclaimsany duty to
investigate, any specific product, service, process,
procedure, design, technique or the like that may be
described herein. The appearance of any Information
in this publication does not constitute endorsement,
Preface
When the National District Heating Association (NDHA) In 2004, Dany Safi, founder and chief executive officer
was founded in the United States in 1909, its mission of Tabreed, suggested IDEA develop an industry guide-
was to be a collegial and vibrant resource of practical book to help transfer the deeptechnical and engineering
engineering and operational information, to connect experience resident within IDEA to support the nascent
people with technical resources and real-world district cooling industry across the Middle East. Now,
solutions, and to advance the district energy industry as IDEA begins its second century in 2009, there is
through education and advocacy on the economic and massive investment in new district cooling systems in
environmental benefits of district heating systems.The the Middle East, where the harsh climate and pace of
cornerstone of the association wasthe open exchange real estate development demand a wide range of
of information on design, construction and safe technical resources. It is this unique market segment
operation of district heating systems. that is the principal focus of this first edition of the
District Cooling Best Practice Guide.
NDHA published the first edition Handbook of the
National District Heating Association in 1921, with The Best Practice Guide is a compilation of practical
subsequent revisions of the district heating handbook solutions and lessons learned by industry practitioners.
in 1932, 1951 and 1983. Over time, the association It is not a compendium of standards, reference
would evolve to encompass district cooling, combined documents and design drawings and is not intended
heat and power and the world beyond North America, to displace long-standing reference sources for codes
resulting in a name change from the National District and ratings. The Best Practice Guide is intended to
Heating Association (NDHA) to the International support engineers, business developers, managers and
District Heating Association (IDHA) in 1968 to the service providers in the business of district cooling. This
International District Heating and Cooling Association first edition may not incorporate every detail of the
(IDHCA) in 1984 to the current International District industry, but any omissions or oversights are uninten-
EnergyAssociation (IDEA) in 1994. Throughout the first tional. IDEA welcomes suggestions and comments to
100 years, IDEA hasremained true to its original mission support improvements infuture editions.
by drawing from the collective experience of all
membership segments - personnel from the operations, On behalf of the many contributors to this Best Practice
engineering and distribution arenas as well asconsultants Guide and the IDEA Board of Directors, thank you for
and manufacturers. your interest in district cooling and for selecting the
IDEAas your industry resource.

"'
Acknowledgements
It may not be possible to properly acknowledge all of design and engineering of numerous district cooling
the contributors to IDEA's District Cooling Best Practice systems around the globe. Important contributions
Guide. By its very nature, a best practice guide reflects were also made by Bjorn Andersson, Peter Beckett,
the collective experienceof industry participants, openly John Chin, Ehsan Dehbashi, Leif Eriksson, Leif Israelson,
sharing case studies, experiences and practical solutions Ryan Johnson, Todd Sivertsson, Sieiman Shakkour and
to the complex business of designing, constructing, Bard Skagestad of FVB Energy; Trevor Blank, Stanislaus
operating and optimizing district cooling systems. Since Hilton and Sai La of Thermo Systems LLC; and Peter
IDEA's inception in 1909, generations of IDEA members Tracey of CoolTech Gulf. Completing the guide
have made successive contributions to future colleagues. It demanded the focused personal commitment of these
is our sincere hopethat publishing this District Cooling Best fine industry professionals who have made a lasting and
Practice Guide will continue and extend the IDEAtradi- substantial professional contribution to IDEA and the
tion of providing guidance to future industry participants entire global industry community.
in developing reliable, efficient and environmentally
beneficial district energy systems. The world demands From the outset and over the extended development
our best efforts inthis arena. process, the IDEA Board of Directors remained committed
to the projectwith continuous support and leadership from
The principal vision for IDEA's District Cooling Best Robert Smith, Juan Ontiveros, Tom Guglielmi and Dennis
Practice Guide began with Dany Safi, CEO of Tabreed. Fotinos. In addition, a core support team of IDEA leaders
In 2004, at the start of his first term on the IDEABoard and volunteers chaired by Laxmi Raoand comprised of Cliff
of Directors, Safi proposed that IDEA assemble a guide Braddock, Kevin Kuretich, Jamie Dillard and Steve
book to help transfer the collective technical and Tredinnick contributed substantially by providing regular
business experience on district cooling that he had technical input and insight and participating in project
encountered over many years of attending IDEA updates and review meetings.
conferences. The principal founder of the burgeoning
district cooling industry in the Middle East, Safi Hundreds of pages of technical content were reviewed
foresaw the value and importance of technical guid- chapter by chapter by industry peers. These individuals
ance and experience exchange to ensure that newly volunteered to support IDEA's Best Practice Guide by
developed systems are properly designed, constructed reading, verifying and editing chapters in their areasof
and operated for highest efficiency and reliability to pre- specialty to ensure editorial balance and the technical
serve the positive reputation of the industry. Safi con- integrity of the final product. IDEA is indebted to peer
tributed personally, professionally and financially to this reviewers John Andrepont, George Berbari, Bharat
guide and deserves special recognition for his Bhola, Joseph Brillhart, Cliff Braddock, Jamie Dillard,
singular and sustaining commitment to a robust and en- Steve Harmon, Jean Laganiere, Bob Maffei, Gary Rugel,
vironmentally progressive global district energy industry. Ghassan Sahli, Sam Stone, Craig Thomas, Steve
Tredinnick and Fouad Younan. We also appreciate the
The principal authors of this guide are Mark Spurr and assistance of the operation and maintenance team at
colleagues Bryan Kleist, Robert Miller and Eric Moe of Tabreed, led by JamesKassim, who contributed insights
FVB Energy Inc., with Mark Fisher of Thermo Systems from their experience in operating a wide variety of
LLC authoring the chapter on Controls, Instrumenta- district cooling systems.
tion and Metering. These gentlemen have dedicated
hundreds of hours in organizing, writing, researching Important financial supportfor the Best Practice Guide
and editing this Best Practice Guide, drawing from was providedviaan award under the Market Development
decades of personal, professional experience in the Cooperator Grant Program from the United States

iv
Department of Commerce. IDEA acknowledges the The IDEA community has grown with the recent
important support of Department of Commerce staff addition of hundreds of members from the recently
including Brad Hess, Frank Caliva, Mark Wells, Sarah formed Middle EastChapter. The chapter would not be
Lapp and Patricia Gershanik for their multi-year in place withoutthe commitment and resourcefulness
support of IDEA. of Joel Greene, IDEA legal counsel from Jennings,
Strauss & Salmon. As former chair of IDEA, Joel has
Tabreed provided substantial financial support during been committed to IDEA's growth in the Middle East
the early stage of the project, and Dany Safi, CEO of region. Additionally, Rita Chahoud of Tabreed, the
Tabreed, made a substantial personal financial contri- executive director of the IDEA Middle East Chapter, is a
bution to sponsor the completion of the BestPractice dedicated and energetic resource for the industry.
Guide. IDEA thanks and gratefully acknowledges the Without her contributions and stewardship, the IDEA
leadership and unparalleled commitment demonstrated Middle East Chapter would not be where it is today.
by Dany Safi and Tabreed, global leaders in the district
cooling industry. Finally, the IDEA membership community is comprised of
dedicated, committed and talented individuals who have
Monica Westerlund, executive editor of District Energy made countless contributions to the success and growth
magazine, provided timely editing of the guide and of the district energy industry. As we celebrate IDEAs
worked closely with Dick Garrison who designed the centennial and begin our second century, I wish to
final layout of the book. This was a challenging task acknowledge the collective energy of our members in ad-
achieved under a tight timetable. Laxmi Rao provided vancingthe best practicesof our chosenfield of endeavor.
management and stewardship throughout the project,
and the printing and binding of the book was ably Robert P. Thornton
managed by Len Phillips. IDEA staff Dina Gadon and President, International District Energy Association
Tanya Kozel make regular contributions to the IDEA Westborough, Massachusetts, USA
community and therefore directly and indirectly
contributed to this effort. The sum of our IDEA parts is September 2008
a much larger whole.

v
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008 International District Enetgy Assodatioo.Allrightsreserved.

Contents
Preface iii
Acknowledgements iv

1. Introduction 1
1.1 Purpose 1
1.2 Overview and Structure of the Guide 2

2. Why District Cooling? 2


2.1 Customer Benefits 2
2.1.1 Comfort 2
2.1.2 Convenience 2
2.1.3 Flexibility 2
2.1.4 Reliability 2
2.1.5 Cost-effectiveness 2
Fundamental cost advantages 2
Load diversity 2
Optimized operations 2
Advanced technologies 3
Better staff economies 3
Customer risk management 3
Costcomparison 3
Capital costs 3
Annual costs 3
2.2 Infrastructure Benefits 3
2.2.1 Peak power demand reduction 3
2.2.2 Reduction in government power sector costs 4
Capital costs of power capacity 4
Power sector operating costs 4
Total costs of electricity 5
Power utility recognition of district cooling benefits 5
2.3 Environmental Benefits 7
2.3.1 Energy efficiency 7
2.3.2 Climate change 7
2.3.3 Ozone depletion 8

3. Business Development 9
3.1 District Cooling as a Utility Business 9
3.1.1 Engineering design 9
3.1.2 Organizational design 9
3.2 Marketing and Communications 9
3.2.1 Positioning 9
3.2.2 Customer value proposition 10
Value proposition summary 10
Building chiller system efficiency 10
Structuring the cost comparison 10
Communicating with prospective customers 11
3.3 Risk Management 11
3.3.1 Nature of district cooling company 11
3.3.2 Capital-intensiveness 11
3.3.3 Will visions be realized? 11
3.3.4 District cooling company risks 12
Stranded capital 12
Temporary chillers 12

vi
DISTRICT COOLING BEST PRACTICE GUIDE
e2008 !mem~tion,,! Di5tnct Energy A5wd~ti(Jfl. Al!nghl:; reservro.

Construction risks 12
Underground congestion 12
Community relations 12
General construction issues 12
Revenue generation risks 12
Inadequate chilled-water delivery 12
Delays in connecting buildings 13
Metering 13
Reduced building occupancy 13
3.4 Rate Structures 13
3.4.1 Capacity, consumption and connection rates 13
Capacity rates 13
Consumption rates 13
Connection charges 13
Regional rate examples 13
3.4.2 Rate structure recommendations 14
Capacity rates 14
Connection charges 14
Initial contract demand 14
Rate design to encourage optimal building design and operation 15
3.5 Performance Metrics 15

4. Design Process and Key Issues 16


4.1 Load Estimation 16
4.1.1 Peak demand 16
4.1.2 Peak-day hourly load profile 17
4.1.3 Annual cooling load profile 18
4.2 Design Temperatures and Delta T 18
4.2.1 Delta T is a key parameter 18
4.2.2 Limitations on lower chilled-water supply temperature 19
Chiller efficiency 19
Evaporator freezeup 20
Thermal energy storage 20
4.2.3 Limitations on higher chilled-water return temperature 20
Dehumidification and coil performance 20
Heat exchanger approach temperature 21
4.2.4 Best practice recommendation 21
4.3 Master Planning 21
4.4 Permitting (Way Leaves) 22
4.5 Integration of District Cooling With Other Utility Infrastructure 22
4.5.1 Growth and infrastructure stresses 22
4.5.2 Paths for utility integration 23
Heat rejection 23
Desalination 24
Natural gas 24
The challenge of utility integration 24
4.6 Designing for Operations 25

5. Building HVAC Design and Energy Transfer Stations (ETS) 26


5.1 Building System Compatibility 26
5.1.1 Cooling coil selection 26
5.1.2 Bypasses and three-way valves 27
5.1.3 Control-valve sizing and selection 27

vii
DISTRICT COOUNG BEST PRACTICE GUIDE
C2oo8Intemation<ll DiS/Iict EneIWAlsodanoo. All rightsreserved.

5.1.4 Building pump control 27


5.1.5 Water treatment and heat-transfer effectiveness 29
5.1.6 Additional economic opportunities 29
5.2 System Performance Metrics at the ETS 29
5.3 Selecting Direct or Indirect ETS Connections 30
5.3.1 Direct connections 31
5.3.2 Indirect connections 32
5.4 Heat Exchanger Considerations 33
5.4.1 HEX temperature requirements 33
5.4.2 HEX pressure requirements 34
5.4.3 HEX redundancy requirements 34
5.4.4 HEX performance efficiency 35
5.4.5 Other HEX considerations 35
5.5 Control-Valve Considerations 35
5.5.1 Location and applications 36
5.5.2 Control-valve types and characteristics 36
Pressure-dependent control 36
Pressure-independent control 37
5.5.3 Control-valve sizing 37
5.5.4 Actuator sizing and selection 38
5.5.5 Quality and construction 38
5.6 ETS and Building Control Strategies 38
5.6.1 Supply-water temperature and reset 38
5.6.2 Supply-air temperature and reset at cooling coils 39
5.6.3 Building pump and ETS control-valve control 39
5.6.4 Capacity control after night setback 39
5.6.5 Staging multiple heat exchangers 40
5.7 Metering and Submetering 40
5.7.1 Introduction 40
5.7.2 Meter types 40
Dynamic meters 40
Static flow meters 41
5.7.3 Designing for meter installation and maintenance 41
5.7.4 Standards 42
5.7.5 Other equipment 42
5.7.6 Submetering 42
Meter reading 42
Conclusions aboutsubmetering 43

6. Chilled-Water Distribution Systems 45


6.1 Hydraulic Design 45
6.1.1 Hydraulic model 45
6.1.2 Customer loads and system diversity 45
6.1.3 Startup and growth 46
6.1.4 Piping layout 46
6.1.5 Delta T 46
6.1.6 Pipe sizing 47
6.2 Pumping Schemes 47
6.2.1 Variable primary flow 48
Special considerations for district cooling systems 49
Design considerations 49
When to use variable primary flow 50
6.2.2 Primary-secondary pumping 50

viii
DISTRICT COOUNG BEST PRACnCEGUIDE
e2008lnremarional Di5frkt Energy Allooiltion.Allrights te5ervro.

When to use primary-secondary pumping 51


6.2.3 Distributed pumping 51
6.2.4 Booster pumps 52
6.3 Pump and Pressure Control 52
6.3.1 Distribution pumps 52
6.3.2 Variable-frequency drives 53
6.3.3 Differential pressure control 53
6.3.4 Pump dispatch 53
6.3.5 System pressure control and thermal storage 54
6.4 Distribution System Materials and Components 55
6.4.1 Pipe materials 55
Welded-steel pipe 55
HDPE pipe 56
Ductile-iron pipe 57
GRP pipe 58
Pipe material selection summary 58
Steel pipe 58
HDPE pipe 58
Ductile-iron pipe 59
GRP pipe 59
6.4.2 Isolation valves 59
Valve chambers 59
Direct-buried isolation valves 59
Cost considerations 61
6.4.3 Branch connections/service line takeoffs 62
6.4.4 Insulation 62
Evaluating insulation requirements 62
Pre-insulated piping insulation considerations 63
6.4.5 Leak-detection systems 64
Sensor-wire leak detection 64
Acoustic leak detection 65
Software-based leak detection 65

7. Chilled-Water Plants 66
7.1 Chilled-Water Production Technologies 66
7.1.1 Compression chillers 66
Reciprocating 66
Rotary 66
Centrifugal 66
Centrifugal-chiller capacity control 66
Inlet guide vanes 66
Variable-speed drive (VSD) 66
Hot-gas bypass 67
Meeting low loads 67
7.1.2 Natural gas chillers 67
7.1.3 Absorption chillers 68
Pros and cons 68
Efficiency 69
Capacity derate 69
Capital costs 69
Equipment manufacturers 69
Operating costs 70
7.1.4 Engine-driven chillers 70

ix
DISTRICTCOOUNG BESTPRACTICE GUIDE
C2008International Di5tn"d Energy A55odation. Allriglll5 re~.

7.1.5 Combined heat and power (CHP) 70


7.1.6 Choosing chiller type in the Middle East 71
7.2 Thermal Energy Storage (TES) 71
7.2.1 Thermal energystorage (TES) types 72
Chilled-water thermal energy storage 72
Icethermal energy storage 72
Low-temperature fluid thermal energy storage 72
7.2.2 Thermal energystorage benefits 72
Peak-load management 72
Energy efficiency 72
Capital avoidance 72
Operational flexibility 73
7.2.3 Thermal energy storage challenges 73
Sizing 73
Siting 73
Timing 74
7.3 Plant Configuration 74
7.3.1 Chiller sizing and configuration 74
7.3.2 Series-counterflow configuration 74
7.4 Major Chiller Components 75
7.4.1 Motors 75
Enclosure types 75
Standard motor enclosure costs 76
Inverter-duty premium 76
Motor efficiency 76
Motor physical size 76
Voltage options for chiller motors 76
7.4.2 Heat exchanger materials and design 77
7.5 Refrigerants 78
7.6 Heat Rejection 79
7.6.1 Overview of condenser cooling options 79
7.6.2 Optimum entering condenser-water temperature 80
7.6.3 Cooling tower considerations 80
Cooling tower sizing 81
Cooling tower basins 82
7.6.4 Condenser-water piping arrangement 83
7.7 Water Treatment 83
7.7.1 Water supply 83
Potable water 83
Treated sewage effluent 83
Seawater in a once-through arrangement 84
Seawater astower makeup 84
Seawater treated using reverse osmosis or other desalination technologies 85
7.7.2 Treatment approaches 85
Chilled water 85
Treatment approach 85
Dosing and control 86
Condenser water 86
Treatment approach 86
Dosing and control 86
Legionella control 87
7.7.3 Zero liquid discharge 87
7.7.4 Service standards 87

x
DISTRICT COOUNG BEST PRACfICE GUIDE
e2008 Inremauonal Di,lIict Energy Asm:i<!UOfl. All righ15 teserved.

7.8 Balance of Plant 88


7.8.1 Piping design for condenser water 88
7.8.2 Sidestream filters 88
7.8.3 Cooling tower basin sweepers 90
7.8.4 Transformer room cooling 90
7.8.5 Equipment access 90
7.8.6 Noise and vibration 90
7.9 Electrical Systems 91
7.9.1 Short-circuit study 91
7.9.2 Protective device coordination study 91
7.9.3 Arc flash hazard study 91

8. Controls, Instrumentation and Metering 92


8.1 Introduction 92
8.2 Definitions 92
8.3 Overview 92
8.3.1 Typical DClCS functions 92
8.3.2 General design factors 93
8.3.3 DCICS evaluation performance 93
8.4 Physical Model 93
8.4.1 Sites 93
8.4.2 Plants 93
8.4.3 Local plant I&C system 93
Local plant controllers 93
Field devices 95
Local operator interface terminals 95
Local workstations 95
8.4.4 Command centers 95
Data server 95
Historical server 95
Command center workstations 96
Terminal server 96
Other servers and workstations 96
8.5 Logical Model 96
8.5.1 Levela 96
8.5.2 Levell 97
8.5.3 Level 2 98
8.5.4 Level 3 99
8.5.5 Level 4 99
8.5.6 Level 5 100
8.6 Sample DCICS 101
8.7 Level a- Best Practices 101
8.7.1 Point justification 101
8.7.2 Criteria for device selection 102
8.7.3 Redundant Level a equipment 102
8.7.4 Local instrumentation 106
8.7.5 Localized overrides for each controlled component 106
8.7.6 Good installation practices 106
8.8 Levell - Best Practices 106
8.8.1 Levell field instrumentation 106
8.8.2 I/O modules and racks 106
8.8.3 Onboard chiller controllers 107
8.8.4 Variable-frequency drives 108

xi
DlSTRIO COOUNG BEST PRAOICE GUIDE
C2008lntefmJUon~1 District. fne.gyAssociaUon. Allrights reserved.

8.8.5 Energy monitoring equipment 108


8.8.6 Metering and submetering 108
8.8.7 Redundant Level 1 field instrumentation 110
8.8.8 Levell network best practice considerations 110
8.8.9 Levell data considerations 110
8.9 Levels 0 & 1 - Choosing Points to Monitor and Control 110
8.9.1 Example equipment segments 111
Primary-secondary systems 111
Variable primary systems 113
Chiller evaporators 115
Condenser-water systems 116
Cooling towers 117
Centrifugal chiller condensers 118
Constant-speed pumps 119
Variable-speed pumps 120
Heat exchangers 121
8.9.2 Level 0 vs. Levell - field instrumentation 122
8.10 Level 2 - Best Practices 122
8.10.1 Types of controllers 122
8.10.2 Selection criteria 123
8.10.3 Distributing controllers 123
8.10.4 Controller redundancy 123
8.10.5 Critical data integrity 124
8.10.6 Time-of-day synchronization between controllers 124
8.10.7 Controller power requirements 124
8.11 Level 3 - Best Practices 125
8.11.1 Connecting local OITs to local controllers 125
8.11.2 Displaying metering data on local OITs 125
8.11.3 Environment 125
8.11.4 Local OIT power requirements 125
8.12 Level 4 - Best Practices 125
8.13 Networking Best Practice Considerations 125
8.13.1 DCICS network categories 125
8.13.2 Level 2+ network infrastructure 129
Fiber optics 129
Wireless 129
Internet 130
8.13.3 Remote control vs. manning individual plants 130
8.13.4 Sophistication 130
8.13.5 Performance 130
8.13.6 Security 130
8.13.7 Physical network topologies 131
8.13.8 Network monitoring via OPC 131
8.13.9 Network bridging and controller pass-through 131
8.13.10 DCICS network and Level 4 equipment ownership 132
8.13.11 DCICS Level 2+ network component power requirements 132
8.14 Control Functions 133
8.15 Human-Machine Interface Functionality 133
8.16 Standardization 133
8.17 Standard Design Documents 134
8.18 Standard Testing Documents 135

xii

-_. __. _ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
DISTRICT COOLING BEST PRACTICE GUIDE
C2008lnremaliooal DirtrktEnergy A550darion, All ri9hl'.i reserved.

9. Procurement and Project Delivery 136


9.1 Design/Bid/Build (DBB) 136
9.2 Engineer/Procure/Construct (EPC) 137
9.3 Packaged Plants 137

10. Commissioning 140

Appendix
A - Abbreviations and Definitions A-1
B - Conversion Factors B-1
C - Arc Flash C-1

Tables
Table 2-1 Combined-cycle power plant operation cost factors
Table 2-2 Conversion of fuel prices in US$ per barrel oil equivalent (BOE) to US$ per MMBtu
Table 3-1 Summary of customer value
Table 5-1 Typical coil (and delta T) performance as entering-water temperature varies
Table 5-2 Sample heat exchanger differences with coldersupply-watertemperature and common building-side
conditions
Table 5-3 Tonnage capacity per heat exchanger
Table 5-4 Recommended maximum chloride content (ppm)
Table 5-5 Control-valve applications and control points
Table 6-1 Impact of delta T on 990 mm (36") pipe capacity
Table 6-2 Impact of delta T on capacity of 1000 hp pump set
Table 7-1 Summary of packaged chiller types and capacities (ARI conditions)
Table 7-2 Impact of delta T in operation on chilled-waterstorage capacity
Table 7-3 Inputs to series-counterflow example
Table 7-4 Performance results for series-counterflow example
Table 7-5 Example dimensions and weights of motor types
Table 7-6 Corrosion resistance and performance of condenser tube material options
Table 7-7 Refrigerant phaseout schedule (Montreal Protocol, Copenhagen Amendment, MOP-19 adjustment)
Table 7-8 Inputs to low condenser flow example
Table 7-9 Performance results for low condenser flow example (3 gpm/ton vs. 2.3 gpm/ton)
Table 7-10 Recommended monthly tests
Table 7-11 Corrosion-coupon standards
Table 7-12 Performance characteristics of sand filters vs. cyclone separators
Table 8-1 PLC vs. DCS - pros and cons
Table 8-2 Level 0 best practice specifications
Table 8-3 Energy meter best practice specifications
Table 8-4 Keyto instrument tagging symbols
Table 8-5 Function identifier key
Table 8-6 Level 0 vs. Level 1 field instrumentation - selection criteria
Table 8-7 Level 4 componentry best practicetips
Table 8-8 DClCS network categories
Table 9-1 Example detailed outline of Owner's Requirements Documents (ORDs) for engineer/procure/construct
(EPC) procurement

Figures
Figure 2-1 Peak power demand reductions with district cooling
Figure 2-2 World oil prices during the past 10 years
Figure 2-3. Oil prices in US$ per MMBtu
Figure 2-4 Projected impact of oil price on price of delivered liquefied natural gas
Figure 2-5 Long-run marginal costs of delivered electricity from new combined-cycle plantat a range of fuel prices

xiii
DISlRlcr COOUNG BEST PRAcrlCE GUIDE
1:12008 inlemaliOfliJiDi.lridEnergyA>soda/i·Ofl. All right>re>erWd.

Figure 2-6 Example of time-of-day power rates compared with power demand, per New England Hourly
Electricity Price Index
Figure 2-7 Annual electric energy consumption savings with district cooling
Figure 3-1 Examples of Middle East district cooling rates
Figure 4-1 Design dry-bulb and mean-coincidentwet-bulb temperatures for selected Middle East cities (ASHRAE
0.4% design point)
Figure 4-2 Design wet-bulb and mean-coincidentdry-bulb temperatures for selected Middle East cities (ASHRAE
0.4% design point)
Figure 4-3 Example peak-day load profilesfor various building types
Figure 4-4 Illustrative peak-day load profile for district cooling servinq mixed building types
Figure 4-5 Illustrative district cooling annual load-duration curve
Figure 4-6 Effect of increased delta T on LMTD of cooling coils
Figure 4-7 Paths for potential utility integration
Figure 5-1 Expected coil performance over the design flow range for typical coil
Figure 5-2 Decoupled direct ETS connection
Figure 5-3 Simplified direct ETS connection
Figure 5-4 Indirect ETS connection (with combined HEX control valves)
Figure 5-5 Indirect ETS configuration (with dedicated HEX control valves)
Figure 5-6 Plate-and-frame heat exchanger installation
Figure 5-7 Plate-and-frame heat exchanger (courtesy Alfa Laval)
Figure 5-8 HEX surface area vs. "approach"
Figure 5-9 Importance of critical customer design
Figure 5-10 Pressure-dependent "globe" valve
Figure 5-11 Common control-valve characteristics
Figure 5-12 Pressure-independent control valve (courtesy Flow Control Industries)
Figure 5-13 Submetering system via fixed wireless
Figure 5-14 Submetering system with an RF handheld terminal
Figure 6-1 Impact of delta T on hydraulic profile
Figure 6-2 Variable primary flow
Figure 6-3 Traditional primary-secondary system
Figure 6-4 All variable primary-secondary system
Figure 6-5 Distributed primary-secondary system
Figure 6-6 Thermal storage tank used for maintaining static pressure in system
Figure 6-7 Weld-end ball valve
Figure 6-8 Weld-end butterfly valve
Figure 6-9 Direct-buried valve with mechanical actuation
Figure 6-10 Direct-buried valve with hydraulicactuator
Figure 6-11 Sluice plate hot tap
Figure 6-12 Example of estimated average ground temperatures at various depths
Figure 6-13 Distribution system supply-water temperature rise for example system at part load
Figure 7-1 Single-effect absorption cycle (courtesy York/Johnson Controls)
Figure 7-2 Engine-based CHP with electric and absorption chillers (courtesy York/Johnson Controls)
Figure 7-3 Turbine-based CHP with electric and steam-turbine-drive chillers
Figure 7-4 Load-leveling potential with thermal energy storage
Figure 7-5 Lift in single and series-counterflowchillers
Figure 7-6 Enclosure premiums above open drip-proof
Figure 7-7 Inverter-duty motorcost premium
Figure 7-8 Motor efficiency
Figure 7-9 Refrigerant environmental impact comparison
Figure 7-10 Counterflow cooling tower
Figure 7-11 Crossflow cooling tower
Figure 7-12 Chiller and tower kW/ton vs. ECWT
Figure 7-13 Rate of power change for chillers and cooling towers

xiv
DISTRICT COOLINGBEST PRACTICE GUIDE
C2008 International Di5trid EnergyA'isociation. All n9h~ resevea.

Figure 7-14 Pumps dedicated to specific condensers


Figure 7-15 Condenser pumps with header
Figure 8-1 DClCS physical model
Figure 8-2 . DClCS logical model
Figure 8-3 Sample DClCS system
Figure 8-4 Primary-secondary systems
Figure 8-5 Variable primary system instrumentation
Figure 8-6 Chiller evaporator supply and return instrumentation
Figure 8-7 Condenser-water system instrumentation
Figure 8-8 Cooling tower instrumentation
Figure 8-9 Chiller condenser supply and return instrumentation
Figure 8-10 Constant-speed pump instrumentation
Figure 8-11 Variable-speed pump instrumentation
Figure 8-12 Heatexchanger instrumentation

xv
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lnremab'onal Di5rrid Energy A55OOalion. Allnghts te5erved.

1. Introduction
1.1. Purpose Chapter 3 - Business Development presents key topics
on the business side of district cooling, including the
The purpose of the International District Energy fundamental importance of approaching district
Association's District Cooling Best Practice Guide is to cooling as a utility business. This viewpoint has
facilitate the design of district cooling businesses and implications for designing all aspects - technology,
systems that are reliable, efficient and profitable. The business and operating structure - of the district
guide is focused on a key district cooling growth cooling company. Other critical business considerations,
market - the Middle East - that has some specific including marketing and communications, risk
challenges due to climate, the nature of the loads and management and rate structures are also covered.
the pace of development.
Chapter 4 - Design Process and Key Issues covers
The guide is not a set of standards, nor isit an encyclopedia essential pre-design tasks with enormous cost and risk
covering every detail of district cooling systems or a implications, suchas load estimationand the fundamental
detailed design and specification guide. Rather, it is design parameters that have significant technical and
intended to share insights into key design issues and cost implications for all elements of a district cooling
"lessons learned" from the recent development and system, such as design supply and return temperatures.
operation of district cooling systems, particularly in the It also suggests approaches to master planning complex
Middle East. district cooling systems and the critical and often-difficult
topic of obtaining permits to develop the district cooling
It is important to emphasize that "best practices" will system. The challengesand opportunities of integrating
vary depending on a wide variety of case-specific district cooling system planning and design with other
conditions, including infrastructure are discussed. This chapter closes with an
.seasonal and daily load characteristics; emphasis on the importance of designingwith long-term
.type of cooling load and any special reliability operation and maintenance in mind, consistent with
requirements(e.g., hospitals, computer servers, etc.); the philosophy that successful district cooling systems
• size of plant site and anyconditions or constraints must be approached as a utility business.
relating to the site (height restriction, air emissions,
noise sensitivities of neighbors, etc.); Chapter 5 focuses on building cooling system design
.availability and prices of electricity, water and and energy transfer stations or ETS (interface
natural gas; between the distribution system and the building).
• local codes and regulations;
• underground conditions affecting pipe installation; Chapters 6 and 7 address district cooling distribution
• organizational resources; and systems and plants.
.financial criteria and strategic goals of the district
cooling company. Although these discussions may appear to be presented
out of order, this structure was deliberately chosen for
The intention of the District CoolingBestPractice Guide several reasons. First, satisfaction of comfort require-
is to address the advantages and disadvantages of ments is the ultimate business and technical purpose
design options, discuss the circumstances under which of district cooling systems, so success is not possible
without good design on this end. Second, the
a given option may be the best approach and suggest
approaches to determining the optimal approach once
economic performance of district cooling systems is
dependent on sound performance of building systems,
key factors affecting a specific case are known.
particularly delta T (temperature difference between
supply and return). The economic implications of delta
The International District Energy Association envisions
T are large and pervasive.
this guide will be updated periodically as technologies
and the district cooling industry evolve.
Chapter 8 - Controls, Instrumentation and Metering
ties the ETS, distribution and plant systems together.
1.2. Overview and Structure
of the Guide The guide concludes in Chapters 9 and 10 with
discussions of options for project procurement, deliv-
The next chapter, Chapter 2 - Why District Cooling?, is ery and commissioning.
a review of the rationale for district cooling, including
its benefits for customers, governments and the A summary of abbreviations and definitions and a list of
environment. It is useful to review the drivers behind conversion factors are provided as appendices. A vari-
the establishment of district cooling systems so that ety of units are used in this document, consistent with
discussion of business and technology best practices practices in the Middle East.
relate to the key reasons such systems are developed.
DISTRICTCOOLING BEST PRACTICE GUIDE
e2008 InremaliooalDi5ln'd Energyk:5ociarioo. Ai!nghl5 reserved.

2. Why District Cooling?


District cooling is being implemented worldwide by it is attractive to be able to provide reliable comfort
many different kinds of organizations, including without worrying about managing the equipment,
investor-owned power utilities, government-owned labor and materials required for operating and main-
utilities, privately owned district energy companies, taining chiller and cooling tower systems. This allows
universities, airports and military bases. District cooling the manager to focus resources on more critical
systems serve a wide variety of types of buildings, bottom-line tasks, suchasattracting and retainingtenants.
including commercial offices, residential, hotels, sports
arenas, retail stores, schools and hospitals. 2.1.3 Flexibility
The pattern and timing of cooling requirements in a
District cooling is growing rapidly for many reasons, building vary depending on building use and weather.
including With building chiller systems, meeting air-conditioning
• increasing demand for comfort cooling, due to requirements at night or on weekends can be difficult
construction of many new buildings that are and costly, particularly when the load issmall. With district
"tighter" than older buildings and contain more cooling, these needs can be met easily and cost-effec-
heat-generating equipment such as computers; tively whenever they occur. Each building can use as
• a growing trend toward "outsourcing" certain op- much or as little cooling as needed, whenever needed,
erations to specialist companies that can provide without worrying about chiller size or capacity.
these services more efficiently;
• reductions in peak electricity demand provided by 2.1.4 Reliability
district cooling; The building manager has a critical interest in reliability
• environmental policies to reduce emissions of air becausehe or she wants to keep the occupants happy
pollution, greenhouse gases and ozone-depleting and to avoid dealing with problems relating to main-
refrigerants; and taining comfort. District cooling is more reliable than
• most important, the customer value provided by the conventional approach to cooling because district
district cooling service in comparison with conven- cooling systems use highly reliable industrial equipment
tional approaches to building cooling. and can cost-effectively provide equipment redundancy.
Staffed with professional operators around-the-clock,
district cooling companies are specialists with expert
operations and preventive maintenance programs. A
survey conducted by the International District Energy
Association (IDEA) shows that district cooling systems
have a documented reliability exceeding 99.94%,
2.1 Customer Benefits which issignificantly more reliable than individual building
When properly designed and operated, district cooling cooling systems.
systems cost-effectively deliver a variety of benefits to
customers, including superior comfort, convenience,
flexibility and reliability.

2.1.1 Comfort
Comfort is the ultimate purpose of air conditioning.
District cooling systems can help keep people more 2.1.5 Cost-effectiveness
comfortable because industrial-grade equipment is
used to provide a consistent and high-quality source of Fundamental cost advantages
cooling. In addition, specialist attention is focused on
optimal operation and maintenance of cooling systems District cooling has numerous fundamental cost
- providing better temperature and humidity control advantages:
than packaged cooling equipment and, therefore, a
healthier indoor environment Buildings are quieter Load diversity
because there isno heavyequipment generating vibration Not all buildings have their peak demand at the same
and noise, making tenants happier and allowing them time. This "load diversity" means that when cooling
to be more productive. loads are combined in the district cooling system, more
buildings can be reliably served at lower cost
2.1.2 Convenience
District cooling is a far more convenient way to cool a Optimized operations
building than the conventional approach to air condi- With district cooling, equipment can be operated at the
tioning because cooling is always available in the most efficient levels, whereas with building cooling
pipeline, thus avoidingthe needto start and stop building equipment, the units operate for most hours each year
cooling units. Fromthe building manager'sstandpoint, at less-than-optimallevels.

2
DISTRlcr COOUNGBEST PRACTICE GUIDE
02008Inh?mational Diwid Energy AAoda~On. All righ~ fe5erved.

Advanced technologies system are generally very low, encompassing piping,


District cooling also offers economies of scale to valves, controls and, in many cases, a heat exchanger.
implement more efficient and advanced technologies, Some district cooling utilities require the customer to
such as pay for the cost of extending pipe from the nearest pipe
• thermal energy storage (TES), which can further main to the building, while other utilities cover this cost
reduce peak power demand, save energy, enhance so that the customer pays only for the piping, valves
reliability and reduce capital expenses for both the and ancillary equipment inside the building wall,
utility and its customers;
• natural gas-driven chillers; With district cooling systems that distribute water at a
• integration with wastewater treatment infrastructure lower-than-normal temperature (such as is possible
through use of treated sewage effluent (TSE) for with ice thermal energy storage or freeze-point
condenser cooling; and depressant chemicals), it is possible to further reduce
• use of seawater for condenser cooling, either for building costs. This is because such systems enable
makeup water in cooling towers or for direct reductions in the size of fans and ducts due to the
condenser cooling. reduced temperature of air produced in air-handling
systems.
Better staff economies
District cooling cost-effectively provides around-the- Annual costs
clock specialized expertise to operate and maintain the District cooling service allows the building manager to
equipment required to reliably deliver building comfort. eliminate the annual costsof operating and maintaining
a building chiller system, including
Customer risk management • electricity,
• scheduled annual maintenance,
For the real estate developer, district cooling systems • periodic major maintenance,
reduce capital risk because no capital is tied up in the • unscheduled repairs,
building for cooling equipment. Operating risks associated • refrigerant management,
with operation and maintenance of building cooling • spare parts,
equipment are eliminated, with more predictable costs. • labor and
ln a competitive real estate market, buildings that • management oversight.
consistently.provide superior comfort will attract and
keep tenants and maintain a higher market value. Poor lt isalso appropriate to account for the opportunity cost
indoor comfort is a primary reason for tenants to leave of the income or amenity value of the building area or
a building or not renew a lease. District cooling rooftop used for equipment. For example, if building
providestechnical benefits that mitigate [ass of tenants. chillerswould be located within the building, this space
might othervvise be rentable (even for storage space),
thereby generating revenue. Space used for roof-
mounted chillers or cooling towers could instead be
used for tenant amenities such as a swimming pool.
Chillers located on the ground take up space that could
be used for parking.
Cost comparison
The costs of the conventional approach to cooling
Further discussion and guidance regarding presentation
involvefar more than the cost of electricity, as described
of cost comparisons is provided in Chapter 3.
below.

Capital costs 2.2 Infrastructure Benefits


By choosing district cooling service, a building avoids a
large capital investment for the total installed capital 2.2.1 Peak power demand reduction
costs of a building chiller system, including The benefits that district cooling offers relative to power
• construction cost of space for equipment; demand and annual energy are key advantages of the
• chiller and condenser cooling equipment; technology. Chiller equipment in the Middle East is
• pumps and controls; typically subject to a difficult operating environment,
.power utility connection fees and/or substation including extreme heat, windborne sand and saline
construction, asrequired; humidity. Equipment performance will degrade as the
• transformers and cables; system ages, particularly if there is not an aggressive
• engineering services; and maintenance program. Over time, the performance,
• replacement capital costs. efficiencyand reliability of this equipment suffers, leading
to high electricity demand, maintenance costs and,
Capital costsfor a building to connect to a district cooling ultimately, to the need for equipment replacement.

3
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lnrematiOl1al Dis!nCt Energy Association. AllrightsreselW'd.

proper accounting of the total cost of power must


include not only fuel and other operating costs, but also
the cost of amortizing the capital to build power plants
and deliver the power to customers.

Figure 2-1 summarizes representative peak electric


demand efficiencies of several major types of district
cooling systems and compares them with representative
peak demand of conventional air-cooled systems.
District cooling reduces power demand in new devel-
opment by 50% to 87% depending on the type of district Capital costs of power capacity
cooling technology used.
New power generation capacity in the Middle East is
typically large [more than 250 megawatts (MW)]
2.00
combustion turbine combined-cycle plants that use
'2 1.75 byproduct steam for desalination. Capital costs for
s power plants have increased dramatically since2005 for

~ 1.50 a variety of reasons, including significant increases in
~
0
1.25· materials costsand a very tight international market for
c qualified contractors, Through 2009, the estimated unit
•E 1.00

0
cost of power generation capacity is US$1,067 per
~
0
0.75
kilowatt (kW). In addition, substantial investment must
~ be made in transmission and distribution (T&D)facilities
•• 0.50 including substations. The estimated average costs of
c•,
T&D infrastructure is US$296/kW, for a total generation
0.25
and T&D cost of US$1 ,363/kW.
0
Air-cooled District District District District
building cooling cooling cool1ng cooling (50% Power sector operating costs
systems (electric) (electricwilh (100% gas- gas-fired with
TES) fired) TES)
Table 2-1 summarizes operating cost factors for a new
Figure 2-1. Peak power demand reductions with combined-cycle power plant. New combined-cycle
district cooling. power plants can reach maximum operating efficiencies
of more than 55% under ISO conditions (16 C or 60 F)
A straight centrifugal chiller plant will cut peak demand outdoor air, 60% relative humidity and 1 atmosphere
(comparedwith the conventional air-cooled approach)by barometric pressure (14.7 psi). However, combustion
about 50%. The impact of thermal energy storage (TES) turbine power output drops significantly asthe ambient
depends on the peak day load profile of the aggregate air temperature increases. For Middle East conditions,
customer base. The graph illustrates a representative combined-cycle generation efficiency is projected to be
situation in a mixed-use development in the Middle East, 48.4% [heat rate 7050 Btu/kilowatt-hour (kWh)]. With
in which TES reduced the peak power demand of the estimated T&D losses of 7.0%, the net (delivered)
district system by about 20%. Natural gas district cooling efficiency is 45.0%.
can provide even more dramatic reductions in power
demand. As discussed in Chapter 7, engine-driven chillers With variable operation and maintenance (O&M) costs
are the most cost-effective gas-driven approach. Figure of US$2.13/megawatt-hour (MWh), fixed O&M costs
2.1 shows the peak power demand of two gas-driven of US$12.93/kW and a capacity factor of 0.60, the
options: 100% gas-driven without TES and a hybrid in average non-fuel O&M cost is US$4.59/MWh.
which 50% of the capacity is gas-driven, 40% is
Power plant heat rate 7050 Btu/kWh
electric-driven and 10% is TES.
Generation efficiency 48.4%
2.2.2 Reduction in government Transmission/distribution losses 7.0%
power sector costs Net efficiency 45.0%
District cooiing reduces the capital investment required Variable O&M 2.13 US$/MWh
for additional power generation, transmission and
Fixed O&M 12.93 US$/kW
distribution infrastructure. District cooling also reduces
power sector operating costs. Because power costs are Capacity factor 0.60
typically subsidized in the Middle East, district cooling Average non-fuel O&M cost 4.59 US$/MWh
saves governments substantially both in capital invest- Table 2-1. Combined-cycle power plant operation
ment and in operating subsidies. In the long run, a cost factors.

4
DISTRlcr (OOUNG BESTPRAcrlCE GUIDE
e2008 lt1remaUonal DiS!fiaEt1f!i9y Am'(;aUon.All right>re5efVed,

30

25
V
20
V
~ /'
~
~ 15
/'
Fuel for power generation may be natural gas or oil
depending on available resources. Although a state-
owned power utility may buy fuel very cheaply from a

~
~
0.
10
/'
/'
::> ,/
state-owned company, it is worthwhile to reflect on the /'
./
opportunity cost of using that fuel to produce power to 5
./
run inefficient chillers. Certainly, oil could instead be
/
1/
sold at the increasingly high international price. (See 0
Figure 2-2.) Figure 2-3 illustrates the conversion of oil
prices from u.S. dollars per barrel to u.S. dollars per
~ ~ l),~ '!>~ Il? ':P r§> '\~ * c§>.sP . . ~ ~ ¢~ .:P ,&
US$ per barrel ofoil
million Btu. The same data is shown in tabular form in
Table 2-2. Figure2-3. Oil prices in US$ per MMBtu.

160 US$ per barrel of US$ per million Btu


oil equivalent (BOE) (MMBtu)
140 0 0
10 1.72
120 20 3.45
·0 30 5.17
~
0 100 40 6.90
~
:; 80 I~ 50 8.62
.0
60 10.34

..'"
••
c,

::>
60
I,P
IJ J
'J.{
70
80
90
12.07
13.79
15.52
40 100 17.24
,.I' r¥
fi ~ 18.97
'" v\
110
20 IY 120 20.69
rw- 130 22.41
0 140 24.14
..,
eo
% %
0>

~ '"
0

~ '"
~
~

'I
~ "' '"in ....'I
~
0
eo
0 150 25.86
, ,j! , , , ,0> , , , , 0> in
Table 2-2. Conversion of fuel prices in US$ per barrel oil
« « « -c « « « « -c ,j! equivalent (BGE) to US$ per MMBtu.
Figure 2-2. World oil prices during the past 10 years.
Long-term infrastructure choices made by Middle Eastern
governments should be made based on the recognition
that, although power generation fuel can be "priced"
internally at a low level, the value of that energy will be
significantly higher. In other words, there will be an
increasing "opportunity cost" associated with using
If natural gas is the power generation fuel, it also has available naturalgasfor power generation insteadof using
an international market value to an increasing extent. it for higher value uses or exporting it as LNG.
Natural gas demand is growing worldwide, driven by
rapidly growing energy requirements in China, India Natural gas or LNG pricesare frequently tied to oil prices.
and other developing nations, continued growth in Figure 2-4 shows the projected impact of changes in oil
industrialized countries and declining domestic reserves prices on the price of delivered LNG, based on extrapo-
in the u.s. The natural gas market is becoming a lation from analysis of historical price data.'
competitive, market-driven sector with a trend toward
liquefaction and export. These trends mean that the As illustrated in Figure 2-2, oil pricesjumped substantially
market price for natural gas will trend upward as it between early2007 and mid-2008. As this report goes to
becomesan increasingly tradable commodity asliquefied print, world oil priceshave pulled back from the highs set
natural gas (LNG) in international markets. in July 2008. However, in the mid-term (2010-2015), the

5
DISTRICT COOLING BEST PRACTICE GUIDE
e2008Infema(ional DiWictEnergy A550cialion. Alln'ght> re5efVed.

price floor is likely to exceed US$140/barrel. Based on


Figure2-4, delivered LNG prices can be expected to seek
a mid-term levelof US$9/MMBtu to US$18JMMBtu,with
an averagevalue of US$13.50/MMBtu.

Excluding the costs of liquefaction, transportation and


regasification, the estimated average "opportunity
cost" of natural gas in the mid-term is US$9/MMBtu,
equivalent to about US$50/barrel of oil equivalent
(BOE). In other words, this is the lost revenue if gas in
hand is burned instead of sold into the LNG market and
is an appropriate basis for long-term valuation of fuel
used in Middle Eastern power plants.

In discussion of fuel prices, prices are referred to in


terms of dollars per BOE, or the cost of the energy in
one barrel of oil. Conversion of fuel prices between U.S.
dollars per BOE, U.S. dollars per MMBtu and BOE per
MMBtu is summarized in Table 2-2 shown earlier.
$20 $2S $3a $40 $5a $6Cl $70 $all $90 $100
Power plant fuel (US$ per barrel 01equivalent)

$30
Figure 2-5. Long-run marginalcosts of delivered electricity
~
:; from new combined-cycle plant at a rangeof fuel prices.
:; $25 - -High factor of 60% was assumed. Capital costs were amortized
..
~
~
Co
$20
, " ....... -Average
assuminga weighted average cost of capitalof 8.7% over
a 20-year term, based on 70/30 debt/equity ratio, 6.0%
• $15 , ",
• • • Low debt interest rate and 15.0% return on equity.

,",'... ... . .....


0
.§. ",
oz ",
$10 Power utility recognition of district cooling benefits
-'
"~ • Governments throughout the Middle East are grappling
$5
~ with the challenge of meeting rapidly growing power
0;
c $0 demands. While district cooling is viewed as beneficial in
$80 $100 $120 $140 $160 $180 $200 this regard, there is generally no recognition of its benefits
in the structure and levels of power tariffs. Most power
Oil price (US$ perbarrel) rates continue to be subsidized and generally do not
incorporate incentives to reduce peak power demand.
Figure 2-4. Projected impact of oil priceon price of
delivered liquefied natural gas.
Total costs of electricity

Governments cannot make good decisions about


allocating capital and natural resources unless all of the
long-run marginal costs of generating and delivering Power utilities in North America, Europe and other
power are considered, including amortized capital and regions often encourage peak power demand reduction
the market value of fuels in the context of long-term through the rate structure or with special incentives.
world energy prices. Examples of this include the following:
.A portion of the cost of service, particularly for large
Figure 2-5 shows the long-run marginal costsfor electricity users, may be paid in a demand charge (or capacity
in the Middle East under a range of fuel cost assumptions. charge).
"Long-run marginal costs" are the total costsof providing • Rates during the high-load summer season are
an additional kilowatt-hour of energy output over and often set above the rates for other parts of the year.
above any energy currently being produced, and they • Rates during high-load times of day are higher
include all capital and operating costs. Thesecalculations than low-load periods (time-of-day rates).
reflect the total costs of building and operating highly • Utilities sometimes provide a capital incentive to
efficient new combined-cycle power plants and power install technologies such as thermal energy storage,
transmission and distribution infrastructure, based on the which is tied to the number of kilowatts of peak
capital and operating costs discussed above. A capacity demand reduced.

6
DISTRICTCOOLING BESTPRACTICE GUIDE
C2008 InremaUonal Dismcr Energy A55fxiab'on. Allnghl5 re~.

Use of demand charges, seasonal and time-of-day rates ~


2.00
anddemand reduction incentives betterreflects the actual ~
cost of service and gives appropriate "price signals" to s 1.75
8-
users, leading to optimaluse of capital andfuel resources.
i& 1.50

In a competitive electricity market, costs of power c


1.25
production can varysignificantly from day to night, and ~c
0
;;. 1.00
thisisreflected in market-based powerrates. For example,
E
prices from the New England Hourly Electricity Price Index ~ 0.75
are shown as bars in Figure 2-6, measured against the 80
scale on the right (in US$/kWh). Not surprisingly, the B 0.50
g
highest prices occurin the periodof highest demand (as
indicated by the curved shaded area).
..,
'a

c
0.25

~
Air-cooled District District District District
The bottom line is thatthere are sound economic reasons buildll\{i cooling cooling cooling cooling (50%
to structure power rates to better reflect actual costs, and systems (electric) (electricwilh (100%gas- gas-fired with
that doing so will increase the value of district cooling TESI fired) TES)
generally andTES in particular.
Figure2-7. Annual electric energy consumption savings
with districtcooling.
$0.70
""
... saee A substantial portion of energysavings results from the
fact that almost all district cooling systems use water
... ~.~
to cool the chiller condensers, an inherently more efficient
~
, . $0.40
~
:t
,
process than air cooling. District cooling systems are
increasingly being designed so that no water isrequired
, . ~.~

'01'
from the municipal water system. Instead, these
systems employ a variety of technologies, such as
~o
$D.l0
• using seawaterto cool the condensers directly(the
water actually runs through the chillers),

...
0 $D.oo
• using seawater for cooling tower makeup,
,,~ ~ /'

..... ~;f'
il"'
.conditioning water by reverse osmosis desalination
"
for use in cooling towers and
Figure 2-6. Example of time-of-day power rates compared .using treated sewage effluent (TSE) for cooling
with power demand, per New England Hourly Electricity
tower makeup.
Price Index.

2.3 Environmental Benefits District cooling's superior energy efficiency results in


reduced fuel consumption, with corresponding reductions
District cooling can help the environmentby increasing in emissions of air pollution and C02 (the greenhouse
energy efficiency and reducing environmental emissions, gas that causes global warming).
including air pollution, the greenhouse gas carbon dioxide
(C02) and ozone-destroying refrigerants. 2.3.2 Climate change
Most Middle East countries are parties to the United
Nations Framework Convention on Climate Change.
With growing international interest in strong action on
climate change, and with generally high emissions per
capita in the Middle East, climate change will become
an increasingly important issue for the Middle East
governments.
2.3.1 Energy efficiency
Figure 2-7summarizes representative annual electric energy TheKyoto Protocol, an international agreement to control
efficiencies of several majortypes of district cooling systems greenhouse gas emissions, isexpected to be replaced by
and compares them with a representative annual efficiency a more aggressive treaty with broader participation. It is
of conventional air-cooled systems. District cooling reduces widelyexpected that future international agreements will
annual electricity consumption in newdevelopment by45% lead to worldwide greenhouse gas emissions trading, po-
to 86% depending on the type of technology used. Note tentially providing economic incentives for energy-effi-
that although gas-driven district cooling drastically reduces cient technologies such as districtcooling. The ultimate
electricity consumption, these systems require the cost of allowances will depend on manyfactors, includ-
consumption of natural gas at the plant. ing the level of greenhouse gas reduction commitments

7
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lnremaUonal Distrid Energy A55ociab'OI1. Allright> re>erVed.

and the specific rules of the "cap-and-trade" programs. International agreements phased out the production of
A number of corporations are using "shadow prices" CFCs as of January 1996 and have scheduled the
(an assumption of C02 emissions cost for the purpose phaseoutof hydrochlorofluorocarbon(HCFC) refrigerants.
of comparing options) of at least US$g/metric ton. Hydrofluorocarbons (HFCs) and ammonia, which are
Prices inthe European Union emissions trading system, also used as refrigerants, are not restricted by interna-
still in the beginning stages of implementation, averaged tional protocols.
US$25/metric ton of C02 equivalent in 2006, spiked
to almost US$40 in early 2006, then tumbled to US$12 District cooling can be a key strategy for accomplishing
later in 2006. Some studies conclude that an emissions an economical and environmentally wise phaseout of
value of US$l OO/metric ton will be required to bring harmful refrigerants. Through their better staffing and
greenhouse gas emissions down to a safe level.2 operational practices for monitoring and control,
district cooling systems are better able to control
emissions of whatever refrigerant is used.

1 "A Formula for LNG Pricing," Gary Eng, December 2006.


2 "Stern Review on the Economics of Climate Change,"
Nicolas Stern, Oct. 30, 2006.

2.3.3 Ozone depletion


Chlorofluorocarbon (CFC) refrigerants used in chillers
destroy the stratospheric ozone layer.The ozone layer's
destruction is of serious international concern because
this layer protects the earth from harmful ultraviolet
radiation which can cause human health and environ-
mental damage, including increased incidence of skin
cancer, cataracts, immune system suppression, damage
to crops and other impacts. CFCs and some other
refrigerants also act as greenhouse gases.

8
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lnlffll<3bonal Disrnet Energy AssociaD'on. All rig~ts resened.

3. Business Development
3.1 District Cooling as a 3.1.2 Organizational design
Utility Business A good engineering design does notensure success unless
the organization is designed and is operated to achieve
It is critically important to emphasize that the design, customer satisfaction. A basic issue is the degree to which
development andoperation of asuccessful district cooling the corporate culture of the district cooling company is
system must be approached as a long-term utility truly customer-focused. Success will require a different
service business. If it is approached primarily as a culture than might have existed within a company that
contractinq job, with a focus on lowest first costs and traditionally simply construded facilities orsold a commodity.
without sufficient consideration of life-cycle costs and
customer satisfaction, the actual return on investment
for the district cooling company will fall short of
expectations. Best practices therefore involve not only
good engineering design, but also good organizational
design. Note also that, relative to engineering, business
and organizational design, it is imperative that district
cooling utilities work with customers (technically and All staff should consider customer satisfaction part of
contractually) to optimize their designs and operations their job description. This orientation should extend
for compatibility with district cooling service. beyond the marketing team to everyone in the district
cooling company, particularly those who have direct
contact with customers, such as accounting people,
meter technicians, etc. Ongoing training is recom-
mended to ensure that all staff view themselves asbeing
in the customer satisfaction business - and that they
send the message to the customer that theyare eager to
understand and solve customer problems. Strong lead-
ership, expert assistance andstaffdevelopment can bekey
3.1,1 Engineering design elements in strengthening the corporate culture.
A focus on district cooling asa long-term utility service
affectsthe design process and design criteria in a number The responsiveness of the district cooling company to
of ways. For example: customer needs or problems is critical to the company's
• Thefoundation of the design should bethe customer success. The prospective customer must be confident
requirements, and the design process should then that the company will do what it takes to ensure the
proceed "upstream" to the pipingand plantsystems, delivery of cooling to the building. Then, once that
ratherthan the other way around. The entire design, customer is connected to the system, the company
including controls, should focuson ensuring achieve- must justify the customer's confidence by providing
mentof the ultimate goal: consistent, reliable comfort excellent service. Increasingly, districtcooling companies
in customer buildings. are also offering customer service past the building
• Building the plantand distribution systems isonly the boundary - helping the customer implement and
first step, and operational costs and reliability operate improvements to the building system so that
ultimately become critical considerations. Operation cooling that is reliably delivered to the building and is
and maintenance (O&M) issues should beconsidered also efficiently distributed within the building. Opti-
from the beginning of the design process, and O&M mization of the building HVAC system can improve
staff should be involved in the design process. both delta T and occupantcomfort.
• Design options mustbeevaluated based on life-cycle
costs and high reliability. 3.2 Marketing and Communications
• Focus on long-term reliability affects design relative
to equipment redundancy. ease of maintenance and Successful district cooling business development
speed of response in the event of equipment failure. requires focused and effective communication with
potentialcustomers and other keystakeholders, such as
the government. It isessential to appropriately position
district cooling service and clearly communicate the
value proposition to customers, to government and to
society asa whole.

3.2.1 Positioning
These engineering design considerations are addressed in Successful marketingof district coolingservice requires
upcoming chapters on design of building connections, educating prospective customers regarding the full
piping systems, plants and controls. value of the technology. An essential first step is to

9
DISTRICT COOUNG BEST PRACTICE GUIDE
Cl2Q08 intema~onal Dilma Energy As>OCialion. All rightsreseM'd.

position district cooling as the option that delivers a


District cooling makes it easy. unique combination of benefits and most cost-effectively
• Increased comfort provides the greatest total value. In other words, in all
• even temperature communications - verbal, marketing materials, adver-
• better humidity control tising, presentations, etc. - the emphasis should be on
value and performance before price.
• healthier building
.Quieter building, less vibration
This is not to say that price is unimportant. A critical
• Convenient service - always available element in marketing and selling district cooling is
• Flexibility to increase or decrease capacity presentation of the total value of district cooling and
• Free uptime to focus on primary business comparison with the costs of other options. This
comparison should not be framed as a question of
District cooling reduces risks. "Which option costs less?" Instead, the question
should be, "Which option delivers the greatest total
o Less capital tied up in building
value most cost-effectively?"
o More predictable costs
• Less price risk as power sector is restructured 3,2,2 Customer value proposition
• Noconcerns regarding refrigerant costs and
management Value proposition summary
o Increased building value
A bulleted summary of the customer value proposition
is presented in Table 3-1. Customer benefits are described
District cooling enhances reliability.
more fully in Chapter 2.
o Highly reliable industrial units
oSophisticated controls
• Professional operators round-the-clock
• Preventive maintenance
o Equipment redundancy

District cooling has cost advantages.


Building chiller system efficiency
oDiversityin building loadsreduces costs
oBetter equipment loading = better efficiency Estimation of building chiller system electricity peak
• Economies of scale to implement advanced demand and annual electricity energy consumption in
technologies the cost comparison deserves note. Consistent with the
discussion in section 2.2.1 regarding power require-
• Better staff economies
ments of building chillers, the peak power demand for
• Diversity of equipment can minimize price risk building chiller systems should be calculated based on
peak ambient temperature conditions and should be
Costs of owning and operating building chiller adjusted for performance degradation over time.
systems far exceed the costs of electricity. Annual electric energy consumption should be based
olnitial capital costs on weighted average temperature conditions and
should also be adjusted for performance degradation
oOpportunity cost of income or amenity value of
due to the difficult operating environment in the Middle
the building area or rooftop used for equipment East. Manufacturer data for brand-new equipment
oScheduled annual maintenance operating under ideal conditions is not an appropriate
• Periodic major maintenance basis for estimating the efficiency of building chiller
oUnscheduled repairs equipment since the specified operating situation
oSpare parts seldom occurs in real life.
o Equipment replacement
Structuring the cost comparison
o Labor
• Management oversight The costs of district cooling can be compared with
oElectricity building chiller system costs in a number of ways. The
• Water and wastewater fees simplest approach is to compare the total annual costs
• Refrigerant management based on current operating cost factors and district
cooling rates. In such a comparison, the capital costs
Table 3-1. Summary of customer value proposition. must be converted into an annual amortization cost. It

10
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 IntemaUonal Di5rrid Energy Assodation Allrights teSM'ed.

is important in choosing the amortization factor to To further reinforce the real estate analogy, it is helpful
makeit consistent with the developer's actual weighted to communicate using real estate terms, including expres-
average cost of capitallyVACC) andwith a termconsistent sion of costs in terms of cost persquare meter orsquare
with the realistic lifeof the building chiller equipment. The foot of building space.
WACC can be calculated as follows:

DR = Ratio of debt to total capital 3.3 Risk Management


ER = Ratio of equity to total capital
DIR = Debt interest rate 3.3.1 Nature of district cooling company
ROE = Targeted return on equity Any business involves risk, and the district cooling busi-
ness is no different. Of course, the risks varydepending
WACC = (DR x DIR) + (ER x ROE) on the nature of the district cooling company and its
customers. For example, a developmentcompany may
So, for example, if the DR is 0.70, DIR is 7.5% and ROE establish a district cooling company to serve its projects,
is 15%, the WACC is 9.75%. and this parent corporation may assume some key
financial risks. On the other hand, a merchant district
The term used for the amortization factor applied to cooling company, serving multiple customers with
building chillersystem capital costs should be consistent different ownership, must pay especially careful atten-
with the realistic expected life of the equipment. With tionto risk management.
the harsh operating conditions in the Middle East (high
heat, dust and saline humidity), equipment lives are Ultimately, each district cooling company mustdetermine
shorterthan indicated by the 2005 ASHRAE Handbook what risks it is willing and able to accept based on its
- Fundamentals. strategic goals, financial objectives and financial resources.

The disadvantage of a simplified annualcostcomparison 3.3,2 Capital-intensiveness


is that it does not account for potential variations in Development of a district cooling system is a relatively
escalation of operating cost factors for building chiller capital-intensive undertaking. Further, capital costs are
systems or for district cooling. This can be addressed "front-loaded" because of the high costs of installing
with a multi-year net present value (NPV) analysis in basic plant infrastructure and pipe mains in the early
which costfactors areescalated based on projections or years - in contrast to adding customers in later years
contract escalation allowances. If a multi-year analysis with relatively short, small-diameter pipe additionsand
is undertaken for a period longer than the expected life the installation of additional chillers in the plant. Given
of the building chiller equipment, it is essential to these characteristics, a fundamental riskin development
include not only the initial capital costs of the chiller of a merchant district cooling system is lower-than-
system but also the costs of equipment replacement projected customer load.This maybe due to a low level
over time. of success in marketing to targeted customers, or as a
result of slower-than-projected buildout of development
Communicating with prospective customers by customers and/or masterdeveloper.

Ineducating prospective customers about district cooling,


3.3.3 Will visions be realized?
it isuseful to helpthem understand the essence of district
Throughout the Gulf region, very ambitious development
cooling as a business as well as a technology. To this
projects are announced on a seemingly daily basis. The
end, it can be helpful to communicate district cooling's
prefix "mega" isfrequently used. Many projects envision
similarities to the real estate business. Both real estate
a buildout of a massive mixed-use developmentover a
development and district cooling typically require pre-
numberof years, starting with an often highlyaggressive
subscription to support financing and benefit from
schedule for the first phase. Yet development projects
long-term customer contracts. The district cooling service
very frequently experience delays in getting the initial
contract islike a real estate lease - demand charges are
phase completed. This problem has increased due to
like base rent and energy charges are like operating
the large numberof "mega" projectsin the regionand
costs. Both are capital-intensive, with capital costs
the resulting competition for materials, equipment and
front-loaded. Targeted returns are achieved when the
contractors. Thus, in the short term, schedule creep is
building (or district cooling system) is fully subscribed.
almost a certainty. In the long term, the reality is that
there is a limited ability for the marketplace to absorb
newspace on a sustainable basis, and master developers
cannot besure thattheir long-term visions will berealized.

In negotiating service agreements, the district cooling


company should agree to no morerisk than the developer

11
DISTRICT COOLING BEST PRACTICE GUIDE
02008 In!emati(lnal [)jjrrictEnergy Association. Allrights reserved.

is accepting so that, in the event the building is not fully data on underground service locations is lacking, safety
sold out the district cooling company isnot then holding margins should be incorporated into the construction
"stranded" investments that can't be paid in the budget. In addition to congestion, underground soil
absence of building occupants. conditions can present surprises for the pipe installer.
Excessive sand will require additional and unplanned
support, while rocks could slow the installation process.
Soil samples in advance of the installation help to
mitigate surprises.

Community relations
Construction of the district cooling distribution system
often results in disruptions that can pose public relations
3,3,4 District cooling company risks risks. The inconvenience of restricted traffic and real or
imagined harm to downtown businesses can lead to
Stranded capital negative feelings among the public, downtown
businesses and the city government. Going the extra mile
Despite the lack of certainty regarding realization of to proactively address potential concerns will pay many
long-term real estate development plans, district cooling dividends. Best practices include these proactive steps:
companies are expectedto design and installinfrastructure oComrnunicate early and often with the potentially
to meet both the short- and long-term requirements. affected parties (building and business managers,
Avoiding district cooling revenue shortfalls if the master city government and the general public).
developer's buildout dreams are not realized requires oInclude affected parties in planning to the
careful attention to ensuring that contracts with master extent possible.
developers and customers mitigate the district cooling oBe accessible, responsible and accountable.
company's risks that infrastructure capital will be • Be aware of upcoming street repairs and closures.
stranded by a delay in buildout or a reduction in the
development's ultimate size.One way to accomplishthis General construction issues
isto ensurethat fixed-capacitychargesare consistentwith As with any other facility construction project, there are
actualdistrictcooling investmentcosts asthe system isbuilt risks associated with unforeseen conditions, accidents
out, rather than the long-term capacity costs per ton ap- or contractor performance, which can lead to higher
plied to the relatively low-ton load in the near term. costs, delayed completion or quality control problems.
Addressing these risks is fundamentally no different
Temporarychillers than other facility construction-related risks. Forexample,
best practices include
All toofrequently, some customers require cooling service .using reputable contractors and vendors under
before a permanent district cooling plant can be built. strong contracts;
Temporary chillers are expensive to operate, particularly o implementing a thorough procedure of pre-operational
if, as is often the case, there is no power available so equipment and system checks, integrated with the
that power generation with engines must also be construction process;
provided to run the temporary chillers. If completion of • being sure to identify who is responsible for risk issues
the permanent plant and related distribution piping is as well as delaysand addressing unforeseen events;
delayed, the district cooling company must operate this oestablishing a reliable and effective communications
expensive capacity for a longer period. This possibility plan and documentation system; and
highlights the importance of being conservative in oaddressing passivationof piping systems that transport
projecting the time required to complete the permanent the district cooling water, up to and including heat
facilities and eliminating, or at least limiting, the district exchangers.
cooling company's liability to absorb high operating
costs for temporary chiller plants. Following best practices is especially criticalfor distribution
system construction because this is a more specialized area
and the cost of rectifying problems is high.
Construction risks

Underground congestion Revenue generation risks


Since underground construction is a key element in
developing district cooling systems, a significant risk is Inadequate chilled-water delivery
higher-than-anticipated costs due to unforeseen Poor comfort control is a revenue generation risk because
congestion in underground services already in the a hot customer is not paying for all the cooling that it
street. Underground obstacles should be considered needs. It is important for district cooling utilities to
early in the planning process. To the extent that good understandthat good control of supply-watertemperature

12
DISTRICT COOliNG BEST PRACTICE GUIDE
e2008 Inteman'OfIilI Dlstn'd Energy Assooatiol]. Alltights 1E5er.ed.

inside customer buildings isthe keyto this. Froma business rates (sometimes called energy rates). Connection
standpoint, it is critical to provide customers with water chargesmay also apply, depending on the application and
cold enough on the building side of the energy transfer economic requirements of the utility and its customer.
station (ETS) to provide all of the required cooling.
The district cooling company may own part or all of the
ETS equipment The ETS is the contractual energy transfer
point and physical boundary between the provider and
customer's equipment.

3.4.1 Capacity, consumption and


connection rates
Delays in connecting buildings
Initiation of district cooling service requires timely action Capacity rates
not only by the distrid cooling company, but also by
customers, who must connect their building systemfor Capacity rates are charged to recover some or all of the
interface with the district loop. As a result, there are risks district cooling provider's fixed costs (i.e., debt service,
of reduced revenues due to delays in connecting build- depreciation, labor, administration). fixed costs generally
ings. These risks can be reduced through ongoing do notvary inthe short run with increases or decreases
customer communication and technical assistance in the amount of energy provided. Capacity rates are
during the building conversion process, as well as linked to the contracted capacityand are usuallyescalated
through contract provisions requiring initiation of at a rate lower than general inflation.
payments ata certain date.
Consumption rates
Metering
Appropriate billing of distrid cooling customers requires Consumption rates are charged to recover at least the
variable costs, which vary in the short run with increases
accurate metering. Risks related to inaccurate metering
include low revenues, resulting in diminished profits, and or decreases in the amount of energy (i.e.,fuel, eledricity,
water and chemicals). Consumption chargesare typically
potential customer relationsproblemsdue to overbillling.
designed to recover the variable costs and may also
help recover some fixed costs.
These risks can be minimized through procurement of
high-quality meters and a strong program for
Connection charges
maintaining them.
Some district cooling utilities also require a connection
charge. This is a one-time fee to connect to the system.
In some instances this is a negotiated tradeoff between
initial capital costs and operating costs based on the
building developer's financial preferences. Other district
cooling companies establish a fixed charge per ton of
peak demand. Others base the connection charge for
Reduced building occupancy a particular customer on the additional revenue
Many residential properties with district cooling service required for the utility to meet its return on investment
are being sold in the Middle East as an investment (RO!) criterion. The amount depends on how much it
opportunity, with little expectation of ongoing will cost for the utility to install pipes and other equip-
occupancy at least in the near term. The extent of ment to connect the customer to the system.
revenue risk associated with low occupancy depends
on the district cooling rate structure. As discussed Some district cooling utilities provide the heat
below, a single rate (price per ton-hour) exposes the exchanger (which transfers cooling energy from the
district cooling company to a variety of risks, including district cooling system to the building air-conditioning
revenue reduction resulting from low occupancy rates system)and the distrid cooling meter, thereby offsetting
or energy conservation measures. A two-part rate costs that the customer would otherwise incur to
structure reduces or eliminates these risks, depending on obtain district cooling service.
the specific rate structure and its relationship to costs.
Regional rate examples
3.4 Rate Structures
Examples of 2007 district cooling rates from the Gulf
District cooling rates may be structured in a variety of Region are illustrated in figure 3-1, showing the break-
ways. Most district cooling rates include capacity rates down of capacity, commodity and connection charges.
(sometimes called demand rates) and consumption Note that not all of the rate examples can be directly

13
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008 Inlemarional[)osmer Energy A55odarion. All tightsreserved.

tomerswill be motivated to reduce peak demand, which


frees the district cooling utilityto sell thiscapacity to others.

A capacity and consumption rate structure can present


marketing challenges if it is too strongly weighted to
the capacity charge. Customers mayfind it difficult to
compared because of differences in electricity and understand why they must pay a significant part of
water costs, which directlyaffect commodity charges. their annual cooling costs in a fixed monthly charge,
even in winter. This should beaddressed through a specific
3.4.2 Rate structure recommendations and well-designed communications effort in marketing
and ongoing customer relations.
Capacity rates
Connection charges
A capacity and consumption rate structure is recom-
mended, and almostall districtcooling utilities use such From thedistrict cooling company's standpoint, connection
a rate structure. If the ratestructure is limited to a single charges can helpmitigate near-term capital requirements,
rate per ton-hour, therewill be a poor match of monthly covering service line and ETS-related costs, and some-
cash flow to monthlycosts. There will also be the risk of times defraydistribution system extension costs. On the
inadequate revenues if annual cooling energy require- other hand, mandatory connection charges can present
mentsarelowerthan projected dueto projection erroror a marketing challenge in that they counter a keyelement
cooler-than-normal temperatures. This isespecially critical in the district cooling value proposition - eliminating or
in serving real estate developments with manyabsentee drastically reducing the building developer's capital
owners with low annual occupancy rates, as is the case costsassociated with cooling. It is often advantageous
with many current developments in the Gulf Region. to providea range of options for balancing connection
charges and capacity charges, thereby increasing the
district cooling company's ability to adaptto a range of
0.18 --,-------------, customer circumstances andattitudesregarding tradeoffs
between capital and operating costs.
0.16 Initial contract demand
"C"
s:
0.14 It is important to establish the initial contract demand
~ 0.12 as accurately as possible because (1) if the demand is
too high, it increases the marketing challenge; and
Q;
(2) if the demand is too low, the district cooling
~ 0,10
en company will not recover its costs, and there may be
2. 0.08 inadequate capacity to meet the actual peak demand.

O"J Although reducing the contract demand istempting as


a: 0,06 a strategy for getting customer contracts signed, this
"iii
~ 0.04 approach should becarefully and infrequently used only
if truly necessary to "jumpstart" a customer base. A
technique that has worked for other startup district
0,02 cooling companies isto offer "curtailable" demand at
o a reduced cost. This curtailable capacity reservation
would be subjectto reduction during peaktimes if the
ABC D E F district cooling company supplier needed thefirm capacity
to serve other customers. This option could introduce
System customer satisfaction issues and therefore should only
IIIConnection charge [iJ Commodity charge be considered asa negotiating tool to close a deal that
IIICapacity charge needs a small price incentive.

Figure3-1. Examples of Middle East district cooling rates.

Capacity andenergy charges also provide a basis for tying


prices to related costs, andif contractdemand isupdated
based on metered demand, this approach provides a
useful price signal to the customer. For example, cus-

14
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 IntematiOllilI osma EnergyAssoddrion. All rights reserved.

Rate design to encourage optimal building 3.5 Performance Metrics


design and operation

One of the biggest challenges in the district cooling Early consideration should be given to metricsthat define
industry is encouraging building design choices and the successful development and operationof a new district
operational practicesthat will help optimize total system cooling system. Such performance metrics must be
performance. Good rate-structure design can help the established and systems put in place to measure the
customer make the best choices with the greatest total key parameters.
cost optimization benefit.
Examples of performance metrics might include the
To this end, it may be worthwhile considering some following:
variations in capacity, consumption and connection
rates based on the compatibility of the building system Customer service
design and operation with optimal district cooling service • number of customer outage hours
parameters. The district cooling company incursadditional • number of customer complaint calls
costs for extra infrastructure, operating and energy
costsif the building system isn't designed and operated System operations
to be optimally compatible. It is important to manage .total variable operating cost (US$/ton-hr)
these elements witha contract thatprovides aneconomic .peak electrical demand (kW/ton)
incentive for the building owner to do the right thing .average electric energy efficiency (kWh/delivered
ton-hr)
for his or her building and the district cooling utility.
.water consumption (l/ton-hr or gal/ton-hr)
Some district cooling utilities address poor delta T per- .system delta T performance at peak (temperature
formance through the consumption charge. For exam- difference between supply and return)
ple, there may be an "excess flow" penalty charge
based on the extent of the difference between actual Financial performance
deita T and the target delta 1. However, such mecha- .capital cost to engineer, procure and construct
nismsgenerally don't address the full economic impact (US$/ton)
of low delta T, which affects not only variable costs but • internal rate of return on total invested capital
(%)
also fixed costs, particularly capital costs.
• return on equity (%)
Another incentive mechanism is revising customer
contract capacity after an initial period of operation Environment
(e.g., two years), based on actual metered peak eestimated emissions impact (C02 emission
demand. This allows contracts to be brought in line reduction/ton-hr)
with actual (instead of estimated) demand. It also .estimated demand reduction on the electrical grid
supplies an incentive for buildings to operate the building (kW/ton)
system in ways that reduce peak demand on the district
cooling system, thereby freeing up capacity for the
system to serve other customers. Incorporating a
contract capacity reset mayor may not be advisablefor
a given district cooling business, depending on the
maturity of the system, the prospects for growth and
technical constraints on growing the customer base.

15
DISTRICT COQUNG BEST PRACTICE GUIDE
e2008 International DlsUict EnergyAssociation. NI nghtsresened.

4. Design Process and Key Issues


4.1 Load Estimation • number of people in occupied areas
.outside air for ventilation
Defining the cooling load is the foundation for designing .occupancy schedule
a district cooling system. Properly estimating cooling loads
affects the design, operation and cost-effectiveness of the The international experience of the district cooling
district cooling system in many ways, including industry over the past 30 years is clear: Conventional
.ensuring sufficient but not excessive plant and methodologies and software tend to overstate peak
distribution capacity, loads. This is understandable, given the consequencesof
• providing the ability to cost-effectively meet the underestimating loads for the purposes for which these
daily and seasonal range of loads and methods are used. The last thing a consulting engineer
• providing a basis for accurate revenue projections. wants is to be blamed for inadequate capacity. Conse-
quently, typical load estimation methodologies tend to
result in unrealistically high load estimates. Design prac-
tices that contribute to high load estimates include
• using higher than the ASHRAE design temperatures
for wet bulb and dry bulb,
.assuming the peak dry-bulb and wet-bulb
temperatures are coincident,
.compounding of multiple safety factors and
District cooling systems typically provide cooling to a
.inadequate recognition of load diversity within
variety of building types, including commercial offices;
the building.
retail shopping centers; hotels; and educational, medical
and residential buildings. Although weather is a key
driver of cooling loads, occupancy, lighting, computers
and other equipment also create load independent of
weather. Depending on building use and many case-
specific factors, these loads can be quite significant.
Operational practices and controls also have a significant
Overestimation of load may be appropriate for a building
impact on total cooling energy requirements (e.g.,
HVAC consulting engineer who wants to make
reducing fresh-air intake at night would substantially
absolutely sure that the customer has sufficient capacity.
reduce dehumidification and cooling requirements).
But for a district cooling company, these conservative
methodologies, or rules of thumb that are similarly
For most district cooling systems, particularly in the
conservative, can be painful in many ways. Theycan leadto
Middle East, customer loads consist primarily of new
.overinvestment in district cooling infrastructure,
buildings. Consequently, in most situations, cooling
.overprojection of revenues, .
loads must be projected without the aid of historical
.disagreements with prospective customers' enqineers
data for the specific buildings. It is possible, however, to
regarding contract loads (excessively high contract
use historical data from similar buildings in the same
demands can sink the economics of district cooling)
climate to help estimate reasonable loads. This type of
and
data should be used to provide a "reality check" on the
• poor efficiencies in meeting low loads in the early
load estimates provided by consulting engineers for
years of district cooling system growth.
developers and building owners and managers. These
estimates, based on HVAC rules of thumb or buildinq
District cooling system load estimatesare often overstated
modeling programs, tend to overstate loads.
because the buildings are not brought online according
to the predicted schedule and the load does not materi-
Computerized building simulation programs are available
alizeuntil late' Thisresults in problemsfor the district cool-
to determine building peak design cooling loads and
ing plant at low-flow conditions (e.g., control valvesizing).
to predict monthly, daily, and hourly cooling loads that
must be satisfied. Load estimation modeling typically
Thereare three major aspects of customer load projections:
addresses these key variables:
.peak demand
.weather .peak-day hourly load profile
.building envelope, particularly windows
.annual cooling load profile
.Iighting and computers

4.1.1 Peak demand


Peak-temperature conditions for cooling design are very
high in the Middle East. Figure 4-1 summarizes the
0.4% dry-bulb and mean-coincident wet-bulb temper-
atures (temperatures exceeded only 0.4% of the time)

16
DISTRICTCOOUNG BEST PRACTICE GUIDE
e2OO8 In!M1ational DistTict Energy Assrxiab'on. Allrights reserved.

per the 2005 ASHRAf Handbook - Fundamentals. for green buildings in the Gulf Cooperation (au neil,
Design dry-bulb temperatures range from 35 (to 47 C the peak cooling demand in new buildings is expected
(95 F to 117 F), with mean coincident wet-bulb to decrease, with values reaching 45 sq m/ton (484 sq
temperatures ranging from 18 ( to 25 c (64 Fto 77 F). ftlton) or more expected in the near future.

Figure 4-2 summarizes the 0.4% wet-bulb and mean- The ultimate level of system load diversity (coincident
coincident dry-bulb temperatures. Design wet-bulb district cooling system peak demand compared to the
temperatures range from 21 c to 31 ( (70 F to 87 F), sum of individual peak demands) depends on the mix
with mean-coincident dry-bulb temperatures ranging of building types, building operating practices and the
from 28 (to 40 ((83 F to 104 F). system's maturity. A district cooling system at the early
stages, with relatively few buildings served and/or
50
relatively little diversity in building types, will have a very
45 small system load diversity. On the other hand, a large
~40+-JI=.~
Eo 35 +-
system serving many types of buildings may have a
e 30 +-111-.- diversityof 0.85 or lower (coincident peakdistrict cooling
~ 25 system load isbelow 85% of the sum of individualannual
_20 building peak demands).
; 15
c 10
, 4.1.2 Peak-day hourly load profile
o The peak-day load profile should be modeled based on
building use, occupancy schedule, weather, HVA( system
characteristics and other case-specific variables. Load
ll!IMesn-coirlCidenl wet bulb
profiles vary significantly with building use. Examples
Figure 4-1. Design dry-bulb and mean-coincident wet-bulb of profiles from the Middle East are shown in Figure
temperatures for selected Middle East cities (ASHRAE 4-3. While offices, hotels and residential buildings tend
0.4% design point). to peak in the late afternoon, retail buildings typically
peak in the evening.

If customer buildings operate with night setback in the


off-peak months or reduce cooling use during the
weekend, there can be very high peak loads coincident
with the initial call for cooling the next morning. This
should be addressed by using controls to limit any
excessive rise in building chilled-water temperature or
space temperature and humidity.

Particularly relative to office buildings, an important


variable is whether or not the building operators shut
Figure 4-2. Design wet-bulband mean-coincident dry-bulb
temperatures for selected Middle East cities (ASHRAE 0.4%
110%
design point). I
100%
90%
. "- .. .. .. Hotel
"Diversityfactors," also called" coincidence factors," are t). ,/
extremely important elements in peak load estimation.
These factors are used to accountfor the fact that not all
'"••
C>
'0 70%
80% ..
-
1\..
Residential

loads have their peak at the same time. This occurs '#. 60% Office
within a building, between buildings and between ••
'C
50%
building usage types (e.g., offices compared to 0•
..J
40% - Retail
residential). In addition, particularly with recreational
30%
investment properties, diversity factors must also
20%
account for variations in occupancy.
10%
Actual peak demands for district cooling customers in 0%
the Middle Eastrange from 20 to 52 square meters per 0 2 4 6 6 10 12 14 16 16 20 22 24
ton (sq m/ton) (215 to 560 sq ft/ton), with a represen- Hours
tative value of 35 sq m/ton (377 sq ftfton) for systems
serving a mix of customer types. With the recent new Figure 4-3. Example peak-day load profiles for various
regulations regarding building efficiency and the drive building types.

17
DISTRICT COOLING BESTPRACTICE GUIDE
C2008lntemaliooal DiWid Energyk5odalion. All n'ghrs. reserved,

down fresh-air intake at night. Decreasing fresh-air can be used. The annual load profile also enables
intake at night would cut down dehumidification calculation of the total annual energy, and thus the
requirements and load. annual equivalent full-load hours (EFLH) for the system,
which is critical for rate structure development and
Figure 4-4 shows an illustrative district cooling system revenue projections.
peak-day load profile for a sample mix of buildings
(40% office, 16% retail, 27% residential and 17% EFLH is the ratio of annual cooling energy to the peak
hotel). In this example, average peak-day load is 78% demand and can be calculated with the following
of the hourly peak, providing a potential opportunity equation:
for thermal energy storage to be used as part of the
district cooling system.
EFLH = Annual Cooling Energy Consumption (ton-hr)
__---,_-"--c-,-"'-'-_-,--'-,_.,:-_-'.
Peak Hourly Consumption (tons)
110%
For Middle East countries,the full-load hours are normally
in the range of 3000 to 4600. In the case graphed in
100% Figure 4-5, there are 3978 EFLH.
,/
V
90%
'C
rn
.Q
f 100%
90%
~

'"rn 80% ••,• 80%


\

"c. V -,
~
=0 70% "- <,
'5 70% ~
~
<;
••
;.- 60%
'if!. .........
I\.. J ~
~
50%
-,

-
60% •a
••
c
40%

30%
r---- -..
-..
50% "
~
20%
10%
40% 0%
0 2 4 6 8 1012141618202224
Time of day
• #' ,f I ,.f ~ l # .J<* ,,,,,0 ••* ,l
Hours peryearwith load at orbelow Bgiven level
Peak-day ••• Average
- - load profile daily load
Figure 4-5. Illustrative district cooling annualload-dura-
Figure 4-4. 11Iustrative peak-day load profile for district tion curve.
cooling serving mixed building types.
4.2 Design Temperatures and Delta T
4,1.3 Annual cooling load profile
Estimating annual cooling energy is essential for proper 4.2.1 Delta T is a key parameter
evaluation of plant alternativesand revenue projections. Delta T is a key parameter in the design and operation
Modeling of hourly loads throughout the year enables of district cooling systems and is an excellent measure
the development of an annual load duration curve. See of total system performance at any load condition. It is
the example annual load duration curve for a mixed- the difference between supply and return temperatures
use district cooling system in the Middle Eastshown in measured across the chillers, plant, distribution, energy
Figure 4-5. transfer stations and customer buildings. Flow is inversely
proportional to delta T. With high delta T, less flow,
The load-duration curve is useful for evaluating plant pump energyand equipmentcapacity arerequired to satisfy
options because it provides information on how many cooling requirements.
operating hours a given element in the dispatch order
District cooling customers expect to receive efficient,
reliable and cost-effective cooling. While it is very
important to achieve high delta T in the distribution
system and in the plant(s), it should not come at the
expense of customer comfort or control. High delta T
(and high chilled-water return temperature) should be
achieved, but not directly controlled.

18
DISTRICT COOLING BEST PRACTICE GUIDE
Energy Association. Allrightsreserved,
C2008lntema~onal District

processthe excess flow:


• Overflow chillers in operation.
• Turn on additional chillers or expend TES sooner.
• Blend return water with supply water.

With a comprehensive strategy to design and operate Noneof theseoptionsisideal for energy, capacity or control.
the systemto achievehigh delta T at all load conditions,
it is possible to reduce unnecessarycapital, operating
and energy costs and significantly improve the
performance and economics for both a district cooling
company and its customers.

This is not a task that should be taken lightly. In the


Middle Eastand in the broader district cooling industry, For district cooling systems serving new construction
low delta T remains one of the most common, trou- (as is the case with most systems in the Middle East),
blesome and unresolved problems. Low delta T results life-cycle costs should be analyzedfor the entire system
in wasted energy, limited available capacity, added (building HVAC, ETS, distribution, plant) to optimize
complexity and loss of comfort control. total economic performance. Forexample, lowering the
supply-water temperature from the plant (with colder
For a district cooling system to be successful, it is chiller leaving-water temperatures, ice storage, or low
essential that all elements of the system are integrated temperature fluid) may significantly reduce the cost of
and operatetogether without compromising performance. pumps, piping, valves, fittings and heat exchangers for
This includes the district cooling company. This can also reduce the
• building HVAC systems, cost of customer pumps, fans and ductwork if lower
• energy transfer stations, supply-water and supply-air temperatures are used.
However, lowering the supply-water temperature has
• chilled-water distribution system and
certain operational and efficiency drawbacks, as
• district cooling plant(s).
discussed below.

Achieving high delta T requires a savvy technical and


Furthermore, high return-water temperatures can be
business approach that goes beyond typical industry
achieved with smart investments in building systems
practice. Tariffs in contracts should enable customers
(control valves, air handlers, cooling coils) and a sound
to make sound economic decisions in their buildings
delta T strategy. Individual system components may
that enhance delta T performance. District cooling
have marginally higher costs (e.g., more cooling coil
companies should prepare technical guidelines and
rows or more coils in series), but the total system capital
work with their customers to achieve success.
and/or energy costs may be significantly reduced.

The goal is to design the plant and distribution system


for as large a delta T as practically possible and to 4.2.2 Limitations on lower chilled-water
provide the design, operations and business guidelines supply temperature
to ensure it will be achieved with each customer in
operation. This means the lowest-possible supply Chiller efficiency
chilled-water temperature and the highest-possible
return temperature. Centrifugal chiller power requirements depend mainly
on how much refrigerant flow the compressor has to
Supply-watertemperature islimited by the district cooling pump and what pressure differential the compressor
plant and distribution system performance. Return- must overcome.
water temperature is typically limited by cooling coil
performance in customer buildings. These factors are The first is dependent on the system cooling load
also interrelated. With proper control, cold supply- requirements, which are a given. The second- is deter-
water temperature to cooling coils enables them to mined by the difference between the condensing and
produce a higher return temperature. evaporating temperatures or what is referred to as the
"lift." Entering condenser water temperature is limited
With low delta T in the distribution system, the district by the ambient wet-bulb temperature as well as the
cooling provider is forced to process the "excess" number and capacity of cooling towers in operation.
chilled water. For example, there are 315 liters per Leaving chilled water can be increased or decreased,
second (I/s) (5,000 gpm) excess flow at 10,000 tons of also changing the lift. The lower the supply chilled-
load if the system is operating at 6.7 C vs. 8.9 C (12 F water temperature, the higher the lift, and hence the
vs. 16 F) design delta 1. There are three choices to more power the compressor has to overcome to help

19
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lnremational Dismc! EnergyAssociation, All tightt~.

produce the same refrigeration effect. The added Thermal storage generally designed for peak shaving
power may be offset by a reduction in pumping power or load leveling can substantially offset part of the
achieved with higher delta T. chiller capacity in the plants and contribute to
reduction of peak electric load.
Evaporator freezeup
4.2.3 Limitations on higher chilled-water
return temperature
The other limitation to how low the chilled-water tem-
perature can go is its freezing point. If chilled water is
Dehumidification and coil performances
going to freeze, it will start to do so at its lowest
temperature location: somewhere inside the evaporator
Higher delta T or "low-flow" designs provide required
tubes. The effects are catastrophic, damaging the evap-
cooling capacity by usingless water at coldertemperatures.
orator. Evaporator tubes may corrode and thin, adding
How does reduced water flow affect the performance
to the problem.
of the cooling coil? An understanding of thermody-
namics and the heat-transferequation, Q = U x A x LMTD,
For safety reasons, the minimum design chilled-water
tells us that less water flow through the coil tubes
temperature is usually determined to be around 3 (
reducesheat-transfer coefficient U (waterside resistance
(5 Fto 6 F) above its freezing point. Minimum velocities
to heat transfer increases). But as Figure 4-6 illustrates,
are set to prevent a sudden drop in heat transfer
the log-mean temperature difference (LMTD) increases
because of laminar flow. Enhanced chiller tubes or
because the entering-water temperature is colder.
turbulators may be selected to help strip away laminar
boundary layer flow. Where even lower chilled-water
temperatures are desired, an anti-freeze agent may be <,
added to the chilled-water media to prevent freezing. r.....
"
~ ~h
23'F
A supply-to-return-water bypass may be added to
ensure minimum flow. 57'F L '1"'"
... AT

Thermal energy storage


L
'. 1
1 ""'.." -...L
';;.. ~;-e df!!,
~
,I" 44 ' F
(121 gallmln)
J,155'F

e 40'F
'WI en gal/minJ
The majority of thermal storage systems in the Middle = EAT· LWT w, = £AT - EWT
Eastare based on chilled-water storage technology. As 1O'FoTwaterside, 2S'FoT alrslde: 17"FoT waterside, 2S'FoT airs Ide:

discussed in Chapter 7, a variety of ice storage systems LMTD 26-11


= /n(26111) =17.4
23-15
!MID = In(23/15) =18.7
are also available.
Figure 4-6. Effect of increased delta T on LMTD of cooling
Most chilled-water thermal storage systems are based coils.
Source: Trane Engineers Newsletter 31 Vol. 1.
on designs that exploit the tendency of warm and cold
water to stratify. That is, cold water can be added to or
Lower supply temperature tends to increase the LMTD
drawn from the bottom of the tank, while warm water
and this helpsoffsetthe reducedheat-transfer coefficient'
is returned to or drawn from the top. A boundary layer
however, a higher return-temperature value has an
or thermocline, which can be from one to a few feet in
opposite effect. The higher the return temperature, the
height, is established between these zones. Specially
lower the LMTD.
engineered diffusers ensure laminar flow within the
tank. This laminar flow is necessary to promote
The total effect on a specific coil performance is a
stratification since the respective densities of the return
balance of the effect of the above factors. To illustrate
water and supply water are in fact almost identical
the effect of high return temperature on coil capacity,
because of the relatively small differential temperature
look at the effect of return chilled-water temperature
of the supply and return.
on the latent heat capacity of the coil. Dehumidification
occurs only when coil surface temperature is below the
Therefore, thermal stratification of the chilled water
dew point of the air touching the coils.
inside the tank has to be maintained at all times. While
maximizing the delta T helps maintain the stratification
For a .100% fresh-air unit, the entering-air design
this is constrained by the fact that the minimum supply
conditions are that of the ambient conditions outside.
temperature is the temperature at which the water
Because the ambient design conditions should not be
density is at its maximum (at 4 ( or 39 F). If supply
overestimated (a common mistake), it is best to use
chilled-water temperature gets below this point, the
ASHRAE's latest published 0.4% values.
less-dense colder water will start moving up in the
storage tank, upsetting the carefully maintained
For example, the 0.4% weather design data for Abu
thermocline and causing mixing.
Dhabi is a dry bulb of 43 ( (109.4 F) and a mean-
coincident wet bulb of 23.8 ( (74.9 F). The dew point

20
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008 Inremational Di5trta Energy Association. All righrs reserved.

at the ambient design conditions 15.0 ((59.1 F),while


the dew point at typical indoor comfort conditions
(recycled return air for comfort air conditioning) is
14.4 ( (57.9 F) at 25.5 ( (78 F) dry bulb and 18.3 ( (65 F)
wet bulb. This means that whenever the coil surface
temperature exceeds the above dew-point temperature
values, the latent capacity of the coils will suffer.
to educate design and operating engineers will pay
many dividends.
To determine the exact impact on coil performance
characteristics, use an ARI-certified cooling coil rating
A successful district cooling system design should push
and selection program to assess performance in different
towards maximizing the delta T. A district cooling
conditions. The typical return-water temperature beyond
system serving new buildings, designed with proper
which coil latent load capacities become too high is
guidance, should be able to achieve a delta T of 8.9 C
about 15.6 ( (60 F). But this is only a rule of thumb
to 12.2 ( (16 Fto 22 F). Forexample,with a typical supply
and has to be checked based on actual load and coil
temperature of 4.4 ( (40 F) delivered to the customer
selection information. That is not to say that special
building system, return temperatures between 13.3 (
coils with more circuits per row and smaller coil
to 16.7 ((56 F and 62 F) are achievable.
diameters that can handle higher-than-typical return-
water temperatures are not available from various
Strategies for achieving high delta T are discussed in
manufacturers, but this usually has some cost penalty.
Chapter 5.
It should be noted, on the other hand, that low flows
tend to reduce the overall costs of a building's HVA(
4.3 Master Planning
system because of the following:
In planning a major district cooling system, it is important
• Smallerpipes and headersto handle the lower flows.
to develop a long-range development plan at the initial
Thismeans smallerfittings, valves and lessinsulation.
design stage based on solid intelligence about the
This is where most of the savingsare realized. potential customer base. The plan should be regularly
• Smaller pumps and pumping power requirements. updated based on new developments and new infor-
With proper control and chilled-water supply and leaving- mation. Here are key steps in developing the initial plan:
air temperatures at design, a cooling coil should deliver
better than design delta T at all load conditions. 1. Gatherdata on the potential load, including estimated
peak demand, age and condition of current cooling
equipment and refrigerant conversion status.

2. Identify the highest concentrations of cooling load.

3. Evaluate potential customers to identify which have


the greatest likelihood of taking cooling service.

Heat exchanger approach temperature 4. Develop a preliminary pipe routing that connects
targeted load and appears feasible from an initial
With indirect ETS connections, the heat exchanger's review of underground space availability and coor-
design has an impact on the chilled-water temperature dination with plans for other utilities and roadways.
on the customer or building side of the heat exchanger.
There is a limit to how low the approach temperature 5. Locate feasible potential plant sites that will utilize
(the difference of temperature between both sides of a space well, are adjacent to the load concentration
heat exchanger) can be driven, after which its cost and and have reasonable access to power supply and
size become determining factors. Typically this limit of sources of condenser cooling water.
temperature differential is around 1.1 ( (2 F) between
the between the entering-primary and leaving-secondary 6. Perform pressure-drop calculations or computer
connections. modeling to locate trouble spots and refine the
distribution design and plant locations as needed.
4,2.4 Best practice recommendation
It is critically important to give customers and their
consulting engineers standards for building-side design.
It is also important to verify that they commission and
balance the building-side system and verify that the
target delta T is achieved. Allocating time and resources

21
DISTRICT COOLING BEST PRACTICE GUIDE
02008lnlemationa/ DIstrict Energy Assodanon, Allrigh!5 re5efVed.

7. Perform a business case analysisof design options. when, development will occur, so the master plan must
be based on assumptions regarding the pace, type and
Consideration of condenser cooling options is critical location of development. This is the plague of district
for district cooling plant siting in the Middle East. In energy system development: Inevitably, a building
addition to considering adequate supply of power for intended to be served by district cooling requires service
a district cooling plant, evaluating condenser cooling before the district cooling loop was planned to be
alternatives should be done at an early stage. Depending extended to that area. In these cases, a temporary
on the condenser cooling option, the plant sitemayrequire chiller plant can be installed, the building can be
• pipeline access corridor to the sea, dropped from district cooling plans, or (if the building
• pipeline access corridor to sewage treatment is big enough) it can be built with its own chiller plant
facilities or treated sewage effluent lines, which can later be used for the district cooling system
• access to municipal water supplies and/or as backup or peaking capacity.
• plant site area for wastewater treatment facilities.
4,4 Permitting (Way Leaves)
It is very important for the district cooling provider to
work with the master developer to identify a strategic Permitting requirements vary significantly depending
plant location(s) for reasonable piping distribution on the location and will likely include interaction with
installation (sizes and pumping energy) and not be municipal and national agencies relative to plant facilities,
forced into placing an unreasonably sizedplant in a bad chilled-water distribution pipes, condenser cooling
corner of the development. Unfortunately, sometimes water supply and discharge piping. Here are some
district cooling companies are pushed to site a huge important related recommendations:
single plant at an extreme end of a large development • Start early to work with permitting authorities.
and pump chilled water long distances through giant • Communicate to these groups the benefits of
pipes, when two smaller, more reasonably sized plants district cooling relative to power demand reduction,
in more strategic locations would have been a much air-conditioning quality and reliability, and air
better solution. The developers deem their property so pollution and carbon dioxide emission reductions.
valuable that they don't want to allocate any space in • Establish and maintain essential close coordination
prime locations for cooling plants and, unfortunately, with roadway and other utility infrastructure
the district cooling companies do not (or think they construction.
cannot) exercise any influence in these decisions. • Proactively address potential concerns about
disruptions caused by plant and distribution system
Planning is critical to minimizing economic risks associated construction - communicate early and often.
with decisions made at the design stage, including
• cost inefficiencies and/orconstraints on expansion
due to lack of a long-range plan;
• installation of more plant capacity than required;
• reduced distribution system capacity due to
inaccurate estimation of the temperature difference
between supply and return; 4.5 Integration of District Cooling
• inability to connect desirable customers due to With Other Utility Infrastructure
routing or sizing of pipes;
• losing opportunities to purchase real estate for 4.5.1 Growth and infrastructure stresses
optimal location of plant facilities;
The Middle East is a dynamically growing area, creating
• inability to usethe lowest-cost production facilities stresses on utility infrastructure including cooling,
for base-load service due to routing or sizing of
power, potable water, wastewater treatment and roads.
pipes; and
District cooling has become a key strategy for reducing
• high pumping costs, poorperformance incustomer
power demands as massive development takes place
heat exchangers and poor utilization of capital
inthe region. However, district cooling systems require
assets due to hydraulic imbalances caused by poor
water for optimal energy efficiency, thus creating
distribution design.
stresses on water supply. Potential water sources
include treated sewage effluent (TSE), brackish ground
It is important to note that the initial master plan is only
water, untreated seawater and partially or fully
a guideline for decision-making, not a blueprint,
desalinated seawater.
because appropriate decisions about buildout of the
district cooling system must necessarily be made in
reaction to the actual timing and location of building
development.

There is usually uncertainty regarding where, or at least

22
DISTRla COOLING BESTPRAalCE GUIDE
02008 Inlemauonal Disffiet Energy A55ociab'on. Ail rights reserved.

Water has always been a fundamental issue in the Chapter 2. District cooling frees up power capacity to
region, even withoutconsidering airconditioning; what meet other electricity requirements of new developments.
has changed is the scale of the challenge. Some Another potential synergy between district cooling and
countries, such as Saudi Arabia, Kuwait and Qatar, use power generation isthe useof gasturbine inlet air cooling,
nonrenewable groundwater resources inlarge quantities, which increases power generation when the ambient
causing depletion of these valuable resources and, in air temperature is high (which is when power demand
some cases, deterioration in water quality. Seawater is high).
desalination is a critical element in meeting growing
water needs throughout the Middle East. At the same Although district cooling's power sector benefits are
time, substantial investment will be made inwastewater desired by governments in the Middle East, the need
treatment facilities to serve new developments. for utility synergy in obtaining the water that maximizes
district cooling energy savings is less well understood.
There are great potential economic and environmental
benefits from integrating planning for energy and Heat rejection
water utilities, not only from the production side, but
also relative to coordination of design and construction District cooling plants typically use cooling towers to
of necessary pipelines. cool the chillers' condensers. Towers require "makeup"
waterbecause some water is lost through evaporation,
4.5.2 Paths for utility integration drift or "blowdown" (in which some water is periodi-
Therearea varietyof paths for potential utility integration, cally removed to maintain water quality in the towers).
as shown in Figure 4-7. Not all paths would be used in Makeup water does not have to be drinking-water
a given system. Tosimplify, however,this figure combines quality. In fact, seawater can be used in cooling towers,
the multiple pathways. but this requires much more expensive equipment and
higher maintenance costs. Other low-quality waters can
There is now widespread recognition of district cooling's be used, including TSE, brackish ground water and
ability to cut power demand and energy, thus reducing partially desalinated water. As the quality of the
government investment in powerinfrastructure as well makeup water decreases, the capital and maintenance
as annual powerutility operating costs, as discussed in costs of the cooling towers increase.

Alternatively, district cooling systemscan use seawater


or other water sources non-consumptively. With this
approach, the water cools the chiller condensers
directly rather than through a cooling tower. Heat is

Seawater for cooling tower makeup or direct condenser cooling

Desalinated water for cooling tower makeup

Treated sewage effluent (TSE) for cooling tower makeup

Sewage
Treatment
Plant
Common
Seawater
Intake

;;;

I

Potable water power plant

Electricity

Electricity

Figure 4-7. Paths for potential utility integration.

23
DISTRICT COOLING BEST PRAcrlCE GUIDE
02008 intematiooal Di5tlictEoorgylWodiition. All nghtsreserved.

added to the water, but the same volume of water can Natural gas
be returned to the sea or used for other purposes.
Natural gas is frequently the ultimate energy source for
Desalination district cooling. Most often it fuels power plants that
provide the electricity to drive district cooling plants.
Desalination is energy-intensive. Multi-stage flash (MSF) Sometimes it is used directly in district cooling plants
plants are the most commonly used, accounting for the to fuel gas engines that generate electricity for electric
majority of global capacity. The use of reverse osmosis chillers, as Tabreed has been doing in some of its plants
(RO) plants is growing due to technological advances for more than five years. Natural gas can also be used
and energy cost increases. MSF requires heatand some to produce the shaft power to drive chillers directly.
electricity, while RO generally requires only electricity
(although some heat can optimize the process). Natural gas transmission and distribution networks are
growing in the Middle East. As this occurs, the gas
Power and desalination plants are often combined in a distribution networks can be planned with the potential
cogeneration process (combined heat and power) in for district cooling in mind. District cooling plants that
which the waste heat from power generation is used use natural gas can relieve pressure on government
for MSF desalination. Cogeneration can also be investment in power plant, transmission and distribution
employed in RO plants by using exhaust steam to infrastructure.
pre-heat feedwater or to run a steam turbine to power
the pressure pumps required in the RO process. Natural gas-driven cooling technologies are discussed in
Chapter 7.
The amount of energy for MSF is fixed for a given
volume of water, but the energy for RO depends on
how salty the water is to start with. For this reason, it
is much more attractive to desalinate brackish (i.e.,
slightly salty) water or treated sewage effluent than it
is to desalinate seawater. Typical salinity values, in parts
per million (ppm):
• Seawater 35,000-45,000
• Brackish ground water 2,000-8,000 The challenge of utility integration
• Treated sewage effluent (TSE) 2,500
• Product water from MSF desalination 25-50
Integrating utility planning in the Middle East can
reduce government capital and operating costs,
Salinity of product water from RO can vary significantly
increase energy efficiency and reduce harmful emissions.
depending on the salinityof the feedstockand the specific
Utility integration is a challenge, however, because
type of RO process employed. In general. the cost of
typically different government entities are responsible
RO decreases as the minimum acceptable product-
for permitting and regulating district cooling systems,
water salinity increases. If RO desalination is being used
power utilities, potable waterand wastewater treatment.
to produce district cooling tower makeup water, the
Not only are different federal ministries involved, but
trade-offs must be optimized: Lower quality makeup
municipal governments are usually also involved.
water means higher district cooling plant and operating
costs, but lower RO plant and operating costs.
Consequently, although district cooling systems could
provide multiple infrastructure benefits and, in turn,
One possibility iscombining district cooling with a hybrid
could be optimized through integrated utility planning,
MSFIRO desalination-powerprocess, in which a seawater
district cooling companies frequently encounterchallenges
RO plant is combined with either a new or existing MSF
in obtaining permits and achieving optimal integration
plant. The MSF plant draws waste steam from a power
with powerand water utilities.
plant and uses the energy in the steam to pre-heat
seawater, which is then distilled in the MSF unit. The
Tremendous economic and environmental benefits
RO unit uses electricity from the power plant and
would result if governmentscreatedeffectivemechanisms
operates during periods of reduced power demand,
for integrating utility planning across federal ministries
thus optimizing the overall efficiency.
and municipal governments. This will not be easy and
will require strong, visionary leadership at the highest
Thisapproach can reduce capitalcostswhile providingfor
levels. But it will be well worth the effort because it will
a variety of blendsof MSF and RO product watersto meet
greatly enhance a country's stature as an attractive
a range of requirements, from potable water to irrigation
place for business investment.
water to optimized district cooling makeup water.

24
DISTRICTCOOUNG BESTPRACTICE GUIDE
02008 International Di5tricr Energy As5ociation. Allright!; re5eM!d.

4.6 Designing for Operations


As discussed in Chapter 3, it iscrucial that districtcooling
be approached as a long-term utility business. To this
end, it isimportantto involve the district cooling company
operations and maintenance staff inthe design process.
Given the fast pace with which most district cooling Districtcoolingsystems should be ableto monitor their
systems are being designed and constructed, this may utilitycosts on continuous basis following these basic rules:
appear somewhat impractical. However, experienced • Essence of measurement: If you cannot measure it,
operating staffcan provide inputthat can reduce life-cyde you cannot manage it.
costs and improve reliability. It is highly desirable for • Accuracy is key: If you cannot measure it accurately,
O&M staff to "take ownership" of these systems and you better not measure it.
for district cooling companies to approach operations o Meaningfu[ reporting: Data mustbe assembled and
proactively rather than reactively. reported in structured automated reports.

25
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008 Inlemarional Di5fJid Energy Association. AIlnghls reserved.

5. Building HVAC Design and Energy Transfer


Stations (ETS)
An energy transfer station (ETS) serves as the thermal building systems as far as the cooling coil and control
energy transfer point between the district cooling valves at air handlers and terminal units.
company and each customer's heating, ventilating and
air-conditioning (HVAC) system. It also demarcates the
physical boundary for ownership, responsibility and
maintenance of equipment. At the ETS, a revenue-grade
flow meter and accurate temperature sensors are used to
calculate cooling energy consumption and demand for
customer billing.

There are both direct and indirect ETS connections, and


there are optimal circumstances for the use of each. A 5.1 Building System Compatibility
direct connection is typically an economic decision to
reduce costs and minimize thetemperature rise; however, Total district cooling system performance depends on the
in most situations, an indirect connection (with heat design, operation and control of the chilled-water system
exchanger separation) is preferred to reduce the static within customer buildings beyond the ETS interface.
head and pressure requirements in the central plant and Building system design as well as district cooling
distribution system. Indirect connections are also applied contracts, tariffs, recommendations and technical support
in many systems to enhance reliability should a failure should all be aligned to help customers achieve the delta
occur in a customer's building that would adversely T performance necessary for a cost-effective district
affect the performance of other customers or the cooling system.
central plant.
A good way to approach this is to consider delta T
It is important for a district cooling utility to work with its performance in the context of the following questions:
customers to establish the best practices for design, • What do customers need from the district cooling
operation, control and maintenance of their building provider in their buildings to ensure comfort, stability
chilled-water systems. Without this effort, the entire and humidity control without excessive building
district system may be destined to suffer from suboptimal pump and fan energy consumption?
performance and high operating costs, and customer • What does the district cooling provider need to pre-
comfort may suffer. Connection, capacity and consump- serve available capacity and minimize energy use in
tion charges should be established to deliver a level of the chilled-water plant(s) and distribution system?
customer performance that also suits the utility's financial .What steps may be taken early in design to reduce
needs. If design or performance of the building system the capital and operating expenses and improve
is poor and it affects the district cooling provider or performance for the provider and its customers?
other customers, there should be economic conse-
quences for the building owner. 5.1.1 Cooling coil selection
Cooling coils should be selected to satisfy the load
considering the expected supply-water temperature on
the building side of the ETS. Temperature gain in the
district cooling distribution pipes as well as heat
exchangers should be taken into consideration when
choosing the design entering-water temperatures. In an
With or without an indirect connection, it is essentialfor indirect connection, the cooling coil return-water
the district cooling utility to maintain proper chilled-water temperature should be selected considering the design
supply temperature control in customer buildings. It is return-water temperature expected at the plant. plus the
equally important for the customer building to deliver approach across the heat exchanger.
high return-water temperature to the plant. Even though
it hasbeen a relativelycommon practice in the industry to Figure 5-1 is an illustration of a typical cooling coil that
directly control delta T, chilled-water return temperature illustratesthe relationshipbetween flow rate, cooling load
or peak flow, these practices are not recommended in (or capacity) and delta T at the cooling coil. At design
normal operation except as measures to temporarily entering-water and leaving-air temperatures, a typical
curtail the load or flow of problem customers. These cooling coil should achieve its design delta T or higher at
tactics are likely to lead to problems relative to building all load conditions.
pump and fan energy, capacityand comfort, as well as a
loss in "latent" cooling revenue for the district cooling Space temperature, humidity and air-flow requirements
utility. The comprehensivesolution to common low delta create demand for cooling in the building. The cooling
T problems requires looking beyond the ETS into the performed at each coil depends on the air flow aswell as

26
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 International Diwl(;tEnergyAssociation. Aildght:i re>erWd.

loadat with lowersupply-water temperature. The sensible


100%
90%
./~
, and latent cooling loads remain constant for the same
~~~~ilT /~_,' entering- and leaving-air temperature conditions and air
..il.
l> 80%
../'
'
,'100%
Des!nn ilT
flow. As would be expected, less chilled-water flow is
70%
,-
..•
0
e
aa
80%
80%
c,?~~~1I:1!......

/../
-:
N'
~.......
,--,
required when supply-water temperature remains low.
Delta T (and chilled-water return temperature) rise when
less chilled-water flow is required to satisfy the load.
,.
0 40% ,
/./,- minimum expected performance
30%
20% ~~.,
~ .. ,' 5.1.2 Bypasses and three-way valves
It is essential to eliminate bypasses and three-way

,," "
10% " (diverting) valves that bypass supply water into the return
0% water to control cooling coiltemperature. These systems
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% operate with virtually constant flow, which isdetrimental
% Design Flow to the system delta T. Even a two-way control valve can
Figure 5-1. Expected col! performance over the deslqn act like a bypass if it does not fully close, or if wears and
flow range for typical coil. leaks internally. When an air handler or terminal unit

the entering- and leaving-air temperature conditions. If


the chilled-water supplytemperature is allowed to rise,
cooling coil capacity and delta T is reduced, and it will
take morechilled-water flow to satisfy the load.

de-energizes, control valves mustbe commanded closed.


There should not typically be any bypasses installed to
maintain minimum building pump flow requirements.
Pump motors needto maintain a minimum speed (not
minimum flow) to air cool the motors and avoid
When existing buildings seek a contractfor new district harmonics. A pump will not require a bypass around it
cooling service, careful evaluation of coils in existing unless the fluid temperature through the pump is
buildings isprudent when considering the loaddemand expected to rise more than 5.5 ( (10 F) at little or no
and available chilled-water supplytemperature. For this flow. If a bypass is used, it should be installed with a
analysis a generic ARI-certified rating andselection program motorized valve controlled by a temperature designed to
(available from numerous coil and air-handler manufac- protectthe pump.
turers) is recommended.
There may bea small bypass at the endof the distribution
Table 5-1 illustrates design conditions for atypical cooling system designed and controlled to maintain cold supply-
coil. It also illustrates the flow rates required to satisfy the water temperature in the loop. This may be especially
important in systems with
night setback to minimize a
Parameter Value sudden demand upon a new
Ventilation Air Flow 28,000cubicfeet per minute(elm) call for cooling in the morn-
[13,215 liters per second (Ips)] ing.
Entering-Air Temp. dry bulb 22.2 ( (72.0 F)
Entering-Air Temp. - wet bub 17.8( (64.0 F) Insome cases achilled water
Leavinq-Air Temp. dry bulb 118 ( (53.3 F) return-to-supply mixing
Leaving-Air Temp. wet bulb 11.7( (53.0 F) valve can be justified be-
Latent Cooling 28.7 tons cause of different supply-
Sensible (ooling 47.2 tons temperature demands (i.e.,
chilled beams, induction
Total (ooling 75.9 tons
units, process cooling).
Entering-Water Temp. 7.2 c (45.0 F) 5.5 (42.0 F)
Leaving-Water Temp. 12.8( (55.0 F) 13.7(56.7 F)
Delta T 5.5 ( (10.0 F) 8.2 ( (147 F) 5.1.3 Control-valve
Water Flow 11.5 Ips (182 gpm) 7.8 Ips (124gpm) sizing and selection
Normalized Flow 0.151 Ipslton 0.103 Ips/ton ETS control valves (with
(2.40 gpm/ton) (1.63 gpm/ton) actuators) are typically
applied on the district cool-
Table 5-1. Typical coil (anddelta n performance as entering-water temperature varies. ing side of the ETS to control

27
DISTRICT COOLINGBEST PRACTICE GUIDE
C2008lnremational District Energy Association. Allnghtt reserved.

pressure at each circuit over a variety of peak-load


conditions. As a system expands, or as the load
requirements change, even a properly sized valve may
have to be replaced or readjusted to account for the
change in differential pressure, otherwise it will be
chilled-water supplytemperature on the building side. improperly sized for the application and won't control
flow through the coil aswell asit could.
Cooling coil control valves (and actuators) in customer
buildings are typically applied to control space temperature A pressure-independent control valve can be properly
and humidity or coilsupply-air temperature conditions. sized bythe design flow rate for the coil alone and adapts
easily to changes in the differential pressure in the
Ineitherapplication, valves should not be used to control location where it is applied or as the system grows. This
the delta T or the chilled-water return temperature technology isnot unlike pressure-independent VAV boxes
unless the intent isto temporarily curtail the load or the that were developed in the 1970s. It is a fundamental
flow to prevent a loss of system capacity or cooling change in design that, when properly applied, hasbeen
delivery to other customers. shown to helpresolve low deltaT andotherperformance
issues in the districtcoolingand HVAC industries.
To achieve high delta T across cooling coils and customer
buildings through a range of load conditions, the control Cooling coil control valves can have anenormous impact
valves and corresponding actuators must on the total districtcooling plant and distribution system
obe able to shut off against the full-rated head of performance. It is important fordistrict cooling companies
the pumps; to helptheir customers broadly consider the system and
ebe properly selected andsized in the hydraulic gradient delta T performance when choosing a control philosophy.
so that the valve uses its full stroke whether it is
located close to or far from the pumps;
ohave high rangeability for controlled operation at very 5,1,4 Building pump control
low flow (leading to high turndown when properly Building pump control may be a negotiating point
sized); and between the building customer and district cooling
oopen and close slowly, and not "hunt:' even in the provider. It is important to achieve high return-water
presence of real-time pressure fluctuations. temperature to the plant without adversely affecting
comfort control in the building. Low return-water
temperature increases the energy consumption and
An oversized control valve will not use its full available
reduces available system capacity. High supply-water
stroke and will have limited system turndown in the
temperature orinadequate differential pressure may result
location where it is applied. On the other hand, an
in poor comfort control and lost cooling revenue. These
undersized control valve doesn't have the capacity to
issues can be avoided with proper district and building
deliver theflow required to serve the load with theavailable
system design, control and operation. The district cooling
differential pressure.
provider needs to educate its customer on how to
properlyoperate and control the pumps or negotiate to
manage pump operation and control themselves.
Ultimately, pump control must ensure that the cooling
load is satisfied in each zone.

Poor valve sizing is one of the most common problems Morethan one differential pressure sensor in the building
leading to poor deltaT performance. Most control valves may be required for pump speed control. By locating
in the industry are selected by linesize, ruleof thumb (for these sensors at the hydraulically most remote point(s),
lowpressure drop), or by an "authority" calculation that the pump control system canensure that there isalways
ignores the location of the valve relative to pumps. This enough differential pressure to satisfy the load conditions.
maybe partially dueto the difficulty, uncertainty and cost If the control point istoo close to the pumps, it is difficult
of modeling the hydraulics, especially in a growing to set the appropriate differential pressure for all load
system. Manual balancing valves attempt to compensate conditions and may overpressure orstarve portions of the
for this by reducing excess differential pressure at each system. If the control point is at the physically, but not
coil, but cannotadjustto growth or changes in the load hydraulically, most remote point(s), it may not enable the
profile. Flowlimiters (automatic balancing valves) clipflow system to provide enough differential pressure to deliver
at 100% over a range of differential pressures, doing chilled-water flow where it is required. Unless the intent
little to prevent low deltaT or loss of comfort control. isto curtail the flow or load, pumps should not be used
to controlthe return-watertemperature or delta 1. asthis
With conventional pressure-dependent control valves, may lead to issues with coil capacity, fan energy and
proper sizing requires knowledge of the differential comfort control. If necessary, the differential-pressure

28
DISTRICT COOLING BEST PRACTICE GUIDE
02008 Intema~onal Di5t1ict EnergyA550daliOfl. All right> reserved.

setpoint may be reset at part-load conditions to further Chilled-water supply temperature on the building
reduce pump speed and energy consumption; however, side of the ETS is at or below the design entering
reset should never compromise thesystem's ability to satisfy water temperature for cooling coils - While it is
the air-temperature and humidity control requirements. possible to raise the chilled-water supply temperature at
part-load conditions and still serve the load, it isn't
5,1,5 Water treatment and necessarily a greatenergy-efficiency strategyeven with a
heat-transfer effectiveness reduction in chiller-compressor lift (work). See section
Proper chemical watertreatmentin the building system is 5.6.1 for more details about supply-water temperature
essential. Cooling coil heat-transfer effectiveness is reset.
reduced by waterside fouling (i.e., slime, scale or corrosion
on the inside of the coil tubes) and airside fouling (i.e.,
dirt buildup). Any reduction in coileffectiveness decreases
coil capacity and increases the flow rateof water required
to deliver the desired leaving-water temperature, thus
reducing delta T. With direct-eonnected customers, water
treatment should bemanaged bythe district cooling utility
or itswater treatment supplier. It isgood practice to have
an inline cartridge filter that is mounted in sidestream Distribution return-water temperature on the district
configuration in each building, especially with side of the ETS is at or above chilled-water plant
direct connections. design - Plant energy efficiency and available capacity
depend on high chilled-water return temperature.
5.1.6 Additional economic opportunities However, directly controlling the return-water temperature
When the district cooling system andthe building systems or delta T with pumps or control valves is not recom-
are considered as an integrated whole. manyopportunities mended in normal practice as it may compromise the
arise to reduce system first cost while improving differential pressure or building supply-water temperature
economics for boththe utilityand itscustomers. If chilled- required to deliver adequate cooling. Ultimately, high
water rate structures are established that drive the delta T is achieved with proper cooling coil and control
customer to make good economic decisions that also valve selection, piping and pumping design and supply-
benefitthe utility, thena frameworkisin place to capture water temperature control.
savingsand improve operations.
Supply-temperature rise between the chilled-water
As an example, when building systems are properly plant and ETS is reasonable - Modesttemperature rise
designed and-controlled, it ispossible to relyon highdelta is expected in districtcooling system supplypipes. It can
T performance. This enables the building and district be higher at low loadwhen the surface area of the pipe
cooling system designers to reduce excess safety margins is large relative to the flow rate. Depending on the
that can increase the capital, energy and operatingcosts climate, depth, geology and pipe design, chilled-water
of the system. temperature mayeither rise or fall in the return pipes. If
the supply-water temperature rise istoo high, it can indi-
As another example, if lowertemperature chilled water is catea problem with pipeinsulation integrity, poor control
produced using ice, low-temperature fluid, or series or return water blending at the central plant through a
chillers, it canreduce the customer's coil,pump, pipefan, primary-secondary decoupler or non-operating chiller.
duct and heat exchanger size in addition to the Ultimately, the district cooling provider must deliver the
distribution pipe size. This enhances the district cooling supply-water temperature promised to customers and
benefit for the customer by reducing building first costs. account foranyheatrise inthe plant's design andoperation.
It also can decrease building pump and fan energy
consumption. For the districtcooling utility, higherdelta T
reduces the distribution pipesize andcost. Peak loads and
electrical infrastructure requirements maybe reduced.

5.2 System Performance


Metrics at the ETS
Distribution delta T is at or above plant design - The
With good metrics it is possible to evaluate the district distribution delta T on the districtside of the ETS should
cooling distribution system performance at each ETS and exceed plant design in both peak- andpart-load conditions.
to take steps to understand and address issues. District If delta T is low, more flow is required per unit cooling.
cooling companies should define their own metrics to This is inefficient, asit may increase the operating hours
evaluate performance for each customer. In the examples of equipment in the plant or reduce available system
belowthe metrics are intended to establish that a system capacity. Ideally, the deltaT will exceed system design. A
is performing well at peak and part load. bestpractice emerging in the districtcooling industry isto

29
~~~~~~~~~

D1STR10 COOUNGBEST PRACTICE GUIDE


102008Intemalional Districr EJ1ergy As$Odalion. Ailrights reserved.

connect chilled-water tariffs to delta T performance. system and causes a serious leak, this could cause the
entire system to shut down if the system makeup supply
Maximum flow rate and load do not exceed cannot rapidly refill the system. Since the customer's
contract capacity - Both the maximum flow and load system consists of many components, the offending
should be monitored and managed because they may source could be any cooling coil or other equipment in a
not always be coincident. Flow with low delta T at hidden location.
part-load conditions could be more than with high delta
T at peak-load conditions. Some customers may shut off Furthercomplicating the design for direct connections are
their cooling at night and let the temperature in the water such devices aspressure-reducing valves in the supply line
rise. If it rises too high there can be a high demand for and pressure-sustaining valves inthe return line. The need
cooling as the system starts. This can be managed with for such devices depends on the size and design of the
controls, a flow limiter at the ETS, or a small bypass at the district cooling system,elevation differences and types of
end of the loop in the building that doesn't permit the customersand building systems.
water temperature to rise too high. Another strategy in
lieu of night setback is to cycle the air handlers at night.

Sufficient differential pressure is monitored and


maintained at the ETS and hydraulically most
remote polntts) in the building - This is intended to
let the district cooling utility know if there is a problem
preventing the delivery and sale of chilled water. A
Direct connections are most suitable in a system with
differential-pressure sensor at the hydraulically most
relatively flat ground and new low-rise buildings where
remote point(s) within a customer's building will provide
the static head in the distribution system can be kept low.
an indication if enough differential pressure is available
The designershould be careful that in no case should the
to deliver adequate flow to each load. This is important
customer's building exert a static pressure on the
whether a customer is directly or indirectly connected.
distribution system greater than the system's return
pressure (pressure holding).
5.3 Selecting Direct or
Indirect ETS Connections In a system with a combination of direct and indirect
connections, the district cooling provider may set a static
Although connecting the customer directly to the district column height limit where heat exchanger indirect
cooling system is an economical option (no heat connectionsare required. The building designer can then
exchanger to add to the cost or approach temperature place a smaller heat exchanger on a higher floor to
to degrade performance), direct connections should be reduce the size and expense while not exceeding the
considered only for low-rise buildings or compact district maximum allowable return pressure in the utility's
cooling systems with a limited number of customers distribution line.
where a strong partnership between the district cooling
service and building personnel can be built. Direct connections may beappropriate inthese instances:

Sincethe water deliveredfrom the plant is also circulated 1. The utility and customer may be the sameowner or
in the customer's internal building system, all involved havea strong working relationship and contract. The
must know and understand the risks and consequences customer and utility both know and understand the
if something unexpected happens in the system. For risks and consequences if and when unexpected
example, failure inone customer's system can cause the problems arise in the system.
entire system to shut down, thus interrupting cooling to
all the other customers. For reliable operation, it is 2. Building height and static head for the customer's
important that the building owner be vigilant in detecting building is not a concern for the utility and will not
leaks and ensuring no contamination occurs to the lead to higher pressure-rated pipe and equipment
circulating water. Also, in direct connections, water in the plant and distribution or issues with open
treatment is provided at the central plant, thus the storage or expansion tanks at atmospheric
treatment program is outside the customers' control. pressure. Components are capable of managing
(possibly with pressure-reducing valves) the full
When designing a direct-connect system, care must be spectrum of pressures induced by the tallest water
taken to protect the safety of the customer installation column and the shutoff pressure of the distribution
and the reliability of the district cooling system. The pumps. All system expansion compensation is
district cooling owner must weigh the benefits of accommodated at the district cooling plant and the
economy against the risk for a serious failure. If one compression tank has adequate capacity for the
customer fails to properly maintain and operate its direct-connection water volume.

30
DISTRlcr COOUNG BESTPRAcrlCE GUIDE
102008 International District Enefgy k500il~on, Allrighl5 reserved.

3. The distribution fluids in the plant and customer's exchanger on both the chilled-water supply and return
building arethe same and can mix. Waterqualityor sides at peak design conditions.
contaminants in the customer's building can be
addressed and won't adversely affect the plant or
other customers. Watertreatmentwill be managed
bythe districtcooling utilityor itstreatment supplier.

4. Available space in the customer's building islimited.


The customer will take advantage of space not
otherwise taken by heat exchangers, pumps,
expansion tanks, water treatment and other 53.1 Direct connections
equipment. Significant first-cost reductions, including A decoupled direct connection asshown in Figure 5-2 is
connection charges, are sought. typically configured with a crossover bridge, building
pump and building supply- or return-water temperature
5. The customer seeks the simplest possible operation control valve. The crossover bridge permits return water
and will follow system configuration, control and to blend with supply and is intended to hydraulically
maintenance recommendations. The contract reflects decouple the building from the central plant and main
the importance of high chilled-water return distribution. The bypass at the end of the loop maintains
temperature to the plant. chilled-water flow in the circuit to reduce the high load
after night setback.
6. (hilled-water flow will be controlled in a manner
that ensures high delta T and prevents demand in
the customer's building from adversely affecting the
available differential pressure and flow to another.
Pumps can't overpressure the return.

7. The makeup water system in the plant has enough


capacity to replenish the loop at a rate in excess of
the possible 1055 at the customer's building.
Alternatively, the customer has a system that will Figure 5-2. Decoupled direct ETS connection.
warn about and prevent chilled-water 1055.
Indistrict cooling operations, decoupled direct connections
8. There are expected first-cost advantages since
may beused when muchcolder supply-water temperature
smaller fans, ducts, pumps and motors can be used
than coil design is produced at the plant. Return-water
and possibly no pumps are needed. Energy
temperature control is not recommended in normal
advantages could result from colder watersupply to
operation as it may lead to supply-water temperature
customer's coils and higher return-water temperature
instability, an increase in building pump and fan energy
to the central plant. consumption, and possible comfort control problems. It
can also reduce the (latent) cooling revenue for a district
An indirect connection should be considered when cooling utility.
othe static head increases the system return (holding)
pressure in the plant or risks increasing the design If the load or flow must be temporarily curtailed for a
pressure for the piping system, problem customer, the control valve inthereturn line to
othe districtcooling utility uses chilled-water additives the plant may be used to manage the return-water
or has a differentphilosophy for watertreatment than temperature on the load side of the crossover bridge;
the building owner, however, the supply-water temperature must also be
othere isa risk of equipmentfailurethat could lead to managed to prevent latent cooling problems.
a loss of water from the plant and adversely affect all
customers and/or As an alternative, it ispossible to provide cooling without
othe district cooling company simply wants a clear a crossover bridge or building pump; however, it takes
physical break between their operations and their careful analysis of the hydraulics to be sure that the cen-
customers' buildings. tral plant(s) always generate enough head in the distri-
bution to satisfy the load. In locations closer to central
The disadvantages of indirect connections are higher plantpumps, wheresufficient differential pressure isavail-
installation costs, less efficient energy transfer and able, a direct-connected building asshown in Figure 5-3
additional space and complexity for the customer. With may require no more than a supply and return pipe with
typical heatexchanger and system design, about 1 ( to the appropriate water treatment, water filtration and
2 ( (1.8 F to 2.7 F) is generally lost through the heat energy metering.

31
-_._-----------------

DlsmlCT COOUNG BEST PRACTICE GUIDE


e2008 Inrema~l)l1al District Energy A55rxialion. Alln'ghl.'.i re>erVed.

As an alternative, a control valve may be applied at each


heatexchanger (Figure 5-5). This may be desirable when
WSPllmpwilllpareilEll redundancy requirements are high. If it isproperly selected
Ily])a!lSBndC!1eCKII8I...e
InstEIIlllCl onlyII bulidlll9 and sized for the differential pressure in the application,
ishyt!rnullcallyrlllTlCttl
it will eliminate additional balancing requirements.

Figure 5-3. Simplified direct ETS connection.

For the customer building, this is the simplest intercon-


nection but mustbe applied with care to avoid hydraulic
issues and low delta T. It saves valuable real estate space CHWR
and eliminates all the additional equipment required in a
typicalindirector decoupled direct connection, including
Figure 5-4. Indirect ETS connection (with combined
piping, pumps, controls, heat exchangers, chemical HEX control valves).
treatment and expansion tanks. This approach can also
be modifiedat hydraulically remote locations with a series
(booster) chilled-water pump that is installed with a
parallel bypass and check valve so that the pump is only
run when required.

Figure 5-5. Indirect ETS configuration (with dedicated


HEX control valves).

5.3.2 Indirect connections


An indirect connection uses heat exchangers (HEX) to In an indirect ETS configuration, the district cooling
physically separate the district cooling provider from the provider typically takes responsibility for the heat
customer. A heat exchanger is a device used to separate exchangers and components on the district side. The
the utility and customer's heat-transfer fluids and building owner takes responsibility for the piping and
pressures. The district cooling provider supplies chilled components on the building side. Other components in
water to heat exchangers to cool the chilled water used an indirect ETS mayinclude makeup water connections,
in the customer's building for comfort and process expansion tanks (upstream of building pumps), water
cooling. Heatistransferred through the device, but fluids treatment and filtration equipment, backflushing valves
and pressures don't mix. and other indication and controls. Ultimately the district
and building-side design and operation must be
Only one heat exchanger is required, but two or more integrated for the ETS and total cooling system to work
heatexchangers may beinstalled in an indirect connection properly. It isgenerally recommended that the building-side
to facilitate maintenance of one unit and provide a level water treatment procedures be reviewed by the district
of redundancy (as shown in Figure 5-4 and Figure 5-5). cooling provider to ensure that the water passing through
Large installations (more than 2500 tons) may require the heat exchangers is sufficiently treated and chemical
multiple heat exchangers just to meet peak-load levels are maintained within recommended limits.
requirements. A y-strainer (not shown) istypically installed
and maintained to keep the heat exchanger and the Figure 5-6 is an example of an indirect connection,
control valves clean and clear. including two heat exchangers, piping, valves and
controls. It shows the district chilled-water supply (CHWS)
On the utilityside a single (high-rangeability) control valve lines and building chilled-water supply as well as the
in the return lineto the plant maybe used to control the chilled-water return (CHWR) lines for each. This installation
supply-water temperature to customer coils provided it is serves a 92,900-sq-m (1 million-sq-ft) building with a
properly sized. Sometimes more than one control valve 3350-ton cooling load.
in parallel isused to increase rangeability andredundancy
or to handle largerflows. Manual balancing valves are
normally not needed for shorter runs with a properly sized
header. For longer runs, a balancing valve may be used to
ensure that differential pressure across each heat
exchanger is held constant.

32
DISTRICTCOOLING BEST PRACTICE GUIDE
02008 Inlem,,/ion<!1 DistJid: EnergyA55DCianOl1. Ail righl5 reserved.

140%
§: \
!• 120%
~
! 100%
\
,•
DistrittCHWR

Building CHWR

Building CHWS
~
~
••
•••
80%

60%
", '-
-,
Oistri~tCHWS •
!
•"
40%
.... "'",
20%

0%
r-- ...r-- ....
0.5 1.0 1.5 2.0
HEX Temperature Loss('C)

Figure 5-8. HEX surface area vs. "approach."

5.4.1 HEX temperature requirements


Figure 5-6. Plate-and-frame heat exchanger installation. The" approach" (temperature difference between the
First cost, stability, energy, complexity andfootprint should district and buildingsupply- or return-water temperatures)
all be considered in evaluating indirect ETS design will drive surface area requirements and cost. A smaller
configurations. Ultimately, supply-water temperature approach requires a larger heat-transfer area. A larger
control and sufficient flow to customer coils are the approach requires a smaller heat-transfer area. Figure
critical parameters for good comfort control, available coil 5-8 showshow the heat exchanger area increases asthe
capacity and building energy performance. If supply- approach temperature on the supply side decreases.
watertemperature iswell controlled, piping configurations
can vary.

5.4 Heat Exchanger Considerations


A typical plate-and-frame heat exchanger isillustrated in
Figure 5-7. Since heat exchangers are one of the major
components in an indirect ETS, it isessential that they be Starting with a baseline districtsupply- and return-water
properly selected to serve the duty required based on both temperature, it is easy to evaluate how increasing the
the district cooling provider and customer temperature, approach on either the supply or return side will change
differential pressure and pressure-rating requirements. the heat-transfer surface area and cost and can help
SS-CLAODED deliverbroadersavings to the districtcooling company or
PRESSURE
CARRYING BAR its customers. A typical districtcoolingsystem may have
I
PLATEPACK
f a design supply and return temperature of 4.4/13.3 (
1
PLrATE'\ (40/56 F) on the districtside and 5.5/14.4( (42/58 F) on
the building sideof an indirectconnection.

---"
SUF'f'ORT
To reduce district cooling distribution and indirect ETS
cost. the approach could be increased and chillers, ice
SUPPORT/if
FOOT Heat Exchanger (HEX) HEX1 HEX2
(ooling Load 1000tons
Inlet Temperature ( (F) 4.4 (40) 2.2 (36)
FRAME PLATE Outlet Temperature ( (F) 3.3 (56) 3.3 (56)
Figure 5-7. Plate-and-frame heat exchanger (courtesy Flow Rate Ips (gpm) 94.0(1489.6) 75.1 (1190.7)
Alta Laval). Pressure Drop kPa (psi) 60.1 (8.71) 40.9 (5.93)
Heat exchanger selection should be broadly integrated Footprintsq It (sq m) 2.62 (28.2) 2.16 (23.3)
with the total district coolingsystem design. Thechoices Relative Cost Index 1.00 .690
madein the system can have a verysignificant impacton
Table 5-2. Sample heat exchanger differences with colder
the capital, energy and operating costs for a district supply-water temperature and common bulldinq-side
cooling utility and its customers. conditions.

33
DISTRICT COOLING BEST PRACTICE GUIDE
C!2008Intemational District Energy A55ocI'ation. All rights reserved.

storage or low-temperature fluid thermal storage could The allowable pressure drop across the heat
be added to lower the supply-water temperature to 36 F exchanger (including pressure drop inports, connections,
(2.2 C) (as shown in Table 5-2). A 20 F (11 C) delta T and across the plates) is one of the critical parameters to
system design reduces the districtflow-rate requirements be considered during selection. The higher the pressure
by 20%. Pipe and fitting size, system pressure and pump drop, the smaller and less expensive the heat exchanger
power requirements all decline aswell aspeak powerand will be. Forthe customer at the hydraulically most remote
electrical system requirements. Building equipment location(s) it is critical to minimize the pressure drop
remains the same. Producing colder supply temperature because that customer will setthe pumping requirements
for thermal storage may increase the chiller energy for the entiresystem. Minimizing the pressure drop at the
consumption; however, it may be offset by the energy critical customer will decrease pump requirements and
saved with coldercondenser water temperature (at night annual pump energycost. Figure 5-9 illustrates how the
in dryer climates) and a decrease in pump energy pump head requirement for the whole system depends
consumption (with higherdelta T). on the design of this critical customer.

Conversely, if customers have incentives in their contracts


to achieve high return-water temperatures, they might ...
............. ;,;.;.+.~....... critical
be inclined to invest in greater capacity coils and better
........... _..·.. ·····~·~·~·+ .. ""+-·.. ,·~t-:-.... ~·~~I~~~er
control to achieve the results that they seek. Again, a
higher approach on the return side decreases the heat
exchanger area and cost. Higher building-side delta T ••••.••.••••••••.••••••..•••••••••••••••••.. . .••.•••.•••••••••••. ~I
,i
,
decreases building pump and piping system cost aswell customer oonnectlons

as pump energy consumption. !

Distance from District Cooling Plant

Figure 5-9. Importance of critical customer design.


A combination of the two approaches could enable the
customerto reduce the supply-air temperature to reduce When converting a building from self-generation to
air-flow requirements, duct and fan size and fan energy district cooling, it is important that the heat-exchanger
consumption while the district cooling company takes differential pressure be compatible with the building
advantage of the expected savings in its system. Boththe pumps. This usually means the pressure drop of the heat
customer and the utilitycan benefitfrom careful technical exchanger should not exceed the pressure drop of the
and economic consideration of delta T optimization. evaporator of the chiller being replaced. If the pressure
drop is greater, then the building system pump-pressure
5.4.2 HEX pressure requirements curve will be changed, which couldcause flow-balancing
The design pressure and allowable pressure differential problems in the building system. However, building
(DP) on both sides of the HEX must be assessed. The systems tend to beoversized, so after some investigation
building side is veryoften the critical parameter because there might be more differential pressure available than is
high-rise structures canexert high staticpressures and low indicatedfrom the projectequipmentschedules.
delta T forcesthe pumpsto generate much higher head
to serve the load. 5.4.3 HEX redundancy requirements
When assessing redundancy requirements, it is important
In most large districtcooling systems in the Middle East, to understand the criticality of each load. Forexample, if
the required design pressure on the cold side (district side) there are 24-hour process loads (e.g., computer room
of the plate heat exchanger istypically 16 bar (232 psi g); cooling or other water cooled process equipment), then
however, in the case of high-rise structures, the building the engineerdesigning an indirectsystem might want to
chilled-water system pressure may dictate the design consider adding a separate heat exchanger for those
pressure classification for the heat exchanger as well as loads. Tominimizeservice disruptions to a hotel, hospital
other piping components. High-rise structures may have or data center, selecting two or more units increases
higher design pressures. Generally. plate heatexchangers system reliability.
can be designed in the following design pressure steps:
10, 16, 18,20 and 25 bar (145, 232, 261,290 and 363 With multiple heat exchangers, the customer can plan
psig). Highernon-standard design pressures ashigh as34 maintenance at part-load conditions or count on at least
bar (493 psig) can also be accommodated by several some cooling capacity when a heat exchanger is
manufacturers. unexpectedly taken out of service. For especially critical

34
DISTRICT COQUNG BEST PRACTICE GUIDE
e2008lnfemillionill District EnergyAssociation. Allnghtsreserved.

customers, it might be necessary to use multiple units i.e.• slime, scale. During commissioning, blockage of the
such that when the largest unit is out of service, the heat exchangers isa verypresent danger. It isessential to
remaining capacity issufficient to meetthe critical load. connect heatexchangers afterproper flushing procedures
are followed. A y-strainer with a maximum mesh size
Theredundancy requirements are typically established on 75% of the channel depth must be used upstream to
an individual customer basis. Generally, the redundancy both circuits duringstartup. It mayneed to be smaller to
requirements are lowerfor a building served from district protect the control valve(s) on the district cooling
cooling compared to individual on-site chiller operation provider's side.
since a heat exchanger has no moving parts and is not
likelyto "breakdown" likea chiller might. Water quality - The material of construction of the heat
exchanger plates ismainly dictated bythe level of chlorides
present in the water passing through them. Table 5-4
Tonnage Tonnage per heat exchanger illustrates recommended limits.
Demand 2-manifolded 3-manifolded 4-manifolded
1000 600 400 300 T=20°C (68°F) T=80°C (176°F)
2000 1200 800 600 pH level AISI304 AISI316 AISI304 AISI316
3000 1800 1200 900 5 20 400 4 30
4000 2400 1600 1200 7 120 1150 32 120
5000 3000 2000 1500 9 500 10000 140 600
6000 - 2400 1800 Table 5-4. Recommended maximum chloride content (ppm).
7000 - 2800 2100
Utilities issue thechloride limits to building-side consultants
Table 5-3. Tonnage capacity per heat exchanger. and usually actively monitor or oversee that water
treatment on the building side oncethe heatexchangers
For example, on a typical energytransfer station in the are in operation.
Middle East, the design would employ one of the
scenarios (with 20% redundancy) shown in Table 5-3. The Partial load analysis - Many district cooling providers
building yearly load profile usually defines the number of ask for a partial loadanalysis for heatexchangers to be is-
heat exchangers manifolded in an ETS. sued by the manufacturer. This informationisrequired to
assess how the heatexchangers will perform at part loads
5.4.4 HEX performance efficiency as well as changing delta T and log-mean temperature
In an indirect ETS configuration, the heatexchanger is a differences (LMTDs).
critical element in the efficient energy transfer from the
district cooling provider to a customer. Having nomoving
parts, the risk of a major mechanical failure of the heat
exchangeris very low, but this does not eliminate the
need to manage the performance efficiency. Efficiency
and reliability depend on system cleanliness, flow rates
andtemperatures. Performance monitoring coupled with
predictive maintenance practices help ensure efficient
energy transfer andsystem reliability.
5.5 Control-Valve Considerations

HEX monitoring - With most heat exchanger connec- A greatdeal of emphasis should be placed on selection of
tionsit isvery important to collect temperatures and pres- control valves and control strategy for both the district
suredrops for both inlets and outletsas wellasthe water and customer to ensure both the district and building
flow rate. systems are operating properly.

Other connections - It is also good practice to have In customerbuildings, demand for flow to cooling coils
connections to enable cleaning in place built into the heat is driven by air-flow, temperature and humidity require-
exchanger piping as this is usually the first line of action ments. Cooling coil control valves typicallymanage the
when heat exchanger performance deteriorates. chilled-waterflow through a circuit to maintaina given
air-temperature setpoint whether it is in the duct or at
5.4.5 Other HEX considerations the zone.
Strainers - Since the heat exchanger is essentially an
interface device between the district cooling provider and In an indirect or decoupled direct connection, ETS control
the building, proper water treatment on both sides is valves are typically used to control the chilled-water supply
essential. Heat-transfer effectiveness isreduced byfouling, temperature on the building side of the interface.

35
DISTRICTCOOUNG BEST PRACTICE GUIDE
02008 International Di5trktEnergy A55ociation. AI!dghlS ff!5ervro.

5.5.1 location and applications depends on an accurate estimate of the differential


Table 5-5 identifies common applications at the ETS and pressure at the location whereit isapplied in the system.
in buildings that require flow control to manage air tem- In contrast, with a pressure-independent control valve,
perature and humidity, as well as chilled-water supply the flow rate through a cooling coil or heat exchanger
temperature. Managing all of these properly will lead to only varies with a change in load. Proper sizing is
higher delta T performance. At an energy transfer station, independent of the differential pressure at the location
flow control may be used to manage the chilled-water whereit isapplied in the system.
supply temperature. Further in the building, an end of the
loop bypass (normally closed) may control flow to keep Pressure-dependent control
cold water in the loop so that high demand isn't created
during morning startup. Alternatively, air handlers may Figure 5-10 illustrates a common pressure-dependent
be cycled at night to minimize excessive demand. "globe" valve. There are many types of pressure-dependent
control valves used in the industry, with a wide range of
Application Control Point!s) quality, characteristics andperformance. Inpractice, many
of these valves are improperly sized andselected for lowest
Common fan coil unit Space temperaturelhumidity
initial cost. It contributes to poor delta T performance,
Advanced fan coil unit Leaving-air temperature especially at part load, leading to longer-term issues and
Constant-speed costs for the district cooling provider and its customers.
air-handling unit Space or return-air
temperaturelhumidity
Variable-speed
air-handling unit Leaving-air temperature
Indiredenergy
transfer station Chilled-water supply temperature
Decoupled direct
connection Chilled-water supply temperature
End-of-Ioop bypass Supply-water temperature
Table 5-5. Control-valve applications and control points.

Figure 5-10. Pressure-dependent "globe" valve.


Control-valve rangeability is a ratio of the maximum to
minimum controllable flow. High-rangeability v-port ball
valves and double-acting globe valves are two types of
Direct control of return-water temperature and delta T high-grade pressure-dependent valves that have been
are poor practices that lead to problems for both successfully used to increase control. Commercial-grade
customers and the district cooling system. When pumps charaderized ball valves are another example. All these
are used as temperature (instead of pressure) control valves must still be properly sized in the hydraulic
devices, theytendto starve hydraulically remote circuits of gradient to be effective and must be individually
the flow they need to satisfy the load. When control controlled to react to real-time pressure fluctuations in
valves are used to control the chilled-water return thesystem to maintain a reasonable setpoint.
temperature or delta T, chilled-water supply-temperature
control is typically lost, leading to other performance Figure 5-11 illustrates the flow rate through controlvalves
issues. These methods should only be considered tem- as a function of valve opening (or actuator position).
porarymeasures designed to curtail the flow or the load. "Equal percentage" charaderistics as shownare intended
to create a consistent lineargain through the flow range
Controlvalves are usually connected in the return lineto when combined with the cooling coil or heat exchanger
reduce condensation andshould be installed isa waythat capacity curve shownearlier in Figure 5-1. Unfortunately,
prevents condensation from dripping onto an electronic the effectof poorvalve rangeability, improper valve sizing
actuator. and increased supply-water temperature is not reflected
in the chart.
5.5.2 Control-valve types and characteristics
Control valves can be divided into two major categories: A valve with poor rangeability will not controlwell at low
pressure dependent and pressure independent. With a flow and may" hunt" for the right position to address
pressure-dependent control valve, the flow rate through changes in load and differential pressure. Common but-
the cooling coil or heat exchanger served will vary with terflyvalves aren'ttypically considered control valves since
changes in load and differential pressure. Proper sizing they have very poor rangeability at low flow. Conven-

36
DISTRlcr COOLINGBEST PRAcrlCEGUIDE
02008 International DiStrict Energy AmxiationAllrighl5 re!£fWd.

tionaI (pressure-dependent) control valves will only use a independent control valve, the only way to change the
portionof theirstroke if oversized, poorlybalanced or in a flow ratethrough the cooling coil or heatexchanger isto
system suffering with low delta T. With poor control or actively rotate the stem in response to a load change.
rising supply-water temperature, the delta T performance Real-time system pressure fluctuations have no effect on
suffers andfar more flow will be required to serve the load. the flow at any loadcondition.

If a pressure-dependent control isselected by the district If pressure-independent control is selected, it is an


cooling company and the building owner, it should be investment decision made by the district cooling
done considering theeffort and accuracy required to size company andthe building owner to improve control-valve
and select control valves for the system. sizing, stability and delta T performance. When properly
applied, pressure-independent controlvalves deliver more
stable controlandhelpoptimizecooling coilperformance
100% r------"'"!'"---==;)I so that high delta T can be achieved in both the district
and building side of the ETS interface without compro-
mising performance.

"if'
15 50% I--+-----..f--,
a:
5,5.3 Control-valve sizing
One of the mostcommon problems in the HVAC industry
isrule-of-thumb control-valve sizing. Whencontrol valves
are selected bythe same pressure drop as the coilserved,
one line size smaller than the pipe or low pressure drop,
it does not account for the differential pressure in the
50% 100% location wherethe valve isapplied in the system. Selecting
Valve opening valves for "control authority" to matchthe pressure drop
Figure 5-11. Common control-valve characteristics. through the othercomponents in the circuit has the same
effect if the hydraulic gradient is not considered. In fact,
Pressure-independent control poor control-valve sizing and selection is one the main
contributors to low deltaT problems.
Figure 5-12 is a schematic of a pressure-independent
control valve. With this type of valve, the internal piston Selection of pressure-dependent controlvalves at the ETS
and spring operate to maintain a low but constant andat coolingcoils requires knowledgeof the maximum
differential pressure across the control surface so that differential pressure expected in operation at the location
sizing does not depend on location and differential where it is applied. A building or coil control valve close
pressure in the system. In operation, the size of the to the pumps will always have higherdifferential pressure
passage between the piston and the valve outlet varies than those further out in the distribution.
as the pressure varies to keep the differential pressure
across the control surface constant. With a pressure- This differential pressure varies at different elevations and
locations relative to pumps and the plant. It will change
~~,9A~J;~,q.~,~,~~f.r. as the system grows or the load changes. It will rise up
® SPRINGS anddown with the deltaT performance achieved at each

PISTON

----
FLOW

building. There may be a great deal of uncertainty in


SEAL modeling the differential pressure given all the variables
that come into play. This mayhelpexplain why contractors
CONTROL SURFACES in the industry almost always size pressure-dependent
Figure 5-12. Pressure-independent control valve (courtesy control valves poorly or use balancing valves and flow
Flow Control Industries). limiters to try and compensate.

37
DISTRICT COOLING BEST PRACTICE GUIDE
C2008lntemational District Energy Association. Allrightsreserved.

Whether pressure-dependent or pressure-independent 5.5.5 Quality and construction


controlvalves areused, it isessential that theybeselected Cooling coil and heat-exchanger control valve and
to match the building's actual thermal loads as closely as actuator performance affects total plant, distribution, ETS
possible. Oversizing reduces valve and actuator life and and building system performance overthe full life of the
causes valve "hunting." Undersizing limits the flow system. For this reason quality, construction and long-term
capability with the available differential pressure in the maintenance requirements should becarefully considered
system. when control-valve investments are made.

If pressure-dependent valves are used, they must be Industrial-grade control valves and actuators are preferred
properly sized with an accurate differential pressure to and should be selected for high rangeability (100:1
deliver acceptable performance. To enhance rangeability minimum) to enable them to control well at low loads
(controllability at low flow),sometimes pressure-dependent andflows. Components should be high qualityand built
valves are installed in a 113,213 arrangement to splitthe to last taking into consideration the flows, pressures,
low and high flows. Proper sizing requires accurate temperatures, chemicals anddebris expected inthe system.
hydraulic modeling as well as a good understanding of
the loads, anticipated growth and delta T performance
at each building. Rule-of-thumb valve sizing is not 5.6 ETS and Building
acceptable, asit will contribute to low delta 1 Control Strategies

A pressure-independent control valve issized bythe flow 5.6.1 Supply-water temperature and reset
rate alone. The designer doesn't need to accurately When chilled-water supply temperature reset or free
estimate the maximum differential pressure to properly cooling is planned at the central chilled-water plant(s),
size the valve in the hydraulic gradient. In general this it isimportant to not losecontrol of the chilled-wateror
enables it to be selected more accurately to use its full supply-air temperature required to satisfy the load and
available stroke. minimize energy consumption. District cooling contracts
should specify the maximum distribution supply-water
5.5.4 Actuator sizing and selection temperature provided to the ETS by the district cooling
Actuators and control valves should be selected together company. In addition, with indirect or decoupled direct
to ensure that they will operate properly as a system. connections, the supply-water temperature on the
There are numerous choices to be made regarding building side of the ETS should also be specified in the
torque (or force), power input, control signal, fail posi- customer control guidelines and properlycontrolled.
tion, feedback, manualoverride, strokespeed, etc., that
are beyond the scope of this guide. Two-position actu- Reset can have broad comfort, energy and economic
ators are acceptable with valves used for staging or iso- implications and must be considered on a system (not
lation, but generally not for control if high delta T component) level. Chilled-water reset is discussed in the
performance is sought. Modulating control-valve actu- chilled-water plant design and control section of this
atorsthat canaccept a proportional-plus-integral control guide. Keep in mind that it makes no sense to reset the
signal are recommended to improve adjustment, accu- chilled-water supply temperature at the plant to reduce
racyand response. chiller-compressor lift and energyconsumption if it leads
to a loss of comfort control or a net increase in the total
energy consumption for the districtcooling company and
itscustomers. Reset mayalso not be suitable in the plant
if it adversely affects even one critical building on the
distribution system.

It is important for control-valve actuators to be sized to


open and close the valve against the maximum possible
differential pressure at the location where they are
applied. In some cases this means full-rated shutoffhead
of the pumps. Low deltaT issues will increase the flow re-
Asthe distribution supply-water temperature rises, delta T
quirements and pump head in operation nearthe ETS or
declines, and there is an increase indistribution pump en-
plant. When actuators are undersized and there are low
ergy consumption. This must be balanced against the
delta T issues, they can sufferfrom inadequate torque or
benefit of a reduction in chiller lift andenergy consumption
forceto function properly especially close to the pumps.
at the chiller. Depending on the plant, distribution system
and ETS configuration, low delta T can also lead to (1)
highplantoperating costs, (2) returnwater blending with

38
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lnlemariOllilI DJ5tJiet fnegy Assodari'on. All righ~ re5efVed.

supply, (3) overflow of running chillers and (4) loss of required) should control the supply-water temperature
thermal energy storage capacity. In addition, reset can on the building side of the interface. Delta T or return
reduce latent cooling capacity, humidity control and water temperature control with ETS control valve may
district cooling company revenue. Customer pump and lead to capacity, energy, and comfort issues and is not
fan energy consumption may riseasthe supply water and recommended except as a temporary measure to
supply air temperature rises. More water and air flow is curtail the load or flow with a problem customer.
required to satisfy the load.
Delta T and pump head are interrelated. In the decoupled
Capability for chilled-water reset at the ETS is not direct connection shown earlier in Figure 5-2, low delta
discouraged, but it is imperative that the district cooling T at the coils forces the pump to generate more head to
company and building owner fully understand the circulate the flow. This creates high suction pressure at
implications of reset throughout the entire system the pump that draws more return water into the supply.
before implementation. As a result, the ETS control valve in the return line opens
up to maintain the supply-water temperature in the loop
5.6.2 Supply-air temperature and reset at setpoint. The low delta T problem in the buildings
at cooling coils transfers right through the ETS to the district side.
In North America, many chilled-water systems in buildings
are designed with electric or hydronic reheat at individual The same pump control strategy applies in an indirect
zones. When a large air handler provides cool air to connection with heat exchanger separation as shown
serve many zones, the reheat coil manages the space earlier in Figure 5-4 and Figure 5-5. Given the physics
temperature at minimum air-flow requirements. This is of heat transfer, the chilled-water return temperature to
intended to prevent overcooling in some of the spaces. the district will always be a little lower than the chilled-
Thisapproachoften wastesa lot of energyin simultaneous water return temperature to the building. This means it
heating and cooling, even though the occupant of the is vital to achieve good return-water temperature
space remains comfortable. performance in the building to achieve high delta T in
the district.
Fan-powered variable-air-volume (VAV) boxes are an
alternative to reheat also used to prevent overcooling in In a simple direct connection, there mayor may not be
individual zones. This approach recirculates the return a need for a building pump, depending on the location
air and blends it with the supply air from the larger air and height of the building relative to the district cooling
handler. When the supply-air temperature is too cold, it plant(s). If a pump is used, it can be installed with a
requires additional energy to operate the smaller fans parallel bypass and check valve so that it is only run at
at the zones. high load if the differential pressure at the hydraulically
most remote point(s) in the building falls below setpoint.
A solution to eliminate overcooling and reduce customer
building energy consumption is to reset the cooling coil
supply-air temperature upward at minimum air flow. As
soon as oneof the primary VAV boxes reaches minimum
air flow, the supply-air temperature is ratcheted up a
notch. This process minimizes overcooling and, with
proper control, will reduce the demand and increase
delta T performance at low load. 5.6.4 Capacity control after night setback
Flow limiters (or automatic balancing valves) are
5.6.3 Building pump and ETS designed to limit the maximum flow rate through a heat
control-valve control exchanger, piping branch or cooling coil. A flow limiter is
Building pumps (if required) should be controlled by not a control valve and will not prevent low delta T
either the district cooling provider or the building issues. It is meant to prevent excess flowinone area from
customer to maintain a differential pressure at the leading to lack of flow in another. These devices typically
hydraulically most remote point(s) in the system. This have an insert chosen for a fixed maximum flow rate.
ensures that all circuits have enough chilled water to
satisfy load conditions. Reset strategies may be applied When a customer chooses to shut off its cooling at
to reduce the differential pressure setpoint at part-load night, the water temperature in the building can rise
provided the air-temperature and humidity requirements and create a high instantaneous demand for flow as the
are met in all zones. To prevent comfort and control system is started in the morning. In district cooling
issues in customer buildings, pumps should not be run systems, flow limiters have been usedat heat exchangers
in normal operation to maintain minimum flow, delta T, to limit the flow rate to a maximum flow based on
supply-air temperature or return-water temperature for contracted tons and design delta T. A problem with this
the building or individual loads. ETS control valves (if approach arises at peak load when design delta T is not

39
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lnrPmaDonal DistrictEnergy Modi/lion. Allrigh/$ reserved.

achieved. Limiting the flow leadsto an uncontrolled rise fine dust, which is present in the water.
in supply-water temperature in the building.
5.7 Metering and Submetering
Another concern if customers shut off their cooling
equipment (including pumps) is that the zero-flow 5.7,1Introduction 1
conditions in the building may cause system hunting The energy meter registersthe quantity of energy trans-
problems and can also lead to a large district-side flow ferred from the user's building system to the district
(leak flow) sincethe control valve(s) will open up to meet cooling system. Cooling energy is the product of mass
setpoint. To prevent this from happening, a pump flow, temperature difference, the specific heat of the
status input should be provided to the ETS control water and time. It is difficult to measure mass flow in
system 50 that the control valves remain fully closed an enclosed pipe system, 50 volume flow is measured.
when the building pumps are not running. The result is corrected for the density and specific heat
capacity olthe water, which depends on its temperature.
An alternative to prevent high demand after night The effect of pressure is 50 small that it can be ignored.
setback is for the customer to manage the flow and An energy meter consists of a flow meter, a pair of
temperature control within the building to minimize the temperature sensors and an energy calculator that
instantaneous load. This can be done with a normally integrates the flow, temperature data and correction
closed bypassvalve «1 % of design flow) at the end of factors. It is desirablethat the energy meter be supplied
the line that is controlled to keep the loop temperature as a complete unit and factory calibrated with stated
from rising too high. Another strategy to limit high accuracy performance ratings in compliance with
demand from night setback is to schedulethe startup of accepted metering standards.
air-handling equipment from unoccupied to occupied
mode and operate with outside-air dampers closed until 5.7.2 Meter types
indoor-air setpoints are recovered from night setback The meter is the district cooling systems' "cash register."
conditions. Do not use cheap, inaccurate meters that may leave
doubt in the mind of the customer that it is being fairly
5.6.5 Staging multiple heat exchangers charged for chilled-water service from the district cooling
With multiple heat exchangers, it is important to properly provider.
manage the flow. In an application with multiple heat
exchangers, isolation valves on both the district and The following are brief descriptionsof the most common
building side of each heat exchanger should be kept flow meters suitable for district cooling use. Meters can
open unless heat exchanger maintenance is being be divided into two major groups: dynamic meters,
performed. It is generally not necessary to provide valve which register flow with the aid of moving parts; and
actuators on the building side to automatically stage static meters, which have no moving parts.
heat exchangers unless there is a desire to maintain a
minimum flow. If water is flowing through a both heat Dynamic meters
exchangers on the district side and only one heat
exchanger on the building side, there will be district There are two types of dynamic meters used in district
supply dumping directly into the return, and poor delta T cooling: impeller and turbine meters.
performance. Conversely, if there is water flow through
a single heat exchanger on the district side and both Impeller meters measureflow with the aid of straight-
heat exchangers on the building side, it will be chal- bladed impellers. There are two types of impeller meters:
lenging to achieve the supply-water temperature nec- multi-jet and single-jet.
essary for good control.
Multi-jet impeller meters are very sensitive to impurities
In general, an indirect ETS should be operated with such as sand and sharp metal particles, but are not
variable flow through all heat exchangers, even at low sensitive to flow disturbances. This type of meter is best
load, to take advantage of the lower pressure drop and suited to medium-sized buildings, but not for small
smaller approach. When parallel heat exchangers are buildings because it does not function well at small loads.
installed, approach temperatures may be reduced below
design in operation given the added surface area. Plate In single-jet impeller meters, the flow runs through a
heat exchangers, unlike shell-and-tube heat exchang- single nozzle directed tangentially to the impeller blades.
ers, will almost always have turbulent flow conditions, Single-jet meters have properties similar to those of
even at 10% to 15% of full-rated flow. If the flow is multi-jet meters, but they are more suitable for small
less than 10% to 15%, excess plate heat exchangers buildings because a very weak flow is enough to start
can be shut down to maintain higher flow and cleanli- the meter.
ness across operational units. Proper "seasonal" shut-
down procedures include draining to avoid settling of In a turbine meter, the fluid in the pipe flows through

40
DISTRICT COOtiNG BEST PRACTICE GUIDE
C2008 IntemalionalDistriet Ene'!lYA5soc'alion. JlJI fight!; re>erVed.

turbine blades, causing them to rotate. A turbine meter to 2% depending on the intermediate to low-flow
records only the cumulative volume of chilled water conditions. The pressure drop is very low; for a DN 40
supplied and does not take into account the difference (1-1/2") flow meter it is about 0.07 bar (1 psi) at 3.8 lis
in temperature (delta T) between supply and return. The (60 gpm).
meter's accuracydepends on the flow profile before the
meter, so strong flow disturbances must be avoided. Recent experience indicates that ultrasonic meters are
Generally, accuracy for turbine meters is in the range of also accurate and cost-effective for large flows.
+1- 1.5% to 3% depending on intermediate to low-flow
conditions. The average pressure loss for a DN 40 5.7.3 Designing for meter
(1-1/2") flow meter a13.81/s (60 gpm) is approximately installation and maintenance
0.55 bar (8 psi) - significantly higher than for a static The flow meter could be installed in either the primary
flow meter. supply or return pipe. In some instances, it may be
beneficial to install the meter upstream of the heat
Theweaknesses of this meter are its high startup threshold exchanger and control valves to minimize the possible
and rapid wearing of bearings at high loads and in dirty formation of bubbles in the flow stream, which could
water. Turbine meters are suitable for high flows, but affect the meter accuracy. In most cases, for dynamic
are not suitable for small buildings. meters to ensure uniform flow and accurate flow
measurements, there should be a length of straight pipe
ten times the pipe diameter before the flow meter and
Static flow meters
a length of straight pipe five times the pipe diameter
after the flow meter. This requirement is typically
There are two types of static flow meters that are used
reduced to half the distance for static meters installed
in district cooling applications: magnetic induction (MID)
with reduced pipe-size diameter. The district cooling
and ultrasonic.
utility and meter manufacturer should be consulted for
The MID meter (or mag meter) is based on induction specific instructions.
of voltage in a conductor moving in a magnetic field.
Flow meters should not be installed in the low point of
The conductor in this case is water. The recommended
the piping system where dirt accumulates. Similarly, they
conductivity is '" 5~S/cm. Generally, district cooling
wateris conductive enough for MID metering. However, should not be installed in the piping at the high point of
it is essential that this be confirmed in each specific case. the system, which would cause air to accumulate in the
Furthermore, the magnetite content of the water should meter. To reduce wear on the bearings of a dynamic
also be checked to verify that the recommended value meter, it is important to fit the meter so that its impeller
of 0.1 ppm (maximum) is not exceeded. shaft is vertical. For magnetic meters, the pipes have to
be grounded. Signal cables should be well protected
The water flows through a pipe made of non-magnetic from external disturbances.
material with an exactly known cross-sectional area.
Electrodes connected to powerful electromagnets sense Temperature sensors should always be installed against
the flow. The voltage induced in the water is measured the flow, with the tip of the probe approximately in the
and amplified and the information is converted by the center of the pipe. In addition, a properly sized
heat calculator. measurement housing for the sensor and the water
thermometer should be installed in the primary piping.
Experiencewith MID meters in district cooling has been Pipe increasers or a measurement housing will not be
good. Although their initial cost is higher than dynamic needed when sensor wells can be installed in pipe
meters, consideration should be given to their reduced elbows or when pipe diameters exceed 1OOmm (4
maintenance and increased accuracy. The mag meter inches). In smaller pipes, wells for heat meter sensors
has excellent accuracy, low pressure drops and good can obstruct the flow. The sensors' surroundings should
rangeability, as well as low maintenance. These qualities always be heat-insulated; otherwise, heat loss/gain from
usually justify the higher cost for mag meters compared the sensors distorts the measurement. The sensors'
to most dynamic type meters. wires should be of exactly the same length (e.g.,
matched pair) unless four-wire metering is used.
Ultrasonic metering is based on changes in the
propagation of ultrasonic waves caused by the velocity An MID meter should be fitted so that it is as easy as
of the flow. These changes are registered by measuring possible to clean the pipe and electrodes. Dirt on the
thetime between the transmission and reception of ultra- electrodes creates an extra resistance that causes errors
sonic signals over anexactly known distance orbymeasur- inthe voltage measurement.
ing changes in the frequency of reflected ultrasonic waves.
MID meters are not very sensitive to flow disturbances.
The ultrasonic meter accuracy is in the range of +/- 1% Manufacturers state that a disturbance-free section of

41
DISTRICT COOUNG BEST PRACTICE GUIDE
C2OO8 Inrema~onal District Energy Azodalion.Alln"gllti reserved.

pipe five times its diameter before the sensor is enough, reduced by 20% in multi-residential buildings with
and they recommend that a pipe section two times its submetering.
diameter should be free from disturbances after the
sensor. However, any meter is more accurate if the The implementation, however, is very capital cost
disturbance-free sections of pipe are longer than the expensive and is seldom cost-efficient for the building
recommended minimums. owner. For the district cooling owner it is important to
make sure to include this cost as an installation or
Meters are generally supplied and installed under the demand charge.
supervision of the district cooling company. The district
may also supply a temporary spool piece, the same size Primary energy metering will normally be performed
as the meter, for installation in lieu of a meter until the according to local regulations or international standards,
system is clean and ready for operation or if the meter however submetering for allocate purposes are not
is removed for recalibration. Meter selection and sizing included and does normally not have to follow any reg-
should be verified by the district cooling company ulations.
and/or its engineer based on the information supplied
by the ETS design engineer. For proper meter selection, Submetering can be employed in following ways:
it is essential that the district cooling company under-
stand the building system operations under maximum 1. Measure the thermal energy used for each
and minimum flowconditions. customer.

5.7.4 Standards 2. Measure the total thermal energy used for the
CSA C900 is a Canadian standard for thermal energy subsystem and consumed water volume for each
meters, but it is not commonly used throughout North customer.
America. There are international standards in place like
3. Measure of room temperature in each apartment.
the OIML-R75and the European Standard EN 1434 that
may be used as references. CSA C900 is adopted from
Measurement of room temperature is the least expensive,
EN 1434 with Canadian deviations.
but also the most inaccurate. This method will not show
accurate energy use when, for example, airing a room,
5.7.5 Other equipment and it is not recommended.
Pressure gauges, thermometers and shutoff valves
should be installed to enable proper monitoring, Submetering the water volume consumed is a cost-
balancing and equipment isolation for maintenance. effective solution for subsystems with similar cooling
usage, such as only residential customers etc. The
A strainer with a mesh of 1.2 mm (3/64 inch) or smaller solution provides not only an accurate measurement,
must be installed to adequately protect the critical butalso a mechanism to reward conservation or penalize
components (i.e., heat exchanger, flow meter and wastefulness.
control valves). To determine when the strainer should
be cleaned, a pressure gauge should be connected to For more complex subsystems where the usage is a mix
both sidesof the strainer.The pressure drop through the of different cooling usages, the thermal energy needs
strainer must be considered in the system design. to be metered. Thiswill then be done in the samemanner
as primary metering (the metering unit comprisesa flow
5.7.6 Submetering meter and two temperature sensors together with an
Submetering of individual townhouses, condominiums energy calculator).
or apartment units in multi-residential buildings is
seldom practiced in district cooling systems. Normally Experience shows that subsystems are often a mix of
the district cooling owner charges the building or different cooling usages and the incremental savings of
subsystem owner and then it is up to the owner to using simple water meters versus energy meters is
allocate the costs based on floor area or some other relatively small.
metric.
Meter reading
However, sometimes the customer requires individual
submetering to provide an incentive for a resident to The other issue to be decidedwith respect to submetering
conserve energy. In fact the European Union promotes individual townhomes or multi-residential apartments is
individual metering of all utilities becauseit gives people how the data should be accessed, i.e., either by local
the opportunity to be responsible for their utility usage readings taken inside the units or by remote readings
and costs. For district heating systems this has been taken from the outside. For either meter type, the data
successfullyimplemented in many countries in Europe. could be accessed in the following ways:
Studies show that the energy consumption has been

42
DISTRICTCOOLING BESTPRACTICE GUIDE
02008 International Diwid Energy As.5ooalion. Allrighrs fe:;ervro.

1. Reading inside an apartmentltownhome unit. Data Submetering system via fixedwireless consists of energy
exchange occurs at the location of the energy meter equipped with radio frequency (RF) transmitter,
meter, and in the mostbasic system, this would be concentrators/collectors, TCP~P and computersoftware.
done using a handheld device or a laptop See Figure 5-13.
computer interfacing either through the optical
head or via a plug-in. Based on cost analysis, the Individual energy meters are fitted with radiofrequency
capital-cost saving with local reading is not consid- modules. Each transmitter collects the meter's data
ered to be worth the additionalongoing labor and periodically and converts the measurement into a
administrative cost. This approach also requires digital signal transmission. This data is transmitted via
entry into the unit, which the resident could radio frequency to a central RF concentratorequipped
consider intrusive. with an external antenna. The concentratorcollects the
datafrom individual RF module, decodes the transmission
2. Remote reading via fixed or drive-by wireless network. and stores the meter reads for billing. The concentrator
Underthisoption, datawould be transmitted via a can handleup to approximately 650 energymeters and
radio signal from an output device included in the can be placed indoorsor outdoors. Computer software
meter to a central receiver or a handheld receiver is used to upload the data via the TCP/IP to a central
outside the residential unit.This method iscommonly computer and each submeter can be identified for
used in Europe and in North America. However, a billing purposes by i15 uniqueaddress.
radio frequency license maybe required. This wireless
approach isproven technology and isless expensive. Wireless communication between an RF module and an
RF concentrator takes place within a dedicated
3. Remote reading via the telephone network. frequency band without thereby disturbing other RF
receivers. For this dedicated, uncluttered frequency
strength, license would typically be required through
4. Remote reading via Internet connection through
appropriate local agencies.
the building fiber optic system. If this system will
be in place, then each energy meter can be fitted
Alternatively, at slightlyhighercost, meters supplied with
with a TCP~P moduleand transmiti15 datathrough
RF modules canalso be read by a person driving by along
TCP/IP (an internetcommunication link)to be read
a preset route with an RF handheld terminal, see Figure
by a central computer. Further, the Internet
5-14. When reading isperformed, the handheld terminal
connection must be within the room where the
is placed in a docking station and data istransferred to a
meter is located. One advantage of this system is
central computer. Computer software is used to export
that the energy meters can directly communicate
this data to a billing or analytical purposes.
over the building Internet line and a dedicated
communication system is not required. However,
this system would be dependent on the qualityand
reliability of the building's Internetconnection.

Meter communication links via a fixed ordrive-by wireless


system is the recommended approach for individual
town homes or multi-residential apartments. It is a
proven technology and a cost-effective solution.
Figure 5-14. Submetering system with an RF handheld

COMPUTER
-1&' SILUNG
terminal.

Conclusions about submetering

c.e~Ji~~~fl;;;~
The following are conclusions about submetering
options:

1. Allocating costs based on floor areas or other


parameters issimple andcheap to implement; how-
ever, it does notprovide anincentive fora resident to
conserve energy. There is no mechanism to reward
conservation or penalize wastefulness.

2. Studies show that submetering reduces energy


MUlT!·l£v1"~
consumption. The implementation, however, is very
TOW~HOMES
R~SlDENnAL
capital-cost expensive andisseldom cost-efficient for
Figure5·13. Submetering system via fixedwireless. the building owner.

43
DISTRICT COOLING BEST PRACTICE GUIDE
C2008lnrema~Onal DisrndEnergy A550ciarion. Ali nghlSreserved.

3. If submeteringisto be implemented, the incremental


savings of using simple water meters versus energy
meters are relatively small. Considering that impelier
meters are less accurate and deteriorate faster and
that static flow meters are more suitable for meas-
uring chilled water, ultrasonic energy meters are
recommended.

4. If submetering is to be implemented, meter


communication links via a fixed or drive-by
wireless system would be the recommended
approach for individual townhomes or multi-
residential apartments. Reading meters inside
individual town homes or apartments units is
generaliy more costlyand considered far too intrusive,
and therefore is not recommended.

1 This section on metering draws heavily on "District Heating


andCooling Handbook," a 2002 publication of the International
Energy Agency, Report 2002:56. The author of the cooling
portion of the reportwas Bard Skagestad of FVB Energy Inc.

44
DISTRICT COOUNG BEST PRACTICE GUIDE
C!2008lntemilb'onal DiWictEnergy A5x>diltion Allright> reoerved.

6. Chilled-Water Distribution Systems


A district cooling distribution system is designed to throughout the system, it is possible to dramatically
safely, reliably and efficiently deliver chilled water to reduce both first costs and operating costs while
connected customers to meet their cooling requirements. providing a better and more economically advanta-
Chilled water leaves the plant(s) cold and returns warm geous service to customers.
after capturing the sensible and latent heat from
process and comfort cooling loads. It also picks up heat This chapter highlights design considerations,
from the ground as it is delivered and returned. challenges and best practices for distribution system
design, pumping schemes and pressure control, and
It is imperative for designers to carefully assess the load, distribution piping materials and components.
diversity, flow rate and pressure requirements as well
as heat gain to ensure available capacity and eliminate 6.1 Hydraulic Design
unnecessary waste or excess in the design. A chilled-
water distribution system is one of the largest capital 6.1.1 Hydraulic model
expenses in any district cooling scheme. The system A hydraulic model is a critical investment when
should be designed to accommodate future expansion designing a chilled-water distribution system for a
and designed to last, as it is very expensive to replace district cooling utility. Hydraulic modeling helps to
or resize buried pipe once it is installed. • properly size, select and locate infrastructure and
equipment;
• evaluate pipe routing scenarios and the impact of
loops;
• consider the impact of future customer connections
and load changes;
• account for system diversity;
In the Middle East. particular attention must be paid to • integrate thermal energy storage or additional
corrosion protection of buried piping and insulation chilled-water plants;
design to minimize heat gain. Buried chilled-water • assess energy performance;
piping in the Middle East is often installed at or below • troubleshoot performance issues (like low delta T);
the water table, and ground water can be highly saline, • evaluate the impact of heat gain and temperature
so it is critical that protection of metallic piping and rise in supply and return piping; and
components from corrosion be carefully considered. • identify hydraulically remote locations for pump
Without proper insulation, the chilled-water supply speed control.
temperature to customers could become unacceptably
high due to heat gain from the ground and ground
water, especially during off-peak times. Proper piping
insulation helps minimize the installed capacity of the
plant and distribution systemwhile reducing the added
operating expense of heat gain in buried pipes.
The hydraulic model is a tool that should be maintained
It'sequally important to develop a delta T strategy to op- and updated after initial system design to assist in
timize performance in operation. Low delta T continues to system analysis and future decisions that affect the
be a chronic problem that adversely affects energy, ca- districtcooling distribution network. Recent developments
pacity, comfort and economics in the district cooling in- in software sophistication now allow for real-time
dustry worldwide; however, sound design can eliminate hydraulic models that interface with utility SCADA
these issues without compromising performance. systems, which can aid in distribution system
operational decisions and may reduce network
instrumentation requirements.

The topics discussed below are important to consider


when developing an accurate and useful chilled-water
system hydraulic model.

6.1.2 Customer loads and system diversity


District cooling systems in the Middle Eastare among As discussed in earlier chapters, market assessment
the largest in the world and located in one of the most and load estimation are critical exercises inthebusiness
severe climates. The large loads, large piping networks evaluation and development of a district cooling sytem.
and rapid development growth in the region make Peak-load and usage-type estimates for the projected
efficient and effective chilled-water distribution espe- customer base also are key to proper planning and
cially challenging. If high delta T can be achieved sizing the distribution system.

45
DISTRICT COOLING BEST PRACTICE GUIDE
e2OO8 International Di5rrid Energy Awxiati'on. Allnght5 re:;erved.

80
One of the big advantages of district cooling is the
opportunity to take advantage of load diversity, as _ plant supply loss 5.6 Cdelta T
70
... • 6.7 Cdelta T
discussed in section 4.1.1. If customers connected to \. _ supply piping loss
- - 8.3CdeltaT
.-. - ..
------
the distribution system are expected to have significant 60
load diversity, then the designer should work to use ¥
.§. 50 '
coincident peak loads in the hydraulic model to size
distribution mains, while ensuring that branch lines and 'll "'-
'-----___ • - • -• -•- •- ••~
-• - I
~ 40
service lines to customers are sized to accommodate -~~L
non-coincident peak loads.
,! . __ ::::-r-
6.1.3 Startup and growth
..
:: 30
!
20
-, ~~~~~~~-------T
The initial hydraulic gradient in a distribution system "<, ~eturn piping loss
pump pressure head
differential
pressur~
will change dramatically as more customers are 10
plant return loss
customer
connected and as the system changes and grows.
Distribution system hydraulic modeling for design
o
Distance from the Source
purposes must take this into consideration, particularly
Figure 6-1. Impact of delta T on hydraulic profile.
since the hydraulic model is used in the sizing and
selection of control valves at customer buildings, sizing are responsible for delta T performance in operation. If
and selection of distribution pumps and defining the delta T performance is overestimated, it can result
system pressure limits. Future implementation of thermal in an undersized piping network, pumps without
storage, colder supply-water temperatures or additional enough capacity or stranded production assets. If the
plants may also come into consideration and should be delta T performance is underestimated, it can lead to an
assessed as part of the long-term distribution system oversized system with larger pumps, pipes and other
strategy. System planning also should consider that in equipment, at a significant impact to first cost.
the early years of a developing district cooling system,
before the distribution system is fully utilized, heat gain If the district cooling utility is not prepared to take the
as a percentage of plant chilled-water sendout will steps required to achieve high delta T, then this must be
generally be higher, and chilled-water supply-temperature factored into chilled-water system hydraulic modeling
rise will be higher. Heat gain and temperature rise are and distribution system design. For example, many district
discussed further in section 6.4.4. coolingsystems consist of a mix of both new developments
and existing buildings, and the existing buildings
frequently require a substantial retrofitting project to
improve their building-side cooling systems to get a
high delta T performance from the building. If the district
cooling utility is not prepared to ensurethat these retrofits
6.1.4 Piping layout happen, then the district cooling system designer must
Thedistribution piping layout can be drivenby a number of make a realistic, and likely lower than desired, estimate of
external factors including access, obstacles, elevations the delta Ts that can be achieved from the existing
and geology. For district cooling distribution systems buildingsthat areexpectedto be connectedto the system.
that will run in public streets or spaces, it is critical that Forsystems that will consistprimarily of new development,
the owner or the owner's representatives engage the but also include a small number of existing buildings, it
municipality as early as possible in the district cooling
system development process. This will give the owner
the best opportunity to obtain a desirable utility corridor
for distribution piping and minimize piping burial depth,
which can provide substantial capital cost savings. Once
the preliminary layout is defined, the hydraulic model
can be used to size and select pipe and also can be used
to consider alternative piping layouts, and pumping may be possible to achieve a satisfactorily high overall
schemes and potential future system changes. system delta T without substantial retrofit of existing
buildings. However, this may require the district cooling
6.1.5 Delta T utility to be more aggressive in ensuring that new
The hydraulic profile in a system that achieves high delta developments are designed and operated to produce
T is dramatically different from a model for a system that a very high delta T to offset poor delta T performance
doesn't, as illustrated in Figure 6-1. from the existing buildings. The key is that the district
cooling utility must consciously prepare its delta T strategy
Cooling coils within customer HVAC systems and control before customer contracts are signed, and before final
valves within customer HVAC systems and utility ETS design of the districtcooling plant and distribution systems.

46
DISTRICTCOOLING BEST PRACTICE GUIDE
C2008 Intema~'onal DistrictfrmrgyA550dation. All ngh!Sreserved.

6.1.6 Pipe sizing delivered at a 2.87 mps (9.4 fps) velocity limit in a 900
Ideally, pipe sizing should be determined via life-cycle mm (36") steel pipe with different levels of delta T
cost analysis, to find an optimal economic balance performance. Increased delta T has a significant impact
between first costs of distribution system capital and on cooling delivery capacity.
operating cost over the life of the system.
Delta T Approx. Capacity
Designers should be cautious about using simple C F (tons)
velocity rulesof thumb to sizedistrict cooling distribution
piping, especially for larger pipe sizes. When using 6.7 12 14,200
hydraulic modeling software to size piping, initial sizing 7.8 14 16,600
can be done using a constant pressure gradient (pressure 8.9 16 19,000
drop per unit length) for the piping network and then 10.0 18 21,400
manual adjustmentsmade from there. Forexample, if the 20 23,800
11.1
critical path for the distribution network is known and is
12.2 22 26,200
not expected to change over time, then selective upsizing
of smaller-diameter (and therefore less expensive) piping 13.3 24 28,500
toward the end of the critical path can be prudent. Table 6-1. Impactof delta T on 900 mm (36") pipe capacity.
Velocities in larger piping can be quite high and still
have a reasonable pressure gradient, but the designer Table 6-2 illustrates the tons of capacity of a 1000
must evaluate water hammer risk and take care that horsepower (hp) pump set pumping through 1524 m
velocities are within the manufacturer's recommended (5000 ft) of 900 mm (36") supply and return piping
limits.for the pipe type selected. (fitting pressure losses not considered) with different
levels of delta T performance.
Special consideration should be given to fitting losses
for distribution systems with large-diameter piping and Delta T Approx. Capacity
installations in densely populated areas to ensure that C F (tons)
the magnitude of pressure loss due to fittings has been
6.7 12 22,400
accurately represented in the hydraulic model. For small
7.8 14 26,100
diameter chilled-water pipe [e.g., less than 250 mm
(10")] runs without too many elbows, fitting losses may 8.9 16 29,900
add less than 5% to piping pressure loss, while large- 10.0 18 33,600
diameter pipe [e.g., 600 mm (24") and up] runs 11.1 20 37,400
requiring a significant number of fittings to avoid other 12.2 22 41,100
buried utilities could have fitting losses that add more
13.3 24 44,800
than 50% to straight-pipe pressure loss.
Table 6-2. Impact of deltaT on capacity of 1,000 hp pump set.
To minimize unnecessary design conservatism and cost,
it is critical that the district cooling utility work with the
customers through their contracts to ensure that the
load and flow demands are realistic and that the delta T
performance that is expected will be achieved.
Lastly, when making distribution system pipe size
selection, the designer should be mindful of commercial
availability of pipe sizesin the project region. Odd sizes
that are not commonly available in the marketplace
and/or are not available cost-effectively should be
avoided. For some odd sizes, steel mills may be able to
provide piping if ordered in quantity, but fittings will
There are numerous design tradeoffs that may be
not be readily available. Since it is common that
considered to reduce distribution pipe sizing and, therefore,
unanticipated fittings are required for piping projects
the first costs and/or operating costs of the
during construction, this could cause significant
distribution system. These choices should be looked at
construction delays.
as investments to improve project life-cycle economics
and enablefuture growth. Some examples are asfollows:
• lowering the distribution supply temperature 6.2 Pumping Schemes
• achieving higher delta T across customer cooling coils
• adding a remote plant or thermal energy storage In the industry, there has been a lot of debate about
pumping and piping schemes used in hydronic system
Table 6-1 illustrates the tons of cooling that can be design. In general, variable primary flow is the growing

47
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008lnrem,,~'on"l Di~ EnergyAs5ociation. Allrightsteservro.

trend and is considered to have modest energy and with accurate and reliable controls as well as metering
first-cost savings advantages, a smaller footprint and and indication. Operators must be trained to run equip-
someadded control complexity. Primary-secondary system ment properly within appropriate limits.
design is considered reliable, conservative and easy to
operate. This section will highlight some of the main _...- , . . . - . . . . . , - - - -....- - - - - I C H W S

issues and concerns when considering alternatives for


hydronic system design in district cooling applications. minimum
avapamtor
In the industry, some suggest that it isadvantageous to
start with primary-secondary pumping as a "base"
"'"
bypass

L.......IT€::D-,..L---_------!CHWR

VIS ~umps

Figure 6-2. Variable primary flow.

The parametric study in a research project titled "Vari-


design scheme and then consider the more complex able PrimaryFlow Chilled Water Systems: Potential Ben-
variable primary flow as an alternative to reduce first efits and Application Issues" conducted and released
costs, footprint, and pump energy consumption. On by the Air-Conditioning and Refrigeration Technology
the other hand, others suggest that variable primary Institute (ARTI) states this in its executive summary:
flow is more tolerant of low delta T issues than primary-
secondary systems because the available capacity of Variable flow, primary-only systems reduced total
chillers is not limited by flow. annual plant energy by 3 to 8%, first cost by 4 to 8%,
and life cycle cost by 3 to 5% relative to
When delta T is low, extra flow is required to serve the conventional constant primary flow/variable secondary
load and will need to circulate through the plant and flow systems. Several parameters significantly
connected buildings. If delta T is low at the plant, the influenced energy savings and economic benefits of
system operator must choose from three options: the variable primary flow system relative to other
• blending return water with supply system alternatives. These included the number of
• overflowing running chillers chillers, climate, and chilled water temperature
• running additional chillers differential. The following factors tended to maximize
variable primary flow energy savingsrelative to other
None of these choices is optimal. Also if the system has system alternatives:
thermal storage, ·it may require running additional • Chilled water plants with fewer chillers
chillers sooner. • Longer, hottercooling season
• Less than designchilledwater temperaturedifferential
A strong delta T strategy will eliminate many of the
control and operational complexities as well as energy Chilled water pumps and chiller auxiliariesaccounted
waste, lost available capacity and comfort control for essentiallyall savings. Differences in chiller energy
issues that can arise in a poorly performing system. It use were not significant from system type to system
also can minimize unnecessary added margin or type. Variable flow, primary only systems'chilled water
conservatism in the design that will drive up the first pump energy use was 25 to 50 percent lower than
cost. Delta T issues should be proactively addressed in that of primary/secondary chilled water systems. In
any system. systems with two or more chillersconfigured in parallel,
chiller auxiliaryenergy savings were 13 percent or more
6.2.1 Variable primary flow relative to primary secondary.
A typical variable primary flow system as shown in
Figure 6-2 has a set of pumps working together to ... it can be concluded that variable primary flow
independently serve multiple chillers. Flow is allowed is a feasible and potentially beneficial approach to
to vary through each chiller as chillers are sequenced in chilled water pumping system design. However, the
and out of service. A minimum evaporator flow bypass magnitude of energy and economic benefits varies
and normally closed control valve serve to maintain considerably with the application and is obtained at
minimum flow through running chillers to prevent the cost of more complex and possibly less stable
freezing in low- and laminar-flow conditions. However, systemcontrol. Theliterature on effectiveapplication of
if the plant cooling demand is such that flow will never variable primary flow is growing and should
fall below the minimum flow requirements of one promote its appropriate and effective use in the future.
chiller, then the bypass is not required. Since greater
demands are placed on chillers and pumps in variable
primary flow applications, the system must be designed

48
DISTRICT COOUNG BEST PRACTICE GUIDE
Cl200lJ Inremab'onal Di5lrid Energy A550darion. Ailright5 reserwd,

Special considerations for district cooling systems Design considerations

The ARTI study excerpt above notes that variable The chiller manufacturer needsto provide the minimum
primary configuration offers greater energy savings to flow requirements for chillers used in variable primary
plants with fewer chillers. It is important to stress the flow applications. Depending on the manufacturer,
significanceof this in the context of large district cooling chiller type and the tube design, this can range from as
system design. Since typical district cooling plants, low as 25% to 60% design flow. Absorption chillers
particularlythose in the Middle East, have a largenumber typicallyhave less tolerancefor variable flow than modern
of chillers in parallel, operating cost savings, on a centrifugal chillers. Chillers used in variable primary
percentage basis,will generally be very small compared flow applications must be designed for rapid response
to individual building cooling plants that may only have to changing flows with microprocessor controls. An
two chillers in parallel. accurate means of sensing flow and load is also
required. Industrial grade magnetic flow meters and
temperature sensors are recommended.

On-off valvesused for chiller staging should be of high


quality and high rangeability as well as slow-acting so
transient pressures and flows don't create problems as
additional chillers are sequenced in or out of operation.
To illustrate this point, consider first a building cooling
Modern sophisticated chiller controls should be able to
plant with two identical chillers, with each sized for
respond to 25% to 30% flow change per minute or
50% of the building peak cooling load, and in a
more. If the change is faster, the chiller may not unload
primary-secondary configuration. As the cooling
quickly enough to avoid freezing and it may trigger
demand moves beyond 50% of the plant design
controls to shut off the chiller to fail-safe (i.e., shutdown
capacity and the second chiller is activated, the flow in
on evaporator temperature safety).
the primary loop is 100% higher than the secondary
loop flow. Then consider a district cooling plant with
Depending on the application and design, it may be
ten identical chillers, each sized for 10% of the system
prudent to slightly unload a chiller before opening a
peak cooling load and in a primary-secondary configu-
chiller valve to bring another chiller online. Designers
ration. As the cooling demand moves beyond 50% of
should also make sure that pressure drops through
the plant design capacity and the sixth chiller is
individual chillers in parallel are the same or very close.
activated, the flow in the primary loop is only 20%
The intent isto design the hydraulic systemto minimize
higher than the secondary loop flow.
rapid and large changes in flow rates while selecting
chiller equipment that can handle it. Chillers can be
This is a simple example that does not considerpossible
sequenced in and out based on plant leaving-water
low delta T issues, or otheroperational considerations,
temperature and calculated load.
but onecan see how energy cost savings accrued from
variable primary configuration versus primary-
secondary will be much lower, on a percentage basis,
for plants with a large number of chillers. The energy
savings percentage will also generally be smaller for
large chiller plants that operate less frequently under
lightly loaded conditions, such as district cooling plants
in the Middle East. The minimum evaporator flow bypass valve is sized for
the minimum flow of the largest chiller. It must be able
Another element that must be considered in the to deliver very low flow and is likely to see high differ-
designer's analysis of whether variable primary is the ential pressure and real-time pressure fluctuations. It is
best alternative for a large district cooling system is the controlled to supplement the flow rate through the
impact to the distribution system. Depending on the chillers with enough extra flow to maintain minimum
system configuration, without primary-secondary evaporator flow rate requirements. If this component is
decoupling the variable primary system may reduce the sized, selected or controlled improperly it will cause
amount of pumping head available to the distribution problems sequencing chillers and maintaining control in
system. This will have a more significant impact to the plant. It must be properly sized in the hydraulic gra-
systems with larger distribution systems, but the dient even as the system grows and have high range-
designer should consider, if applicable, the costs of ability to modulate well at low flows. The actuator
distribution system piping upsizing and/or increased de- should be industrial-grade, rated for continuous duty
sign pressure in the plant or distibution system required and able to close off against the maximum differential
to accommodate a variable primary arrangement. pressure the pumps can produce.

49
· . -- ----- - - _ .

DISTRICT (aGUNG BEST PRACnCE GUIDE


02008 Inlemab'ooal Di511icr EnergyAssodab'on. All rights~.

Pump selection takes into account the pressure loss 2. Modest variations in the chilled-water supply
through the chiller evaporator as well as the piping temperature are acceptable - There may be a
network. Typicallythe pumps are installed upstream of temporary rise in supply-water temperature
chillers but can be installed downstream if necessary to leaving the plant as additional chillers are
reduce operating pressure in the chiller evaporator as sequenced in. This is because return flow is
long as suction head at the pump intake is well- circulated through the additional chiller to protect
managed. Flow is introduced through a chiller before it it before it is started. Returnwater blends with the
starts and maintained until it stops. Pumps are leaving water from other chillers.
manifolded, so that they are not dedicated to chillers
and can be staged to operate for the best operational 3. Flow andtemperature measurement equipment is
efficiency. Pump speed should be controlled with accurate - There is less margin for error in a
variable-frequency drives to maintain a minimum variable primaryflow system soflow and temperature
differential pressure at the hydraulically most remote equipment must be regularly calibrated and
points(s) in the system. maintained. Flow meters must accurately measure
low flows to be an effective control input.

4. System designers understand and operators are


trained to properly maintain minimum evaporator
flow requirements - This is a critical control task
Choosing variable primary flow to manage low delta T that is required to minimize system faults no
problems or to try to increase the available load capacity matter what the load or number of chillers
of chillers in "flow-limited" primary-secondary systems running. Improperly sizing, selecting or controlling
is not recommended. This approach falls short at peak equipment can lead to significant issues.
load conditions when low entering condenser water
temperatures aren't available and will contribute to 5. The chillers can handle the pressure - In a large
other energy and performance problems. The best system, with pumps upstream of the chillers, the
practice is to fix low delta T issues at their source, the supply pressure may be high. It may continue to
customer buildings, no maller what flow configuration grow as the system grows. If delta T in operation
is selected. is low, it will be even higher.

When to use variable primary flow 6,2.2 Primary-secondary pumping


A traditional primary-secondary system, as shown in
It is most advantageous to use variable primary flow
Figure 6-3, combines a constant-flow primary (chiller
when the following apply:
plant) loop with a variable-flow secondary(distribution)
loop. Primary pumps are constant-speed and sized for
1. The cooling load and flow varies - The system is
the head and flow required in the primary loop alone.
designed for variable flow and isn't intended for
Secondary pumps are variable-speed and sized to
constant process cooling loads or full thermal
deliver chilled water through the distribution network
energy storage.
to connected loads.
2. Footprint is a premium - Variable primary flow
systems reduce the footprint taken up by extra
pumps, pipes and connections. It mayor not be ...- , . . . -....-1.~..... ------~CHWS
possible to take advantage of the smaller foot-
print, depending on the facility and layout.

l:......:i:-_....l ..... ---_-;CHWR

Figure 6-3. Traditional primary-secondary system.


Variable primary flow should only be used if the
following apply:
In this configuration, a decoupler separates the primary
1. Chillers are compatible with variable flow - and secondaryloops.Theflow through eachchiller in the
Different types of chillers have different capabilities primary loop remains constantwhile flow in the secondary
and limits. Absorption chillers are generally less loop varies in response to the cooling load. To maintain
tolerant of variable flow. The rate and magnitude design supply temperature leaving the plant, flow in the
of flow-rate changes must be compatible with primary loop is maintained higher than (or equal to) the
chiller operation. flow in the secondary loop. Flow through the decoupler,

50
DISTRICTCOOLING BESTPRACTICE GUIDE
C2008 International Di$lnCl EnergyAssociab'on. All ngh!5reserved.

therefore, is intended to be in the direction from supply It is possible to convert existing primary-secondary
to return as additional chillers are sequenced in and out systems to variable primary flow. In fact, if delta T
of operation. Temperature in the bypass can be used to performance can be improved prior to the conversion,
indicate the flow direction, and a capacity shortfall, to then existing secondarypumps may be suitable without
trigger the start of another chiller. replacement provided consideration is given to pressure
management at the pump suction and to the minimum
An all-variable-speed primary-secondary system as evaporator flow bypass location.
shown in Figure 6-4 is similar to a traditional primary-
secondary system except that the primary pumps are 6,2.3 Distributed pumping
collected together so that any pump can serve any Distributed pumping is a scheme where chilled water is
chiller. In this configuration, chiller flow generally pumped through the district cooling distribution
remains constant butthere is more opportunity to over- piping system via pumps located at individual customer
flow the chillers as necessary. buildings, rather than at a central cooling plant. The
pressure profile for this type of system is opposite that
If delta T islow, it permits variable-speed drives to control of the pressure profile for a system with centralized
primary pumps so that there is always more flow distribution pumping; pressure in the return piping is
circulating in the primary loop than in the secondary higher than the pressure in the supply piping and the
loop. This prevents the secondary pumps from drawing pumps generating the highest head are the ones that
return chilled water into the supply and degrading the are most hydraulically distant from the central plant.
temperature provided to connected customers. It also Generally, this scheme is employed as a primary-
can be controlled to allow extra flow through the chiller secondary distributed pumping arrangement, where
so it can generate more than its design capacity when pumps in the central cooling plant handle in-plant head
entering-condenser-watertemperature is less than design. requirements, with a decoupler hydraulically separating
the plant from the distribution system.

r-r--"'T....([:::)f'-....- - - - - - / C H W S

l -......T-€J>-1.....----o------jCHWR
Themainadvantage of a distributed pumping arrangement
is significantly lower distribution pumping energy.
VIS pumps
Centralized distribution pumps must produce the head
Figure6-4. All variable primary-secondary system. required to serve the most hydraulically distant
customer for the full system flow, with excess head
When to use primary-secondary pumping consumed by customer control valves. With distributed
pumping, on the other hand, distribution pumps at
It may be advisable to use a primary-secondary pumping each customer premises produce the distribution head
scheme when the following apply: and flow requiredto serve only that customer, so there is
no energy wasting consumption of excess head.
1. Chillerscan't handle variable flow - Chillers are used
that can handle only minor flow variations. This The main disadvantage of a distributed pumping
could be the case with absorption chillers. arrangement is lack of flexibility. For a distributed
pumping system to be practical and effective, the
2. Chillers can't handle the pressure - It is a large designer must have a clear picture of what the
system and the pumps are installed upstream of the distribution system will look like over time, so that the
chillers. High supply pressure now or in the future distributed distribution pumps installed at a customer's
will exceed chiller capabilities. building can be properly sized. For most district cooling
systems that build out over time and where the ulti-
3. Loads and flows don't vary - The system has steady mate customer base for the district cooling system is
process loadsor full thermal energy storage. Variable not known in the design phase, a distributed pumping
flow doesn't offer an added energy advantage. system is generally not practical. However, for systems
with well-defined system extents and a low level of
4. Owner values familiarity - The facility owners, uncertainly regarding future loads, it would be prudent
operators, engineers and contractors are far more for designers to considera distributed pumping scheme.
comfortable with primary-secondaryand understand Figure 6-5 illustrates an arrangement where the
the long-term energy and cost implications. customers are directly connected to the system and the

51
DISTRICT COOLING BEST PRACTICE GUIDE
02008 InlemariOJ1al Disrricr Energy AW:Xia~'on. Allrightsre~.

distributed pumps at the customer premises also


handle the pumping through the buildings' internal
HVAC systems. It is also possible to have a distributed
pumping system with indirect connections (heat
exchangers separating the district-side and building-side
systems) or direct connections with decoupled tertiary
loops at customer buildings. In these cases, the pumps However, in cases where there are significant
that handleheadrequirements for the customer's building- differences in chilled-water production costs between
side chilled-water system are separate from the pumps two district cooling networks with a significant distance
providing the building with chilled water from district between them, booster pumping stations may prove to
cooling distribution system. be an economical solution. Booster pumps may also be
an attractive option for existing systems with
CHWS CHWR CHWS CHWR constrained capacity, where replacing existing pipe
W~~l mains is impractical or cost-prohibitive, but delta T
on-oflv
'''~ ~ pu~:(S)~ l!IJildlng VIS:sl'
pump(sJ
=-''1
BuUdlng

CHWS
improvement opportunities should generally be
investigated first.
f i ~
In most cases, the optimal design for a booster pumping
~@ @
J CHWR
station in the distribution system consists of booster
pumps installed on both the supply and return lines,
Figure 6-5. Distributed primary-secondary system. with identical sizing. The symmetry of boosting pressure
on both supply and return mitigates water hammer
It is also possible to have a "hybrid" system that effects in the event of booster pump trips. Also. this
combines central distribution pumping at the district arrangement typically maximizes the amount of pressure
cooling plant with distributed pumping at hydraulically boost that can be achieved at the booster pump station
distant customer buildings. However, designers should within the design pressure constraints of the system.
be very cautious about attempting to implement such Since booster pumps in the distribution system will be
a system. In addition to the challenges discussed above operating in series with distribution pumps at the
for a "pure" distributed pumping system, a hybrid central plant. the control strategy must be carefully
system introduces the added complexity of having considered so that the arrangement does not result in
centralized distribution pumps at the plant operating unexpected operating conditions or system instability.
in series with distributed pumps at customer buildings.
Unless this type of distribution system is very carefully 6.3 Pump and Pressure Control
designed and managed, with a robust controls system
and experienced operators, this can result in
6.3.1 Distribution pumps
unexpected operational conditions and an unstable
Horizontal or vertical split-case pumps are typically
distribution system.
selected for chilled-water distribution pumps in district
cooling systems, due to their high efficiency, ease of
6.2.4 Booster pumps
maintenanceand cost-effective availabilityin large sizes.
Forvery large distribution systems, or for interconnection
Although inline vertical pumps can reduce plant floor
of multiple subsystems, it can make sense to have
space requirements, among plant operations and main-
booster pumps at a strategic point in the distribution
tenance personnel. selection of inline vertical pumps is
system. Generally, it is impractical to incorporate
generally discouraged, with some of the cited reasons
booster pumps into a looped network; booster pumps
as follows:
are used where a single pair of supply and return pipes
• Bearings are unevenly loaded.
feeds into a given area. Booster pumps allow for
• Greasing iscritical. but difficult do with verticalpumps.
chilled-water transmission further away from a central
• Removing the casing is difficult and can be unsafe.
plant, as an alternative to increasing distribution pipe size.
• Vibration measurement is more difficult.
• Resonance problems are worse.
Booster pump stations can be expensive, especially if a
dedicated facility must be constructed to house the
Distribution pumps should be selected based on quality.
booster pumps and associated equipment, and
reliability and a life-cyclecost analysis that includes first
life-cycle costs should be evaluated carefully. A booster
cost and operating cost at a minimum. Whenever
pump station may be the lower capital cost alternative
versus increased piping cost, but will have increased
pumping energy costs that must be considered aswell.
Very often, it makes more sense to have separate
district cooling systems than to try to interconnect service
areas that have significant distance between them.

52
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 Intemabonal District Energy AsWOabon Allrightsreserwd.

possible, any difference in maintenance costs between variable-speed pumps be included in a bank of pumps
different pump selections should be considered in the before adding constant-speed pumps. This way, if one
life-cycle cost analysis as well. of the variable-speed pumps is out of service then the
bank of pumps can still be operated with variable-flow
6.3.2 Variable-frequency drives capability.
For a bank of distribution pumps operating in parallel
on a common header, the energy savings benefit from 6.3.3 Differential pressure control
the useof variable-frequency drives (VFDs) for variable- Variable-speed distribution pumps should be controlled
volume operation is highest for the first pump brought to maintain the minimum required differential pressure
online and successively lower for each additional pump (DP) at the most hydraulically remote customer in the
brought online. Depending on the quantity of pumps in distribution system. The minimum required differential
the pump bank, the energy savingsfrom variable-speed pressure at a customer is the differential pressure
operation of the last pump engaged can be very small. required to maintain valve authority, and therefore
However, for banks of distribution pumps with controllabilityacross the circuit. Fordistrictcoolingsystems
low-voltage motors, installing VFDs on all the pumps is with indirect connections or hydraulically decoupled
best practice in most cases nowadays due to fact that direct connections, this valve (or valves) is located at the
low-voltage VFDs and soft starters have similar costs. customer ETS. For district cooling systems without
Installing VFDs for all pumps in a bank of pumps also decoupled connections at customers, this valve (or
allows run hours to be balanced equally among all the valves) is located at the most hydraulically remote cooling
pumps, and can simplify controls and operation. coil within the customer building.

VFDs for medium-voltage motors are very expensive The amount of pressure drop required to maintain valve
and large. Therefore, in cases where pumps with authority across the critical control valve in the
medium-voltage motors must be used due to plant distribution system will vary according to the amount of
design constraints, or regulations imposed by local flow through (and therefore pressure drop across) the
electrical utilities, it is worthwhile for the designer to critical. circuit. The minimum pressure drop required at
evaluate life-cycle costs to determine the economically times of lower flow, such as part-load times, will be
optimal number of VFDs for pumps in the distribution lower than the minimum pressure drop required at
system bank. This can be especially pertinent to peak flow. Therefore, it is good practice to reset the
variable-flow primary systems, where chiller-loop minimum DPat the critical customer to reduce pumping
pressure drop is added to the distribution-system energy. One common way that this is achieved is to
pressure drop, which may push pumps from low reset theminimum DP based on outside air temperature,
voltage to medium voltage. or simply developing a reset schedule based on
seasonality. More complicated schemes have also been
Regardless of the optimal economic breakpoint, if used, such as resetting the minimum DPbased on valve
variable- and constant-speed pumps are mixed, best position at the critical customer, but such schemes are
practice is to have at least three pumps with VFDs only recommended with an advanced control system
before mixing with constant-speed pumps. A single and experienced system integrators.
variable-speed pump must not be operated with one
or more constant-speed pumps, since this could result
in a situation where bringing on the constant-speed
pump causes the variable-speed pump to back all the
way up on its curve (deadheading), and thus operate at
an unsafe condition.
6.3.4 Pump dispatch
Control of variable-speed distribution pumps is
Two variable-speed pumps can be safely operated with
achieved by increasing or decreasing pump speed to
one or more constant-speed pumps as long asthe control
maintain the minimum DP requirement at the critical
system is (1) sophisticated enough to interlock the VFDs
customer in the system. District cooling plants generally
such that the variable pumps both operate at the same
have several distribution pumps, and some plants may
speed at all times and (2) capable of ensuring that
operate by simply bringing on-line another pump once
when only one of the two variable-speed pumps is in
the running pump or pumps cannot maintain the
service, it is operated only with its speed fixed at 100%.
minimum DP requirement at full speed. This is not an
It is recommended, however, that a minimum of three
optimal way to dispatch a bank of variable-speed
pumps and will typically result in significant energy
waste, dueto pumps operating at inefficient points on
their pump curves. Instead, best practice is for
distribution pumps to be dispatched to minimize power
consumption based on system flow andheadrequirements.

53
DISTRICT COOLING BEST PRACTICE GUIDE
C2OO8 Intemab'onal DiWl'ct Energy k=iat!on. AllriglltsreservrKi,

One way this can be achieved is for the designer to distribution pump trips at plants due to power failure.
develop a dispatch schedule for the pumps that seeks Figure6-6 shows an example of a thermal storage tank
to optimize pump efficiency.The first step in developing that is also used formaintaining system pressure. However,
a pump dispatch schedule is to estimate the overall if the thermal storage tank cannot be constructed tall
distribution system curve (plot of flow versus head) for enough to cover static pressure requirements of the
the plant to be dispatched. Using flow and head figures system, then the strong pressure holding of the open
from the system curve and the pump curve (or curves) tank could compound surge effects due to pump trips,
for the distribution pumps, the designer can determine and special equipment such as surge tanks and fast-
closing valves may have to be designed into the system.

an efficient dispatch for the pumps, from minimum


chilled-water flow for the plant through peak flow. A In addition to thermal storage tank height and elevation,
dispatch schedule can then be prepared that dispatches the designer should give careful consideration to the
pumps based on plant flow. The operating logic for the optimal location for the thermal storage tank. If the
pump dispatch should incorporate time delays and thermal storage tank will be chilled-water storage
hysteresis to reduce pump cycling and minimize (versus ice storage), it does not necessarily need to be
pressure fluctuations in the system. When preparing located in close proximity to the chiller plant. If there is
the dispatch schedule the designer must keep in mind an opportunity to locate the chilled-water storage tank
that, as discussed above, when more than one variable- at a hydraulically remote location in the system, this can
speed pump is operated at the same time they should
always be operated at the same speed.

After the initial distribution pump dispatch schedule has


been prepared, the dispatch schedule should be
revisited if there are substantial changes to the system
that impact the system curve in a significant way, such
as a major piping extension or a new plant added to
the distribution network.

Another alternativefor optimizing dispatch of distribution


pumps is to utilize the new generation of sophisticated
chilled-water plant management software to dispatch
pumps automatically. This type of software, integrated
with the plant control system, uses actual equipment
pump curves to determine the optimal number of pumps
to run for all system conditions. A significant benefit to
this approach is that there is no dispatch schedule that
needs to be revisited as the system curve changes over
time, as is often the case for district cooling systems.

6.3.5 System pressure control and Figure 6-6. Thermal storagetank used for maintaining
thermal storage static pressure in system.
A very good arrangement for system pressure control
can be an "open" thermal storage tank (i.e., one that improve system hydraulics dramatically and could allow
is effectively open to the atmosphere), acting as an the designer to reduce distribution pipe sizing in the
accumulator for the system. However, this means of system, or reduce pumping power requirements, or a
pressure control is only optimal if the tank can be combination of the two. Another benefit that open
located at a hydraulically appropriate location in the storage tanks offer is the ability to accommodate large
system and with the right height. If a thermal storage system fillings quickly, while maintaining system
tank can be constructed with a height that is tall pressure requirements.
enough for the thermal storage tank to meet the static
pressure requirements of the highest point in the If an open thermal storage tank cannot be used for
system, then the strong pressure holding of the tank pressure control, then the best arrangement is usually
can protect the system from surge effects in the case of to maintain system pressure requirements via makeup

54
DISTRICT COOUNG BEST PRACTICE GUIDE
C2D08lntemi11i0fli11 Di5trid Energy A550cii1tion. Allnght5 re>erVed.

water pumps feeding water into closed expansion solution for steel piping is a pre-insulated piping
tanks in the system. The pumps add water to increase system. Pre-insulated piping is available from a number
system pressure and a control valve is opened to relieve of vendors and, when properly installed, the use of
system pressure. It is generally good practice to have a pre-insulated piping from reputable vendors can result
small pair of pumps for pressure control and a larger in a contiguous, watertight piping system. Another
pair for rapid supply of water to the system for service substantial benefit to pre-insulated piping systems is
line extensions, refilling lines that have been drained the fact that they are available with integrated leak-
formaintenance and other such operational requirements. detection sensor wires. This type of leak-detection
system, which can significantly enhance system
reliability, is discussed in section 6.4.5. Piping and fit-
6.4 Distribution System
tings are pre-insulated with rigid polyurethane foam
Materials and Components insulation and have a high-density polyethylene (HDPE)
or fiberglass jacketing.
6.4.1 Pipe materials
Welded steel. high-density polyethylene (HDPE) and
Characteristics of the foam insulation are discussed in
ductile iron are the most common piping materials used
section 6.4.4. EitherHDPE or fiberglass jacketsare suitable
in district cooling distribution systemsworldwide. Glass-
for pre-insulated chilled-water piping, but HDPE is usually
reinforced plastic (GRP) is also relatively common in
a better jacketing choice because it is more cost-effective
some markets. Strength, toughness, installation ease,
in most cases and fiberglass jacketing may be prone to
thermal expansion/contraction, availability with
stress cracking due to soil loading if piping is not
pre-insulation, corrosion resistance and contractor
installed properly. As an added layer of protection, the
familiarity are some of the main characteristics of pipe
steel carrier piping may be epoxy-coated prior to
materials that must be considered in addition to cost.
application of insulation and jacketing. This also
protects the carrier pipe from developing surface rust in
Stress analysis may be a necessary step in the chilled-water
high-humidity regions, such as those in the Middle East.
piping system design,depending on pipe material, climate
and piping configuration. System pressures, operating and
Field jointing kits are provided with pre-insulated piping
ambient temperatures, flow velocity, dynamic effects
systems to insulate and jacket the pipe in the field at
(surge), soil corrosivity and reliability requirements should
welded carrier-pipe joints. It is generally recommended
all be taken into consideration in materialselection and pip-
ing system design. Special attention should be paid to joints
and joining processes to ensurereliable chilled-water serv-
ice and avoid-future problems.

Welded-steel pipe

Welded steel is the most common piping material used that field joint kits be of the type that allows for an air
in large chilled-water distribution systems. Steel is the test of the joint jacket integrity before filling with
strongest and most forgiving material under most insulation, which provides assurance that all joints in the
conditions. distribution are watertight. However, joint kits of the type
that do not havean air test, but havea double heat-shrink
sleeveare also suitable, under the following conditions:
• Joint kit shrink sleeves/wraps are made of cross-
linked PE (PEX).
• Sensor wire leak-detection system is installed and
put into operation.
Although welded steel is generally more expensive to • Piping is not installed below the water table.
install than some of the other chilled-water piping
options, its strength, ruggedness, water tightness and Field joints should resist axial movement once they are
higher velocity allowance can justify the higher initial bonded to the pipe jacket. Otherwise, if the bonding
investment and also significantly reduce maintenance force is not great enough, the joint sleeve could shift
costs over the life of the system. With adequate relative to the pipe during thermal expansion/contraction
protection from corrosion, such as watertight jacketing and create and opening for groundwater to penetrate.
of a pre-insulated piping system, it can last indefinitely Resistance of field joints to axial movement may be
when properly designed, installed and operated. Steel reviewed for compliance with relevant industry stan-
piping is readily available throughout the world and in dards, such as EN 489.
a wide range of sizes, ratings and specifications.
As discussed in section 6.4.2, in addition to the pre-
Whenever insulation is required, the recommended insulated piping itself, pre-insulated isolation valves

55
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lnremaUonal District EnergyAssociaUon. Allrightsreserved.

with weld-end pipe stubs are also available, which protection of the pre-insulated piping system.
allows isolation valves to be direct buried with the same
watertight jacketing as the piping system. All-welded, standard-weight steel piping is highly
resistant to damage from hydraulic shocks and water
External corrosion can occur in steel piping systems hammer due to its very high maximum allowable pressure
from ground water and soil chemicals if a proper rating at chilled-water temperatures and its resistance
corrosion protection solution is not implemented. As to buckling. However, due to the rigidity of steel as a
discussed above, properly installed pre-insulated piping material, the magnitude of surge pressure created due
system can preclude the need for anyadditional corrosion to a given velocity change will be higher for steel piping
protection. For piping systems that do not require in- than for plastic piping such asHOPE or, to a lesser extent,GRP.
sulation, piping can be coated forcorrosion protection.
HOPE pipe
Primarycoating options are fusion-bonded epoxy, fiber-
glass and polyurethane. Steel pipes can also be High-density polyethylene (HOPE) is a plastic piping
manufactured with an outer polyethylene jacket. It is material that has been gaining popularity in district
highly recommended that, in addition to external cooling distribution-piping systems worldwide. It is
coatings, cathodic protection be considered in areas considerably tougher than other plastic piping systems.
where chlorides or sulfates are present in the soil, or It's strong and handles well in the field. It's flexible and
where there are exposed metal surfaces. If a cathodic easy to install, especially when crossing water,
protection system is employed, it must be monitored micro-tunneling or managing numerous bends andoff-
and maintained; this ongoing operating cost should be sets in crowded street conditions.
considered in any economic evaluation of corrosion
protection alternatives. Generally, cathodic protection is The best means of joining HOPE pipe segments for
not required with pre-insulated piping, even below the chilled-water pressure pipe applications is via the
water table, as long as all the external jacket joints are butt-fusion thermal welding process that, when properly
watertight. Internally, steel pipe is not significantly cor- executed, creates a joint as reliable and strong as the
roded by clean, treated chilled water. pipe itself for all pipe sizes. Electo-fusion couplings can
also be used to join HOPE pipe segments, but should
Since steel pipes expand and contract with significant only be used for smaller sizes where the joint created
temperature gradients, stress analysis is generally will be as strong as the pipe itself. Joints also can be
recommended for chilled-water systems in areas that flanged when fusion is impractical or at the interface
experience very high ambient temperatures, such as the with a piping system of a different material. The
Middle East, especially for systems that will be installed distribution system designer should carefully consider
in the summer or have long, straight runs of piping. the local conditions and should only select HOPE if
Most chilled-water systems with frequent directional trained and experienced personnel will be available
changes will not develop stresses that exceed code who are familiar with its installation. For these con-
limitations. However, if a system has long, straight runs tractors, HOPE is relatively flexible and easy to install
of piping, then high stresses may be developed at and can prove more economical than welded steel
directional changes, especially at branch take-offs near piping in manysituations, especially for smallerpipe sizes.
the ends of such runs. This should be analyzed to
determine if anchors or special branch take-off
configurations are required to maintain stresses below
code requirements or if foam pads should be installed
at directional changes to accommodate pipe movement
and relieve stresses.
HOPE is virtually immune to internal and external
If a pre-insulated piping system is used, it is important corrosion but may be susceptible to embrittlement and
to ensure thatthecarrier piping, insulation and jacking loss of stress resistance with strong oxidizing chemicals.
are all permanently bonded to each other. The bonding It is electrically non-conductive and immune to stray
strength should be strong enough to ensure the current attack. Though HOPE is a poor heat conductor,
system moves together as a single unit and may be the piping itself does not have very significant insulation
reviewed for compliance with industry standards, such value. For example, the insulating value of a nominal
as EN 253. If the carrier piping is not bonded to the 600 mm (24") dimension ratio (OR) 17 pipe with 50
insulation and is able to move within the insulation or mm (2") of polyurethane insulation is 24 times that of
jacketing with thermal expansion/contraction, then the pipe by itself. Therefore, for a piping application
insulation at elbows could be damaged. In the worst where insulating isappropriatefor other piping materials,
case, the jacketing could be torn, allowing ground such as steel, it is unlikely that selection of HOPE as the
water into theinsulation and compromising thecorrosion piping material will allow insulation to be avoided.

56
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 Intemil~'O!lal DistIiet Energy AssodaliOll. Allrigh~ re:;erved.

However, HDPE piping is available pre-insulated with water, such as a river or channel. with chilled-water
polyurethane insulation and an outer jacketing as distribution piping. Corrosion isn't an issue, and the
required for local thermal conditions. That said, the smooth surface of HDPE piping discourages algae,
economics of HDPE pipe versus steel pipe are more barnacle or limpet growth when in contact with fresh-
attractive for HPDE when insulation is not required, water and seawater. Pipes are quite flexible and can be
since uninsulated HDPE does not require pipe coatings produced in very long lengths or fused together on land
or cathodic protection, even when buried inaggressive and floated out into the body of water for deployment.
soil conditions. The pipe bed will often be dredged and a minor cover
applied to the pipes. If the bottom is muddy or soft it
In smallersizes, pre-insulatedHDPE pipe isavailable in the can be enough just to sink the pipes to the bottom and
Gulf region in coils of up to 200m of pipe. This can they will soon be covered by mud. If larger boats or
significantly reduce the number of field joints required, ships are crossing the pipe route it may be prudent to
making installation more cost-effective. Piping of this type cover the pipes with macadam, gabions or something
is ideal for small chilled-water service linesto customers. similar. The location of the pipe crossing should be
distinctly displayedand identified on local marine charts.
HDPE pipe wall thickness is designated by a dimension
ratio (DR) number, which is the ratio of the pipe'soutside Care is required when pressure testing HDPE, and
diameter to the pipe's wall thickness. The pressure rating manufacturer's instructions should be followed closely.
of HDPE pipe is dictated by a combination of the DR, HDPE pipe exhibits a relatively rapid radial deformation
safety factor and material class (PE 80 or PE 100). rate initially, followed by a slower and more constant
Thicker walls relative to steel reduce the carrying deformation rate over time. As the pipe expands the
capacity for a given nominal pipe size and velocity, but pressure decreases and more water must be pumped
a lower friction coefficient reduces the pressure drop. into the pipeline to maintain pressure. Also, when
With large pipe sizes, such as those over 400 mm to pressure testing HDPE piping, the relationship between
600 mm (16-24"); higher design pressures; and systems temperature and pressure rating must be considered
requiring a large number of fittings, HDPE can become and the test pressure adjusted accordingly. This can be
prohibitively expensive. In addition, large pipe requires especially important to consider in hot climates like the
large fusing equipment that can make jointing in Gulf region and for sections of piping that are exposed
trenches difficult or impractical. In these situations, it to direct sunlight.
may be sensible to have a hybrid system with both
HDPE piping and steel piping, joined with flanged steel- Ductile-iron pipe
to-HDPE couplings.
Ductile-iron pipe and fittings are generally more
Thermal expansion coefficients are significantly larger expensive than steel piping, but the overall installation
for HDPE than metal pipe and other types of plastic cost is often less than welded steel due to ease and
pipe, so expansion and contraction must be considered speed of installation. The interior of ductile-iron piping
during installation. Smaller-diameter pipes can usually is typically mortar-lined, which provides a smooth,
be buried in a "snaked" arrangement to provide corrosion-resistant interior to the pipe. This mortar
adequate allowance for thermal movement. For larger lining, however, is subject to erosion at higher fluid
piping where this is not practical, careful consideration velocities, so ductile-iron pipe is subject to velocity
must be given to contraction issues, which can be min- limitations. The traditional push-joint (bell-and-spigot)
imized with anchors, especially at building, chamber designfor ductile-iron pipe is more susceptible to leakage
and manhole walls. Pipe installed on the surface or in due to construction practices, misalignment, thermal
unprotected trenches mayrequire extensive anchorage expansion/contraction and pressure surges. The push-
to ensure the movement is controlled when exposed to joint installation is also an unrestrained jointing, which
the sun. requires thrust blocks to restrain the piping at directional
changes. Ductile-iron pipe is also available with a
Due to the fact that HDPE material can undergo defor- lugged mechanical pipe joint design that is more
mation slowly over a considerable period of time, rugged and leak-tight than push jointing. The lugged
flanged HDPE connections may requiretightening during ductile piping installation is also more expensive than
the initial months following installation to preventleakage. push joints, but is a restrained system that does not
Forthis reason, whenever practical, flanged HDPE joints require thrust blocks.
should be installed so they are accessible by maintenance
personnel. If flanged HDPE joints cannot be made A common misconception is that ductile-iron pipe is
accessible, then it is recommended that flanges with a inherently corrosion-resistant. Ductile-iron pipe can
higher pressure classthan the pipe be installed. have a very long useful life when installed without
corrosion protection in non-corrosive or very mildly
HDPE is an excellent material for crossing a body of corrosive environments. However, without proper

57
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 International DistriCl Energy Association. All rightsreservrod.

corrosion protection, ductile-iron piping installed in which may be unacceptable to some system owners
corrosive soil is susceptible to pitting corrosion and from a reliability perspective. Also, if the GRP piping is
microbiologically enhanced corrosion as well (e.g., joined using laminated joints (layup joints), this type of
sulfate reducing bacteria), which can result in an jointing requires controlled conditions and skilled
unacceptable useful life and/or reliability. personnel.

GRP pipe can be a very good alternative for installations


Research indicates thatincorrosive soils ductile iron and where corrosive fluid, like seawater, is being carried.
carbon steel have similar corrosion rates. There is also This is especially true for terrestrial installations of very
controversy regarding whether the most common large-diameter piping, where HDPE piping is either
traditional means of corrosion protection for ductile-iron cost-prohibitive or unavailable in the required size and
pipe, loose polyethylene encasement, is an effective pressure rating.
means of corrosion protection. The best solution for
corrosion protection of uninsulated ductile-iron piping, Pipe material selection summary
when required, is likely to be a combination of bonded
piping coatings and cathodic protection - similar to The following summarizes the pipe materialcharacteristics
recommended corrosion protection schemes for discussed above and providesinitial guidelines regarding
uninsulated steel piping. pipe material selection for chilled-water distribution
systems. These bullet points are generalizations and
If ductile iron is being considered as the pipe material cannot, for brevity's sake, address the many subtleties
for a chilled-water distribution system, it is important related to variations of materials and components. For
that a materials expert be consulted to determine the example, more robust jointing technologies exist for
impact that local site conditions will have upon the ductile iron and GRP that can eliminate requirements
ductile-iron pipe and what type of corrosion protection, for thrust blocks and boost reliability. However, these
if any, is required to meet expectations for system life jointing options are more expensive and can defray the
and reliability. If corrosion protection of ductile-iron capital cost advantage that these piping materials can
piping is required, then the first cost advantages of have over welded steel.
ductile iron over other pipe materials will be reduced.
Steel pipe
In some markets, such as the U.S. market, there are May be good choice of material if
often more contractors available that are familiar with • a tough and leak-tight piping system with high
ductile-iron pipe than other materials since it has been reliability is valued,
around for many years in the municipal water industry. • insulation is required,
Familiarity generally leads to reduced installation costs. • clean water can be maintained in the chilled-
However, in other markets, such asthe Middle East, the water distribution system and
use of ductile-iron piping is quite uncommon, especially • the ability to operate at high velocities is desired.
for chilled-water applications.
Consider different material if
GRP pipe • speed of installation is a high priority,
• insulation is not required and
In certain markets, such as the Middle East market, • minimizing first cost is a top priority.
glass-reinforced plastic (GRP) piping has been used with
some frequency in chilled-water distribution systems. HDPEpipe
In other markets, such as the U.S. and European May be good choice of material if
markets, GRP piping is not typically used for chilled- • insulation is not required and trench conditions
water service. are aggressive,
.the system is a lower-pressure system (HDPE is
A significant benefit of GRP is that it is virtually immune expensive at higher pressure ratings),
to corrosion. It also can be more cost-effective than • the system hasroutings with many small directional
other piping alternatives, like steel piping, especially in changesthat can be accommodated by natural
the large sizes. The significant disadvantage to GRP flexibility of pipe,
pipe is that it is not as rugged or impact-resistant as • pipe sizes aresmaller (whereHDPE is more
piping of other materials and so is more vulnerable to cost-effective) and
accidental damage than other piping alternatives, • the routing is a water crossing (channel, river, etc.)

58
DISTRICT COOUNG BESTPRACTICE GUIDE
02008 International Di5trictEnergy As5odation, All nghl5re:;erved.

Consider different material if customers should have isolation valves, with the optimal
o flexibility to increase system design pressure in the location for these valves typically being just inside the
future is desired, customer building wall. If distribution system
o piping network requires a large number of fittings development or expansion is to be phased, isolation
and valvesat the connection point between the phases may
o the region has low labor costs. be prudent.

Ductile-iron pipe Some systems have implemented automatic actuation


May be good choice of material if of distribution system isolation valves. Automatic
• soil conditions are not corrosive to ductile iron, actuation can increase responsiveness and reliability,
• insulation is not required and but the additional cost can be significant, especially for
• minimizing first cost is a top priority. valves that are not near a power source or communication
network. The added expense of automatic valve
Consider different material if actuation may be justified if it prevents or minimizes
o the ability to operate at high velocities is desired; interruption of service to customers who have critical
o long-term, leak-free, reliable service is a top priority; cooling requirements and demand high reliability. There
o pipe routing is complicated, with many horizontal may be opportunities to pass the capital cost premium
and vertical directional changes; and of automatic isolation to these customers. Also, if there
.the pipe corridor available cannot accommdate are valves in the system that are regularly opened and
thrust blocks (if unrestrained system). closed to optimize system hydraulics, then these valves
would be good candidates for automatic isolation.
GRPpipe
May be good choice of material if
• insulation is not required and trench conditions
are aggressive and
• minimizing first cost is a top priority.
There are two main methods of installation for buried
Consider different material if chilled-water distribution system isolation valves:
o flexibility to increase system design pressure in in-chamber and direct-buried.
the future is desired,
• toughness and impact resistance to maintain Valve chambers
reliabilityof service are a top priority and
-the pipe corridor available cannot accommodate Historically, valve chambers have been required for
thrust blocks (if unrestrained system). maintenance to make it possible to reach isolation
valves, system drains and air vents for operation and
6.4.2 Isolation valves maintenance. Now, with modern fittings and
components available in the market, valve chambers
When planning a new chilled-water distribution can be eliminated in many cases. However, chambers
network, there is usually a struggle between individuals can be justified at locations with large cross-sections,
responsible for operations - who would like to install branches, numerous isolation valves and drainage
many isolation valves in the piping network - and the in- requirements. In general, the chilled-water distribution
dividuals responsible for the financial side, who would like system designer should strive to minimize their use, as
to minimize the number of valves for cost considerations. they are often the more expensive alternative and may
require a lot of maintenance.
In evaluating the quantity of isolation valves to include
in the system, these are the main questions to address: When valve chambers are located under the ground-
elf a section of pipe must be drained for repair, how water table it is very difficult to keep them free of
long can this be allowed to take? water. With a cast chamber, the critical waterproofing
o How many customers will be affected by shutdown points are the pipe entrance and the joints between the
of a pipe section? roof and the walls. Special water barriers have been
oWhich customers on the system havethe most critical developed to address different needs. Even with ade-
cooling requirements (e.q., hospitals, laboratories, quate waterproofing there may be humidity issuesthat
housing for the elderly), and can the reliability of can adversely affect electronics and components.
service to these buildings be improved by location
of isolation valves? Direct-buried isolation valves

As a baseline, a distribution system should have isolation Use of direct-buried isolation valves in an underground
valves at all major branch points. Service lines to chilled-water piping system allows for the elimination

59
DISTRICT COOLING BEST PRACTICE GUIDE
02008 In!emarional District Energy A55ocia~'on. Alln'ghtl' fe5efVed.

of valve chambers, which take up a lot of space, are


expensive, and can be troublesome to maintain. Some
types of direct-buried isolation valves also eliminate
flanges, which are potential leakage points in the
system.

For a distribution system of pre-insulated, buried steel


piping, the best solution for direct-buried valves for
most pipe sizes is the use of pre-insulated, weld-end
ball valves. Versus isolation valves in chambers, this
solution has been used throughout Europe for many
years and is considered the best and most cost-effective
practice in this market for all but the largest sizes. Along
with the benefit of eliminating the valve chamber, use of
weld-end valves eliminates flanges (a potential source
Figure 6-7. Weld-end ball valve.
of leaks) and results in a contiguous welded piping
system, where the valvesare as strong as the pipe itself. owner would have to excavate the street to repair or
replace the valve. However, weld-end ball valves are
When pre-insulated valves are used in conjunction with designed to operate for more than 20 years without
a pre-insulated piping system from a reputable vendor,
need for maintenance or replacement, as long asvalves
the result can be a distribution systemwith a contiguous, are exercised at least once a year. This has been
watertight jacketing that is immune to corrosion. Figure substantiated by hot water systems in Europe that have
6-7 shows a weld-end ball valve before pre-insulation.
had direct-buried ball valves in place for more than 35
Standard weld-end ball valves are rated up to 25 bar years without significant problems.
(363 psi)

Prior to pre-insulation, weld-end isolation valves can


also be combined with vents, drains, bypasses, etc. to
form a complete pre-insulated supply- and return-valve
assembly. These types of assemblies reduce fieldwork
and pipeline installation time and can allow for a more
compact installation. Since these assemblies are
constructed under controlled shop conditions, utility
owners are ensured leak-free jointing. Figure 6-8. Weld-end butterfly valve.

One disadvantage to pre-insulated, weld-end ball valves Direct-buried valves can be installed with mechanical
for direct burial is that they get very large and expensive actuation via a shaft extended to the surface directly
in the large pipe sizes. Weld-end, metal-seated butterfly above the valve stem/gearbox. This is the most typical
valves can be also be pre-insulated and direct-buried and cost-effective solution for actuation of direct-
and are a more economical alternative to ball valvesfor buried valves. Figure 6-9 shows a partial installation of
large pipes [e.g., more than 600 mm (24")]. However, this type.
with metal-seated butterfly valves, shutoff may not be
as tight, and there is a risk of debris collection at the Another solution that is available is a hydraulic actuation
seat impeding shutoff. Figure 6-8 shows a weld-end, system. This system can be used when it is a priority to
metal-seated butterfly valve before pre-insulation. get the access point to the valve actuator out of the
street. With this system, hosesfrom hydraulic actuators
Another disadvantage to direct-burying valves, of on the valves can be run to a pit or cabinet located off
course, is that if there is a problem with the valve, the of the street so that operators do not need to disrupt

60
DISTRICT COOLING BEST PRACTICE GUIDE
C2008/nlemauooa/ DistrictEnergy Association. All rights reserved.

traffic to actuate the valves, and valves are actuated


using a hydraulic pump. The valves are direct-buried,
and the hydraulic actuator typically resides in a small
well or handhole.

Figure 6-10. Direct-buried valve with hydraulic actuator.

material will survive the environment for the particular


application since there may be different requirements for
materals, connections or corrosion protection depending
on the aggressiveness of the sailor ground water.

Cost considerations

In the European market installation of direct-buried,


pre-insulated, weld-end isolation valves is generally
more cost effective than installation of valve chambers.
In markets where manual labor costs are cheaper, such
as the Middle East, valve chambers with flanged
butterfly valves can be the least-costoption, depending
Figure 6-9. Direct-buried valve with mechanical actuation. on pipeline size and bury depth.
Figure 6-10 depicts such an arrangement. Note that for
deeper pipe installations (with direct-buried ball valves), Cost considerations are obviously very site specific but,
the hydraulic actuator can be installed in a vertical as a general rule, for installations of welded steel
orientation, jutting up into the bottom of the well. This chilled-water pipelines in the Middle East at shallower
hydraulic actuation system could be an excellent burydepths(-1-2 m),direct-buried, pre-insulated weld-end
solution for valves requiring relatively frequent actua- valves tend to have a lower first cost for 150 mm (6")
tion and located in a busy thoroughfare. This type of sizes and below, while valve chambers with flanged
actuation also is commonly used in Europe for large butterfly valves tend to be more cost-effective on a first-
valves where mechanical actuation is slow or cumber- cost basis for sizes above 250 mm (10"). However, for
some. This system could be installed with a permanent pipelines with a deep bury depth (4+ rn), where civil
hydraulic pump at the site to drive the hydraulic actu- costs are substantially higher, the direct-buried, pre-
ators on the valves, but more commonly and cost-ef- insulated valves tend to be more cost-effective up to
fectively, the system is installed without a permanent sizes of around 600 mm (24").
hydraulic pump, and utility personnel use a portable
hydraulic pump to actuate the valves instead.

If use of direct-buried isolation valves that are not


pre-insulated is considered, then it is recommended to
consult with a materials expert to ensure that the valve

61
DISTRICT COOLING BEST PRACTICE GUIDE
e2008lnremationalDistrict Energy Am>da~'on. Alln'ghrs reserved.

Whenever possible, the life-cycle cost of the isolation supply insulationkitsfor branches that can be installed over
valve installation should be considered, including the welded type of hot tap, such that a contiguous water-
maintenance and replacement costs for valves and tight pipe jacket can be maintained at the hot tap branch.
chambers.

6.4.3 Branch connections/service


line takeoffs
When the owner of the district cooling system has a
high level of confidence that a potential customer will
contract for district cooling service, it can be prudent to
install service stubs for the potential customer when For situations where it is desirable to have a valve
the main pipeline is installed. It also may be necessary immediately after the service line branch off the main
to install service stubs to connect future customers if pipe, a weld-end ball valve can be welded to the hot
there is a moratorium on opening up the road that tap branch tee, which then remains in place once the
could result in customer opportunities being missed. hot tap is completed. In most cases, the best practice is
to use a full port valve so that there is not a high
The issuance of such moratoriums is often the case for pressure-loss constriction at the branch takeoff point. In
district cooling systems being installed in greenfield some situations, however, it is difficult to accommodate
developments or in conjunction with rehabilitations of the weld-end ball valve given space constraints,
major thoroughfares. If a servicestub is already in place, especiallyfor larger sizes.
then service can be extended to the customer without
disrupting service to other customers. If a service stub
is not already in place, then it can be highly desirable to
be able to extend service to the new customer without
having to drain the main pipeline, which can be
accomplished by hot tapping. The term "hot tapping"
is used to describe anyoperation where a branch con-
nection is made to a pipe main while the pipe remains
in service or "hot" (a bit of a misnomer for chilled-
water pipes).

Hot tapping can be performed on all of the pipe materials


previously discussed and has the following benefits:
• No interruption of service to existing customers.
• Eliminates costly and time-consuming draining of
the main pipe.
• Defers capital outlay until customer contract is
secured.

Hot tapping is cost-effective enough in small sizes [up


to 100 mm (4") or so] that it can preclude the need to
install service stubs in the main even in cases where a
Figure 6-11. Sluice plate hot tap.
future customer connection is highly probable.
For steel piping there are two main types of hot taps: There is another very useful hot tap method, pictured
• Branch pipe is welded directly to the main pipe. in Figure 6-11, where a sluice plate is used in conjunction
• Mechanical clamp fitting is attached to the main with a special fitting to hot tap the line without the
pipe and the branch pipe welded to this fitting. need for a valve to be used to execute the hot tap. This
method results in an all-welded connection and is
Fora pre-insulated steeldistribution piping system, when- especially helpful when there is not room to
ever it is feasible to do so, the welded type of hot tap is accommodate a weld-end ball valve due to pipe bury
recommended to maintain the integrity of an depth or branch configuration. This scheme can be
all-welded piping system. Welding onto an active chilled- usedon pipelines with pressuresup to 25 bar (363 psi).
water line for a hot tap can be performed as long as care
istaken. ASME piping code requires preheat to 10 C (50 F) 6.4.4 Insulation
to ensure the weld's integrity.Thispreheat can be achieved
usingthermal blankets, or other meansof heatingthe pipe, Evaluating insulation requirements
while operating the pipesectionwith asIowa chilled-water
flow aspossible. Most pre-insulated piping manufacturers The following general steps should be taken when

62
DISlRlCT COOLING BEST PRACTICE GUIDE
C2008lntemil~"on,,1 Di5tnttEneigY AssOOation. Alln'ghl5re5elVed.

evaluating whether to include insulation on distribution


piping:

1. Estimate the ground temperature at pipe bury


depth throughout the year.

2. Prepare heat-gain calculationsfor each pipe material customers. When usingthe heat-gain analysis to evaluate
to determine if annual energy and peak capacity the acceptability of supply temperature rise, the
loss economically justify insulation. designer should consider
• contractual customer supply-temperature require-
3. Use heat-gain analysis to evaluate supply-water ments,
temperature rise against customer supply-temper- • the supply temperature required to maintain
ature requirements throughout the year. customer comfort and
• impact of increased supply temperature to utility
Estimated ground temperatures at various bury depths ton-hour sales.
and times throughout the year can be calculated using
mean annual ground temperature and surface temperature In addition, the designer should consider that the optimal
amplitude figures. Figure 6-12 is an example of results operation of some of the technologies used in district
of these calculations. cooling systems, such asdeep water cooling and thermal
storage, may be sensitive to degradation in supply
When considering whether insulation is economically temperatures.
justified, the designer should consider both the energy
cost of thermal losses throughout the year and the It is useful to highlight the fact that temperature rise is
capital cost of lost capacity at peak times. If considering generally less significant in larger piping due to smaller
a steel distribution piping system, only the marginal surface area relative to pipe volume and higher veloci-
life-cycle cost of pre-insulated piping over the cost of ties. Conversely, temperature rise can bequite extreme in
coated piping and/or cathode protection should be smaller-sized piping - particularly at part-load operation.
considered, . since properly installed pre-insulated Therefore, even if economics don't justify insulation,
piping system from reputable vendors precludes the often times it is still necessary to insulate smaller supply
need for other means of corrosion protection. lines. Figure 6-13 shows an example of calculated supply
temperature rise along the chilled-water piping path
Even if insulation is not economically justified on the from a cooling plant to a customer interconnection, at
basis of thermal losses, insulation may be required on part-load service and illustratesthe dramatic difference in
certain pipes to limit supply-temperature rise to temperature risefor smaller pipe versus larger pipes.

40 Pre-insulated piping
38 --l__L insulation considerations
36
The insulating material for all
34 pre-insulated piping for
buried chilled-water applica-
s... 32
tions is polyurethane foam,
! 30 but the properties of the
~ 28 polyurethane foam can vary

0. 26 __ ~ u _
significantly. The polyol and
E
J! 24 ---:_-!---!1' :/ isocyanate components of
the insulation are fairly stan-
dard among manufacturers
22
and do not have a significant
20
impact on the foam's insulat-
18 Ad. ing properties.
16
,
c;
, • ,> ,, -, c, > ,e However, the choice of blow-
c•
~ 0
~
••
Ii ~
0
" u, ~ < ~ -s
" ~ 0 z -s
ing agent (the gas that fills
Month ofYear
the foam's hollow cells)has a
--x--- Surface -.- 0.6 mBury Depth direct effect on insulating
-x---1.5 mBu De lh ......e---3.0mBu Delh
value and aging of the pipe.
Figure 6-12. Example of estimated average ground temperatures at various depths. HCFC-141b has the best

63
DISTRICT COOLING BEST PRACTICE GUIDE
02008 Intemaliooill Di5!rict Energy Awxiilli'on. Allrights reserved.

1.30 control procedures in place


1.20 and test their piping and com-
-s- No insulation
- 1.10
T ponents in accordance with
international standards. The
E
• 1.00 f- -e- Insulation on all / type of manufacturing

5~ 0.90 f-
pipes
/ process used to produce the
pre-insulated pipe can also
*- Insulation on pipes /
.E 0.80 less than 450mm impact the quality of the pip-
e
~ 0.70
--+ Pipes less than 450mm
/ ing. Insulation that is spray-
applied is preferable to
~ 0.60
/ injected, as it has more uni-

't• 0.50 / form foam density and me-


chanical properties and there
1i.
go 0.40 / is much less likelihood of
Ul Pipes 450mm and larger ...- / voids intheinsulation. Gener-
0.30 ally, these issues are less im-
-Ki
A portant for chilled-water
0.20
0.10
-: ~ piping than they are for hot
water piping, but should still
0.00 be taken into consideration.
o • • • 1. 1. 2100 Also, for higher-quality foam
applied at field joints, it is op-
Piping Distance from District Cooling Plant (meters)
timal to usea mobile foaming
Figure 6-13.Distribution system supply-temperature rise for example system at part load. machine instead of hand-mix-
ing and pouring techniques.

One parameter that should be considered in selection


and procurement of pre-insulated piping isthe "aging"
of the insulation, i.e., the degradation in the insulating
value over time. One significant influence on the aging
of the insulation is the blowing agent and its diffusion
rate through the urethane cell boundaries of the foam.
thermal insulating value of the blowing agents still in The HCFC, HFC and cyclopentane blowing agents all
use, but production of this HCFC has been phased out have similar diffusion rates and, therefore, pipes of the
in most countries due to its ozone depleting potential; same construction withthese blowing agents have similar
it is only in use as a blowing agent by certain manu- rates of aging. Carbon dioxide, however, more readily
facturers and in certain regions. Most of the blowing diffuses through urethane cell boundaries and there-
agents developed as replacements for HCFC-141b, fore ages more quickly. Note that some pre-insulated
such as HFC-245fa and cyclopentane, have very pipes are available with a diffusion barrier between the
similar insulating properties and have thermal conduc- piping insulation and the outer jacketing, which prevents
tivity coefficients that are around 20% higher than the insulating gas in the polyurethane foam from
HCFC-141 b. These replacements are being used world- diffusing through the pipe jacket over time. This
wide. The other blowing agent still in useby some manu- barrier effectively eliminates "aging" of the pipe, and
facturers is C02, which has a thermal conductivity so the life-cycle cost implications of this benefit should
coefficient that is approximately 60% higher than be considered during pipe selection and procurement.
HCFC-141b.
6.4.5 Leak-detection systems
The other main parameter that has a significant effect
on insulation performance is the foam cell structure. Sensor-wire leak detection
Polyurethane foams that have small, uniform cells and
have a high closed cell content have better insulating Pre-insulated piping systems from several reputable
performance, and are also more effective at preventing vendors are available with a leak-detection system that
ingress of water vapor. Foams with small, uniform cells includes alarm wires integrated into the pre-insulation
also have better mechanical properties (compressive of the piping. This system uses electric resistance to
and sheer strength) for a given foam density. detect moisture in the insulation. A major benefit to
this system isthat it will detect if the outer jacket of the
It is strongly recommended that pre-insulated piping be pre-insulated piping has been compromised, which can
procured from vendors that have documented quality give the system owner time to schedule maintenance

64
DISTRICT COOUNG BEST PRACTICE GUIDE
&1ergy A5locIation. All ngh~ le5erved
e2008l1tema~OnaJ lliInct

on the pipe well in advanceof the carrier pipe corroding Listening rods or aquaphones are used to listen for leak
to the point of potential failure. sounds at any accessible contact points with the pipe,
such as in valve chambers, or within customer ETS
rooms. Acoustic leak instruments can listen to flow
noise through sensors coupled to a pipe magnetically or
mechanically. Leak noise is transmitted through the
pipeline either as a pressure wave through the water
or conducted through the wall of the pipe itself, and
can be transmitted over long distances. Pipe leaks also
In the early years of their development these types of induce vibration in the soil that is transmitted to the
leak-detection systems, initially used on district heating surface which can then be identified using a ground
systems, gained a bad reputation for false positive microphone, but only within close proximity to the leak.
alarms on chilled-water systems. These bugs were
worked out and today the systems are used success- Typically a leak is initially identified using a listening rod
fully in chilled-water systems, provided they are prop- or aquaphone at an accessible, but remote, contact
erly installed and maintained. This type of system point and then pinpointed using a ground microphone.
should only be considered if the district cooling owner Use of manual listening devices is straightforward, but
is committed to closely monitoring the distribution the effectiveness of this method is highly dependent on
system contractor's work to ensure that the leak-de- the user's level of experience. Leak noise correlators are
tection system is implemented and documented prop- sophisticated portable devices with microprocessors
erly. Accurate record keeping iscriticalto operation of the that can automatically detect a leak and access its lo-
leak-detection system, and it is in the owner's interestto cation. Acoustic data loggers can be used in conjunc-
make sure the installation is properly documented before tion with leak noise correlators to remotely record leak
the piping is buried and inaccessible. Due to the special- noise data as it occurs.
ized nature of these systems, whenever possible, con-
tractors with experienceinstalling them should be used. Metallic pipes transmit leak noise over long distances
very effectively, so it may be possible to locate leaks
with only leak noise correlation at a remote contact
point, without the use of ground microphones. Non-
metallic pipes do not transmit water-leak noise as well
as metallic pipes and will generally require more ground
microphone readings in between pipe contact points.

For district cooling systems installing new distribution Software-based leak detection
systems utilizing pre-insulated steel piping, installing a
sensor-wire leak-detection system is recommended, due If the physical leak-detection systems described above
to its accuracy and its capability to giveearlywaming when cannot be used, one other possible solution for leak
the pipe jacket has been breached. detection is a software-based solution. Real-time
hydraulic modeling software linked with a district cooling
Acoustic leak detection utility's SCADA system can compare actual SCADA data
to model results in real time to determine the approximate
This method of leak detection is done with acoustic location of a leak in the system. However, this technology
leak-detection sounding equipment. This acoustic is still being refined and at this time can only detect
equipment includes listening devices such listening leaks of substantial magnitude, and the accuracy of the
rods, aquaphones (or sonoscopes) and geophones (or leak detection will be highly dependent on the accuracy
ground microphones). Acoustic equipment also of flow and pressure measurements from the utility's
includes leak noise correlators. SCADA system.

65
DISTRICT COOLING BESTPRACTICE GUIDE
C2008Inrem~~'on~1 Di5tria EnergyA%oci,}rl'oo, All righ~ re:;erved.

1. Chilled-Water Plants
This chapter provides an overview of the key topics engines, combustion turbines, steam turbines or a
related to design of large district cooling plants operating combination of technologies, as discussed below.
in a Middle Eastern climate:
.chilled-water production technologies Like centrifugal pumps, an impeller provides the force
.thermal energy storage (TES) to compress the refrigerant vapor. Centrifugal chillers
• plant configuration can use single-stage or multiple-stage compressors.
• major chiller components With multiple-stage compressors the efficiency can be
• refrigerants improved through the use of inter-stage economizers.
• heat rejection Compressors can be either open or hermetic.

With open drives the compressor drive shaft extends


7.1 Chilled-Water Production through the casing to the motor. Since the motor is
Technologies outside the refrigerant, all motor heat isemitted outside
of the refrigerant cycle. A major element in selecting a
There are essentially two majorcategories of commercial chiller is efficiency; when evaluating chiller perform-
chilling technologies: compression and absorption. ances one must properly account for the motor heat
rejected to the environment by open-drive chillers. In
7.1.1 Compression chillers the eventof a catastrophic motor failure, an open-drive
The three basictypesof compressors used in packaged machine can be repaired and placed back in
water chillers are reciprocating, rotary and centrifugal. service relatively easily. However, open-drive machines
have seals that can leak and are subjectto failure. On
Table 7-1 belowsummarizes the size ranges olthe various high-pressure machines refrigerant can leak out and on
packaged compression-chiller types at ARI conditions. low-pressure machines air can leak in, causing more
For Middle East design conditions, packaged single- purge compressor run time and loss of efficiency.
compressor chillers areavailable up to -2500 tons, and
packaged dual-compressor chillers are available up to With hermetic drives the motor is containedwithin the
-5000 tons. same housing as the compressor and the motor is in
direct contact with the refrigerant; consequently, the
Chiller Type Range heat emittedby the motor isabsorbed bythe refrigerant
(tons) Since hermetic machines do not have a seal like 'an
Reciprocating 50 - 230 open-drive machine, theyareless likelyto leak refrigerant
Screw 70 - 400 Motor failures(although rare) tend to be catastrophic,
contaminate the refrigerant and cause the unit to be
Small centrifugal 200 - 1500
out of service a long time, with a great repairexpense.
Large single-compressor centrifugal 1500 - 3000
Large dual-compressor centrifugal 2000 - 6000
Centrifugal-chiller capacity control
Table 7-1. Summary of packaged chiller types and
capacities (ARI conditions), The three common forms of capacity control for
centrifugal compressors are inlet guide vanes, variable-
Reciprocating speed drives and hot-gas bypass. With all of these
forms, the manufacturer must be careful to prevent
A reciprocating compressor uses a piston drivenfrom a compressor surge. Surge, is a condition that occurs
crankshaft. Similarto a carengine, refrigerant is drawn when the compressor is required to produce high lift at
into the cylinderduring the downstrokeandcompressed low flow, thus it often sets the lower limit to how far a
in the upstroke. compressor can be turned down.

Rotary Inlet guide vanes


For capacity control, centrifugal chillers use inlet guide
Although rotary compressors can usescrolls or rotating vanes (also called pre-rotation vanes). The adjustable
vanes: the more common type for packaged water vanes are located in the suction of the impeller and
chillers is the helical screw-type. exert a rotation to the refrigerant in the direction the
impeller is moving. These pre-rotationvanes change the
Centrifugal impeller'sflow characteristics and thus allow the chiller
to operate at partial load.
Large commercially available compression chiller systems
are based on centrifugal compressors. Usually the Variable-speed drive (VSD)
compressors are driven with electric motors, but it is Along with inlet guide vanes, capacitycan be changed
also possibleto drive chillers directly with reciprocating by varying the speed of the impeller. The impeller must

66

-------------------------------
DISTRICf COOLING BEST PRACfICE GUIDE
e2008lntemabonal Di~triet Energy AswdariOfl. Alltights reserved.

provide the lift to move the refrigerant from the requirement remains the same while the load is
evaporator to the condenser. The lift required decreased; thus, efficiency is poor when hot-gas bypass
determines just how slow the impeller can be rotated. is used for capacity control.
Lift is the pressure difference between evaporator and
condenser, and since the refrigerant is operating at the Meeting low loads
saturation point, the lift is directly related to the corre-
sponding temperature difference. When the impeller It is not uncommon that a large plant is envisioned, but
speed has been reduced as much as it can, further in the early years must supply only a fraction of the
capacityreductionsare made usingthe inlet guide vanes. ultimate load. The question then is how to meet low
loads, particularly in these early years of operation.
Variable-speed drives on chillers can dramatically
improve part-load efficiency, but this is primarily Some people believe that a pony chiller (small chiller)
because ECWTs are typically lower than design ECWTat should be incorporated into the design for this purpose.
part-load operation. VSDs on chillers are not especially However, in general, there usually are few systems that
helpful to efficiency for part-loaded units operating at havea small enough load initiallyfor this to be considered;
design ECWT. VSDs on chillers also do not appreciably inthese cases, theloads exist only fora few seasons.
improve how much chillers can be unloaded.
With current technology and controls, chillers can be
SinceVSD chillers allow for more efficient operation of operated down to loads in the range of 15% to 20%
chillers at lower ECWT than chillers without VSDs, it of full load. Also, variable geometry diffusers (VGD) can
can be very advantageous to include VSDs on some significantly reduce compressor noise at low-load
chillers in a large central plant, even though individual operation. With optional hot-gas bypass, a chiller can
chillers in large central plants are rarely operated at be operated down to 10% load or even all the way
lightly loaded conditions. Low-voltage VSDs are very down to 0% load depending on bypass valve size.
economical and can also be unit-mounted on smaller However, as noted above, when hot-gas bypass is used,
chillers. Medium-voltage and high-voltage VSDs are the chiller efficiency is poor. With hot-gas bypass the
very expensive, cannot be unit mounted, and take up chiller will operate with lower efficiency, but with
considerablespace. Also, some system operators report consistent loading. In contrast, with on/off cycling there
that medium-voltage VSDs are not as reliable as is more wear and tear onthechiller. Given theimportance
low-voltage VSDs. of efficiency and the fact that with district cooling
chillers need not be cycled frequently, specifying chillers
If space is available for VSDs, then the cost of the VSDs with hot-gas bypass is usually not required or
must be weighed against chiller energy savings on a recommended.
life-cycle cost basis. It is important to stress that a
life-cycle cost exercise is required to determine the For district cooling systems that have such small loads
quantity of VFDs that are appropriate for a given appli- in the off-peak season that one chiller cannot operate
cation, especially for medium- or high-voltage chiller at a low enough loading (generally systems in their
applications. For the more cost-effective low-voltage early years that are under-subscribed), a common strat-
chillers, there may be an economic payback to putting egy is to operate the chillers at a higher load by
VSDs on most of the chillers in a district cooling plant, "subcooling" the chilled-water distribution loop and
and it could even make sense to put VSDs on all chillers then shutting the chiller down and using the thermal
to be able to balance run times. For medium- and high- inertia in the distribution system to meet the load.
voltage chillers, however, it may only make economic Using this strategy a chiller would typically be operated
sense to put VSDs on one or two chillers; additional for an hour and then shut it off for three hours. It is
VSDs must be carefully evaluated. important that if this strategy is used, the district cooling
provider should beconscious of customers' requirements
regarding supply temperature and supply-temperature
variations. It also would be advisable to inform the
customer about this operating scheme - or potential
operating scheme - preferably through contractual
terms with the customer.

Hot-gas bypass In systems with thermal storage, part-load operation is not


As the name implies, the hot gas from the compressor a concernbecause the storageprovides the thermal inertia.
discharge is bypassed to the suction. This control
methodcanbe used to unloada machine to zero; however, 7.1.2 Natural gas chillers
this is usually not required for district cooling plants in Technologies for directly producing cooling with natural
the Middle East. As hot gas is bypassed, the kilowatt gas include

67
DlSTRla CaaUNG BEST PRACTICE GUIDE
C2008/ntemaa'onai Disrriet Energy As-5OCiaailn. Alln"ghrs reserved.

eengine-driven chillers using reciprocating gas or is drawn to the absorbersection by the low pressure
diesel engines or gas turbines; and resulting from absorption of the refrigerant into the
• direct-fired natural gas absorption chillers absorbent. Cooling water removes the heat re-
(double-effect). leased when the refrigerant vapor returns to the liq-
uid state in the absorption process. The diluted
Technologies for indirectly producing cooling with solution is circulated back to the generator.
natural gas include • Solution heat exchanger - The heat exchanger
.engine power generators feeding electric chillers; transfers heat from the relatively warm concentrated
egas turbine power generators feeding electric solution being returned from the generator to the
chillers; absorber and the dilute solution being transferred
.boilers with steam turbine chillers; and back to the generator. Transferring heat between
.boilers with steam absorption chillers, including the solutions reduces the amount of heat that
single-effect and double-effect. has to be added in the generator and reduces
the amount of heat that hasto be rejected from the
In addition, there are integrated technology systems absorber.
that combine multiple types of drives and chiller
technologies. These approaches can optimize cost-
effectiveness, increase energy-efficiency, promote
operational flexibility and enhance the ability to deal
with uncertain future costs of natural gas and electricity.
Forexample, engine-driven chillers could provide base-
load chilled-water capacity, with peaking provided by
electric centrifugal units. In addition, waste heat from
engine-driven or turbine-driven chillers could be
recovered to drive absorption chillers.

7,1.3 Absorption chillers


The absorption cycle uses heat to generate cooling
using two media: a refrigerant and an absorbent.
WaterMhium bromide is the most common refrigerant! Figure 7-1. Single-effect absorption cycle (courtesy
York/Johnson Controls).
absorbent media pair, but other pairs can be used. The
absorption process uses an absorber, generator, pump
and recuperative heat exchanger to replace the Direct-fired absorption chillers work in the same manner
compressor in the vapor-compression cycle. asthe traditional steam or hot water absorption chillers
and are available in the double-effect configuration.
The absorption cycle, illustrated in schematic overview
in Figure 7-1, can be summarized asfollows: In double-effect absorption cycles, heat derived from
eGenerator - Gas, steam or hot water is used to boil refrigerant vapor boiled from solution in the first stage
a solution of refrigerant/absorbent (water/lithium generator is usedto boil out additional refrigerant in a
bromide). Refrigerant vapor is released and the second generator, thereby increasing the efficiency of
absorbent solution is concentrated. the process. Double-effect absorption requiresa higher
.Condenser - The refrigerant vapor released in the temperature thermal source, but uses less thermal
generator is drawn into the condenser. Cooling energy per ton-hour of cooling produced.
watercools and condenses the refrigerant. Heat will
be rejected from condenser to the cooling tower Three types of double-effect absorption chillers are
stream. commercially available and all offer comparable per-
• Evaporator - Liquid refrigerant is dropped in formance. These three types - series-flow cycle,
pressure when it flows through an orifice into the parallel-flow cycle and reverse-flow cycle - are
evaporator. Due to the lower pressure in the differentiated by the path that the absorbent!refrigeant
evaporator, flashing takes place. The flashing cools solution flows to the primary and secondary generators.
the remaining liquid refrigerant down to the
saturation temperature of the refrigerant at the Pros and cons
pressure present within the evaporator(approximately
4 C or 39 F or for a water/lithium bromide chiller). Absorption chilling technology it is not very common
Heat is transferred from the chilled water to the in the Middle East, because of the
refrigerant, thereby cooling the chilled water and .very substantial capacity and performance
vaporizing the refrigerant. degradation due to the high design wet- bulb
• Absorber - Refrigerant vapor from the evaporator temperatures typical for the Middle East,

68
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 InlemaU"",,1 DiSlnd: Energy Associalioo. All n'ght> ""served.

.higher heat rejection (cooling tower load) than cen- double-effect. absorption chiller selected for design
trifugal chillers, conditions of.4.4 ( (40 f) CHWST and 35 C (95 F)
.larger space requirements (about 40% largerfoot- ECWT, the loss in capacity is abouf40% compared with
print than electric chillers of the same capacity) and nominal ARI conditions of 6.1,C (44 F) CHWST and
.extremely high installed cost per ton of cooling ca- 29.4 C (85 F)ECWT. For example: to meet a cooling load
pacity. of 1000 tons at theseconditions. the absorption chiller
must be sized for 1667 nominal tons, 67% higher than
In addition, absorption chillers require an extremely the design cooling load. ',.-
low-cost heat source to be potentially economically viable.
Sinceabsorption units are not well-suited for low supply-
temperature production and undergo a substantial
derate to do so, it may make sense to develop a plant
configuration where absorption chillers are installed in
series with centrifugal chillers, which are better suited
for producing low supply temperatures. In this config-
uration, chilled-water return water would be partially
cooled by absorption units first and then cooled down
to design supply temperature by centrifugal chillers.

Some of the benefits of absorption machines over


If absorption units are intended to be usedby themselves
vapor-compression chillers:
(i.e., not in series with centrifugal units) with a higher
• lower electrical requirements for chiller operation
supply-water temperature, then the designer should
• lower sound and vibration levels during operation
take into consideration the impact of reduced chilled-
eability to utilize recovered heat and convert it to
water delta T on the system. With higher flows from a
cooling energy
reduceddelta T either pumping energyfor the system will
.refrigerant solutions typically do not pose a threat
be higher, or larger sizes for plant piping/equipment,
to ozone depletion of the atmosphere
distribution piping and customer energy transfer
stations (ETS) will be required.
Efficiency
It is also important to remember that there is an upper
Single-effect absorption systems have a coefficient of
limit to the ECWT As the condenser-water temperature
performance (COP) of about 0.65, i.e., 0.65 Btu of
increases, the pressure in the absorber/evaporator
cooling is produced with 1.0 Btu of driving thermal en-
section increases, resulting in a higher boiling point and
ergy. Double-effect absorption chillers have a COP of
the potential inability to meet chilled-water design
about 1.0.
temperatures. In addition, the pressure in the
condenser section is also increased, which elevates the
As noted above, absorption chillers require more con-
pressure in the generator section of the chiller. As the
denser heat rejection than electric centrifugal chillers,
condenser temperature and pressure increase, the
which means that either additional power will be re-
pressure inside the generator can goabove atmospheric
quired for cooling tower fans and pumps - -110%
and the system will shut down to avoid solution being
more for single-effect and -60% more for double-ef-
forced out of the system. Typically, absorbers are not
fect - or cooling towers and condenser-water piping
rated for use with condenser-water temperatures over
must be larger.
35 C (95 F) and are not considered safe to operate at
these temperatures.
Capacity derate
Capital costs
For absorption chillers, nominal equipment capacity is
based on ARI conditions of 6.1 ( (44 F) for chilled-
water supply temperature (CHWST) and 2·9.4 C (85 F) Absorption chiller plants require a smaller electric service
entering condenser-water temperature (ECWT). Typical than electriccentrifugal plants. However, an exhauststack
chilled-water supply temperatures are 5.5 C to 6.7 C is required for direct-fired absorption. In addition, the
(42 Fto 44 F). To operate at the 35 (.(95 F) ECWTand chillers are more costly, and cooling towers are more ex-
4.5 C (40 F) CHWST that is typical for district cooling pensive because absorption chillers require more heat re-
systems in the Middle East, absorption chillers are jection than electric chillers, as discussed above.
substantially "derated", i.e., more nominal capacity
must be installed to achieve the desired tons capacity at Equipment manufacturers
these conditions. The capacity derate for absorption
units operating at typical Middle East conditions is Direct-fired absorption chillers are available in sizes
much larger than it is for centrifugal chillers. For a ranging from about 100 tons through 1000 tons from

69
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 Inrema~'onal District Energy k50darion. Aildgllrs feservOO.

a wide variety of manufacturers. One manufacturer on the type of fuel used and generally can be made to
makes units as large as 3300 tons (at ARI conditions). comply with local regulations. Exhaust after-treatment
options are available to further reduce the stack
Operating costs emissions if required.

Operating costs are primarily related to the cost of Keytechnical considerations for an engine-driven chiller:
generating heat used to drive the absorption cycle. In
addition, higher operating costs are incurred due to the • Ventilation air is required to provide combustion air
increased electricity, water and water treatment chemical as well as remove the heat radiated by the engine
consumption associated with higher condenser cooling and exhaust stack. It is important to maintain proper
requirements. Maintenance costs depend on howthe ventilation air to the machine room to maintain
unit is loaded and operated but, generally, maintenance combustion, efficient engine operation and to
costs for absorption chillers are similar to those for protect eledronic components and equipment.
electric centrifugal units.
• Fuel supply piping should be designed to provide
the required quantity of fuel at the required
7.1.4 Engine-driven chillers
pressure. Natural gas engines' pressure require-
Engine-driven chillers (WCs) are vapor-compression
ments can vary from 0.5 to 50 psig depending
chiller systems using a reciprocating engine instead of
on engine type and size.
an electric motor to rotate the compressor shaft. They
are typically provided as a packaged system with the
• The exhaust system should be designed to
compressor and engine closelymatched and optimized
remove the products of combustion as well as
to maximize performance. Engine-driven chillers use
reduce engine exhaust noise by installing a muffler
variable-speed engines to maintain high efficiency
or silencer. Manyexhaust heat-recovery systems are
through all operating ranges. The EDC provides the
designed to also act as silencers.
highest fuel-to-cooling efficiency of any chiller (COP =
1.5 to 1.9). Efficiency can be further enhanced by
.Sound attenuation is required for most plants
adding engine heat recovery to drive absorption chillers
and generally consists of baffles, insulation and
or provide domestic hot water.
enclosures.
Important issues such as costs, space, exhaust stack
.Vibration isolation is required to prevent engine
venting, vibration, noise, maintenance and environ-
vibration traveling through piping and floors and to
mental emissions need to be addressed to provide a
prolong the life of the equipment. This is normally
highly efficient and reliable chiller system. Engine-driven
accomplished through the use of spring isolators
chillers are considerably more expensive than electric
mounted to a steel frame.
motor-driven chillers, and they also require more space.

The WC is a combustion system and therefore requires 7.1.5 Combined heat and power (CHPJ
fuel supply, combustion-air supply and exhaust There are also integrated technology systems that
removal. It also requires heat removal from the engine combine multiple typesof drivesand chillertechnologies.
(which can be used to drive absorption chillers or These approaches have the potential to increase
provide heating), vibration control and sound attenuation energy-efficiency, promote operational flexibility and
around the engine and in the stack. If engine heat is enhance the ability to deal with uncertain future costs
recovered and used (for example to drive absorption of natural gas and electric energy. Depending on price
chillers), the rest can be rejected to the chiller cooling factors, they also can improve cost-effectiveness. Of
tower by slightly increasing its size (about 10% com- particular note is the potential for cogeneration or
pared with electric centrifugal chillers). combined heat and power (CHP).

Engine-driven chillers are generally employed where For example, one configuration is a central electrical
there is insufficient electric infrastructure orwhen electric combined heat and power plant consisting of reciprocating
power costs are high compared to natural gas or oil engines with heat recovery driving single-stage
costs. The major costs to operate an WC are made up absorption chillers. The electrical power generated
of fuel and maintenance. Maintenance is significantly would be used to supply large package electric motor-
more expensive and requires more specialized expertise driven centrifugal chillers. The concept of this plant
than for an electric chiller. configuration is shown in Figure 7-2.

Engine-driven chillers consume fuel directly on site to A similar concept using combustion turbine CHP is
generate cooling and thereby create emissions at the illustrated in Figure 7-3.
site. Emissions associated with the engine are dependent

70
DISTRlcrCOOLING BEST PRAcrlCE GUIDE
e2008lntemauonalDistJiet Energy A5sociau'oll. All rightt reS<'rved.

as primary baseload, which increases utilization and


energy cost savings. The electric-driven chillers would
Exhaust Heat Recovery be operated as load-following and peaking-capacity
units. The selection of the optimum configuration is
dependent on the assumptions for electrical utility
price, natural gas fuel price, and the cost of capital.

7.2 Thermal Energy Storage (TES)

Storage of chilled water, low-temperature fluid or ice is


an integral part of many district cooling systems. Thermal
energy storage (TES) allows cooling energy to be
Figure 7-2. Engine-based CHP with electric and absorp-
generated at night for use during the hottest part of
tion chillers (courtesy York/Johnson Controls).
the day. This process helps manage the electrical
demand and reduce the need to build power plants
and transmission and distribution lines. Thermal energy
storage also allows a reduction in installed chiller plant
capacity, often reducing net capital cost.

..
Ambient Air

To Electrlc~
Chiller
Figure 7-4 illustratesan example of cooling loads during
a peak day in the Middle East, showing how TES can
shift cooling loads from on-peak to off-peak periods.
Cooling energy can be stored during the night for use
during the peak-load period. In this example, there is a
potential 20% reduction in peak power demand via
utilization of load-leveling thermal storage, when
Steam-Turbine
Drive Chiller compared to operating only chillers to serve the load,
Steam and a similar reduction in the required installed chiller
plant capacity. This is a representative value for Middle
East district cooling systems serving a mixof customer
Figure 7~3. Turbine-based CHP with electric and steam types (office, residential, hotel, retail, etc.).
turbine-drive chillers (courtesy York/Johnson Controls).

100%
7.1.6 Choosing chiller type in the Middle East
90%
r: '/ -,
~ ::;; ::;:;
/\
With relatively low power prices currently prevailing in '0 ./\
the Middle East, electric-driven centrifugal chillers are
•0 80%
very cost-competitive. The high capital costs of
-'
~

•~
70%
1% ~ t::1 rf TES DlsJarge --' :d/ -::0
I~
absorption chillers, particularly with the capacity
derate requiredat regional ambient designtemperatures,
a.
'0 60% I'< ~ I'---... _T'
/

'$.
make them an uneconomical choice. Natural gas 50%
engine-driven or turbine-driven chillers are potentially
competitive depending on natural gas costs, electricity 40%
tariffs and chiller load factor. o 2 4 6 8 10 12 14 16 18 20 22 24
"Time of Day (hr)
Most promising are hybrid configurations in which the I --Peakdayloadprofile - - Averagedallyload
natural gas-fired chillers are installed for a portion (e.g.,
50%) of the installed plant capacity, with the balance Figure 7-4. Load-leveling potential with thermal energy
being electric-driven centrifugal chillers. In this case, the storage.
natural gas engine-driven chillers would be operated

71
DISTRlcr COOUNG BEST PftAcrlCEGUIDE
Cl2008lntemationa/ DiWkrEnergy AssocialiOl1. Alln'ghrs ~.

7.2.1 Thermal energy storage (TES) types fluid storage provides colder supply, but requireschillers
to operate at lower temperatures. Also, unless the
Chilled-water thermal energy storage low-temperature fluid is also used in the distribution
system, heat exchangers and pumps are required to
Chilled water is the most common and simplest form of isolate the low-temperature fluid system from the
TES, using concrete or steel tanks to store chilled water chilled-water distribution system.
at 39 F to 42 F (3.9 C to 5.6 C) that is generated with
conventional chillers. Under normal conditions a 7.2.2 Thermal energy storage benefits
chilled-water storage tank is always filled with water.
During discharge, cold water is pumped from the bottom Peak-load management
of the tank, while an equal amount of warm return
water is supplied to the top of the tank. Due to the One of the key benefits of TES is a reduction in electrical
different densities for water at different temperatures, demand at peak-load conditions. This is especially
a stable stratification of layers of water can be obtained. important in dense urban areas where the electrical
distribution grid is capacity-constrained. Thermal
Where space is cost-effectively available for chilled- energy storage is charged at night when the electrical
water storage,the economies of scale for this technology load in the grid is reduced. Off-peak charging is
can provide significant economic advantages over ice important to electricity producers whosee variations in
storage. real-time generation costs, even when they sell power
at a flat rate.
Icethermal energy storage
In markets where there are time-of-use rates, peak
Ice generation and storage is a well-developed power "ratchets" or wholesale power purchasing by
technology, and allows storage in a more compact large district cooling providers, there can be large and
space - oftena key issue in urban environments where direct economic benefits to district cooling providers
land is expensive. Ice is blended with chilled water to implementing TES. Although this is typically not the
produce a chilled-water supply temperature typically in case in the Middle East, the economics of power
the range of 1.1 C to 4.4 C (34 F to 40 F). The volume generation will ultimately result in some type of
required for ice storage is 15% to 25% of the volume premium on power during peak-load periods. In addition,
required by chilled-water storage for the same energy by reducing the peak electrical demand, less efficient
storage capacity. Ice storage provides an opportunity electric powerproduction facilities may remain offline,
to reduce the distribution supply temperature, increase thereby reducing fuel use and emissions of air pollution
the delta T, and thereby reduce distribution and ETS and carbon dioxide. For those district cooling providers
system costs. with on-site CHP or power generation, implementing
TES provides a large economic benefit by reducing the
District cooling with ice storage can also reduce capital amount of installed generation required.
and operating costs in customer buildings. Colder
chilled-water supply makes it possible to supply colder Energy efficiency
air to satisfy the cooling load. Colder air requires less air
flow, smaller fans and reduced duct space in customer There are numerous opportunities to improve on-site
buildings. Colder air could also cause condensation on energy efficiency with TES. Chillers (and their auxiliaries)
ductwork, so it must be done with caution, especially may beoperated in a narrow output range to maximize
for existing buildings that were not initially designed their efficiency. Nighttime operation, depending on the
for colder supply air. When implementing ice storage, climate, can rely upon cooler condenser-water temper-
the economic advantages must be weighed against the atures to reduce chiller lift and minimize the kW/ton of
higher capital and operating costs for ice-making chilled-water production.
equipment relative to water chillers alone.
With ice and low-temperature fluid storage, chilled-
Low-temperature fluid thermal energy storage water supply temperatures can be reduced, enabling
higher distribution system delta T and less pump
Low-temperature fluid storage uses additives in chilled energy consumption. When colder supply water is
water to enable storage at temperatures in the -1.1 C provided to buildings, it can enable colder air production
to 2.2 C (30 Fto 36 F) range. Like chilled-water storage, to reduce airvolumes and fanenergy consumption as well.
low-temperature fluid TES is sensible cooling and does
not undergo a phasechange. However, low-temperature Capital avoidance
fluid TES, with its lower supply temperature and larger
Delta T, requires a somewhat smaller tank volume than TES should be considered early in the design processto
doeschilled-water TES. Likeicestorage, low-temperature minimize capital investment. Thermal energy storage

72
DISTRla COOUNG BESTPRAalCE GUIDE
02008 Il1tefmO'onal Di,1;rict El1ergy Assaooo'on.Alll1gh~ reSf'l'lled

used for load-leveling can reduce the necessary TES tank in operation with a six-hour discharge rate and
installed chiller plant capacity and also provide for an 8.9 C (16 F) design delta T. Thermal energy storage
redundancy requirements. A remote and unmanned capacity is reduced with low delta T performance and
"satellite" chilled-water storage facility may be installed enhanced with high delta T.
in a growing system to serve more load without
increasing the size of buried pipes or distribution pumps Siting
at the main chiller plant. Chilled-water storage can also
double as fire protection and could even serve as a All large-scale district cooling TES technologies require
water reservoir for cooling tower makeup. Ice or a tank. Volume requirements are higher for chilled-
low-temperature fluid can be used to lower the supply- water and low-temperature fluid storage than for ice
water temperature and raise the delta T, enabling the storage, but the footprint can be minimized with a tall
use of smaller pipes and pumps. tank if it is feasible relative to the site (See Figure 6-6 in
Chapter 6 for an example of a tall chilled-water TES
Operational flexibility tank). A large delta T will also reduce the TES tank
footprint for a given tank height. Tanks are made of
Another significant TES benefit is increased operational concrete and steel and can be above ground, below
flexibility. Thermal energy storage helps facilitate chiller ground or partially buried. Round tanks are generally
maintenance, even during high-load conditions. most cost-effectivefor chilled-water and low-temperature
Storage plus emergency pump power enables service fluid TES. Ice TES tanks can be round as well, but are
even after an electrical power outage. A TES tank could often rectangular when space is at a premium, since
also be used to provide fire protection water and this allows coil density to be maximized. Ice storage
emergency condenser water or chilled-water makeup. requires a physical location that is relatively near the ice
production chillers. In contrast, chilled-water storage
7.2.3 Thermal energy storage challenges tanks may be located at a remote location in the
distribution system, far away from chillers.
Sizing
Forthe large-scale TES usedin districtcooling applications,
It is generally not practical or cost-effective to size a TES tanks are almost always atmospheric tanks (versus
district cooling system for full TES. Full storage enables pressurized). Therefore, it is very important to give careful
the system to deliver the peak load with the storage consideration to tank height and the location of the
capacity alone. Partial energy storage usesthe storage tank hydraulically in the system. If an atmospheric TES
capacity to supplement chiller operation. Since there tank must be located at a geographic low point in the
are typically very few hours at peak load during the system and/or cannot be constructed tall enough to
year, even a partial storage system may be operated as meet the system'sstatic head requirements (dependent
full storage for much of the time. on customer ETS or building elevation), then pressure-
reducing valves may be required on the tank return.
The capacity of both chilled-water and low-temperature These pressure-reducing valves waste energy, and this
fluid systems is directly proportional to the delta T arrangement can also make thesystem more vulnerable
performance. As an example, Table 7-2 illustrates the to water hammer. Ideally, the TES tank would be
capacity of a 10,221 cu m (2,700,000 gal) chilled-water located at a geographic high point in the system or
constructed tall enough that the system's static pressure
requirements are met without the need for pressure-
Delta T in Energy Load Capacity reducing valves. However, the designer should be
Operation Capacity, Capacity, vs. Design cautious that TES tank height and location does not
ton-hr tons result in a significantly higher static pressure than the
deg C deg F (6 hours) system requires, othervvise distribution pump head may
56 10 18,750 3,125 63% be unacceptably limited, or a higher pressure class
required for the distribution system.
6.7 12 22,500 3,750 75%
7.8 14 26,250 4,375 88% The static pressure issues discussed in the previous
8.9 16 30,000 S,OOO 100% paragraph are avoided if the TES tank is isolated from
10.0 18 33,750 5,625 113% the chilled-water distribution system via heat exchangers,
11.1 20 37,500 6,250 125% but this solution results in increased capital cost for
12.2 22 41,250 6,875 138% exchangers and additional pumps, increased pumping
energy and increased supply chilled-water temperature
13.3 24 45,000 7,500 150%
due to approach acrossthe heat exchangers. However,
Table 7·2. Impact of delta T in operation on chilled-water this solution can be attractive for low-temperature fluid
storage capacity. TES, since it precludes having to use low-temperature

73
DISTRlcr COOUNG BEST PRACTICE GUIDE
02008 InremariOOilI Disrricr Energy Association. Ailrights noservro.

fluid throughout the distribution system. It is useful to evaporator and condenser-water circuits running in
note that the chemical investment required to enable opposite directions (counterflow). This configuration
low-temperature operation is partially offset by the reduces the lift between the evaporator and condenser,
supplemental benefit of chemical treatment provided thereby reducing the amount of work done by the
by the low-temperature fluid. chiller compressors, as illustrated in Figure 7-5. A
series-counterflow arrangement enhances chiller
Timing performance and can improve overall chiller plant
efficiency. However, it is important to note that the
To capture the greatest benefit from an investment in energy savings from increased chiller efficiency is
TES, it is imperative to assess the benefits and costs typically partially offset by the increased pumping
early in the design effort. Low-temperature supply power required.
water or a hydraulically strategic TES tank location can
reduce distribution pipe size requirements. However, Condenser

~
once the chilled-water piping is procured or the
footprint is allotted for the plant, it may be too late to
take advantage of all of the significant capital and/or Compressor
operating cost savingsthat are possible with TES. Also, Lift

~------'----
whenever possible, the cost-benefit of TES should be
evaluated before customer contracts are signed and
new customer buildings are designed to take full Evaporator
advantage of the benefits of low-temperature supply
water to customer buildings. Single Chiller

Architectsinvolved in the masterplanningof developments


that will be served by district cooling systems should be
consulted early in the planning process regarding the
aesthetics and siting of chilled-water (or low-temperature Compressor
c;:zj
Condenser
_+L",;ft,,-Reduction

fluid) storage tanks. This will likely minimize possible L;ft


Compressor
issues late in the planning efforts and result in the best

Redu-ct;Cio-n+---~
Lift
chance to implement TES tanks with optimal dimensions
and at optimal locations. Lift
Evaporato"'r- " - - ' - - -

7.3 Plant Configuration


Series-Counterflow Chillers
7.3.1 Chiller sizing and Figure 7-5. Lift in single and series-counterflow chillers.
configuration
The type, number and arrangement of chillers for a In the example summarized in Table 7-3, the performance
district cooling plant is dependent upon the cooling of a 20,000-ton plant was evaluated for parallel and
load profile for the system and the magnitude of cooling series-counterflow. In the parallel chiller case both the
load to be supplied from the plant. For the very large evaporator and condenser areassumed to betwo-pass.
chilled-water plants typically required in the Middle For the series-counterflow case the evaporators and
East, the best practice is generally to use the largest condensers were both assumed to be single pass. Even
packaged chillersavailable, configured in a series-coun- with single passes, the pressure drop through the chiller
terflow, variable primary arrangement. The variable heat exchangers is higher for the pairs of series-coun-
primary pumping configuration isdiscussed in Chapter 6. terflow chillers than it is for the single chillers in the
parallel case.
7.3.2 Series-counterflow configuration
The series-counterflow configuration puts pairs of In both cases the chillers were dispatched againsta typical
chiller in series with one another, with flow through the Middle East load configuration. The results are

74
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 /11 tern,; rionalDf5triet fna-gy Assodalion. All right>reserved.

Parallel Chillers Series-Counterflow Chillers Enclosure types

10 chillers at 2000 tons each 5 chillers at 4000 tons per pair Open drip-proof (ODP) enclosures are the
2-pass evaporator 1-pass evaporator standard motor enclosure suitable for most
13.3 C (56 F)entering 13.3 C (56 F) entering industrial applications. Cooling air enters
4.4 C (40 F) leaving 4.4 C (40 F) leaving through louvered openings, passes over the
Flow: 189 lis (3000 gpm) Flow: 379 lis (6000 gpm) rotor and stator, and exitsthrough the open-
Pressure drop: 3.45 m (11.6 ft) Pressure drop: 4.14 m (13.6 ft) ings in the sides of the frame. This open
2-pass condenser 1-pass condenser enclosure design should not be selected for
33.9 C (93 F) entering 33.9 C (93 F) entering outdoor installations, or wash-down areas.
39.2 C (102.6 F) leaving 39.2 C (102.5 F) leaving These motors will typically meet an 85 DBA
sound-level requirement. All heat from the
Flow: 379 Ilw (6000 gpm) Flow: 757 Ilw (12,000 gpm)
motor is rejected into the room or
Pressure drop: 6.25 m (20.5 ft) Pressure drop: 7.32 m (24.0 ft)
surrounding area.
Table 7.3. Inputs to series-counterflow example.
Weather-protected type II
(WP-II) is an open enclosure
designed for use in adverse
Savings (cost) 15-yr present value at 10.5% outdoor conditions. The air
kWh/yr at US$.03/kWh at US$.04/kWh at US$.05/kWh intake is in the top half of the
motor to minimize entrance
Chiller 1,267,058 $281,052 $374.736 $468,420
of ground level dirt or rain.
Condenser -476,721 ($105,744) ($140,992) ($176,239) The air passage includes
Evaporator -172,984 ($38,370) ($51,160) ($63,951) abrupt 90-degree changes in
Net Savings 617,354 US$136,938 US$182,584 US$228,230 direction plus an area of
reduced velocity to allow solid
Table 7-4. Performance results for series-counterflow example. particles or moisture to drop
out before the ventilating air
summarized in Table 7-4 and show that the power contacts active parts of the motor. Virtually all particu-
consumed by the series-counterflow chillers (compres- lates except for super-fine dust are eliminated. WPII
sors) is substantially less than the parallel chillers, but the motors are typically 2-3 DBA quieter than ODP motors,
additional pumping power required due to higher and all heat from the motor is rejected into the room
pressure drop across the condenser-water and chilled- or surrounding area.
water circuits is a significant offset to the savings in
chiller power. Totallyenclosed water-to-air-cooled (TEWAC) enclosures
isolate all critical motor components from the
It is common to consider a series-counterflow pair of surroundings. They can be used indoors or outdoors and
chillers to be one production unit, rather than two in clean or dirty environments.TEWAC enclosures include
separate production units. It is often sensible to omit a water-cooled heat exchanger mounted in the top
bypasses around each of the chillers in the series- portion of the motor to cool the recirculated ventilating
counterflow pair. Bypasses add cost and require more air. Motor heat is conducted away by circulating water
space, and failure modes where flow could not still be and not by discharged air. TEWAC motors will require
pumped through the chiller tubes - even if the chiller is some heatexchanger maintenance to maintain optimum
not operating - are uncommon. Also, regular performance, and the heat exchanger must be
maintenance that does not allow flow though the constructed to resist ambient conditions that could cause
chillers, such as tube cleanings and overhauls, can be corrosion. Heat from the motor is' rejected into the
scheduled for off-peak times when both chillers in the cooling water rather than to the room.
pair can be taken out of service. Thus, bypasses are
generally not justified for chiller plants that have many Totally enclosed air-to-air-cooled (TEAAC) enclosuresare
series-counterflow chiller pairs in parallel, such as the similar to the TEWAC in that the enclosure also isolates
large tonnage plants that are typical in the Middle East. critical motor components from the surroundings. The
enclosure uses a top-mounted air-to-air heatexchanger
7.4 Major Chiller Components where external airis drawn in by a shaft-mounted fan.
The air is forced through the cooling tubes at high
7.4.1 Motors velocity to promote efficient cooling and cleaning of the
This section addresses options for motor enclosures, tubes, A TEAAC motor tends to be noisier than an ODp,
costs for standard- and inverter-duty motors and motor WPII or TEWAC motor. Typical sound levels are around
efficiency. 90 DBA. Unless the motor heat is ducted outdoors it is
rejected intothe room or surrounding area.

75
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lntemariOOilI District Energy A5s0ciariOfl, AllrighlJi re:;ervro.

120% ,,%
~
l100% +--------,rr------1
r~ 50%
~

;§ 80% +-----;o=;_~
ii 40%

C
". +---1 J 30%
~

a
E

i
40%

'0%
t----IJ--
1 20

.... 10%
%

5 0%
~
0%
2000hp 700 hp 450 hp 160hp ODP WPII TEWAC TEMe
Motor size (hor"poWflr) Motortyptl
I.wp II .TEWAC STEAAC OTEFC I .2000hp .700hp s4S0hp D150hp

Figure 7-6. Enclosure premiums above open drip-proof. Figure 7-7. Inverter-duty motor cost premium.

Totally enclosed fan-cooled (TEFC) enclosures are often premium rangesfrom about 10% at 2000 hp to more
supplied on smaller motors for compressors where than 40% for 150 hp motors.
isolation of critical motor components from the
surroundings is required. Due to the cooling fan the Motor efficiency
sound levels can be 90 DBA or above unless lower
levels are specified. All heat from the motor is rejected Motor efficiencies typically run from 95.5% to 96% for
into the room or surrounding area. the larger motors to 94.5% to 95% for smaller motors.
Efficiency tends to remain fairly flat to 50% load.
Standard motor enclosure costs Figure 7-8 graphs motor efficiency versus load for the
four sample motor sizes.
The premium for enclosures that provide better
protection of the motor from the ambient conditions 98
ranges rather dramatically as shown in Figure7-6 (note 97
that 150 hp motors are not available in TEWAC and
TEAAC). It should also be noted that the values
graphed represent only the cost premium associated
-96
~
i;' 95
.. . - - . . . .. . .
~

with the enclosure.Thusthe costsof piping and pumps c


~ 94 .'"
must be added to the cost of the TEWAC enclosure. IE
w 93 /'
When specifying motors for open-drive chillers in the 92
1/
Middle East, it generally makes sense to use totally 91
enclosed water-to-air-cooled (TEWAC) enclosures 0% 25% 50% 75% 100%
because this type of enclosure allows rejection of motor Percent load
heat to the coollnq tower as opposed to the chiller 1- - 2000 hp 700 hp "450 hp
room where it would have to be removed, requiring Figure 7-8. Motor efficiency.
additional investment in chiller capacity and air-
handling equipment.
Motor physical size

Within a given motor horsepower size, the open


drip-proof enclosure is the smallest. Since the heat
exchangers for totally enclosed water-to-air and
totally enclosed air-to-air enclosures are mounted on
top of the motor, those enclosures are taller. The
Inverter-duty premium TEFC enclosure is generally not as tall as TEWAC or
TEAAC (except for the 2000 hp motor), but they tend
Motors rated for inverter duty should always be used to be longer because the enclosure must accommodate
with variable-frequency drives (VFDs). The premium for the motor cooling fan.
inverter-duty motors (compared to standard motors) is
relatively independent of the enclosure type, as shown Voltage options for chiller motors
in Figure 7-7 (note again that 150 hp motors were not
available in TEWAC and TEAAC). Since enclosureswith For large-tonnage chillers, it has been common to use
heat exchangers cost more, the percentage increase is medium-voltage (3.3 kV) motors, but it is becoming
a bit lower. On a percentage basis, the inverter-duty more common to usehigh-voltage motors (11 kV). The

76
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008 International District fne<gy Awx:ia~'on. All right5 reevea.

corrosion-resistant enough
Motor dimensions in feet (L x W x H)
to be suitable for reliable,
Enclosure long-term service as a chiller
2000 hp 700 hp 450 hp 150 hp
Type condenser-tube material
ODP 62"x30"x29" 34"x30"x29" 44"x21 "x22" 39"x21 "x22" when using seawater. Cop-
WPII 64"x30"x54" 56"x30"x54" 48 " x42 "x48" 42"x32"x36" per-nickel 70/30 offers sea-
water corrosion resistance
TEWAC 64"x30"x54" 56"x30"x54" 48"x42 "x48" N/A
that is far superior to 90/10-
TEAAC 64"x30"x54" 56"x30"x54" 48 " x42 "x48" N/A copper-nickel and may be a
TEFC 106"x42"x85" 62"x36"x32" 56"x30"x34" 44"x21 "x22" suitable chiller tube material,
Motor weights in pounds but it is critical to have a cor-
rosion specialist conduct a
ODP 9600 3700 2350 1350 corrosion analysis using sea-
WPII 10,600 4500 3200 1900 water samples from the in-
take area. For some areas,
TEWAC 11,400 4500 3200 N/A
such aspolluted harbors with
TEAAC 11,400 4500 3200 N/A especially aggressive seawa-
TEFC 15,000 10,200 4600 2400 ter, copper-nickel 70/30 may
not be an acceptable selec-
Table 7-5. Example dimensions and weights of motor types. tion. Titanium is the best
tube material for seawater
advantages of high-voltage rnotors are that applications and is virtually immune to corrosion, but it
• soft starters may not be required, is the also the most expensive alternative. Major chiller
estep-down transformers may not be required, manufacturers are still evaluating the super-ferritic
.space for electrical equipment is reduced, stainless steel alloys that are being proposed by tube
etransformation losses are reduced and manufacturers to assess their impact on chiller effi-
e plant efficiency is increased. ciency. These super-ferritic tube materials have a lower
first cost than titanium, but also have a bigger impair-
In circumstances where the electric utility only provides ment to chiller efficiency than titanium as well.
medium-voltage power, it is important to verify restrictions
on ampere draw and to assess the need for soft starters. Table 7-6 showsthe levelof seawater corrosionresistance
and the approximate performance degradation for var-
·7.4.2 Heat exchanger materials and design ious tube material alternatives(and indicatesif efficiency
Today's centrifugal chillers almost always come with reduction figures are for internally enhanced or inter-
enhanced copper tubes for the evaporators and nally smooth-bore tubes). The costs for thesealternative
condensers. However, depending on the water quality, tube materials have been highly volatile over the past
it may be necessary to consider alternate materials and several years based on supply and demand, and have
smooth-bore tubes. This is true for condensers and seen enormous increases sincethe year 2000. Between
especiallytrue when the coolant is seawater from direct 2005 and 2008 quotes for chillers outfitted with tita-
cooling or seawater cooling towers. When seawater is nium condenser tubes and tubesheets compared to
used for condenser cooling, copper tubes are not
appropriate and tube rnaterials that better resist the
Seawater Approximate
corrosive nature of seawater must be selected. The Condenser Reduction
Corrosion
traditional alternatives are titanium or copper-nickel Tube Material in Chiller
Resistance
alloys, and recently special super-ferritic stainless steel Efficiency
alloys are being proposed. All of these alternative tube
Copper (enhanced) N/A 0%
materials are not as efficient in transferring heat as
(Base)
standard copper tubes, which results in less efficient
chiller operation, to varying degrees. CuNi 90/10 (enhanced) Somewhat
Resistant -3%
CuNi 70/30 (enhanced) Resistant -6%
CuNi 70/30 (smooth) Resistant -8%
Super-ferritic SS (enhanced) Highly
Resistant -10%
Titanium (enhanced) Immune -9%
Copper-nickel 90/1 0 has been used in the past for heat Table 7-6. Corrosion-resistance and performance of con-
exchange applications using seawater, but is not denser tube material options.

77
DISTRICT COOUNG BEST PRACTICE GUIDE
Q2008/ntemiltiooill Di!itrictEnergy A55ociil~on. All nghrsreserved.

chillers with standard copper tubes and tubesheets have


Refrigerant Year Restrictions
ranged from a cost premium of 50% to a cost premium
of more than 100%. Due to this price volatility, specific CFC-11 1996 Ban on production
costs have not been listed here, but the material types CFC-12 1996 Ban on production
listed in Table 7-6 are listed in order of relative cost in
HCFC-22 2010 Production freeze and
2008, with standard copper tubes the cheapest and ti- ban on use in
tanium the most expensive. new equipment
2020 Ban on production
In addition to" using alternative materials for seawater
applications, unless titanium tubes areused, it may also HCFC-123 2015 Production freeze
be necessary to use smooth-bore tubes instead of 2020 Ban on use in new
enhanced tubes. The primary concern is under-deposit equipment
corrosion associated with an aggressive fluid with fine 2030 Ban on production
solids, such as seawater. If enhanced tubes are used, it
would be necessaryto increase the frequency of tube
HFC-134a -- No restrictions
cleanings, and the cleanings would have to be done Table 7-7. Refrigerant phaseout schedule (Montreal
very carefully. Under-deposit corrosion occurs when Protocol, Copenhagen Amendment, with MOP~19
deposits collect at the base of the tube. The roots of adjustment).
internal tube enhancements act as collection points for
deposits, increasing the potential for under-deposit quirements were modified byvarious amendments, lead-
corrosion, and also make the tubes difficult to clean ing to the complete phaseout of CFC production on
thoroughly enough, even with automatic tube- January 1, 1996. The Copenhagen Amendment (1992)
cleaning systems. brought hydrochlorofluorocarbons (HCFCs) under the
same scrutiny. Table 7-7 lists the phaseout schedule for
Smooth tubes, on the other hand, resist collection of refrigerants.
deposits, are much easierto clean and can be cleaned
thoroughly with automatic tube-cleaning systems. Ozone depletion potential (ODP) is a scale that
However, the reduction in chiller efficiency by using compares the relative abilities of chemicals to deplete
smooth-bore tubes is quite significant, approximately the ozone layer compared to CFC-11 as the base. In
1.5% to 2%, but the reduction in chiller efficiency is addition to ozone depletion potential, another significant
offset somewhat by reduced pressure drop across the environmental issue for refrigerants is global warming
condenser. Given the risk of under-deposit corrosion, potential (GWP). This is the "greenhouse" effect in
smooth-bore tubes are recommended for copper-nickel which these gases absorb infrared energy leading to
70/30 tubes used in a seawater condenser cooling the warming of the earth. GWP is the relative ability of
application. the gas to contribute to global warming compared to
C02 as the reference gas.
7.5 Refrigerants
An HCFC known as R-22 has been the refrigerant of
Until recently, chlorofluo-
rocarbons (CFCs) were
the most common refrig-
erants in the world. How- HFC-407c
ever, these compounds
were discovered to cause HFC-134a
the destruction of
stratospheric ozone layer, HCFC-123
which is the protective
part of the Earth's atmos-
HCFC-22
phere that filters out and
reduces the sun's harmful
ultraviolet radiation. CFC-12

The world's developed CFC-11


nations responded in
1987 with an interna- o 0.2 0.4 0.6 0.8 1,2
tional agreement, called
'" Global Wanming Potential (GWP) /10,000
the Montreal Protocol, es- • Ozone Depleting Potential (ODP)
tablishing CFC phaseout
requirements. These re- Figure7-9. Refrigerant environmental impact comparison

78
DISTRICT COOUNG BEST PRAcrlCE GUIDE
02008 tllEmarional DistrictBlagy AssodaliOl1. Ail r!Jh~ reeveo.

choice for small cooling systems (residen- Condenser Flow - 3 gpm/ton Condenser Flow - 2.3 gpm/ton
tial and light commercial) for more than
5 chillers at 4000 tons per pair 5 chillers at 4000 tons per pair
40 years. Currently many major HVAC
manufacturers use R-22 in the majority of 1-pass evaporator 1-pass evaporator
the systems they build. However, use of 13.3 C (56 F) entering 13.3 C (56 F) entering
this refrigerant in new equipment will be 4.4 C (40 F) leaving 4.4 C (40 F) leaving
banned in 2010. R-123 is also an HCFC,
but it faces a longer-term schedule for Flow: 379 lIs (6000 gpm) Flow: 379 Vs (6000 gpm)
phaseout. Pressure drop: 4.14 m (13.6 ft) Pressure drop: 4.14 m (13.6 ft)
t-pass condenser l-pass condenser
Even though HCFCs are considerably
33.9 C (93 F) entering 33.9 C (93 F) entering
safer for the environment (at least 95 per-
cent less damaging to the ozone layer 39.2 C (102.6 F) leaving 40.8 C (105.4 F) leaving
than CFCs), they still have an adverse ef- Flow: 757 lIs (12,000 gpm) Flow: 582 Vs (9231 gpm)
fect on the environment. Pressure drop: 7.32 m (24.0 ft) Pressure drop: 5.09 m (16.7 ft)

HFCs (halofluorocarbons) currently have Table 7·8. Inputs to low condenser flow example.
no phaseout requirements under the
Montreal Protocol. HFCs are targeted for reduction As part of the MOP-19 agreement, developed countries
under the Kyoto Protocol because of their GWP, but (Article 2) will phase out all new equipment using
there are currently no specific phaseout dates for HFCs HCFCs (including HCFC-l23) by 2020 instead of 2030,
under the Kyoto Protocol. The Kyoto Protocol, a treaty the previous deadline. The new agreement also calls for
that came into force on February 16, 2005, was rati- reduction steps of 75% in 2010, 90% in 2015 and
fied by most industrialized countries with the notable allows 0.5% for servicing chillers during the period
exceptions of the United States and Australia. Gulf 2020-2030.
countries such as Qatar and the UAE have ratified the
Kyoto Protocol, but Bahrain is currently not a partici- As of 2008, no specific phaseout dates have been
pant. The Kyoto Protocol specifies reduction targets for established under the Kyoto Protocol for HFC-134a, and
emissions based on a GWP-weighted basket of six spec- it is likely that production will be allowed for another 20
ified gases or groups, which include HFCs. HFCs are a to 30 years. For all HFCs and HCFCs it is likely that the
small fraction of the total emissions, but are the com- refrigerant quantities needed to service both HFC and
ponent that is increasing the fastest. HCFC chillerswill be available for at leastseveral decades
beyond existing or proposed phaseout dates.
Figure 7-9 illustrates the comparative environmental im-
pact of various old refrigerants (CFC -11 and CFC -12) 7.6 Heat Rejection
and the recent replacement refrigerants (HCFC-123 and
HFC-134a) that are now being used. The data indicates This section includes condenser and cooling tower
that HFC-134aand HCFC-123 are more environmentally issues as they specifically relate to large district cooling
friendly refrigerants than R-22. plants in the Middle East:
• overview of condenser cooling options
While there is scientific justification for the current .optimum entering condenser-water temperature
regulatory reprieve for HCFC-123 and HFC-134a (under .cooling tower considerations
the Kyoto Protocol), the political and economic aspects .condenser-water piping arrangement
are hard to predict. The 19th Meeting of the Partiesto
7.6.1 Overview of condenser cooling options
the Montreal Protocol (MOP-19) on substances that
Heatgeneratedfrom the chilled-water production process
deplete the ozone layer concluded with a historic
must be rejected from the chiller condenserto the outside
agreement to accelerate the phaseout date of
environment - to the atmosphere or a river, lake or sea.
manufacturing equipment using hydrochlorofluorocarbons
The proper selection and control of the heat-rejection
(HCFCs) by 10 years.
equipment is a significant
component of district cooling
Savings (cost) lS-yr present value at 10.S%
plant operating costs. Heat-re-
kWh/yr at US$.03/kWh at US$.04/kWh at US$.OS/kWh jection systems in the Middle
Chiller (925,124) ($205,206) ($273,608) ($342,010) Eastare typically basedon one
Condenser 1,535,855 $340,675 $454,234 $567.792 of the following types:
• cooling towers with
Net Savings 610.732 US$13S,469 US$180.626 US$22S.782
potable water for makeup
Table 7-9. Performance results for low condenserflow example (3 gpm/ton V5. 2.3 .cooling towers with
gpm/ton). seawater for makeup

79
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lnrf'm<lfi(J(lal Di5trict Ene<gyk5odab'on.Allright5 reserved.

• cooling towers with recycled wastewater for makeup Moist, Warm


.chiller condensers for direct use of fresh water or AirOul

seawater through condensers for heat


rejection

Warm c::::::> h;:::;~~~;:::;~;;:~


Water In

7.6.2 Optimum entering condenser-water


Dry Airc::::::>
In
fill 11111 ¢::::l Dry Air
In

temperature
When determining the optimum condenser flow rate, Figure 7 M10.
Counterflow cooling tower.
the impact on the chiller must be weighed against the
impact on the condenser system and cooling tower.
Moist,Warm
Common practice inthe past was to size the condenser Air Out
system based on 3 gpm/ton condenser-water flow,
equivalent to approximately 5.3 C (9.5 F)riseacrossthe Warm Water In
condenser. Current trends are to use a larger con-
denser-water delta T. A larger condenser-water delta T Distribution
increasesthe power required by the chiller, but results Basin

in lower flow and therefore lower pumping power or


smaller pipes, and reduced tower sizes or fan power, Dry Air
which offsets the increased chiller power cost. In c:::::>

Toput this into perspective, an evaluation was prepared


of the combined effect on chillers, pumps and towers CoolWater
for a 20,000-ton plant operating under a Middle East- out ¢:::::Ii Basin
~----------"

ern climate and load profile, with 5 series-counterflow


Figure 7-11. Crossflow cooling tower.
pairs of chillers in parallel. The analysis is based on the
inputs listed in Table 7-8. Although the power required
by the tower fans will be somewhat different, this with drier air entering the cooling tower and moister air
example assumes the tower power remains the same leaving the cooling tower.
between the two cases. The results are summarized in
Table 7-9 and show that the extra power required by Counterflow towers use high-pressure spray nozzles to
the chiller compressor is more than offset by the savings distribute warm condenser water uniformly over thetower
in pumping power due to lower pressure drop through fill. Inlet air flow enters the tower below the fill and then
the condenser water circuit. Designers should evaluate passes verticallyupward through the fill, againstthe down-
the optimal condenser-water flow for a district cooling ward flow of water through the fill. A resultof this coun-
plant in lieu of using a rule of thumb such as terflow design is that the driestair comesinto contact with
3 gpm/ton. the coolest condenser water, which maximizes the
performance of the tower. Figure 7-10 is a diagram of a
7.6.3 Cooling tower considerations counterflow cooling tower.
The large cooling towers that are typically usedfor district
cooling plantsare designedin two different configurations, Crossflow towers have warm condenser-water basins
counterflow and crossflow, which refer to the direction of over the top of the cooling tower fill, and orifices in
air flow relative to water flow in the cooling tower. For these basins are utilized to distribute water uniformly
crossflowcooling towers, airflow isperpendicularto water across the tower fill. Inlet air entersthe tower horizontally,
flow, while for counterflow cooling towers air flow is and passes through the fill perpendicular to the
parallel to water flow, but in the opposite direction.These condenser water flow though the fill. Figure 7-11 is a
differences inwater- and air-flow configuration give cross- diagram of a crossflow cooling tower.
flow and counterflow cooling towers different efficiencies
and characteristics, which must be evaluatedto determine Counterflow towers generally have a smaller footprint
which cooling tower type is appropriate for a given appli- than crossflow towers, but require additional height
cation. For both of these cooling tower types, condenser and operating cost. Condenser-water pumping costs
water iscooled primarily by the latent heat of vaporization, will be somewhat lower with crossflow towers versus

80
DISTRICT COQUNG BEST PRACTICE GUIDE
02008 international DistrictEnergy A550dation. Allrightsre:>erved.

counterflow towers, since water distribution though _ 0.7


the fill is achieved via gravity for crossflow
,
0 ~
towers versus nozzles with head loss for counterflow ~ 0.6
towers. Fan power costs will also be lower for cross-
flow tower, due to a larger inlet louver area and less
i
1>
0.5
E 0.4
resistance to falling water than counterflow towers. 0
Crossflow towers also offer easier access to the water •a 0.3
distribution system for maintenance and a larger range u
; 0.2
of acceptable condenser-water flow while maintaining
0
efficient operation. ~ 0.1

Both counterflow and crossflow cooling towers are


C
:J 0.0 - - "-- -
23 24 25 26 27 28 2' 30 31 32 33 34 35
cost-effective meansof heat rejection for a districtcooling Entering Condenser Water Temperature {el
plant and can serve the end user well. In general, the [B.ndon 15.6C{60 FjWtt BulbI
decision to consider one over the other is based upon - - Tower -ChillerS -ChilierA
site-specific criteria and limitations and is typically
driven by space constraints. Counterflow towers are Figure 7-12. Chiller and tower kW/ton versus ECWT.
generally the best selection when space requirements
are a primary concern, which can be the case when
towers will be located on the roof of the cooling plant 0.020
and are driving overall plant building footprint. Cross- ~
0 0.018
w I-
flow towers are a good choice if space is not limited or E 0.016
at a premium, or if it is a high priority to minimize ,•• 0.014
operating costs. ~ • 0.012
•• I--
Cooling tower sizing

The space needed by roof-mounted cooling towers


••"
•0
e

0.010
0.008
0.006
0.004
(
\
'-
~ -- ... 01 inishi Row
~- I-
0
tends to drive how large the building footprint must
be. When space is at a premium, the engineer is often
S
~
0.002
0.000
- --
sa as
faced with tradeoffs. However, it is a mistake to
undersize the cooling towers. Undersized tower
23 '4
" " " " " 30 31
Entering CondenserWaler Temperature Ie)
33 34

[BQlld on15.6 C(60 FJ Wet Bulb]


capacity could limit chilled-water production at a time
when it is most needed. It doesn't make sense to skimp - - Tower ChillerB -ChmarA

on towers if they will constrain chiller output of the


chillers, which are more costly than towers. On the Figure 7-13. Rate of power change for chillers and cool-
other hand, oversizing the tower doesn't make sense ing towers.
either. . The key is to size cooling towers based on a
realistic wet-bulb temperature and an appropriate on 15.6 C (60 F)wet-bulb temperature (common during
approach that balances cooling tower size against off-peak periods in the Middle East). At 15.6 C (60 F) wet
chiller performance. A practical general guideline for bulb, cooling towers selected for a 3.9 C (7 F) approach
sizing cooling towers is to usea 3.9 C (7 F)approach to at design conditions generally cannot achieve ECWTs
the ASHRAE 1% wet bulb. colder than around 24 C (75 F) at full fan-speed opera-
tion. The key point from this figure is that for Chiller A,
When determining an appropriate operating control sce- around 24 C (75 F) ECWT is also the point where the
nario, there aretradeoffs to consider. Chillers are more ef- additional power consumedby the tower startsto exceed
ficient with lower entering condenser-water temperatures. the power saved in the chillers. Therefore, for Chiller A,
However, the cooling tower requires more fan power to the wet-bulb temperature would have to be lower than
produce colder temperatures. In Figure 7-12, the power 15.6 C (60 F) before there is any net energy savings by
consumption from two chiller types (hermetic-type and reducing fan speed, and therefore power consumption.
open-drive type) is plotted along with the power con- Note that for Chiller B, at 15.6 C (60 F) wet bulb, the
sumption of a cooling tower. Thisrelationship must be an- tower and chiller lines never cross; it is likely that for this
alyzed for the specific situation to determine what the chiller the tower fans could run at full speed at all times
optimum control strategyshould be. and the overall plant power consumption would be
minimized. Although this example does not considerthe
To further illustrate this point, the data from Figure 7-12 impact of providing lower than design condenser-water
is recast in Figure 7-13 showing the rate of change in flow to the cooling tower, for the counterflow towers
powerrequirement versus ECwr. This example is based typically installed in the Middle East, flow cannot be

81
- - - - - - - - - - --_. __...

DISTRICTCOOUNG BEST PRACTICE GUIDE


C2008lnlwnab'onal Di!itrid Enl!f'9Y Allociation. Alln'ghts reserved.

. 1 J
-
Balancing ~.......
"'...
"Balancing

Roof Mounted Cooling Towel'S RoofMounled Cooling Towers


1

Standby
Pump Pump
Hall ....

nnnnllll Standby
Pump

c
o
N
o
E
c
0
N
0
E
c
000
N
DOD
E
c
N

E
c
N

E
c
o
N
o
E
c
0
N
0
E
c
0
N
0
E
rrrrfffJ
c
000
NNNNNNNN
c c c
0
c
0
c
000
c c
N N N N N N N N
S S S S S S S S
o 0 0 0 0 DOD
E E E E E E
EEEEEEEE
E E
NNNNNNNN

tt t
R R R

t 11i i
SSSSSSSS
EEEEEEEE

Chiller Hall

Figure 7-14. Pumps dedicated to specific condensers.


iiiitttt Chiller Hall

Figure 7-15. Condenser pumps with header.


reduced appreciably below design flow before tower
performance is seriously impaired. For multiple cooling towers, or cooling tower cells, that
are fed by a common condenser-water header, the flow
Variable-speed drives can be useful on towers, but rate of cool water drawn from the basin of each
under Middle Eastern conditions there are very few tower/cell will never be exactly the same as the flow
hours where partial speed is needed. For those periods rate of the warm water fed into the tower inlet. To
it would be useful to haveVSDs on some cooling tower prevent basins from overflowing or running dry, the
cells, but not all. flow into each tower should be balanced as well as
possible and an equalizer line should be installed to
Cooling tower basins interconnect the towers/cells.

For multi-cell towers, common in large district cooling The function of the equalizer line is to allow flow by
plants, the cells should be connected together with a gravity from one basin to the next to maintain equal
headeron both the supplyand return sides with isolation basin water level. Since the head created by differences
valves to separate the sections. This design approach in water levels between basins is the only motive force
enables future expansion of cooling tower capacity that creates flow through the equalizer line, it is critical
when buildout is phased in to match the system load. that the equalizer line is sized large enough that
To minimize cost, butterfly valves are typically used on pressure drop in the line is minimal. The equalizer line
the cell supply lines. These valves can be used for should be sized to handle 15% of the design flow rate
balancing, although "high-performance" butterfly for each cell,with the pressure lossthrough the equalizer
valves would serve this function better than" standard" piping at this flow rate not exceeding the water level
butterfly valves. The supply valvesshould be fitted with difference between normal operating water level and
electric motor actuators so they can be opened and tower overflow. The recommended approach is to
closed automatically when the cell is operated. install equalizer lines external to the tower. Tofacilitate

82
DISTRICT COOLING BEST PRACTICE GUIDE
(;)2008 Inrem"~DI1a/ DIstrictEJ1ergy A55OdaUon. Ail nghtsreselW'd.

maintenance on a cell while the others are in operation, 7.7.1 Water supply
each branch of the equalizer line to a basin should have Water is required for the distribution network (primarily
a manual isolation valve. the initial filling and, infrequently, makeup) and for
condenser cooling. Generally, potable water from
7.6.4 Condenser-water piping arrangement municipal water mains is used inthedistribution network,
In large district cooling plants, pumps can be connected although it is possibleto use softened ground water.
to condensers in two arrangements:. One is to have
one pump for each condenser as shown in Figure 7-14, District cooling systems can use a variety of options for
and the other is to connect the pumps to a header and cooling the chiller condensers, but generally water-
then to the condensers as shown in Figure 7-15. cooled systems using cooling towers are used. A variety
of sources can be used for makeup water for cooling
In both arrangements, as a chiller comes online another towers, including:
pump is started. The advantages of arranging the opotable water,
pumps in a header are that any pump can supply any oground water (may be brackish),
chiller and a backup pump can be provided, usually at otreated sewage effluent (TSE),
less cost than when one pump is dedicated to a specific oseawater used for tower makeup directly and
condenser. The header arrangement is particularly • seawater or brackish water treated using reverse
advantageous when the towers and pumps are located osmosis or other desalination technologies.
remotely from the chillers. Additionally, with a header
system it can be possible to reduce the number of Seawater can also be used in a "once-through"
pumps; for example, one pump could serve two tower arrangement, where seawater is passes directly through
cells. However, each pump would require variable- chiller condensers for heat rejection and cooling towers
speed drives and the condensers would require flow are not used.
control valves to maintain a constant differential
pressure across the condenser. On a practical side, the With water supplies becoming scarcer worldwide,
pumps may become so large that the number of especially in arid areaslike the Middle East, district cooling
suppliers might be so small that bidding may not be operators are obliged to consider all supplies that are
competitive. In addition, the motor efficiency and available. When considering alternative supplies it is
horsepower may not be acceptable. worthwhile to consult with a water services provider
who has working experience of the particular sources
7.7 Water Treatment being considered.

As water quality varies from region to region, there is no


Potable water
one recommended water treatment program. The intent
of this chapter is provide guidelines for the design of a
Potable water is commonly used in non-arid areas and
successful water treatment program which will
is the preferred source for tower makeup. Standard
• minimize deposition,
materials can be used: copper for chiller condenser
.minimize corrosion and
tubes and galvanized or coated steel for cooling towers.
oeffectively control microbiological activity.
However, potable water is not readily available in the
Achieving these goals will lead to maximized plant life, Middle Eastand in some localesits use in cooling towers
efficiency of operation and safe operating waterside is prohibited. This has driven district cooling companies
conditions. Unless there isa depth of in-house experience to search for alternate sources for cooling tower makeup.
in the districtcooling company, a qualified and experienced
water service provider should be consulted. This water Treated sewage effluent
service provider should be ISO-certified, use environ-
mentally acceptable chemicals and have experience in Treated sewage effluent (TSE) is an important option to
operating water treatment prog rams at the utility level consider. Given that the developments served by
in the area where the plant is constructed. district cooling also generate wastewater, it is useful to
evaluate integration of wastewater treatment and
The topics addressed in this chapter include district cooling as discussed in Chapter 4. Alternatively,
ochilled-water systems, it may be possibleto obtain TSE from existing wastewater
.condenser-water systems, treatment systems.
owater supply,
_treatment approaches, There are a number of challenges with using treated
• dosing and control, sewage effluent, including availability and timing .
oLegionella, Treated sewage effluent may not be available at the
ozero liquid discharge and time and in the quantities needed by the district cooling
• service standards. plant. The potential TSE quantity usually is based on a

83
DISTRICT COOUNG BEST PRACTICE GUIDE
OZ008Intemab'onal Di5trict Energy A55a6atioo. Allnghts feser.W.

mixed-use development that includes office, retail and 4. Pipingand condenser-tube materials must be capable
residential. Since offices generate less wastewater than of withstanding the aggressive nature of seawater. For
residential buildings, for example, if office space is piping, this means using non-ferrous materials such as
developed first, then there could be an imbalance since the glass-reinforced plastic (GRP) and high-density
available TSE is not sufficient for cooling tower makeup. polyethylene (HDPE). For the condensers, this means
using special tube materials (such as titanium,
A second challenge is competition with other usesfor super-ferritic stainless or copper-nickel alloys), specially
TSE, which in the Middle East is primarily irrigation. If clad tube sheetsand internally coated water boxes.
the development plans to use TSE for irrigation then it
is possible that no TSE would be available for cooling 5. Biological activity must be controlled. The sea is a living
towers, or the quantity might be so small that it isn't fluid that changes seasonally and can experience
worth pursuing, or the excess might not be available blooms of algae or sea creatures such as microbial
until the later construction phases. mollusks.Typically, seawater must be chlorinated to kill
the biological growth and to maintain cleanliness in the
In addition, TSE quality is not predictable and can create piping and condensers. The required water treatment
problems in the tower and condenser system. Recent can lead to environmental concerns. The conventional
experience has found that significant levels of algae treatment chemical is sodium hypochlorite (bleach),
grow in TSE storage tanks, which therefore require usually generated from seawater on site. Also, seawter
more frequent cleaning and increased levels of chlori- velocity should be maintained above 1.8 m/s (6 ftls)
nation. Chlorine is aggressive to some metals, including inside the chiller condenser tubes to avoid fouling
stainless steel fasteners used in cooling towers. Also, buildup.
sulfates present in TSE are aggressive toward copper,
which is commonly used in chiller condensers. If the 6. A final concern is control of suspended biological
TSE quality is poor, special tube materials like super-fer- material and silt/sand particles that may result from
ritic stainless or titanium maybe required. turbulent seas or land reclamation activities. The plant
must have intake design, filtration equipment and
With good quality water, i.e., low in dissolved minerals, material selections to accommodate anticipated
cooling towercycles of concentration can beincreased. seawater intake material loads, and land reclamation
Experience with TSE indicatesthat cycles of concentration activities may need to be monitored by the district
must be reduced to about 2.5, which results in more cooling utility to ensure acceptable loading levels are
waterconsumption because more water is blown down. not exceeded.

Seawater as tower makeup


Seawater in a once-through arrangement
Use of seawater in cooling towers requires far less
It is possible to circulate seawater straight through the water than once-through seawater cooling, and
chiller condensers so that no cooling towers are concerns about rejecting hot water into the sea are
required. In areas where cooling towers cannot be reduced, provided the water is discharged after the
sited, once-through cooling may be the only tower basin. However, the cooling tower blowdown
option. Using once-through seawater offers formida- will likely be warmer than the sea during off-peak
ble challenges: periods when the sea is cool and the dew point is
relativelyhigh. Therefore, thermal diffusion studies may
1. The volumes of water required for once-through still be required by the environmental authorities.
cooling are immense compared to cooling tower
makeup, resulting in significant piping costs. Distance Since seawater is used, all the precautions mentioned
to the sea is a key consideration. above about material selection must be considered, as
well as using corrosion-resistant cooling towermaterials
2. The seawater available in most Middle East locations such as polyvinyl chloride (PVC).
is quite warm, particularly where the sea is shallow.
Peakseawater temperatures can reach as high as 38 C In addition to using oxidizing biocides (sodium
(100 F), which approaches the upper limit for hypochlorite), additional chemicals will be required,
condenser cooling with standard packaged chillers. including non-oxidizing biocides and dispersants. Also,
an anti-sealant may be required, as some dissolved
3. Environmental studies must be undertaken to obtain solidsmay reach their saturation limit due to evaporation
permission from environmental authorities. Since thewater of seawater.
is heated, diffusion modeling is required to confirm envi-
ronmental regulations for temperature are met.
hydrodynamic studies may alsobe required to confirmthat
the warm discharge isnot recirculated backinto the intake.

84
DISTRICTCOOLING BEST PRACTICE GUIDE
e2008lntemaliOflal Di5/IJCt Energy As-5Odao'on. Allngh!l' ~r'Rd.

Seawater treated using reverse osmosis or other 7.7.2 Treatment approaches


desalination technologies Any water treatment program must address the problems
of deposition, corrosion and microbiological activity
Potable water is commonly produced by desalinating throughout the entire system. In the paragraphs that
brackish groundwater or seawater. This technique can follow, treatment approaches will be discussed for both
also be used by district cooling companies. Since chilled and condenser-water systems.
"normal" materials can be used in condensers and
cooling towers, the plant cost is reduced, but the Chilled water
savings are offset by the cost of the desalination plant.
The two major categories of desalination technologies In the chilled-water portions of the plant and in the dis-
are reverse osmosis and distillation. tribution network, the problems encountered include
• corrosion inthechiller tubes,
.deposition in the chiller tubes,
Reverse osmosis uses semi-permeable membranes and
• microbiological activity and
does not require heating the water. Although it is
commonly used in the Middle East, reverse osmosis
.corrosion in thesystem pipe network.
poses several challenges when raw seawater is used,
Treatmentapproach
and the operator must be careful that the pre-
Following are the recommended treatment approaches
treatment is functioning properly.
in a district cooling plant where pipes can be flushed:
• Membranes are easily fouled by organic material.
• Pipes should be cleaned in sections using a non-acid
The Gulf is biologically active and subject to frequent
cleaningagent in conjunction with a temporary pump
and regular periods when algae blooms. These
and filter system. The water usedfor cleaning should
periods often occur during summer months, but
therefore be retained in the system. Thiswill conserve
they are quite unpredictable. Chlorine chemicals
water.
such as sodium hypochlorite are commonly used to
• To lift debris off the lower section of the pipes, the
kill biological matter, but chlorine attacks reverse os-
water velocityshould be a minimum of 1.5 mls (5 ftls)
mosis membranes. Although chlorine-resistant mem-
during this process. If necessary, the pipes should be
branes are coming onto the market, they can only
cleaned in sections to ensure that this velocity is main-
tolerate chlorine for short periods of time.
tained. In unusual situations it may be necessary to
.Dredging for land reclamation projects generates
mechanicallyclean pipe sections.
high silt levels which is also a source of problems
.Water should be recirculated for 24-48 hours while
for the membranes. Reverse osmosis plant opera-
the filters remove debris from the system. It should
tors are always paying close attention to the silt
be noted that this process can be made more effec-
levels, even to the level of colloidal matter. The sus-
tive by keeping dirt out the pipeline in the first place.
pended particles must be removed, which
This means carefully handling and installing pipe
usually results in large settling ponds. If the operator
works during the construction stage.
is not careful, mistakes can ruin a number of
• Water should be treated with a nitrite or molybdate
expensive membranes.
product (or a combination of these) to finally passivate
Distillation desalination can take several forms: the metal. There are reports of success with organic
• multi-stage flash (MSF) distillation corrosion inhibitors, but these are still regarded as less
• multi-effect distillation (MED) effective approaches.
evacuum vapor compression • Pipeline passivation should be a continuous process
immediately before commissioning. If there is a delay
Since heat is required, most distillation plants operate in commissioning the plant, resulting in standby
in conjunction with power plants or some othersource conditions, then the system should be treated with
of low-grade and low-cost waste heat. twice theamount ofcorrosion inhibitor orrecirculated
daily for at leastone hour.
Naturally, desalination plant operators look for water • A biocide such as isothiazalone should be added to
that is not subject to algae blooms or high silt loadings. prevent microbiological activity. If molybdate is used,
Taking water from brackish aquifers is one source - if biocide may not be necessary.
the authorities will allow it. Alternatively, water can be • Finally it may be necessary to drain parts of the system
taken from "protected" sources rather than from open from time to time to remove settled solids. In this
intakes. Protected sourcescan be vertically drilled beach case, local regulations may affect how the treated
wells or horizontally drilled intake fields similar in water can be disposed. The water treatment special-
concept to septic tank drainage fields, but in reverse. ist usuallycan help in determining the proper course
Both options serve as the first level of treatment to of action.
reduce biological contamination and suspended solids.
Unlike the piping in the district cooling plant, which is
mostly smaller sized and often vertically oriented,

85
DISTRlcr COOUNG BESTPRAcrlCE GUIDE
02008 Inlemarion<JI Di5tridEnergy /Wociarion. IV!right> re!iSVf!d.

chilled-water distribution piping is mostly large and pri- Treatl1lentapproach


marily horizontal. This situation presents specific clean- Since energy efficiency isof vital importance to district cool-
ing and disposal problems. Low-lying areas in the system ing operators, emphasis should be given to every means
may harbor debris, and flow velocities may be difficult possible for keeping heatexchanger surface areas clean.
to achieve. In this case flushing probablywill not be ef-
fective and some other form of mechanical cleaning Pre-cleaning thecondenser-water system is less arduous
("pigging") will be necessary. Depending on the condi- than the chilled-water distribution system, but it isjustas
tions and circumstances, a bare-type pig could be used important. A significant factor in keeping the condenser-
to remove construction debris and dirtor a wire brush water system clean isthe cooling tower basin design. The
or scraper pig could be used if the pipe internal surfaces basin should be configured with a weir design, whereby
need to be cleaned. debris in the system water is likelyto settle in the basin
before passing over the weir into the return to the
Dosing and control condenser pumps. There area variety of options in these
Chilled-water qualityisbest monitored by testing the sys- designs andthe cooling tower supplier canadvise on this.
tem water for chemical residual and dosing the appro- Here are the key elements to consider:
priateamount of treatment to the system. • Before starting the cleaning process, the cooling tower
basin should be cleaned manually to remove debris.
Two suitably sized dosing pumps should be connected to While doingthis, care should betaken not to damage
a bypass to the system. These should befed from dosing any system coating.
tanks (with containment dikes or bunds), with one tank • On filling with water, the system should be cleaned
containing corrosion inhibitor and the other biocide. using a non-acid cleaning chemical ensuring that all
Manual control using a limit timer should be used. parts of the system are cleaned. It may be necessary
to carry out a two-stage cleaning process whereby
A pot doser should be used as a standby mechanism.
the condenser section of the chiller is cleaned after
Condenser water the cooling tower section and pipes. This process
should be runfor 24 to 48 hoursprior to opening the
On the condenser-water side the problems can include blowdown system to remove cleaning chemicals. It
.corrosion in tube sheet and end cap(waterbox), will be necessary to ensure that blowdown quality
• corrosion in copper tubing, complies with local disposal standards.
• The system should then be treated with a scale/cor-
• deposition in tubes,
.corrosion in system pipe work, rosion inhibitor as recommended by thewater service
• deposition in cooling tower fill (fouling), provider The product's use should meetdisposal stan-
.corrosion incooling tower materials and dards as setby the local authorities. Initially, the prod-
uct should be dosed at the passivation level as
• microbiological activity.
recommended by the supplier, and then reduced to
While most of the above problems can be controlled by the maintenance level.
effective pre-cleaning and maintenance treatment, the • Microbiological control in the system should be
problem of corrosion in the tube sheet and end cap starts achieved using oxidizing biocides dosed preferably on
long before thechiller arrives onsite. Inthefactory, the chiller a continuous or semi-continuous basis using redox
ishydrotested andthen drained priorto shipping. This hy- control. A biodispersant also should be incorporated
drotesting initiates thecorrosion process. Subsequent treat- into the program to aid the effectiveness of the bio-
ment isnot enough to clean and passivate this metal and cide. A permitted non-oxidizing biocide should be
often spectacular corrosion is seen intheform oftubercules used on an occasional basis.
(nodules of rust) at the firstannual inspection.
Dosing and control
This is particularly soon the condenser-water side where The waterwithin the cooling tower system should becon-
the level of chemical treatment is not sufficientto passi- trolled via a programmable logic controller (PLC).
vate the metal, and the oxygenated, suspended-solids- Following are key recommendations for dosing andcontrol:
laden water drives the corrosion process further. This • The blowdown system should controlled for conduc-
problem is further worsened if low flow results in tivity to manage the dissolved solids at the optimum
stagnant conditions in the water box. level.
• Dosing of scale and corrosion inhibitor chemical
Two general solutions are to have the tube sheet and should be carried out proportionally. This can be
water box coated with epoxy by the manufacturer or at achieved by a contact head water meter or even by
the hydrotest stage use a corrosion inhibitor to prevent level control in the cooling tower basin.
water box rusting. Inanyevent, the tube sheetshould be .Dosing of biocide and biodispersant should be
inspected on delivery to allow any remedial work to be controlled by timer if semi-eontinuous dosing is used.
done beforethe chiller is installed. Otherwise control of the oxidizing biocide should be

86
DISTRICT COOLING BEST PRACTICE GUIDE
02008 InwmatiomilDistrictEnergy Association. NI nghlS reserved.

by redox control. and can increase the effective cycles of concentration as


.Suitably sized pumps should be used for scale/corro- the product water maybe low in dissolved solids. Thedis-
sian inhibitor, oxidizing biocide and biodispersant. advantage isthat it does have an operating cost, and dis-
.Suitably sized chemical dosing tanks in opaque posal of reject water mayneeda special application such
polyethylene should be used. Tanks should be asthermal evaporation. Following arekeyfactors to con-
calibrated externally to observe product level, and sider:
the tanks should also be bunded (diked)to contain .Availability and price of alternative water supplies. If
any chemical leaks. water is cheap and plentiful, ZLD becomes uneco-
nomic. If it isexpensive or the supply isrestricted, then
The above should be installed in a bypass system, which ZLD maybe an option.
should be valved to allow isolation. A water sampling • Plant size. The plant must be largeenough to justify
point should also be included. It is preferable to the capital expenditure or rental terms.
skid-mountthis equipment and install it in an easily ac- • Available space. There must be sufficient plant area to
cessible area to allow recharging of chemicals, changing install the RO plant.
of corrosion coupons and other maintenance work. • Disposal of reject. Often there are regulatory limita-
tions on disposal, and evaporation may necessary.
LegioneJla control Options for evaporation include thermal (increasing
There is much justified concern about the dissemination initial costand operating cost)or evaporation ponds
of Legionnaire's disease by cooling towers. Manyauthor- (increasing initial costs and space requirements).
ities and professional bodies have produced common
sense guidelines to controlling the risk, including 7.7.4 Service standards
.ASHRAE guideline 12-2000, "Minimizing the risk of In working with a water-quality service company, it is
Legionellosis associated with buildingwatersystems"; essential the district cooling operator setthe agenda for
.the UKHealth & Safety Commission, "Thecontrolof service and the key success parameters. It is recom-
Legionella bacteria in water systems" (this publication mended that the service company
is known as L8); and .be ISO 9001- and ISO 14001-registered;
• Eurovent 9/5, "Recommended code of practice to • provide a copyolthe company's environmental policy;
keep your cooling system efficient and safe."
Condenser Water
In essence, these guidelines advise system operators to
.pH
_assess the risk and take reasonable measures to
reduce it (use a complete water treatment program, • conductivity
including suitable biocides); • calciumltotal hardness
_ensure that the cooling tower iscorrectly maintained; .chloride
.sterilize the system regularly(2 x per year); and
.monitor water quality, including microbiological • M alkalinity
activity, and keep records. .iron
.calcium balance
The risk of Legionella growth isever-present, but vigilance • inhibitor level (provided by company)
and common-sense action will reduce the risk to a mini-
.dip slide total count
mum. It is recommended that the relevant sections in the
above-referenced guidelines be studied andincorporated Chilled Water
into the districtcoolingoperator's maintenance program. .pH
• conductivity
7.7.3 Zero liquid discharge
When applied to cooling towers, zero liquid discharge .inhibitor level (provided by company)
(ZLD) is a process where blowdown is recycled. For .iron
example, blowdown would be treated in a reverse osmo-
Table 7·10. Recommended monthly tests.
sis plant and the product water then reused for tower
makeup. Economics and legis-
lation drive this process
depending on location. System Test Frequency Standards
Condenser water Carbon steell 1 per month 3 milslyr maximum
The economics of this aresys- copper 1 per 3 months 0.1 milsiyr and no pitting
tem-specific and should be
Chilled water Carbon steell 1 per 3 months 1 milsiyr maximum
considered on a case-by-case
copper 1 per 3 months 0.1 milsiyr and no pitting
basis. Theobvious advantage
isthat it saves makeup water Table 7-11. Corroslcn-coupon standards.

87
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lnrffi1a~onal DiwictEnergy Asrodation. Ail right!; re:;erved,

.supervise and report on the pre-cleaning process as contaminants, such as sand, dust, soot, insects and
well ascommissioning of all equipment; debris, which are all scrubbed into the condenser water
obe prepared to commit to a minimumof 12visits per at the cooling towers. These contaminants will increase
year, duringwhich the tests listed in Table 7-10should the chemical demandandfoulingfactor, reduce the cool-
be carried out and reported in writing; ing system efficiency, shorten the equipment lifespan and
.formally train site personnel insimple monitoring tests increase energy costs. This is of particular concern inthe
and problem-solving techniques; Middle East. where the level of sand and dust in the air
ocheckrecords produced by site personnel; can be significantly higherthan other locales.
oconducttwice yearly tests for Legionella (it would also
be wise to carry out independent tests on Legionella); There are several mechanical filtrationsystems available to
• carry out corrosion coupon readings with the stan- effectively remove suspended solid contaminants. There
dards shown in Table 7-11; are also two basic approaches to cooling tower water
oconduct depositanalysis as required; and filtration,full-flow filtration andsidestream filtration. With
oimplement quarterly review meetings to highlight full-flow filtration, the filtration equipment is installed in
problems and set timetablefor improvements. the primary flow path, and the entire system flow is
strained continuously. With sidestream filtration, only a
7.8 Balance of Plant portion of the water is pumped continuously from the
cooling tower sump by means of a bypass filtration
Balance of plant means components otherthanthe major system and returned back to the cooling tower sump.
mechanical and electrical equipment. This section Sidestream filtration is not aseffective as full-flow filtra-
addresses the following topics: tion, but full-flow filtration is not cost-effective for the
opiping design for condenser water very high condenser-water flow rates of large district
• sidestream filters cooling systems.
.cooling towerbasin sweepers
.transformer room cooling Sand mediafilters and cyclone separators are commonly
.equipmentaccess used as a sidestream filtration. Sand filtersare the more
• noise and vibration effective filtration method, but require a larger footprint
and consume backwash water during their automatic
backwash cleaning cycle. Cyclone separators are a less
7,8,1 Piping design for condenser water
effective filtration method but have a smaller footprint
The two choices for piping material are welded steel or
and require no backwash. Cyclone separators canalso be
glass-reinforced plastic (GRP). GRP isalso known as fiber-
used as a full-flow filtration.
glass-reinforced plastic (FRP). Although steel is tougher
and morefamiliar to many mechanical contractors, GRP Typically, sidestream sand filtersare sized to continuously
merits consideration because it is lighter and easier to filter the cooling tower basin water inventory at a rate
install and is resistant to corrosion. Ifthe condenser water equivalent to about 3% to 5% of the total circulation
pH ismonitored and controlled in applications using steel flow rate through tower. In contrast, cyclone separators
pipe, corrosion should not be a problem, but using GRP are typically sized to circulate about 10% to 15 % of sys-
offers a corrosion-free solution. tem flow. Both systems can be used with sweeper jets in
the basin to keep the basin floor cleaned and minimize
The supporting requirements for GRP are significantly manual cleanings. However, if the sweeper jet option is
different than for steel. Concentrated loads must be selected, it is important to get expertadvice on its imple-
avoided, thus saddles should be used to spread the mentation and operation at the design stage.
weight from clevis or roller hangers over a greater area;
for larger pipe, the distances between supports should In general, the designer's decision whetherto select sand
be shortened to achieve the same level of support. GRP filters or cyclone separators is based on a variety of
issusceptible to ultraviolet damage and sunlight-induced factors, with primaryconsiderations, including
biological growth, sooutside GRP pipingmustbe painted ospace availability,
or covered. To avoid potential water hammer issues, • cost considerations,
water velocity should be kept below 3 mls (10 IVs) and osizes and characteristics of particles requiring filtra-
the friction coefficients appropriate for pipingandfittings tion and
should be used. Using lower velocities can reduce the • acceptable level of maintenance requirements.
flow imbalances induced by non-symmetrical piping
arrangements. Using lower velocities also results inlower The experience of districtcooling plant operators in the
pressure drops and, in turn, less pumping power. Middle East has suggested that sidestream filters in the
chilled-water system have limited utility after the
7.8.2 Sidestream filters commissioning and initial operating phases. However,
Water treatment programs can control dissolved solids, most experience has been with systems using indirect
but cannot remove suspended solids. Air contains solid customer connections. When customers are directly

88
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008 Inlemar;onal District Energy A55ociar;on. All nghl5reserved.

Performance Characteristic Cyclone Separator Sand Filter


Particulate removal ability on sidestream 98% efficient in removing 45 micron 95% efficient in removing 10 micron
application and largerparticulates with specific and larger particulates {will remove
gravityof 1.6 or greater(removes heavier particulates aswell as particles
particulates that sink in water). that float in the water).

Removal of particles lighter than water Very low efficiency of removal. Light High efficiency in removing Iighterl
(floating particulates) particles will tend to pass right through. floating particulate.

Susceptibility to fouling by oil or grease Presence of oil or grease does not affect Oil and grease will foul media.
performance.

Positive media filtration Does not use centrifugal forces to Silica sand forms 1a-micron pockets
remove particles. that trap particles in the media bed.

Centrifugal forces Uses centrifugal forces to cause particulate None; uses positivemedia filtration.
to spin out of suspension.

Pressure drop across unit Pressure drop across separator isconstant Pressure drop across sand filter will
at specific flow rate. Pressure drop across increase as media bed becomes full of
separator unit will not increase aspurge debris. When differential across vessel
chamber becomes full of debris. Separator reaches 16-psi differential,the pressure
will just pass debris ratherthan removing. switch will initiate backwash.

Full-flow application Best application for cyclone separator as Normally not recommended for sand
pressure dropacross unit isconstant. filter, aspressure drop across vessel
increases asunit becomes dirty.

Backwash cycle Nobackwash; purgeonly. Sand filter backwashes for 3 minutesat


its designed flow rate.

Backwash frequency Does not apply. Backwash is generally onceevery24


hours. When differential across filter
vessel reaches 1.1 bar (16psi) differential,
filter will go into backwash mode.
If pressure switch doesnot activate
backwash, then 24-hour time clock will.

Purge cycle Separator can be manually or automatically Does not purge.


purged to drain. Time needed to clean
lowerpurgechamber is 10-15 seconds.
Waterloss isminimal.

Drainsize required Minimal quantity purged. In general, size Needs to be sized to accommodate 3
the sanitary drain to equate to the size of minutesof backwash at design flow
the purge valve; for example, 1" for 1", rate. If drain available is not big enough,
consider using holding tank.

Purge or backwash water recovery Bag filter can be plumbed into separator Bag filter can be plumbed into backwash
purge outlet,with outlet of filtertypically outlet. Need to size bagfilter to accom-
plumbed to suction side of the pump. modate size of backwash. Advantage is
Advantage iszero water loss. Disadvantage zero water loss. Disadvantage is regular
isregular bagcleaning. bag cleaning - even highermaintenance.
Frequency of filter media replacement If used, backwash water recovery bags Silica sand usedshould last 5-6 years.
will last6-12 months. Sand may need replacing earlierif oil-
fouled or biologicallyfouled. If used,
backwash water recovery bagswill last
6-12 months.
Required maintenance Lower maintenance due to fewer moving Potentially highermaintenance with sand
parts. If skid packages chosen, pump filter skid. In addition to pump seals,
seals, pump motorsand auto-purge pump motors and media pack needing
valves mayneedreplacement overtime. replacement, the valves, linkage, timers,
valve actuatorand pressure switchmay
need replacement overtime.
Footprint of skid plus flexibility of design Footprints of skid systems with flow rates Sand filter skid packages with flow rates
9.5 Vs (150 9pm)andhigher, the separator of 9.5 Vs (150gpm)andhigher tend to be
tendsto be significantly smaller in size. larger andheavier (due in partto weight
Also, the separator can be configured of filter pack). As an example, a 63.1 lIs
from a vertical profileto a 22-1/2 degree (1000 gpm) sand filter system could be
profilewherethere is height limitation 5-6 times the size of a similarseparator.

Table 7-12. Performance characteristics of sand filters vs. cyclone separators.

89
DISTRIQ COOUNG BEST PRAQICE GUIDE
02008lntermlUon~1 Dis!Tict Energy Ass"ocialion Allrights re5fNVed.

connected to the districtcooling distribution system, side- how chiller motors and compressors will be removed if
stream filters may be useful. Since the district cooling and when that becomes necessary.
company has little or no control over the customers'
piping, contamination from the customers' sides is a It is generally difficult to justify the costs of 3-degree
concern and sidestream filters maybe appropriate. movement bridge cranes. Instead, 2-degree movement
monorails often provide the mostappropriate facilityfor
7,8.3 Cooling tower basin sweepers maintaining and movingheavy loads, provided the space
Although coolingtower basin sweepers have been used is clear to get the component from the operating
successfully in many North American and European position to the floor for subsequent replacement or
installations, experience has shownthey offer little bene- repair. Therefore, it is important to keep the hoisting
fit in the Middle East, wherethe primary "contaminant" pointsabove equipment components clear Lighting isim-
is the extremely fine sand that so often blows through portantfor maintenance, but lights (orcable trays) should
the area. Much of thisfine sand isonlystirred up by basin not be placed in the way of the hoists. Likewise, pipingto
sweepers and requires manual removal from the basin. the chillers also must not encroach into the access
Also, manual labor costs are much lower in the Middle removal areas or prohibit component removal.
East than in North America and Europe, making manual
basin cleaning more cost-effective. During design, it is also importantto anticipate the need
for removing components from the cooling tower.
7.8.4 Transformer room cooling
Although transformers are efficient, theydo give off heat- Lifts (elevators) facilitate movement of thetools, equipment
- as much as 0.8% of thetransformer rating. This heatmust andsupplies required for maintenance andcan be consid-
be dissipated in some fashion. If the transformers are ered an elementin the planthealth andsafety program.
located outdoors, then they are cooled using natural
convection. However, when the transformers are located
7.8.6 Noise and vibration
Since districtcoolingplants are oftensited in densely pop-
inside rooms, the heat must be removed mechanically.
ulated areas of high-value real estate, understanding and
Ventilation cooling and air conditioning are the two
controlling sources of noise and vibration are fundamen-
mechanical options available for cooling transformer rooms.
tal tasks for the districtcooling plant design. Increasingly
common is integration of the district cooling plant with
After the transformer heatgainisdetermined, ventilation other building uses, so controlling noise and vibration is
cooling air flow can be calculated for various levels of critical to maintaining positive public relations with the
temperature rise. Since transformers are derated at higher other "tenants."
ambient temperatures, it is important to understand the
tradeoff between the volumes of air circulated (size of The appropriate strategy depends on the specific plant
air-handling units)and the possible derating of the trans- configuration, proximity to neighbors, site conditions and
formers. Additionally, the large volumes of air that have local codes or ordinances. To set the proper framework
to be moved require large openings, and if noise emis- from which to assess noise and vibration, thedistrict cool-
sion is a potential issue, these openings will require sound ing company should engage an experienced acoustics
attenuation. Additionally, since dry-type transformers are consultant to document background noise levels and to
less efficient with dust on them, it is important to recommend control strategies.
thoroughlyfilter the outside air.
Theacoustics consultant commonly will have datafor the
Air conditioning canbesupplied using chilled waterfrom various noise sources; however, the analysis will be im-
the districtcooling plant. Equipment sizes will be much proved if actual sound dataisavailable for the equipment
smaller compared to the ventilation fans, and it will be proposed for the plant.The potential sources of noise and
easier to mitigate noise problems; however, thetons used vibration include
to cool the transformer rooms will not beavailable to sell .chillercompressors and motors;
.chilled-water pumps & motors;
to district cooling customers, sothe life-cycle cost of using
.condenser-water pumps and motors;
air conditioning will be significantly greater than using
• noise generated from water flowing through piping,
ventilation cooling. especially from cooling towers where towers are
located above other "tenant" spaces;
7.8.5 Equipment access • cooling tower fans;
Designers know to provide clear space to pulland replace .cooling tower water falling through fill materials;
evaporator and condenser tubes, but similar care should .auxiliary mechanical equipment;
be provided for other equipment likepumps, air-handling .control valves;
units. motor control centers, etc. Asexamples, the design • main electrical power transformers; and
engineer should consider how pump cases will be • emergency power generators.
removed from large horizontally split case pumps and

90
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lntemanOflal D!sfTiet Energy Alloo'arion. Alldgllt5reserved.

The acoustics consultant will establish sound level criteria Normally the study would confirm that over-current
and propose strategies for reducing noise to meet the protective devices are capable of interrupting the
criteria. These strategies might include maximum-available fault currents, andsince this depends
ohigh-density wall and floor construction, on the utility impedance values, it is important to start
osound reduction at all wall and floor penetrations, discussions with the electric authority very early in the
osound-rated door and frame assemblies, design process.
esound-attenuated ductwork penetrations,
osound-attenuated piping penetrations, 7.9.2 Protective device coordination study
oacoustically efficient selection of mechanical equip- The main objectives of the protective device coordination
ment and methods of installation study are to prevent injury to personnel. minimize damage to
o mechanical piping and ductwork insulation with system components and limit the extent and duration of
sound transmission barriers and/or service interruption due toequipment failure orhuman error.
• equipment inertia bases. The results of the coordination study will determine settings
for protective devices to trip in the desired sequence during
afaultcondition. This tripping sequence, inturn,isolates the
7.9 Electrical Systems
faultarea from the remaining portions of the powersystem,
thusminimizing plantoutages.
Proper electrical design has always been important in
district cooling plants, and as equipment sizes and
Short-circuit studies determine withstand ratings (thefault
voltages increase, it becomes even more critical that
current level which a device can safely handle for a
design is comprehensive and thorough. Because of the
defined time without failing) for electrical equipment. If
critical nature of electrical design and hazards, the design
rule-of-thumb values are used with the idea that the
engineer rather than the contractor should be responsible
contractor will to perform the final calculations, it is
for electrical design. If the contractor desires to change the
possible the electrical equipment, which tend to be long-
design, those changes or deviations should be reviewed,
lead items anyway, will be delayed even longer as the
evaluated and approved by the design engineer.
contractor and owner settle why the contractor's offer-
ing must be differentfrom the design engineer's rules of
Engineers should perform such critical studies as the thumb. To avoidthis confrontation, the design should be
oshort-circuit study, completed by the design engineer.
• protective device coordination study and
oarcflash hazard study. 7.9.3 Arc flash hazard study
The main objectives of the arcflash hazard study are to
7,9,1 Short-circuit study determine the necessary flash-protection boundary
Short-circuit studies determine the magnitude of currents distances and incident energy to determine the minimum
flowing throughout the power system at various time personal protective equipment (PPE) requirement. The
intervals aftera "fault" occurs and at various locations in results of the arc flash study can be used to reduce the
the plant. The output of the study PPE requirement, since adjustments to reduce the arcfault
oidentifies whether the system and equipment can conditions will result in reduced PPE requirements. It is
withstand the available fault current; expected that the outcome of this study, when imple-
ospecifies the ratings of the equipment; and mented, will result in mostCategory 4 PPE requirements
• describes conductor construction, lengths, and being decreased to Category 1 or 2.
reactance to resistance (XlR) ratios, transformer
impedances, ratings, wiring connections and short- For further informationon arcflash studies please see the
circuit protective device ratings. Appendix C.

91
DISTRICT COQUNG BEST PRACTICE GUIDE
02008lnrema/ional Dis/ncr EnergyAssodaM{J, Allrightsreserved.

8. Controls, Instrumentation and Metering


8.1 Introduction I/O input/output
mADC milliamps DC
District cooling instrumentation and control systems OIT operator interface terminal
(DCICSs) can be complex and distributed in nature due OLE object linking embedding. A technology
to the number of locations that must be controlled and that supports the linking and embedding
the necessity to interface equipment from various of objects from one application, seamlessly,
vendors at each location. DCICSs vary greatly from one intoanother application.
provider to another. Even the equipment owned by a OPC OLE for process control. A standard that
single provider can vary greatly from site to site. specifies communication of real-time
plant data between devices from different
manufacturers.
PC personal computer
PLC programmable logic controller
Provider district cooling provider
RTTMS real-time thermal modeling and simulation
SCADA supervisory control and data acquisition
SOP standard operating procedure
A standard terminology must be developed to begin
UPS uninterruptible power supply
any "best practices" discussion. This chapter begins by
VDC voltage DC
presenting a few models that introduce this terminology
VFD variable-frequency drive
in a graphical format. Then a sample district cooling
instrumentation and control system is introduced, using
8.3 Overview
a "real-world" example to further clarify the models
previously presented. The remainder of the chapter 8.3.1 Typical DCICS functions
poses some best practice guidelines for each of the Depending on the provider, a typical district cooling
components contained in the models and the example. instrumentation and control system may perform anyor
all of the following functions:
Some of the concepts presented may not apply to every .Control and monitor process conditions at the
district cooling provider's system. For example, the district cooling provider'svarious plants automatically,
sample system described in this chapter is comprised with little or no user intervention.
of a network of various types of plants communicating • Provide a common user interface for the provider's
with two separate command centers. It should be personnel, allowing them to monitor and control
understood that some district cooling providers may their plants either locally within the plant or from
not require this level of automation. Their network command centers located strategically throughout
architecture may not include any command centers at the provider's district.
all, electing to control and monitor their plants locally .Automatically gather accurate energy metering
instead of centrally. data and store this data in a format and location
that is readily accessible by the provider's accounting
The models, sample system and concepts presented systems for billing purposes.
here are meant to be generic in nature and are not .Automatically gather and store other types of data
intended to refer to any specific provider or equipment for maintenance and energy efficiency optimization
manufacturer. purposes .
• Alarm when process conditions traverse outside of
8.2 Definitions established normal operating ranges or when
equipment failure is detected both locally at the af-
The following terms and abbreviations are used fected plant and remotely as mandated by the
throughout this chapter. provider's standard operating procedures (SOPs).
• Provide indication of certain process parameters
BAS building automation system local to where the parameters are being measured.
DCICS district cooling instrumentation and .Allow any device that is usually controlled by the
controls system. Pronounced D-KICKS DCICS to be overridden and controlled at the site
DCS distributed control system where the device is installed.
DDC direct digital controller • Provide a common data VO interface for real-time data
EEMS expert energy management systems exchangewith external applicationssuchasexpert en-
EEPROM electrically erasable programmable read ergy management systems (EEMS) and real-time ther-
only memory mal modeling and simulation (RTTMS) systems.
HDA historical data acquisition
HMI human-machine interface
I&C instrumentation and controls

92
DISTRICT COOLING BEST PRACTICE GUIDE
02008 Intemil~'onill DistrictEnergy Association. All nghts reserved.

the system.
• Ease of disaster recovery.
• Ability to interface to the different types of
equipment that can be found in typical plant,
distribution, energy transfer and storage systems.
• Initial and ongoing operating costs of the system .
• Ability to grow as the provider's chilled-water
8.3.2 General design factors infrastructure grows, including integrating new
There are some general factors that must be considered
equipment without affecting existing operations.
before undertaking any DCICS design effort. These
factors will greatly influence the overall design and
deployment of the system:
• How will the provider operate and maintain the sys-
tem? Will control and monitoring functions be per-
formed locally at the plant level, remotely at
strategically positioned command centers, or a
combination of both?
.If remotely, is the communication infrastructure in
place in the provider's district to support the large 8.4 Physical Model
amount of inter-plant networking that is required
with this approach? figure 8-1 models the physical nature of a typical
.Will the plants be manned or unmanned? How will district cooling instrumentation and control system. The
equipment be sequenced on and off - manually, purpose of this model is to introduce a standard
automatically or semi-automatically? terminology that is used throughout this chapter.
• How will energy metering data be gathered? Man-
ually or automatically by the DClCS? Will sub me- A brief description of the various entities that make up
tering of the individual tenants be performed or will the DClCS physical model can be found in the following
the provider simply meter their customers' build- sections. A typical DCICS may contain any number of
ings and/or complexes as whole units? these entities.
• How will data be "forwarded" to the provider's
accounting systems? Electronically, or transcribed 8.4.1 Sites
manually? A typical DCICS site may physicallycontain the following
.WiII the DCICS be required to interface to any third types of installations:
party packagessuch as energy efficiency optimization .plant(s)
programs or maintenance scheduling programs? .command center(s)

8.3.3 DCICS performance evaluation 8.4.2 Plants


The following are key metrics to use in evaluating the for the purposes of this chapter, a plant is defined as a
performance of a DCICS: collection of equipment, piping and infrastructure that
• The system's ability to control and monitor the produces, stores, distributes or transfers cooling energy.
plant, distribution, energy transfer and storage sys- Examples of plants include, but are not limited to
tems in the most efficient and cost-effective man- • chilled-water production plants,
ner to satisfy their customers' chilled-water .thermal energy storage plants,
demand . .thermal energy transfer stations and
• Stability of the system. The system should be avail- • pumping stations.
able for provider use 24 hours a day, 365 days per
yearwith minimal or no downtime. Frequent or ran- Plants can be manned or unmanned.
dom "crashes" are not acceptable.
• Reliability of the system. 8.4.3 Local plant I&C system
• Accuracy and availability of the data generated by Each plant will typically be controlled by one local
the system. plant's instrumentation and controls (I&C) system. Each
.Ability of the system to monitor energy generation, local plant's I&C system will contain
demand and consumption and to act on that data .local plant controller(s),
in an effort to increase the district cooling provider's .Iocal operator interface terminal(s) and/or
overall efficiency. .operations workstation(s).
• Ease of use for the provider's operational personnel.
e Ease of development and serviceability. Local plant controllers
• Supportability of the system by multiple vendors, as
opposed to being tied to one vendor for the life of Local plant controllers are the "heart" of the local

93
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 International Di5tJict Energy As:socian'on. All rightsre~.

plant's 1&( system. They interface directly to the plant's


equipment, monitoring and collecting critical plant
data, while at the same time automatically executing
the algorithms that control the plant's overall operation.

Lovel5
Dlsb1ct
Cooling Intorfocos WI
CoolingProvldo(s Co
I&C ,-'- NeitworkFor:Cciriri8cti
System
;;';;,~e~lJ~r_'S;§lInli~·~~,:::ti'::\,';
, . Accounting Sys\oms,Export ,.
Ono '. :',Energy~anagem8llt'~~TII:;',:-H:i:'
-'-Malntenance,Syst~mS;,_:;,j:::,;::"j,;:::::,:,,:;-,
Optimization Sys\oms,'< ','
Opef8~on.s SlIPpprtSyStems; Eitc,
One Or Many
~LD-----...

Sites

Ono

None Or Many None Or Many


r-.L..L:'--" r-.L..L:'--"
Examples'
Chiller Plant, Command
Plants Energy Transfer station. Centers
Pumping station,
Thermal Energy storagePlant.
Ono

Ono

Local
Plant
I&C
System

Ono

Figure 8-1. DClCS physical model.

94
DISTRICT COOLING BEST PRACTICE GUIDE
e2008lntema~'onal Dim-Jet Energy A£;oda~'on. All n'gh!S reserved.

Field devices In its simplest form, a command center will consist of


a single computer performing all of operator interface,
Each local plant controller will have numerous field data logging and reporting functions required for the
devices connected to it. These field devices are either plant(s) that it serves.
inputs into the DClCS used for monitoring conditions
and equipment at the plant or outputs from the DClCS
used to control the plant's equipment. Field devices are
typically connected to the local plant controllers in one
of two ways:
ohard-wired signals, directlyinto the controllers' va
racks
oproprietary, high-speed industrial communication
networks

In more complex configurations, command centers may


consist of several server class computers, workstations,
displays, printers and other peripherals all working
together to provide the required services.

The number, type and purpose of each component in


a command center will vary greatly from one
Local operator interface terminals implementation to another. The terminology that each
manufacturer of command center equipment uses for
Local operator interface terminals (OITs) typically each component also varies greatly. The following
communicate at the local controller network level, sections utilize a standard terminology to categorize
connecting directly to the individual plant controllers. The some of the more commonly used components. Not all
purpose of the local OITs is to allow personnel to categories listed will be required in everyimplementation,
interface with the DClCS locally at the plant level. OITs and some implementations may require categories
are typically mounted on local control panels that are other than those listed.
generally installed in the vicinity of the controlled
equipment orsystems. For providers whodonotutilize a Data server
command center approach, as discussed below, the local
OITs function asthe primary userinterface into the DClCS. The data server is a computer that communicates
directly to the local plant controller(s). In a very simple
Local workstations configuration the data server may be the only computer
in the command center. In this type of configuration,
Local workstations provide an alternate user interface the data server polls all of the plant controllers that are
into the DClCS for providers who utilize a command in its purview for data and serves this data up to other
center approach. They can offer more functionality than applications that are running on the data server.
local OITs and are typically installed remotely from the
command center that services the plant (such as in a In more complex configurations, the data server may
supervisor'soffice or in an enclosure on the plant floor). be one part of a redundant array of data servers, polling
Unlike local OITs (that in a well-designed DCICS all of the plant controllers in its purview and serving the
communicate to the plant controllers directly), local resultant data up to other applications running on that
workstations communicate to the plant controllers data server and to other data servers and workstations
indirectly, through data servers in the corresponding that are part of the DClCS. In this configuration, all of
command center(s), and are thus dependent on the the applications running on the other servers and
command center equipment for their operation. workstations get their data indirectly from the plant
controllers via the data server.
8.4.4 Command centers
District cooling providers that elect to operate their Historical server
plants remotely will do so from what are referred to as
command centers. The command center provides a The historical server's role is to periodically collect data
centralized point of operation for the DCICS. A provider from the data server, to store that data to a mass
may have one central command center or may elect to storage device (i.e., hard drive) and to serve this data up
install several local command centers throughout their to the other equipment and systems that require it. A
district at strategic locations. A command center may typical historical server will collect, among other things,
also be dedicated to a specific plant, such as in the case customer metering data, process variables, alarms and
of a local plant control room. operator-initiated events.

95
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 International Disrnet Energy Association. All right!; re5eflled.

Terminal server

For district cooling providers who wish to give users in


their organization remote access to their DClCS from
computers that do NOT have any special software
installed on them, a terminal servermay be required. A
terminal server is a machine that hosts applications and
In a very simple configuration, the historical server serves them up to remote users without the need for
software may run on the only computer in the the remote usersto have any specialsoftware installed.
command center: the data server. The applications are installed and run on the terminal
server, not the remote users' machines. The remote user
In more complex configurations, the historical server simply logs in to the terminal server (typically using a
may part of a redundant array of historical servers, standard web browser) and starts the application as if
periodically polling the data server(s) for data and it was being run from the user's local hard drive.
storing this data to mass storage device(s) that are
accessible to the other equipment and systems that Other servers and workstations
require it.
Depending on the hardware and software selected to
Users of the data collected and stored by the historical implement the command center, other servers and
server include other DCICS applications aswell as many workstations may be required. One example may be a
types of Level 5 systems (i.e., accounting, maintenance, gateway server that bridges between the DClCS and
billing systems). an expert energy management system (EEMS) installed
on the provider's corporate network. Another example
Command center workstations may be a domain controller, which handles the
authentication of users and security policies in some
Local workstations were introduced during the operating systems. The number and types of other
discussion of the different plant components earlier in servers and workstations that may be required vary with
this chapter. Command center workstations serve the the scale and scope of the DCICS.
same function as local workstations except they are
installed in command centers. Both typesof workstations
8.5 Logical Model
provide windows into the DClCS for the provider's
Due to the distributed nature of a typical district
personnel.
cooling instrumentation and control system, it is easier
to visualize its various components logically as opposed
Another type of workstation that is typically found in a
to physically. Figure 8-2 maps the physical components
command center, but not locally at the plant, is an
that make up a typical DCICS onto a logical model.
engineering workstation. An engineering workstation
allows properly trained personnel to troubleshoot and 8.5.1 Level 0
modify the different objects (displays, graphical objects, Level 0 equipment is installed in the field and directly
programming objects, reports, etc.) and programs that
monitors or controls the production, storage, distribution
perform the DCICS functions. or transfer of the cooling energy and its media. Level 0
devices do not utilize a network to connect to the
Regardless of whether a command center workstation DCICS controller(s) directly; instead, they are connected
is used for operational or engineering purposes, it is via hard-wiring through a Level 1 device.
typically an office-grade machine that has software
installed on it that allows it to communicate to the data Examples of Level 0 equipment include sensors and
transmitters that monitor process variables such as
temperature, flow, pressure, electrical current, electrical
voltage and contact closures. Other examples of Level
o equipment that control equipment in the field are
motor starters for constant-speed pumps and fans,
solenoids for isolation valves and transducers for
modulating control valves.

server, the historical server and any other server Typically, Level 0 devices are configured and calibrated
required to perform its stated purpose. Additionally, an via switches, potentiometers, and/or jumpers located
engineering workstation will have development directly on the devices. Due to their hard-wired nature,
versions of that same software, as well as other there is typically a limited amount of information that
programming/configuration tools installed on it. can be obtained from Level 0 devices.

96
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lntemd~Ondl Dislri:! &1ergy A5:ioda~on Ailrightsreserved.

LevelS- District Cooling Provider Corporate Network


• systems on this network that typically Interface to the
DCICS Include but are not limited to

remote DCICS users

billing and accounting systems

expert energy management systems

maintenance systems

optimization systems

operations support systems
• levelS equipment Is beyond the scope of this chapter

Level 4 communicateswith level 5


over the central data network
through the use of a network
bridgelroutetfflrewall.
Level 3- Local Plant Operator Interface Terminals Level 4- Human Machine Interface{HMI)Systems
• typically installed in control panels directly on the • components typically installed In command centers
plant floor • master/backup data servers
• should not be dependent on level 4 equipment to • historical data servers
communIcate with the level2equlpment • terminal servers
• allows operators to control and monitor plant In cas
• workstations
of loss of communication to the level 4 equipment • components typically Installed locally at the plants
• workstations
Level4 devices communicate
with each other over the central
data networi<. The central data
network should Mbridge- all of the
controller networks.
Level 2 communicateswith
levels 3 and 4 via the central or
local controller networks
Level 2- Local Plant Controllers
examples:

·· condenser water(CVII) system controller


cooling tower(CT) controller

·• chllied water(CHW) system controller


energy transfer statlon(ETS) controller

· pumping station controller

Levell communicateswith level


2 via proprietary high speed
Industrial networks or the
controller's back plane

Level 1- Smart-Network_Read~Field Instrumentation,Controlied


Devices, And Interface EqUipment
examples:

·· smart-network ready transmitters


local and remote controller I/O racks and
modules

·• on-board chiller eentreners


variable frequency drives

· energy monitoring equipment


Level 0 communicateswith Levell
via hard wiring.

Level 0- HardoWlred,Field InstrumentatIon And Controlled


Devices
examples:

·· hard-wired sensors and transmItters


motor starters for pumps and fans

·• solenoids for isolation valves


transducers for modulating control valves

Figure 8-2. DClCS logical model.

8.5.2 Level 1
Level 1 devices connect directly to their associated
controller via proprietary high-speed industrial networks
or directly to the controller'sinternal communications bus,
not by hard-wiring, as is the case with Level 0 devices.
Certain Level 0 devices utilize communication protocols
that are superimposed on the hard-wired I/O signals Levell devices are "smart" devices that are typically
(i.e., HARTprotocol). Thesetypes of deviceswould still configured and calibrated through the use of special
be classified as Level 0 devices since the physical configuration software over the same network that
connection to the DClCS controller(s) is via hard-wiring, connects them to their associated controllers. In
not a communication network. addition to the process variable(s) that they monitor,

97
DISTRICTCOOUNG BEST PRACTICE GUIDE
C2008 Intelmtional DJStnd EnergyAllrxiation.Allrightsreserved.

many other variables such as tag names, ranges, erating data and alarm/diagnostic information, can be
malfunction reports and configuration details can be obtained from the onboard chiller controller over this
read from Levell devices by the controllers that are high-speed network.
connected to them. This type of information would not
be available using an equivalent Level 0 device. Variable-frequency drives - Variable-frequency drives
(VFDs), which are also called variable-speed drives
Examples of Levell equipment include "smart-net- (VSDs), are devices that control the various types of
work-ready" transmitters, local and remote I/O racks motor-driven devices that are found in a typical plant
and modules, some variable-frequency drives and most (compressors, fans, and pumps). The proper use of
energy meters. VFDs is one of the best ways to increase plant energy
efficiency.
Some Levell devices, such as "smart-network-ready"
pressure transmitters, are standalone and do not VFDs are typically connected to the DClCS via a high-
require any Level 0 devices to perform their stated speed industrial network due to the large number of
function, Other types of Levell devices, such as chilled- control and monitoring points that are available from
water energy meters, require that hard-wired Level 0 them. However, some providers continue the practice of
instruments (temperature and flow transmitters) be using hard-wiring to connect critical control points, such
connected to them to perform their energy calculations. as start/stop, speed control and running status. In this
Thesole purpose of yet other typesof Level 1 devices, such scenario, where critical points are hard-wired, the high-
speed network is still typically connected, but the data
gathered over it is used for monitoring purposes only.

Energy monitoring equipment - Energy monitoring


equipment, as the name implies, is used to monitor the
energy (both electrical and thermal) produced and/or
consumed. A typical energy meter will consist of the
as local and remote VO racks and modules, is to conned
meter itself, several hard-wired Level 0 devices (such as
Level 0 devices to their associated controller. Regardless of
temperature sensors/transmitters, flow sensors/trans-
a device's function, if it is connected to the DCICS
mitters, current transducers, voltage transducers) and a
controlleroveranysort of high-speed industrialnetwork or
high-speed industrial network data connection to the
through the controller's internal communications bus, it
meter's associated controller. The network connection
should be considered a Levell device.
is required due to the large amount of metering data
that is available from a typical energy meter. Hard-
Following are descriptions of some of the typical types
wiring of all of these signalswill not be practical in most
of Levell devices:
circumstances. These devices are critical to the district
cooling provider's businesssincethey are typically used
Local I/O modules - Hard-wired Level 0 devices are
for billing purposes and evaluating plant operating ef-
connected to their associated controllers via local I/O
ficiencies.
modules. These modules are installed in the same rack
as the controller and communicate with the controller
Field instrumentation - Most manufacturers of field in-
over its internal communications bus.
strumentation (temperature, flow and pressure trans-
mitters, etc.) provide communication options for their
Remote I/O racks and modules - Remote I/O racks and
equipment which allow them to communicate to their
modules serve the same function as local I/O modules
associated controllers over a high-speed industrial net-
in that they are the termination point for any Level 0
work, as opposed to hard-wiring them. If field instru-
devicesthat need to interface with the controller. How-
mentation is provided with a communication option,
ever, unlike local I/O modules, remote I/O modules are
then it would be categorized as a Levell device, not a
installed in remote I/O racks, not the controller rack.
Level O.
The remote 110 racks are, in turn, connected to the con-
troller over a proprietary high-speed industrial network.
8.5.3 Level 2
Onboard chiller controllers - The chiller manufacturer Level 2 is reserved for the local plant controllers.
typically supplies the onboard chiller controllers with Controllers come in many shapes and sizes and are
the individual chillers. These standalone controllers available from a multitude of vendors. As mentioned
monitor and control essential chiller operations, such during the discussion of the physicalm, the controllers
as modulation of chiller capacity and interlocking of the are the "heart" of the local plant I&C system,controlling
chiller safety circuitry. Chiller controllers will typically and monitoring the plant's overall operation.
communicate with the DClCS over high-speed indus-
trial networks. Real-time Information, such as chiller op- Basically there are three categories of controllers

98
DISTRICT COOLING BEST PRACTICE GUIDE
C2008Intema~OnaIDlW!ct Energy AssoClaOOn. Ai/rights ""served

available on the market: that either type of system is adequate to control any
oprogrammable logic controllers (PLC) provider's DClCS. It should also be pointed out that
o distributed control systems (DCS) with the technology available today, it is possible (and
o direct digital controllers (DDC) even likely) that some providers will elect to install
hybrid PLClDCS systems.

Table 8-1 summarizes some of the pros and cons of


each type of system. The purpose of the table is not to
recommend one type of system over another, but to
assist the district cooling provider in selecting which
type of system to implement for its DClCS. However.
more often than not, this selection will be made based
Direct digital controllers (DDC) are ideally suited for
on lesstechnical criteria, such aspreviously installed sys-
commercial building automation Systems (BAS), but are
tems, familiarity with a particular system and the avail-
not usually a good fit for the industrial nature of a
ability of local vendor support.
modern DCICS. As such, they will not be discussed in
this chapter.
8.5.4 Level 3
To compare the other two categories of controllers Local operator interface terminals (OIT) reside at Level
(PLCs and DCSs), it is helpful to understand the history 3 in the logical model. These terminals are installed
behind their design, development and deployment. locally at the provider's various plants, typically in
oPLCs were originally designed to control discrete control panels mounted directly on the plant floor. The
types of systems. Most of their inputs and outputs main purpose of these OITs is to allow the provider's
were discrete (or binary) in nature. Since little personnel to control and monitor the equipment locally
computing power was needed to process binary at the plant.
data, PLCs tended to operate very quickly, making
them ideal for machine control where speed is of For providers who do not utilize Level 4 equipment, the
the essence. local OITs serve as the only interface to the plant's
o DCSs, on the other hand, were originally designed equipment. For provider's who do utilize Level4 equip-
to control processes. The majority of their inputs ment, the local OITs often serveas secondary interfaces
and outputs were analog in nature, measuring into the DCICSthat are used only if the link to the Level
process variables such as temperatures, pressures, 4 equipment is severed.
flows, pH and conductivity. Complex algorithms
were bum into the operating systems of the original The local OITs are often connected directly to the Level 2
DCSsto handle these types of signals and, as such, controllers and do not rely on any Level 4 equipment
they tended to operate more slowly than PLCs, (e.g. Level 4 networks hubs, switches or routers) to com-
which in most cases was acceptable for the types of municate with the controllers. Thisis key to ensuring that
systems they were controlling. the plant can still be monitored and controlled even if
the Level 4 equipment is taken off line for any reason.
Since the early 1990s everything about computers has
increased at almost exponential rates (processor power
and speed, memory sizesand speeds, storage capacity,
etc.), while at the same time the costs of computers
and computing components have decreased at nearly
the same rate. This has caused the line between PLCs
and DCSs to blur to the point where the two are
almost indistinguishable from each other from the point The choice of local OITs will often be based on what
of view of their capabilities. Today's PLCs can handle equipment is being used at Level 2 (i.e., the controllers)
huge numbers of analog points and havethe instruction because they are so tightly coupled with those con-
sets necessary to process those points for most appli- trollers,
cations. Conversely, modern DCSs are usually fast
enough to handle most "discrete intensive" machine Local OITs in a DClCS environment typically have much
applications. less functionality than their Level 4 counterparts and
will have little or no permanent data storage capabilities.
Of course there are still some tasks where a PLC will
out-perform a DeS and vice versa. Any discussion at- 8.5.5 Level 4
tempting to compare the two types of systems would Level 4 in the logical model is the domain of the
invariably lead to both positive and negative arguments human-machine interface (HMI) equipment. Equipment
for each. For the purposes of this chapter, it is assumed at this level is unique in that some of it may residein the

99
DISTRICT COOLING BESTPRACTICE GUIDE
02008/nremao'ona/ Districr Energy AssodaMn.AI! nghrs~.

Controller
Pros Cons
Type

Programmable Logic • Easily integrated with tbird-party hardware. • Because the programming languages arevery
Controller (PLC) • Easily integrated with third-party user inter- flexible, PLC programs can be difficult to
face systems (Levels 3 and 4). troubleshoot and maintain if the programs
• Programming languages are very flexible and are not written according to a pre-approved
easyto troubleshoot, provided the programs standard.
are written according to a pre-approved stan- • The controller and userinterface systems are
dard. usually not as tightly integrated as with a
• The ability to have multiple manufacturers' DCS, which may increase application devel-
PLCs seamlessly integrated to each other and opment time.
to a single-user interface.
• Therearethousands of integratorsworldwide
who can support and service PLCs. If a
provider's relationship with a particular PLC in~
tegrator sours, ongoing support for their
DClCS is usually easy to find.

Distributed Control • The controllers (Level 2) and user interfaces .A DCS is proprietaryin nature. Once a DCS is
System (DCS) (Levels 3 & 4) aredesigned asone system. One selected, the provider is usually married to
"front-end" isusedto program both the con- that manufacturer's controller, I/O and user
trollers and the user interfaces. This usually interface equipment and software.
meansfaster application development time. elt is necessary to usethe DCS's userinterface.
• A DCS typicallyhasadvanced algorithms built Connecting to third-party HMI systems may
in that makescomplicated processing of ana~ be cumbersome and even impossible.
log points easier than PLCs. However, most elf none of the built-in algorithms meet the
DCICSs will never need to take advantage of requirements of the system, the program-
these types of algorithms. ming languages are usually not powerful
• Because the controllers and userinterfaces are enough to createyour own algorithms.
designed asone system they will typicallyhave • Des manufacturerstend to limit the number
advanced self-dlaqrostk capabilities. of companies who support their equipment
to a select few per region. Finding ongoing
support for their DCS may prove difficult if
the relationship between the provider and
the companywho originallyinstalled the DCS
is severed for any reason.

Table 8~ 1. PLC vs. DeS- pros and cons.

provider's command center(s), while other components integrated into the DCS. In fact, manufacturers of DCS
may be located on the plant floor(s). systems may argue that there is no distinction at all
between Levels 2, 3 and 4. However, for the purposes
of this chapter and the sake of consistency across
platforms, these levels will remain as previously defined.

8.5.6 Level 5
Level 5 systems are installed on the provider's corporate
network and interfacewith the DClCS. Examples include
Examples of Level4 equipment that reside in command .Iinks to remote DClCS users;
centers include master/backup data servers, historical .billing and accounting systems;
data servers, terminals servers, operations workstations .maintenance systems;
and engineering workstations. Note that command .optimization systems, such as real-time modeling
centers may be local to the individual sites (such as in and simulation software;
a control room in a chilled-water production plant) or eexpert energy management systems; and
may be located remotelyat strategic locationsthroughout • operations support systems.
the provider'sdistrict. Typically, the only Level 4 equipment
that resides on the individual plant floors themselves is Level 5 equipment is beyond the scope of this chapter.
operations workstations.

It should be noted that if a DCS system is used at Level


2, then the distinction between Level 3 and Level 4
equipment is often non-existent. A DCS generally
deploys only one type of user interface and it is tightly

100
DISTRla COOLING BEST PRACTICE GUIDE
C2008 klflm<llli:m,,1 DistricfEm1Igy As5ocfa~'on. /lJlnghtsreserwd

i p'SJWCT COOl lUG


t eecseee
Ilo""'''''''T~c<:rporaleNe"""k
i FerC,mnta;y;'yTo; , QCAl COMMANDCEm~R
I R~mot" U"""'.
Bil""!' and Ac::ounling 51$1~"''',
Mmn!lffiaO""5, ...em ..
'"a.<l<"p
M """,Dffi.So",,,
D.IO5.......,
Op'Jm'''''tlOn5y:;'"",s, H;"""ic.,ISeN",
I
',."_1« TwoOnemh"n, Wo~.m,,",,

II
,~I.-=--~_~
TYII"; TlJ><m:>'Enug,'S:-'<>S"
/ PlAIJT-9' PI.ANT_D' CHwrrES cw
Typ<" E""'ID'T,""~!!tatio" T,;»: En"'!JY TJ'ao.lar Slauon COIll"'!"',At-~l"""l ConI""''''AIld
IIOl.1od,.., \.OO.lliOMoo",,,,,

g,,,,,rU'! lA'rIa~l.
~""'" OnMool ~"",gy
MO"'lo"n, ''ORa<'" CM.,
Contro;ler;
fro"""""
00....
Mo-,it<>r,ng
~Q";pm,nl l.,dM:>J""" ~o";pm""l

""""""
Tl'l"" CI>,~<-dW,a.-
P'OduCMn
CHW ow
Conlm'., Aod Conl'ol .. And ~
L,,,,,I
orr, 09<"''''n.
W¢<,_".t;pr,
LCMll10 """,,,,,,. 110Moo",,",

CM:,.I
'M
Nw.-mk F.,r",'ilY V<.r1.~[<'
En.'lI\'
Moo;;oo"g
1.1.,,,,,orln~ F"'G"""CY E<t'J;p...,o"'
~quiPl"."1 Dr,. ..

Figure8-3. Sample DClCS system.

8.6 Sample DClCS .water-quality conditions(conductivity, resistivity, pH)

Figure 8-3 illustrates a sample DCICS. The purpose of It is important to specifythe proper instrumentation to
this figure is to further clarify the models previously effectively monitor and control a plant's operation. An
introduced in this chapter. It is not intended to represent under-instrumented plant will be difficult to operate,
any specific provider's system or to imply the use of any maintain and troubleshoot. An over-instrumented plant
specific manufacturer's equipment. To simplify the will be expensive, confusing to operate and will not
figure, Level 0 equipment is not depicted. necessarily lead to a "better" control system. Both
situations should be avoided.
8.7 Level 0 - Best Practices
Careful analysis should be conducted of the plant's
The sections that follow present some guidelines for operating requirements. In order for a point to be
specifying and installing Level 0 equipment. considered, it must be needed to
.effectively control the plant's operation based on a
8.7.1 Point justification pre-approved sequence of operations;
The following process variables are monitored and .gather information about the plant's operation for
controlled by Level 0 instruments in a typical district accounting or administration purposes (i.e., for
cooling instrumentation and control system plant: customer billing or efficiency calculations);
.temperature .notify plant operations that the plant is not
.Iiquid/steam flow operating properly or that a problem has occurred
.Iiquid/steam pressure or is about to occur; and
.outside-air humidity .drive external Level 5 applications like optimization

101
DISTRICT CaaUNG BEST PRACTICE GUIDE
C2008 Inremabonal OlwJet Energy AmJoalion. All n'ght> re:.ervro.

applications and operations support systems. sensors that are available for some process variables
that are typically found in a plant and some best
8.7.2 Criteria for device selection practice specifications that should be considered when
Before selecting an instrument, its purpose must be specifying each type of instrument.
considered. Forexample, if a temperature transmitter is
being used for customer metering it will require a 8,7.3 Redundant Level 0 equipment
higher accuracy than if it were used solely for Where the monitoring of a certain process variable is
troubleshooting purposes. critical to the plant'soverall operation, redundant Level 0
instrumentation may be required. The controller that
Once the purpose of the instrument is ascertained, the the instrumentation is connected to would determine
specification of the proper instrument for the task can which transmitter to use and should alarm if the values
be made. Table 8-2 outlines the different types of being read from the transmitters differ from eachother

Process
Sensor Types Best Practice Specifications
Variable
Temperature • RTDs - resistive temperature 1. End-to-end accuracy: Liquid:
detector(preferred) Critical: +/- 0.56 C (+/- 1 F)
• Thermistors Non-critical: +/- 0.56 C (+/- 1F)
Air(dry bulb): +/- 1.11 C (+/- 2 F)
2. Resolution: +/- 0.56 C (+/- 1 F)
3. Process connections: Liquid: Use thermo wells that pene
trate the pipethey are installed in by
the lesser of half the pipe diameter or
six inches. Air: Provide protection
from direct sunlightand the building's
exhaust when installed out doors for
moreaccurate readings.
4. Sensor range: RID: -260 C(-436 F) to 650 C(1202 F)
Thermistor: -136 C(-212 F) to 150 C
(302 F)
5. Transmitter range: 4-20 mADC (preferred), 0-20 mADC,
0-5 VDC, 1-5 VDC, 0-10 VDC, 2-10
VDC, or -10-10 VDC signal propor-
tionalto a specified range within the
overall sensor's range.
6. Transmitter type: 2-wire (preferred)
7. Cost RTD: Moderate
Thermistor: Low
8. Stability: RTD: High
Thermistor: Moderate
9. Sensitivity: RTD: Moderate
Thermistor: High
10. Linear: RTD: Yes
Thermistor: No
11.Number of sensor wires: 3 or 4 wiresare acceptable
12. Transmitter mounting: Integral to sensor or located remotely
on a pipe, instrument stand, wall or
panel areall acceptable. Should be
easy to access for maintenance and
calibration purposes. If thereis a local
display, it should be at eye level and
easily read. Note that some con-
trollers can accept RTD and therrnis-
tor inputs directly without the need
for a separate transmitter.
Liquid Flow • lnllne magneticmeter 1. End-to-end accuracy: In-line magnetic meter:
(preferred) Highest +/- 1% full-scale typical
• Ultrasonic meter Ultrasonic meter, vortex meter:
• Insertion magnetic meter High +/- 2% full-scale typical
• Vortexmeter Insertion magnetic meter, insertion

Table 8-2. Level 0 best practice specifications. Continued


102
DISTRICT COOUNGBEST PRACTICE GUIDE
02008 Intema~"onal Dis/ncr En«gyAssocfa~i:ln. All n'ght5 re~

Process
Sensor Types Best Practice Specifications
Variable

Liquid Flow • Insertion turbine turbine:


(continued) • Insertion paddle Medium
• Orifice Insertion paddle, orifice:
Low
2. Resolution: 0.063lis (1 gpm)
3. Process connections: Adhere strictly to manufacturer's
requirements for straightrunsof pipe
upstream and downstream of meter.
4. Turndown ratio: Inline magnetic meter: 1000:1 typical
Ultrasonic meter: 1000:1 typical
Insertion magnetic meter: 50:1 typical
Vortex meter: 30:1 typical
Insertion turbine: 30:1 typical
Insertion paddle: 10:1 typical
Orifice: 5:1 typical
5. First cost: Inline magnetic meter: High
Ultrasonic meter: High
Insertion magnetic meter: Medium
Vortex meter: High
Insertion turbine: Medium
Insertion paddle: Low
Orifice: Medium
6. Ongoing maintenance Inline magnetic meter: Lowest
cost: Ultrasonic meter: Low
Insertion magnetic meter: Low
Vortex meter: Medium
Insertion turbine: High
lnsertion paddle: High
Orifice: Medium
7. Transmitter range: 4-20 mADC (preferred), 0-20 mADC,
0-5VDC, 1-5 VDC, 0-10 VDC, 2-10
VDC, or -10-10 VDC signal propor-
tional to specified range within the
overall sensor's range.
8. Transmitter type: Integral to sensor or located remotely
on a pipe, instrument stand,wall or
panel areall acceptable. Should be
easy to access for maintenance and
calibration purposes. If there isa local
display, it shouldbe at eye level and
easily read.
9. Transmitter mounting: Integral to sensor or located remotely
on a pipe, instrumentstand, wall or
panel areall acceptable. Should be
easy to access for maintenance and
calibration purposes. If there is a local
display, it should be at eye level and
easily read.
10. Other considerations: Ultrasonic meters mayprovide false
readings if air or other particles pass
throughthem.
Orifice meters require a pressure drop
to operate, which increases energy
consumption and are not recom-
mended for usein a typicalDClCS.
Paddle, turbine and vortexmeters
typically require more maintenance
then magnetic and ultrasonic meters
and are also not recommended.

Table 8-2. Level a best practice specifications. Continued

103
DJSIRICT COOLINGBEST PRACTICE GUIDE
C2008lntemiltionalDistrictEnergyAssOCIation. All right! reserved.

Process
Sensor Types Best Practice Specifications
Variable
liquid Pressure • Capacitance 1. End-to-end accuracy: +/- 1% full-scale typical
• Piezoresistive 2. Resolution: 6.9 mbar (0.1 psi)
(eithertype is acceptable for
most DCICS applications) 3. Maximum operating Sensor-specific. Mustbe greater than
pressure: the normaloperating pressure that
the instrumentwill experience when
installed.
4. Normal operating Application-specific - should be
pressure: specified during detailed DClCS
design. Must be less than the
maximum operating pressure that
the instrumentis designed for.
5. Burst pressure Sensor specific. Must be greater than
the maximum operating pressure that
the instrumentis designed for.
6. Process connections: Typically provided through capillary
tubing. Isolation valves should be
used at all capillary pressure tapsinto
the main process piping sothat the
instrumentcan be isolated for
maintenance purposes. Three-valve
isolation/equalization manifolds
should be used on all differential
pressure applications. Provisions
should be provided for blow down
of the capillary tubing in situations
where fouling mayoccur
7. Transmitter range: 4-20 mADC (preferred), 0-20 mADC,
0-5VDC,1-5VDC,0-10VDC,2-10
VDC, or -10-1 0 VDC signal proper-
tional to a specified pressure range.
8. Transmitter type: 2-wire (preferred)
9. Transmitter mounting: Typically, integral to sensor. Capillary
tubesshouldbe routed sothat the
sensorltransmitter assembly iseasy to
access for maintenance and calibration
purposes and the tubes themselves
aresafe from damage. If there isa
local display, it should beat eye level
and easily read.
Outside-Air Humidity • Bulk polymer relative humidity 1. End-to-end accuracy: +/- 5% relative humiditytypical
• Thin-film capacitance relative 2. Resolution: 0.1 % relative humidity
humidity
(eithertype is acceptable for 3. Measurement range: 0.0 to 100.0 % relative humidity
most DCICS applications) 4. Use: In a typical chilled-water production
plant, the outside-air wet-bulb
temperature is needed for efficient
plant operation. There are wet-bulb
temperature sensors available that
monitor wet bulb directly, but are
moreexpensive and require more
frequent calibration then RH sensors.
It is recommended that RH sensors
be used and that the controller that
the humidity instrumentation is
connected to calculates the wet-
bulb temperature from the RH and
dry-bulbtemperatures using industry
standard calculations.
5. Transmitter range: 4-20 mADC (preferred), 0-20 mADC,
0-5VDC,1-5VDC,0-10VDC,2-10
VDC, or -10-10 VDC signal propor-
tional to 0.0 to 100.0 % RH.

Table 8-2. Level 0 best practice specifications. Continued

104
DISTRICt' COOLiNGBEST PRACt'JCE GUIDE
02008lntema~ona/ District fr>ergyAssocialioo All rights ~

Process
Sensor Types Best Practice Specifications
Variable

Outside-Air Humidity 6. Transmitter type: 2-wire(preferred)


(continued) 7. Installation considerations: Install alongwith an outside-air
dry-bulb temperature transmitter.
Most manufacturers make a
combination RHldry-bulb temperature
instrumentjust for thispurpose. Both
sensors should be protected from
directsunlightandthe building's
exhaust. Forlarge installations it is
often advantageous to install multiple
sensorsltransmitters at strategic
locations around the installation and
the controller can determine which
one to use.
Water-Quality • Conductivity 1. End-to-end accuracy: +/- 1% full-scale typical
Conditions • Resistivity 2. Resolution: Conductivity: 0.01 ~S/cm
e pl-l Resistivity: 0.01 mega-ohms per
centimeter (MQ-cm)
pH: 0.01 pH
3. Maximum ranges: Conductivity: 0.00 to 100.00 ~S/cm
Resistivity: 0.00 to 100.00 MQ-cm
pH: 0.00 to 14.00 pH
4. Process connections: These types of probes require
frequent maintenance and calibration.
/J.ssuch, they should be installed in
the linethey are monitoring bythe
use of ball valve assemblies that allow
the probes to be removed from the
process without shutting the process
down. In addition, most pH probes
have the requirement that they are
neverallowed to be "dry." Special
consideration must be paid to this
fact during detailed design.
5. Transmitter range: 4-20 mADC (preferred), 0-20 mADC,
0-5VDC, 1-5 VDC, 0-10 VDC, 2-10
VDC, or -10-10VDC signal proper-
tional to a specified range within the
maximum range of the probe type
beingused.
6. Transmitter type: 4-wire (24VDC power preferred)
7. Transmitter mounting: Typically, remotely fromthe probe.
Pipe, instrument stand, wall and
panel areall acceptable means of
mounting the transmitter. Should be
easy to access for maintenance and
calibration purposes. If a local display
is used, it should beat eye level and
easily read. The cabling from the
transmitter to the probe mustbe of
sufficient length and routed sothat
the probecan be removed from the
process piping(via the ball valve
assembly mentioned above).

Table 8-2. Level 0 best practice specifications.

by more then a predetermined amount.

Redundant instruments have the added advantage of


ease of maintenance and calibration because one
instrument can be temporarily taken out of service
while the plant continues to run using the other
instrument.

105
DISTRICT COOLINGBEST PRACTICE GUIDE
C2008ln!efmltional District Energy Association. Alln'ghtJ; re:;erved.

The obvious disadvantage to Level 0 instrumentation .Pneumatically actuated valves: pneumatic auto/
redundancy is cost. For this reason, careful thought manual loading stations.
should be given during design as to which instruments .Chillers: local onboard chiller control panels with
(if any) should be installed redundantly. A general rule push buttons, pilot lights, selector switches, and/or
of thumb is to install redundant instruments if failure of operator interface terminals.
a particular instrument would cause the entire plant to .Air compressors: local onboard compressor
shut down. If the answer is yes, then redundant instru- control panels with push buttons, pilot lights,
ments should be considered, but are not mandatory. selector switches, and/or operator interface terminals.
Redundant Level 0 instrumentation should be handled
on a case-by-case basis and should only be utilized in 8.7.6 Good installation practices
the most critical situations because it will increase A number of good installation practices were discussed
initial costs and ongoing maintenance costs. in detail in section 8.7.2 for each type of instrument
found in a typical plant.
8.7.4 Local instrumentation
When a particular process variable must be monitored
locally at the processand remotely by the district cooling
instrumentation and control system, one approach is
to install transmitters with local displays, rather than
installing separate local gauges to monitor the same
point. An obvious drawback to this approach is that if
power to a transmitter with a local display is lost, and
In general, a well-designed DCICS will allow Level 0
there is no local gauge, then there would be no way to
field instrumentation to be easily serviced, maintained
monitor the process variable in question, either locally
and calibrated by properly trained personnel while
orfrom the DClCS. Therefore it istypicallybest practiceto
minimally affecting the overall operation of the plant.
use local gauges for critical processvariablesthat must
Extensive use of thermo wells, isolation valves and
be monitored locally even if transmitter power is lost
insertion instrument ball-valve assemblies should be
or if the DClCS is down.
employed so that instrumentation can be removed and
serviced while the plant is running.
If a particular process variable only needs to be moni-
tored locally at the process, then local gauges are the
All instrumentation wires, cables, and tubing should be
obvious choice.
properly labeled following a pre-approved labeling
Regardless of how the local reading is obtained - from
scheme.
a local display on a transmitter or from a standard local
gauge - the reading should be easily obtained without
Local codes for conductor sizes, colors and insulation
should be adhered to.
obstruction or the need for a ladder.

All field instruments should be tagged for easy identi-


8.7.5 Localized overrides for each fication. Tagging should include the instrument's asset
controlled component tag number along with a brief description of the
When a field device is controlled by one of the plant's instrument's purpose.
controllers, it is good practice to provide a means of
operating that device, locally at the device, bypassing Test ports should be specified at all major equipment
the DClCS altogether. This ensuresthe plant can still be for testing pressures and temperatures.
operated in the event of a failure of the DCICS that
would otherwise leave the plant inoperable. Different 8.8 Level 1 - Best Practices
types of controlled devices will require different methods
of local control, as summarized below. The sectionsthat follow present guidelines for specifying
.Constant-speed pumps/fans: hand-off-auto (HOA) and installing Levell equipment.
switches .
• Variable-speed pumps/fans: hand-off-auto (HOA) 8.8.1 Level 1 field instrumentation
switches for start/stop control; local/remote (UR) The following process variables are monitored and
switches for speed control selection; potentiometers controlled by Levell instruments in a typical district
for local speed control. cooling instrumentation and control system:
.Electrically actuated two position (open/closed) .temperature
valves: open-close-remote (OCR) switches. .Iiquid flow
• Electrically actuated modulating control valves: local- .Iiquid pressure
off-remote (LOR) switches for position control mode .outside-air humidity
selection, potentiometers for local position control. .water-quality conditions (conductivity, resistivity, pH)

106
DISTRICT COQUNG BESTPRACTICE GUIDE
Cl2008ll1rema~Onal District Energy Association.
Allrigh~ re~.

These same process variables can also be monitored by doing so reintroduces a single point of failure (the I/O
Level 0 transmitters (see section 8.7). Some criteria to module and/or rack) into the system for the Level 0 devices.
consider when deciding to specify a Level 0 or a Level
1 field instrument are covered in section 8.9.2. 8.8.3 Onboard chiller controllers
Most modern chillers are provided with stand-alone on-
The same best practice considerations that apply to board controllers that monitor and control the essential
Level 0 field instrumentation apply to their Level 1 operation of the chiller. These controllers will typically
counterparts as well (see section 8.7). In addition, the have network connectivity of some sort built inand can
network that connects the Level 1 field instruments to also accept hard-wired control signals.
their respective controllers must also be specified,
designed and installed properly. Section 8.8.8 contains Whether the DClCS will interface to the onboard chiller
some best practices that should be followed when controller(s) over its network or via hard-wiring, or a
specifying, designing and installing Levell networks. combination of both, is dependent on the designer's
confidence in the networking capabilities of the
8.8.2 110 modules and racks onboard chiller controller(s) and the robustness of the
Level 0 equipment connects to its respective network's design and implementation. Network
controller(s) via I/O modules. I/O modules are installed confidence should be based on reliability. throughput
in two locations with respect to their controllers: and security. Not all of the networks that are supported
• Locall/O modules are installed in the same rack by chiller manufacturers aresuitablefor control purposes.
as their controllers and communicate with the
controller over the controller's internal communi- If the designer has little or no confidence in the
cation bus. network's capabilities, then hard-wiring should be used
• Remote I/O modules are installed in an I/O rack for all controlled points, and the network would be
remotely from their controllers and communicate used for monitoring only those points that are non-
with the controller over a high-speed industrial essential to the plant's overall operation. Conversely, if
network. the designer has a high level of confidence in the
Since a loss of a remote I/O network may affect many chiller's networking capabilities, then it is acceptable to
instruments simultaneously, special thought must be put perform both monitoring and control functions over
into the design and deployment of these networks. the network, provided the best practice guidelines in
Refer to section 8.8.8 for items to consider when section 8.8.8 are followed when specifying, designing
specifying, designing and installing any Levell network. and installing the network.

For analog signals, the most important design criterion


to consider is the resolution of the analog to digital
(AID) and the digital to analog (D/A) converters that are

employed in their circuitry. This resolution should be At a minimum, the following points should be accessi-
high enough as to introduce negligible error into the ble from the onboard chiller controller(s) via hard-wiring
end-to-end accuracies of Level 0 devicesto which they and/or over the network:
are connected. Most modern analog I/O modules utilize .chiller start/stop command
at least 12-bit converters, which is usually more than .chiller funning status
adequate for most DCICS applications. As microchip .general alarm status (alternately, individual alarms
technology continues to improve, more and more may be available)
manufacturers are switching to 16-bit converters, .supply-temperature setpoint
which even further improves the end-to-end accuracy .electrical voltage, current and energy
of the entire circuit. A minimum of 12 bits is eevaporator refrigerant temperature
recommended, but 16 bits is preferred when available. .evaporator refrigerant pressure
.evaporator chilled-water proof of flow status
When redundant Level 0 equipment is utilized, thought .condenser refrigerant temperature
must be put into whether or not to utilize redundant .condenser refrigerant pressure
I/O modules and/or racks as well. It may not be .condenser-water proof of flow status
acceptable to wire the redundant Level 0 devices into .compressor discharge refrigerant temperature
the same I/O module or even the same I/O rack, since .guide vane position

107
DISTRICT COOLING BESTPRACTICE GUIDE
C2008lnlema~'onal Dis/n'a Energy As5OdaHOI1. All rightsreevea.

8.8.4 Variable-frequency drives from a typical DClCS VFD via hard-wiring and/or over
Most modern industrial VFDs the network:
.can be equipped with a network option for control .starVstop command
and monitoring purposes, .running status
.can be controlled and monitored via hard-wiring .fault status
or .speed command
.can be used with a combination of both strategies. .speed feedback
.voltage, current, and electrical power data
How the district cooling instrumentation and control .disconnect status
system will interface to the VFDs is dependent on the .bypass/normal status
designer's confidence in the networking capabilities of .local/remote status
the VFDs and the robustness of the network's design .hand-off-auto status
and implementation. Again, network confidence
should be based on reliability, throughput, and 8.8.5 Energy monitoring equipment
security. If the designer has little or no confidence in Both thermal and electrical energy production and/or
the network's capabilities, then hard-wiring should be consumption are monitored in a typical DCICS. Energy
used for all controlled points, and the network would meters are used to monitor this energy data for
be used for monitoring only those points that are accounting or administrative purposes (i.e., for billing,
non-essential to the plant's overall operation. plant efficiency calculations and other purposes).
Conversely, if the designer has a high level of
confidence in the VFDs networking capabilities, then it Table 8-3 outlines the two types of energy meters that
is acceptable to perform both monitoring and control are found in a typical DClCS plant and some best
functions over the network, provided the best practice practice considerations that should be taken into
guidelinesin section 8.8.8 arefollowed when specifying, account when specifying each type of instrument.
designing and installing the network.
8.8.6 Metering and submetering
At a minimum, the following points should be accessible The decision to meter entire buildings or submeter the
individual building tenants is application specific and
should be handled on a case-by-casebasis.

Regardless of whether metering and/or submetering is


utilized, it is usually carried out by ETS controller(s) and
energy meters that are installed in the customer's build-
ings but are owned, operated and maintained by the

Process
Sensor Types Best Practice Specifications
Variable

Thermal Energy Temperature: RTDs, thermistors, 1. End-to-end accuracy: +/- 5% full-scale typical
sensor/transmitter assemblies 2. Resolution: Consumed/produced energy:
(RIOs preferred)
1ton-hour
Instantaneous energy: 0.1 ton
Liquid Flow: alltypes listed as
Flow: 0.063 Vs (1 gpm)
acceptable in section 8.7.2. Temperature: 0.056 C (0.1 F)
Online magnetic meter preferred)
3. Process connections: Two temperature sensors or
sensorltransmitter assemblies, one
for supply andthe otherfor return.
See the process variable temperature
section 8.7.2 for process connection
details.
One flow sensorltransmitter. See the
process variable-liquid flow section
8.7.2 for process connection details.
4. Transmitter connectivity It isrecommended that energy meters
to DClC5: used in a typical DClCS connect to
the plant controllers via a high-speed
industrial network, not hard-wiring,
making them Levell devices. This is
dueto the large amountof data
that is available from most modern
energy meters.
Table 8-3. Energy meter best practice specifications. Continued

108
DISTRICT COOLING BEST PRACTICE GUIDE
02008 Intema~bna! Dls/Tiet Energy A55ooil~On_ Ai! ngh!5reSlYVed.

Process
Sensor Types Best Practice Specifications
Variable
Thermal Energy 5. Local displays: Every energy meterinstalled in a
(continued) DClCS application should have a
local display that allows the provider's
personnel to take readings, locally at
.the meter, in the eventthe link to the
controller issevered for any reason.
6. Transmitter mounting: Pipe, instrument stand, wall or panel
are all acceptable means of mounting
the transmitter. There should be easy
access for maintenance and calibration
purposes. Thelocal display should be
at eye level and easily read.
7. Monitoring for billing If an energy meteris being used for
purposes: billing purposes, it should be capable
of calculating andstoring metering
data internally, independent of the
controller it isconnected to, sothat
if the link to the controller is lostfor
any reason, the metering datawill
not be lost. This isgood practice even
in non-revenue type meters.
Electrical Energy Current and voltage transformers 1. End-to-end accuracy: +/- 5% full-scale typical
2. Resolution: Energy: 1.0 kWh
Real power:0.1 kW
Reactive power:0.1 kVAR
VA:0.1 VA
Power factor: 0.1
Voltage: 0.1 volts
Current 0.1 amps
3. Process connections: One currenttransformer(Cf)
per phase.
One voltage transformer (Fl) per
phase.
Should be installed in a motor control
center (MCC).
4. Transmitter connectivity It isrecommended that energy meters
to DCICS: used in a typical DClCS connectto
the plantcontrollers via a high-speed
industrial network, not hard-wiring,
making them Level 1 devices. This is
dueto the large amount of datathat
are available from most modernen-
ergy meters. There areother types of
energy meters that provide an analog
output (i.e., 420 mADC) that is pro-
portional to the instantaneous electrical
power (kW)being measured or a pulse
output that indicates the amount of
electrical energy (kWh) that has been
consumed/produced since the last
pulse. These types of meters are not
recommended in a typical DClCS
application.
5. Local displays: Every energy meterinstalled in a
DClCS application should have a
local display that allowsthe provider's
personnel to take readings, locally at
the meter, in the eventthe link to the
controller is severed for any reason.
6. Transmitter mounting: Typically; electrical energy meters
are installed through a door in the
switchgear lineup for the circuits they
are monitoring. There shouldbe easy

Table 8-3. Energy meter best practice specifications. Continued

109
------- - - - ----------------------_._---_.

DISTRICT COOLING BEST PRACTICE GUIDE


02008 /n!ematiomlDisoo EnetgyAAociaUon. Ail rightsre>erVf!d.

Process
Sensor Types Best Practice Specifications
Variable
Electrical Energy accessfor maintenance and calibra-
(continued) tion purposes. The local display should
be at eyelevel and easily read.
7. Monitoring for billing If an energy meteris being usedfor
purposes: billing purposes it should be capable
of calculating and storing metering
data internally, independent of the
controller it is connected to, so that
if the link to the controller islostfor
anyreason, the metering datawill
not be lost.
Table 8-3. Energy meter best practice specifications.

district cooling provider. A well-designed and imple- and control of the plants occurs over these networks.
mented ETS will allow for submetering of individual For this reason, the proper specification, design and
customers as well as for metering of entire buildings. installation of Level 1 networks is critical.

Someprovidersmay elect to utilize Level 5 real-time ther- A well-designed Level 1 network will not allow for a
mal modeling and simulation (RTIMS) systems that are single point of failure, where the failure of a single
capable of performing "virtual metering" as a backup to device on the network causes all of the devices on the
their normal mode of physical metering. These applica- network to lose communication with their controller(s).
tions are beyond the scope of this chapter, but should be This includes, but is not limited to, network interface
considered during the design of any large-scale district devices, bridges, routers and hubs.
cooling instrumentation and control system.
Level 1 network cable routing also must be considered.
The network cable should be routed in such a way that
a break in any segment of the network should
minimally compromise the controller's ability to
communicate to the rest of the equipment on the
network. In some situations this may mean installing
redundant cabling and network infrastructure devices.
When redundant cabling is used, the two redundant
8.8.7 Redundant Level 1 field
networks should be physically routed in different paths
instrumentation
to decrease the likelihood of the same event taking out
When a certain process variable is critical to the plant's
both networks. Redundant network cables should
overall operation, and that process variable is
never be run in the same conduit or along side of each
monitored by a Level 1 field instrument, redundant
other in separate conduits over long distances.
Level 1 instrumentation may be required. The controller
that the instrumentation is connected to would deter-
mine which instrument to use and should alarm if the 8,8.9 Level 1 data considerations
values being read from the transmitters differ from each During the detailed design phase of a DClCS, it is
other by more than a pre-determined amount. important to consult the manufacturer of any planned
Level 1 equipment to ensure that all of the data
Redundant instruments have the added advantage of required by the application will be available over the
ease of maintenance and calibration because one in- high-speed industrial network that will connect it to the
strument can be temporarily taken out of service while associated controller. The data format accuracy when
the plant continues to run using the other instrument. read over the network and its refresh rate over the
network are also important requirements to consider
The obvious disadvantage to Level 1 field instrumentation and should be specified on a case-by-case basis.
redundancy is cost. For this reason careful thought is
required during design regarding which instruments (if 8.9 Levels 0 & 1 - Choosing Points
any) should be installed redundantly. to Monitor and Control
8,8,8 Level 1 network best practice This section presents some illustrations that depict what
considerations points should be monitored and controlled for different
Level 1 networks are, in some respects, the most critical equipment segments that can be found in the various
networks in a DClCS because the low-level monitoring types of plants owned and operated by a typical provider.

110
DISTRICT COOUNGBEST PRACTICE GUIDE
02008 Intemarional Districtfne<gy Aswdation.Ail right'ire:.erved.

The examples that follow illustrate both Level 0 and infrastructure available in the district cooling
Levell instrumentation implemented together. Table provider's district, this may be miles away from the
8-4 provides a key to the instrument tagging symbols plant at an energy transfer station that the plant
used and explains how Level 0 and Levell devices are supplies (see section 8.9.1/Heat exchangers) or it
depicted in the examples. Table 8-5 describes how to may be in the plant itself.
interpret the function identifiers that are shown in the .Control the speed of the running secondarypumps
examples. A discussion is provided after the examples based on this differential pressure.
regarding the criteria that should considered when .Stage the secondary pumps based on this
deciding to whether to specify Level 0 or Levell field differential pressure (customer demand).
instrumentation or a combination of both. .Monitor the supply flow (FIT-1001) and tempera-
ture (TIT-l 001), the return temperature (TIT-2001)
and the chilled-water energy (JIT-1001) being
delivered to all of the customers on the loop. Note
that individual customers are typically
metered at the energy transfer stations, not at
the chiller plants. Submetering of individual users
at each customer site isalso an alternative that may
be considered and should be accounted for in the
design and implementation of the DCICS.
8.9.1 Example equipment segments .Stage primary pumps based on chiller status.
• Stage chillers based on chiller load (IIT-1380, see
Primary-secondary systems section 8.9.1/Chiller evaporators), supply tempera-
ture (TIT-l001), supply flow (FIT-l001), andlor
Figure8-4 illustrates the recommended instrumentation direction of chilled-water flow (deficit vs. supply) in
for a primary-secondary system. Forclarity, the following the decoupling line (FIT-3000).
discussion refersto the tag names depicted in the figure. .Monitorthe temperature being supplied from all of
the chillers (TIT-lOOO).
At a minimum, the instrumentation should be in place • Monitor the temperature being returned to all of
to perform the following functions: the chillers (TIT-2000).
• Monitor the differential pressure across the customer .Monitor the temperature (TIT-3000) and bi-direc-
load at the furthest possible hydraulic point(s) from tional flow (FIT-3000) in the decoupling line.
the secondary pumps (PDIT-l 000). Depending on the
physical "tayout and the communication The purpose of the bi-directional flow meter in the

Instrument that is installed in the field,infree space.


@"YYlZ"
Instrument that is install inthe fieldin a utilitypanel,and is accessiblefrom the front of the
@"YYlZ"
panel.

Instrument that is installed inthe fieldin a utility panel,and is NOT accessiblefrom the front of
@"YYlZ"
the panel.

~"
Instrument that is installed in the fieldin a control panelthat is accessiblefrom the front of the
control panel.
YYlZ"

~"
Instrument that is installed in the fieldin a control panel that is NOT accessible from the front of
the control panel.
YYlZ"
DCICS hardwired Input,output, or function that is accessibleby the user via the Level 2 and/or
~"YYlZ"
Level 3 user interfaces. When connected to a field deviceit indicates that the field device Isa
level0 device.

~"
DCICS hardwired input, output.or function that is NOT accessible by the user. When connected to
a field device it indicates that the fielddevice is a level0 device.
YYlZ"
DClCS input.output or function,acquired through a communicationlink,that is accessible by the
@"YYlZ"
user via the tevel z and/or Level 3 user interfaces. Whenconnected to a field device it
indicates that the field device is a level1 device.
DCICS input, output or function,acquired by a communicationlink,that is NOT accessible by the
@"YYlZ"
user. When connected to a fielddevice it indicates that the fielddevice is a level1 device.

XXX)( = Function Identifier (see Table 8-5) ZZ = Equipment number


YY = P&IO number (or system identifier) 01 and 02 = Textfields used to further explain the purpose of the point.
Table 8-4. Key to instrument tagging symbols.

111
DISTRlcr COOUNG BEST PRAcrlCE GUIDE
02008 InlM1a~onal Dis!fietEnergy ksoa'ation. All right'.irroservro.

FIRST-LETTER (4) SUCCEEDING-LEITER (3}

MEASURED OR READOlTTOR
INITIATING PASSIVE
VARIABLE MODIFIER FUNcnON DUTPlTTFUNcnON MODIFIER
Analysis Alarm
A
Burner.Combustion User'sChoice Button Blue
B
Conductivity Control Closed
C
Density(Mass) Or Differential
D SpeclficGravitv SpecificGravity
Voltage Sensor(Primary
E Element)
Flow Rate Ratio(Fraction} Forward
F
User'sCholce Gauge-Local G~"
G Vlewlna Device
Hand High
H
Current{Electrical) Indicate
I
J Power sa"
Time.TImeSchedule TImeRateOf Change Control Station
K
Level Ught low
L
Moisture Or Humidity Middle.lntermedlate
M
User'sChoke
N
User'sChoke Ofdke. Restricflon Open
0
Pressure Point.(Test)
p COnnection
Quantity Integrate.Totalize
Q
Radiation Regulating Record Red.Reverse. Remote
R
Speed.Frequency Safety Switch
5
Temperature TransmIt
T
multivarlable Multifunction Multifunction Multifunction
U
Vibration.Viscosity Valve louver
V Damper"
Welght.Force well WhIte
W
Run.Energize X Axis
X """ate Actuate
VAxis Relay.Compute Yellow
y Status.Evenr.State
Of Presence Of Presence Convert
Position.Dimension ZAxis Driver.Actuator
Z Undassifietl Final
Control Element

Table 8-5. Function identifier key.

decoupling line (FIT-3000) is to detect surplus or deficit supply flow transmitter (FIT-lOO1) at the plant. An
flow conditions. Decoupling line flow in the supply to alternative involves eliminating the customer-supply
return direction indicates a surplus flow condition. flow transmitter and adding up all of individual chiller
Decoupling line flow in the return to supply direction flows (FIT 1370, see section 8.9.1/Chiller evaporators)
indicates a deficit flow condition. This same information and using the resultant sum as an indication of total
can be obtained by trained personnel in other ways, flow to the plant's customers. Also, it is important to
thus eliminating the need for the decoupling line flow provide ways to determine how much flow is presentin
meter (FIT-3000). Some alternate methods include the decoupling lineand the directionin which it isflowing .
• observing the chiller supply (TIT-l000), return This means that if the customer-supply flow transmitter
(TIT-2000) and decoupling line (TIT-3000) tempera- (FIT-lOO1) is eliminated, then the decoupling line flow
tures and meter (FIT-3000) must usuallybe provided(the decoupling
.adding up all of the individual chiller flows (FIT-1370, line is usually smaller than the supply line).
see section 8.9.1/Chiller evaporators) and comparing
the result to the flow to be delivered to the If the customer-supply flow transmitter (FIT 1001) is
customers (FIT-l001). eliminated, and the provider still wishes to have an
independent customer-supply energy meter at the plant
Due to the large size of the supply line in a typical (JIT-l00l), then the plant controller must provide the
district energy primary-secondary system, it may not customer-supply energy meter (JIT-1 00 1) with a flow
always be feasible to install an independent customer- value proportional to the value that it calculates from

112
DISTRICT COOUNG BEST PRACTICE GUIDE
e2OO8Infemilbonill Di,l!id Energy A>,oo'aUon. All right> re~

!V-10Cl1 I

CHILLER
BANK ,orr
,~

IV-UN12 I
o

Figure 8-4. Primary-secondary system.

the individual chiller flows and the flow in the decou- At a minimum, the instrumentation should be in place
piing line. to perform the following functions:
• Monitor the differential pressure across the customer
In addition to eliminating the independent customer- load at the furthest possible hydraulic point(s) from
supply flow transmitter (FIT-1Q01), the independent the distribution pumps (PDIT-l 000). Depending on the
customer-supply energy meter (JIT-l00 1) can also be physical layout and the communication infrastruc-
eliminated. If it is eliminated, then the individual chiller ture available in the cooling provider's district, this
energy meters (JIT 1370, see section 8.9.1/Chiller may be miles away from the plant at an energy
evaporators) would be used to determine the total transfer station that the plant supplies (see section
chilled-water energy that the plant is delivering to its 8.9.1/Heatexchangers) or it may be in the plant itself.
customers. Also, any flow present in the decoupling oControl the speed of the distribution pumps to
line would need to be accounted for and figured into maintain a minimum customer differential pressure
the overall plant efficiency calculations. (PDIT-l000).
oStage the distribution pumps based on customer
demand (PDIT-l 000).
oStage chillers based on chiller load (IIT-1380, see
section 8.9.1/Chillerevaporators), supplytemperature
(TIT-l000) and/or supply flow (FIT-l 000).
o Monitor the differential pressure acrossthe chiller
bank (PDIT-3000).
oAutomatically modulate the bypass control valve
Variable primary systems (CV/PY-3000), based on the chiller bank differential
pressure (PDIT-3000) to maintain a minimum flow
Figure 8-5 illustrates the recommended instrumenta- through the chillers. Normally this valve should be
tion for a variable-primary system. For clarity, the fol- closed and should only modulate open under very
lowing discussion refers to the tag names depicted in low customer demand conditions.
the figure. oAllow operators to manually control the bypass

113
DISTRICT COOUNG BEST PRACTICE GUIDE
02008In~aliooal District Energy Assodali'oo. Allrightsreserved.

control valve locally at the valve, bypassing the plant's customers. However, this scheme only works if
DClCS altogether (HS-3000). the bypass control valve (CV 3000) remains closed. If
.Monitor the remote status of the bypass control the bypass valve does open, a way of determining how
valve's local-off-remote (LOR) switch (HS-3000). much flow is present in the bypass line must be
• Monitor the position of the bypass control valve (ZT- provided. This may involve installing a flow meter in the
3000) . bypass line (the bypass line size is typically much smaller
• Monitor the supply flow (FIT-WOO) and temperature than the supply line size)or using a delta Ptype of valve
(TIT-WOO), the return temperature (TIT-2000) and in the bypass line and calculating bypass flow based on
the chilled-water energy (JIT-1 000) being delivered the valve's position.
to all of the customers from the plant. Note that in-
dividual customers are typically metered at the en- Regardless of how it is calculated, if the customer-
ergy transfer stations, not at the chiller plants. supply flow transmitter (FIT 1000) is eliminated, and the
Submetering of individual users at each customer provider still wishes to have an independent customer-
site is also an alternative that may be considered. supply energy meter at the plant (JIT-1 000), then the
plant controller must provide the customer-supply
Instead of using the differential pressure across the energy meter (JIT-1 000) with a flow value proportional
chiller bank to control the bypass valve, the individual to the value that it calculates.
chiller flows may be used (FIT-1370, see section
8.9.1/Chiller evaporators), thus eliminating the need for In addition to eliminating the independent customer-
the chiller bank differential pressure transmitter supply flow transmitter (FIT-WOO), the independent
(PDIT-3000). customer-supply energy meter (JIT-1 000) can also be
eliminated. If it is eliminated, then the individual chiller
Due to the large size of the supply line in a typical energy meters would be used to determine the total
district energy variable primary system, it may not chilled-water energy that the plant is delivering to its
always be feasible to install an independent customer- customers. Note that any flow present in the bypass
supply flow transmitter (FIT-WOO) at the plant. An line would need to be accounted for and figured into
alternative involves eliminating the customer-supply the overall plant efficiency calculations.
flow transmitter and adding up all individual chiller
flows (FIT 3001 through FIT-3003) and using the
resultant sum as an indication of total flow to the

1,,"1001 i
------., 0

CHILLER
BANK

I~=I

Figure 8·5. Variable primary system instrumentation.

114
Dlsmlcr COOLING BEST PRAOICE GUIDE
102008 International Distn'ct EnergyA5soclab"on. Ail rightsreserved.

Chiller evaporators • electrical voltage (EIT-1380)


• electrical current (IIT-1380)
Figure 8-6 illustrates the recommended instrumenta- .electrical energy being consumed by the chiller
tion for the supply and return piping to a single chiller (JIT-1380)
evaporator. For clarity, the following discussion refersto • evaporator refrigerant temperature (TIT-1380)
the tag names depicted in the figure. • evaporator refrigerant pressure (PIT-1380)
• evaporator chilled-water flow switch status
At a minimum, instrumentation should be in place to (FSL-1380)
perform the following functions: • Guide vane position
oAutomatically isolate the evaporator's supply from .Use the same communication link to remotely
the chilled-water supply piping with a modulating start/stop the chiller (XS-1380) and to reset its sup-
control valve (CV-1370). ply-temperature setpoint (TC-1380).
o Monitor the actual position of the evaporator oLocally monitor the chilled-water supply (PI-1323)
supply isolation valve (2T-1370). and return (PI-1320) pressures as close to the evap-
oAliow operators to manually control the evaporator orator as possible.
supply isolation valve via a local-off-remote (LOR)
switched located locally at the valve, bypassing the A modulating evaporatorsupplyvalveisnot a requirement
DClCS altogether (HS-1370). . since these valves are typically set to either full-closed
oMonitor the remote status of the evaporator when the chiller is not in use or some other position
supply isolation valve's LOR switch (HS-1370). (usually full-open) when the chiller is in use. Rarely are
o Manually isolate the evaporator's return from the these valves actually modulated. Therefore, in this
chilled-water return piping with a hand-operated example, the modulating evaporator supply valvecould
valve (V-1371). Note that some providers may elect be replaced with a simple isolation (full-open/close)type
to automate this valve as well as the supply valve. of valve. Another alternative would be to not automate
However, there would be no reason to make this a these valves at all and require the provider's personnel
modulating type of valve if it was automated. A to manually open these valves prior to starting the
simple isolation valve would suffice. chiller. However, the modulating valve does provide
oMonitor the flow (FIT-1370) and temperature some degree of flexibility in the system's operation,
(TIT-1370) of chilled water leaving the evaporator, especially in variable primary systems.
the temperature (TIT-1371) of the chilled water en-
tering the evaporator and the chilled-water The discussion above is based on the assumption that
energy.(JIT-1370) being produced by the evaporator. the local plant controller communicates to the onboard
oCommunicate with the chiller's on board controller to chiller controllers via a high-speed industrial network
obtain the following minimum information: for both control and monitoring purposes. It is still
• running status (XI-1380) common practice in the industry to hard-wire control
• general trouble status (XA-1380) signals and to use the high-speed industrial network

nr
,m """""'
nr
"n
m
_.-
•~~""'

"n
n
m, -•

OiUllDWATaI
~~

( I
I '"
Y.l»l
CHWR

Figure 8-6. Chiller evaporator supply and return instrumentation.

115
DISTRICT COOLING BEST PRACTICE GUIDE
C2008lntemaliooal Dlnn'ct Energy As5OCia~on. Allrightsresevea:

for monitoring purposes only. However, with the .Stage the condenser-water pumps on and off based
increased reliability available in modern high-speed on the number of chillers running or the current flow
industrial networks, either approach (hard-wired or requirements of the condenser-water loop.
networked) is acceptable provided the network is .Maintain the cooling tower basin Level (L1T-9010,
robust and fail-safe. see section 8.9.1/Cooling towers) by controlling the
makeup flow to the towers (AV-8020).
If a provider requires that the evaporator supply and • Monitor the full-open/full-close status of the
return pressures be monitored remotely as well as condenser-water makeup isolation valve (lSO-
locally, indicating transmitters can be used and the local 8020lZSC -8020).
pressure gauges (PI-1320, PI-1323) can be removed. .Allow operators to manually control the condenser-
water makeup isolation valve locally at the valve,
Condenser-water systems bypassing the DCICS altogether (HS-8020).
.Monitor the remote position of the condenser-
Figure 8-7 illustrates the recommended instrumentation water makeup isolation valve's open-close-remote
for a condenser-water system. For clarity, the following (OCR)switch (HS-8020).
discussion refersto the tag names depicted in the figure. .Communicate with the chemical treatment system's
onboard controller to obtain the following minimum
At a minimum, instrumentation should be in place to information:
perform the following functions: • condenser water conductivity (AIT-8030)
.Monitor the condenser-water supply (TIT-801 0) and • condenser water pH (AIT-8031)
return temperatures (TIT 8011). • general alarm status (XA-8030)
• Control the cooling tower fans and valves to main- .Use the same communication link to command the
tain the condenser-water supply temperature (TIT- chemical treatment system to manually open/close
8010) to setpoint, the blowdown valve (AV-8030).Normallythe chemcal
.Stage the cooling towers to meet the demands of treatment system's onboard controller will automa-
controlling condenser-water supply temperature ically control this valve based on condenser-water
(TIT-801 0) to setpoin!. conductivity (AIT-8030).
• Monitor the outside-air temperature (TIT-8000) and .Monitor the condenser-watermakeup flow (FIT-8020)
relative humidity (MIT-8000). Calculate the outside- and the blow down flow (FIT 8030). Totalize these
air wet bulb (MIY-8000) from these values. values to calculate the total amount of water

CooUNG
TOWER
SANK

CONDENSER
WATER
MAKEUP

CHEMICAL
CHEMICAL INJECTION
mEATMENT
SYSTEM
CONDENSER
WATER PUMPS
(CONSTANT SPEED)

• CHIUERBANK

MANLBLOWDOWN
(CONDENSERS)
H~
00
,,,,,"''''''' SLOWDOWN
TODRAIN

Figure 8-7. Condenser-water system instrumentation.

116
DISTRICT COOUNG BESTPRACTICE GUIDE
e2008lntema~bna//)j<;rTlct £n~ AWJoEJtIiln. AIIn'ghtsre5efVed.

delivered to the plant (FIO-8020) and the total designed DClCS will allow the provider to take advantage
amount of water sewered by the plant (FlO 8030). of these credits when they are available. To calculate
the amount of water evaporated from the cooling towers,
The proper selection of the condenser-water supply- the blowdown flow total (FlO8030) is subtracted from
temperature setpoint is the key to saving energy in the the makeup flow total (FlO 8020).
condenser-water loop. A setpoint that is too low will
require more energy to maintain the setpoint while Another way to decrease the operating cost of a
providing little or no impact to chiller efficiency. chilled-water production plant is to research alternate
Conversely, a setpoint that is set too high will result in sources of makeup water. Depending on the location of
inefficiencies in the chiller's operation and may even the plant this may be in the form of well water and/or
cause it to trip off. The selpoint should be set to a value condensate captured from other equipment.
that is within the recommended range specified by the
chiller manufacturer. Strategic selection and location of the chiller plant
equipment (i.e., cooling towers, chillers) instrumentation
Using the calculated outside-air wet bulb (MIY-8000) and valves will allow providers in certain temperate
to reset the condenser-water supply temperature within climates to utilize free cooling during the colder months
an acceptable range will also provide potential energy of the year.
savings if implemented properly. A well-designed and
implemented district cooling instrumentation and A well-designed and implemented DCICS will be able
control system will support condenser-water supply- to support one or more of the following methods of
temperature reset. free cooling:
• refrigerant migration
Some water authorities offercredit allowances to their .strainercycle
customers for waterthat is delivered to their customer's oplate-and-frame heat exchanger
plants but is not sewered. In the case of a chilled-water
production plant, this volume of water represents the Cooling towers
water that is evaporated from the cooling towers. To
qualify for the credit allowance some form of water Figure 8-8 illustrates the recommended instrumentation
usage documentation is usually required. A well- for a typical cooling tower. For clarity, the following

~= NOIIIMI.mT.

>

" -=~

-
~

"
"
~m

-=-

cws

Figure 8-8. Cooling tower instrumentation.

117
DISTRICT COOLING BEST PRACTICE GUIDE
e2008lnrem~~'0fl~1 District EnergyAssociation. Allrightsreser.W.

COfIVENSERWATBl

< CWR
"",," I

CONDENSERWAmI
SUPPLY
CW' ) 1/
I v-mil


Figure 8·9. Chiller condenser supply and return instrumentation.

discussion refersto the tag namesdepicted in the figure. LAL-9010). Stop the fan if a high-vibration or a low
oil-level situation exists.
At a minimum, the instrumentation should be in place • Monitor the temperature of the condenser water in
to perform the following functions: the cooling tower's basin (TIT 9012) and turn the
.Automatically modulate the cooling tower's supply basin heater (XS-9012) off and on to maintain that
valve (FY-901 0) and bypass valve (FY-9011) to main- temperature to setpoint.
tain condenser-water supply temperature to .Allow operators to manually turn the basin heater
setpoint. off and on locally at the basin, bypassing the DClCS
• Monitor the actual positions of the cooling tower's altogether (HS-9012).
supply valve (ZT-901 0) and bypass valve (2T-9011). • Monitor the auto status of the basin heater's hand-
• Allow operators to manually control the cooling off-auto (HOA) switch (HS 9012) .
tower's supply and bypass valves, locally at the .Monitor and maintain the level of the condenser
valves, bypassing the DCICS altogether (HS-9010 water in the cooling tower's basin (L1T-9010) to
and HS 9011, respectively). setpoint by opening and closing the condenser-
.Monitor the remote status of the cooling tower's water makeup valve (AV-8020, see section
supply and bypass valves' local-off-remote (LOR) 8.9.1/Condenser-water systems).
switches (HS-9010 and HS-9011, respectively).
• Stage the cooling tower fan as needed to maintain An alternative to monitoring the electrical energy being
the condenser-water supplytemperature to setpoint. consumed by a plant's individual motors is to monitor
.Communlcate with the cooling tower fan's VFD to the electrical energy at one or two locations, in the
facilitate the following minimum functionality: switchgear that feeds all of the motors, thus eliminating
.Automatically start/stop the fan from the DCICS the energy meters at each motor.
(XS-9010).
• Monitor the fan's running status (XI-9010). It may be acceptable to some providers to install
• Monitor the fan's VFD fault status (XA-901 0). low-temperature and high/low-level switches instead
• Automatically modulate the fan's speed from the of transmitters in the cooling tower basins.
DClCS (SC-9010) to maintain condenser-water
supply temperature to setpoint. Centrifugal chiller condensers
• Monitor the actual fan speed (SIT-901 0).
• Monitor the electrical voltage (EIT-9010), current Figure 8-9 illustrates the recommended instrumentation
(IIT-9010), and power (JIT-901 0) being consumed for the supply and return piping to a single centrifugal
by the fan . chiller condenser. For clarity, the following discussion
• Monitor fan vibration sensor and oil level (VAH-9010, refers to the tag names depicted in the figure.

118
DISTRICT COOliNG BEST PRACfICE GUIDE
02008 Inlema(ionalDistJict Energy Associa(ion. Ail ngilts reserved.

At a minimum, the instrumentation should be in place mentation for a constant speed pump. For clarity, the
to perform the following functions: following discussion refers to the tag names depicted in
• Automatically isolate the condenser's return from the figure .
the condenser-water return piping with a modulating
control valve (CV-3140). At a minimum, the instrumentation should be in place
• Monitor the actual position of the condenser-water to perform the following functions:
return control valve (2T 3140). .Automatically isolate the pump's supply with an iso-
.Allow operators to manually control the condenser- lation valve (AVIXS-1380).
water return control valve locally at the valve, • Monitor the full-openlfull-c1ose status of the pump's
bypassing the DClCS altogether (HS-3140). supply isolation valve (250 1380IZSC-1380).
• Monitor the remote status of the condenser-water .Allow operators to manually control the pump's iso-
return control valve's local-off-remote (LOR) switch lation valve locally at the pump, bypassing the
(HS-3140). DClCS altogether (HS-1380).
• Monitor the presence of flow through the condenser .Monitor the remote status of the pump's open-
(FSL-3180). close-remote (OCR) switch (HS 1380).
• Monitor the condenser head (refrigerant) pressure .Manually isolate the pump's discharge with an iso-
(PIT-3180). lation valve 01-1389). Note that some providers may
.Control the condenser head pressure (PIT-3180) elect to automate this valve as well.
to setpoint by modulating the condenser-water .Automatically start/stop the pump from the DClCS
return control valve (CV 3140) when the chiller is (XS-1341).
funning. • Monitor the voltage (EIT-1341). current (IIT-1341)
• Monitor the condenser refrigerant temperature and power (JIT-1341) being consumed by the pump .
(TI1-3180). .Allow operators to manually start/stop the pump
• Monitor the flow (FIT-3140) and temperature locally, bypassing the DCICS altogether (HS-1341) .
(TIT-3140) of condenser water leaving the condenser .Monitor the auto status of the pump's hand-
and the temperature (TIT-3130) of the condenser off-auto (HOA) switch (HS-1341).
water entering the condenser. • Monitor the status of the pump's local disconnect
.Local~monitor the condenser-water supply (PI-3181) switch (HS-1342).
and return (PI-3180) pressures as close to the .Monitor the differential pressure across the pump
condenser as possible. (PDIT-1341 ).
• Locally monitor the pump's supply (PI-1341) and
If a provider requires that the condenser supply and discharge (PI-1342) pressures as close to the pump
return pressures be monitored remotely as well as as possible.
locally, indicating transmitters can be used and the local
pressure gauges (PI-3180, PI-3181) can be removed. If a provider requires that the pump supply and
discharge pressures be monitored remotely as well as
Constant-speed pumps locally, indicating transmitters can be used and the local
pressure gauges (PI-1341, PI-1342) can be removed. In
Figure 8-10 below illustrates the recommended instru- this scenario, the differential pressure transmitter

< DISCH H,f-I/1--,----1


~ Iv.UlII i ,------1

Figure 8-10. Constant-speed pump instrumentation.

119
DISTRICT COOUNGBEST PRACTICE GUIDE
C2008lntetmltiooal Diwkt EnergyAssociation. Allright:; rf05erwd.

(PDIT-1341) could also be removed and the DClCS • Manually isolate the pump's discharge (V-3021).
could calculate the differential pressure from PI-1341 Note that some providers may elect to automate
and PI-1342. this valve as well.
.Communicate with the pump's VFD to facilitate the
Variable-speed pumps following minimum functionality:
.Automatically start/stop the pump from the DCICS
Figure 8-11 illustrates the recommended instrumentation (XS-3020).
for a single variable speed pump. For clarity, the • Monitor the pump's running status (XI-3020).
following discussion refers to the tag names depicted in • Monitor the VFD's fault status (XA-3020).
the figure. .Automatically control the pump's
speed from the DClCS (SC -3020) .
At a minimum, the instrumentation should be in place • Monitor the actual pump's speed (SIT-3020).
to perform the following functions: • Monitorthe electrical voltage (EIT-3020), current
.Automatically isolate the pump's supply with an iso- (1IT-3020), and power (1IT-3020) being consumed
lation valve (AV/XS-3020). Note that depending on by the pump.
where the pump is installed, the automated isola- .Allow operators to start/stop the pump locally,
tion valve may actually be on the pump's bypassing the DClCS altogether (HS-3020AlB).
discharge; however, the following discussions .Monitor the auto status of the pump's hand-off-
assume an automated supply isolation valve and auto switch (HS-3020A).
a manual discharge isolation valve. .Allow operators to control the speed of the pump
• Monitor the full-open/full-dose status of the pump's locally, bypassing the DClCS altogether (HS-
supply isolation valve (ZS 3020/ZSC-3020). 3020CID).
.Allow operators to manually control the pump's • Monitor the remote status of the pump's local-
supply isolation valve locally at the valve, bypassing remote speed control switch (HS3020C) .
the DCICS altogether (HS-3020). • Monitor the normal status of the VFD's bypass/nor-
• Monitor the remote status of the pump's supply mal switch (HS-3020E).
isolation valve's open-close-remote (OC R) switch .Monitor the status of the pump's local disconnect
(HS-3020). switch (HS-3020F).

D1SCONNECTSTAT. HS VFD
HS
0'" DI 3020F
<OCA1.OISC. HS VFD
3020E BYPASSINORMAl.

REM.SPO.Crt.

AD
r-_~~~~====,-_-+.~~REMOTEsrAT.
01

ISUPPLY

I~,.. I~
I

Ci j
'-302

3020
I

~r Porr

3020
D1Ff.PRES.

AI

Figure 8~ 11. variable-speed pump instrumentation.

120
DISTRIO COOUNGBEST PRACTICE GUIDE
Cl2008 Intf!mil~Onill DistJictEnergyAssooaboo. All rights mserved.

This example uses a communication link to the VFD, heat exchanger'scustomer-side supply temperature
not hard-wiring, making it a Levell device. Because of to setpoint.
the wealth of information that is available from industry .Monitor the actual position of the heat exchanger's
standard VFDs, this is usually the more cost-effective provider-side return valve (2T-3000).
approach. The slight increase in cost of a 'network .Allow operators to manually control the heat
ready' VFD is more than offset by the installation cost exchanger's provider-side return valve, locally at the
of hard-wiring all of these signals. Some providers may valve, bypassing the DClCS altogether (HS-3000).
elect to implement a hybrid approach, where all of the • Monitor the remote status of the heat exchanger's
control signals (start/stop, speed control) are hard- provider-side return valve's local-off-remote (LOR)
wired, but a communication link is used to gather all of switch (HS-3000).
the other information. Still other providers may only .Monitor the provider-side supply flow (FIT-l00D)
hard-wire the control signals and not collect the other and temperature (TIT-1000), the return temperature
data at all. (TIT-3000) and the chilled-water energy (JIT-l 000)
being delivered to the heat exchanger by the
Heat exchangers provider.
• Monitor the heat exchanger's customer-side return
Figure 8-12 illustrates the recommended instrumentation temperature (TIT-4000).
for a single heat exchanger utilized in a typical energy .Monitor the approach temperature of the heat
transfer station (ETS) application. For clarity, the exchanger to trend heat exchanger performance.
following discussion refers to the tag names depicted in .Locally monitor the pressures at each of the heat
the figure. exchanger's ports (PI-1000, PI 2000, PI-3000 and
PI-4000).
At a minimum, the instrumentation should be in place • Monitor the differential pressure across the
to perform the following functions: provider's side of the heat exchanger (PDIT-l000).
.Monitor the heat exchanger's customer-side Ensure that this signal is communicated back to the
supply temperature (TIT-2000). controller in the plant(s) that supplies chilled water
.Automatically modulate the heat exchanger's to this heat exchanger. The speeds of the distribu-
provider-side return valve (FY3000) to maintain the tion pumps in the plantsshould becontrolled to main-

0'0 """" 1...... '!l<J» I


o
n
,~

HEAT
EXCHANGER
1== I
~
,~

o
!..mlJU» I

-,
m

CHWS

Figure 8-12. Heat exchanger instrumentation.

121
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lmeman'onal Districtfn!!lfJY Aswciab'on. All ri9h~ reservro.

tain this differential pressure to setpoint (seesections are connected to).


8.9.1/Primary-secondary systems and 8.9.1Nariable • Typically, Levell instruments provide more data
primary systems). This pressure can also be used to to the DCICS than Level 0 instruments.
determine fouling of the heat exchanger. .A well-designed DClCS will allow properly trained
• This example assumes that the customer-side equip- personnel to "drill down" from higher networks to
ment will be controlled by the customer's control Levell networks to connect to a particula rfield in-
system, not the DClCS. However, there may be rare strument that may be having a problem, thus pro-
situations where the provider will be called upon to viding the ability to remotely troubleshoot
control this equipment. Typically, the customer-side the system.
distribution pumps are staged on and off, and their
speeds are modulated to control differential pres- The main disadvantage of using Levell over Level 0 field
sure across the customer's use points to setpoint. It instrumentation is cost increases resulting from the fact
may also be beneficial to monitor the actual posi- that Levell instrumentation is typically more expensive
tions of the customer's individual cooling coil then Level 0 instrumentation, and that programming and
control valves and to reset the differential pressure configuration costs are alsousually higher. However, these
setpoint to more closely track current customer costs are more than offset by savings in installation costs
requirements. Actual space temperatures could also when there are a large number of instruments and they
be used for this purpose. In any case, most are located far way from each other and from the
customers will elect to control the equipment on controller to which they are to be connected.
their side of the heat exchangers with their own
control system. As a result, this discussion is not Due to the additional data that they provide, their
applicable to the DCICS. inherent troubleshooting features, and the potential
installation savings that can be realized by using them,
8.9.2 Level 0 vs. Level 1 - field the trend in the industry is to specify Level 1 field
instrumentation instruments whenever it is cost effective to do so.
The illustrations provided above are just examples and
are not intended to stipulate that, if a particular field 8.10 Level 2 - Best Practices
device is depicted as a Level 0 or a Levell device in the
example, that it must be so specified in practice. The The sections that follow present some guidelines for
choice of whether to specify Level 0 or Level 1 field local Level 2 plant controllers. Local plant controllers
instrumentation, or a combination of both, is application- provide the actual control and monitoring functions at
specific and should be handled on a case-by-case basis. the plant level by interfacing to Level 0, 1, 3 and 4
equipment.
Table 8-6 lists some criteria that should be considered
when making this decision. 8.10.1 Types of controllers
The different types of controllers that are typically used
Following are advantages to using Levell over Level 0 in a district cooling instrumentation and control system
field instrumentation: and the advantages and disadvantages of each type are
.Reduced installation costs (provided there are a discussed in section 8.5.3. To summarize, programmable
large number of instruments and they are not logic controllers (PLCs) and distributed control systems
located close together or to the controller they (DCSs) are acceptable for most DCICS applications.

then select field


instrumentation of
If the following is true ... this type:
Level 0 Level 1
The field instrumentation count is small and the instruments are located in the same
vicinity as the controller to which theywill be connected (such as in the case of an ETS). ,J
Thefield instrumentation count is largeor the instruments are distributed throughout
the plant far away from the controller to which they will be connected (such as in the
case of a large chilled-water productionplant). ,J
The field instrumentation provides morethen one or two variables that mustbe accessed
bythe controller to which theywill be connected, wherehard-wiring allof these variables
would be cost-prohibitive (such as in the case of energy meters and VFDs). ,J
Table 8-6. Level 0 vs. Levell field instrumentation - selection criteria.

122
DISlRlCT COOUNG BEST PRACTICE GUIDE
C2008lnlemab'onal osma Energy A55ooilb'on. Allrights reservro.

modules that the points are wired into should be


Proprietary direct digital controllers (DOC) are better configured through software (not DIP switches or
suited for commercial applications and are usually not jumpers) whenever possible. These configurations should
used in a DCICS. be stored and downloaded with the controller's program.

8.10.2 Selection criteria It is essential that the controller have a large internal
The controller(s) selected should support at least one variable capacity to perform the complex tasks typically
of the following pictorial programming languages: required by a district cooling instrumentation and con-
• Function block diagrams trol system application .
• Ladder logic diagrams
.Sequential function charts Since the controller must communicate to many types
of external devices (Levell, 3 and 4 equipment), it must
High-level, general purpose languages, such as C, C++, support a variety of communication protocols and
Pascal, Fortran and Visual BASIC, while very powerful, media.
should be avoided due to their complexity.
Most controllers are installed in harsh environments and
Regardless of the programming language selected, its must be capable of operating in those conditions. Fol-
instruction set must be robust enough to build the lowing are typical environmental:
complex logic, math, sequencing, timing, counting, and .Operating temperature: 0 C - 60 C (32 C - 140 F),
other algorithms that are required in a typical DCICS typical
application. Some of the control functions that are seen .Operating relative humidity: 5% RH - 95% RH
in different types of plants are discussed in section 8.14. (non-condensing), typical
The ability to create, modify, upload, download and .Others to consider:
save controller programs using an engineering work- _vibration
station is recommended. Once stored in a controller, _shock
the proqrarns- and their associated data should be • radiated RF immunity
protected by battery andlor EEPROM, which prevents
accidental loss in the event of a power failure. 8.10.3 Distributed controllers
For large plants it may be beneficial to design the
The ability to make online changes to the controller's plant's control system using distributed controllers as
logic while the plant continues to operate should be opposed to using one controller for the entire plant.
required by all DClCS controllers. That way, if a particular controller must be taken offline
for any reason, only those devicesthat are controlled by
The programming environment used by the controllers that controller must be operated manually in order to
must support a broad range of debugging and keep the plant running, instead of all of the devices in
troubleshooting tools including cross-referencing, the plant, as is the caseif a single controller is used.
advanced search-and-replace features, and data table
lookups. Online program monitoring and tracing that For example, controllers could be distributed in a large
graphically presents the different states and values of chilled-water production plant as follows:
the program's instructions and the data they are .Controller 1 - Cooling tower controller
operating on must be supported. .Controller 2 - Condenser water loop controller
.Controller 3 - Chilled water loop controller
The controller selected must be able to process a large .Controller 4 - Balance of plant controller (HVAC,
number of 1/0 points reliably and quickly. The 110 electrical energy monitoring, chemical feed sys-
tem monitoring and control, etc.)

8.10.4 Controller redundancy


For critical plants, redundant controllers should be used.
Most manufacturers of PLC systems and DCSs offer
redundant controller options. Redundant controllers
eliminate a single point of failure, allow one controller
to be serviced while the other controller continues to

123
DISTRICT COOLINGBEST PRACTICE GUIDE
C2008 IrltematiOflilI {)isrrkr Energy Associao'on. All rightsreserved.

8.10.6 Time-of-day synchronization


between controllers
All of the controller real-time clocksin a highly distributed
DClCS application should be synchronized to a single
source. This is very helpful in determining the sequence
of events that occur during major system upsets. If the
operate the plant, and can eliminate the need to install real-time clocks are not synchronized between plants.
many distributed controllers (see previous section). it may be impossible to determine what the root cause
of the upset was.
One of the key design factors to consider when
deploying redundant controllers is setpoint synchro-
nization. If an operator makesa setpoint to the master
controller, it must be copied to the backup controller, or
unpredictable operation may occur when the
controllers are switched.

Redundant controllers will also typically require addi-


tional programming and a mechanism must be put in Time synchronization may be as simple as tying all of
the controllersto a central time controller that periodically
place at the Level 4 data servers in order for them to
switch to the current master controller for their data. updates all of the remote controllers to its internal clock
or as complex as connecting all of the controllers to
IRIG-B satellite signals.
8.10.5 Critical data integrity
Some of the data gathered by a DCICS is critical to the
provider's business (i.e., billing and efficiency data). The 8.10.7 Controller power requirements
Sincecontrollers provide all of the low-level control and
financial impact to the provider if this data is lost can be
disastrous. For this reason, critical data should be col- monitoring functions for the plants in which they are
lected and stored locally at the controller to which the installed, the power feeding these controllers (and their
metering instrumentation is connected, so that if the 110 racks and modules as well) should be backed up by
connection to the historical data server is lost, the data emergency generators andlor uninterruptible power
will not be. When the connection is restored, the data supplies (UPS).
that was stored while the connection was down can
then be forvvarded. Emergency generators require the use of an automatic
transfer switch (ATS) to automatically toggle between
Since there is no way of anticipating how long the normal power and the emergency power being pro-
connection between a plant controller and its historical duced by the generator(s) that is started when normal
data server will be down, controllers that collect and power is lost. The automatic starting of an emergency
generator and the activation of the ATS takes time (<30
store critical data should be equipped with flash cards,
read-writeable CD/DVDs or some other removable seconds typically). A UPS is needed to keep the con-
non-volatile storage media. The plant controller should troller energized for the short amount of time required
to start the generator and transfer to emergency
periodicallybackup critical data to this media. Procedures
should be in place for restoring data in the event that power. The UPS should be sized to keep the controller
a controller needs to be replaced. energized during this short power transitional period.

There may also be situations where an emergency


generator is not available at a particular plant. In these
A good rule of thumb is that controllers that perform situations a UPS is required and should be sized to keep
metering functions should store their metering data the controllers energized for a much longer period of
internally as follows: time. The length of time is dependent on the individual
.current daily totals provider's requirements.
• Iast 30-day totals
.current monthly totals The UPS shouId
.Iast 12-month totals .be industrial grade;
.current yearly totals .have power conditioning and filtering capabilities;
.Iast 10-yeartotals .have the capability to shield control equipment

124
01STR10 COOUNGBEST PRAalCE GUIDE
02008 Intemarional D15trid Ene<gy Association. Ail rights reserved.

from voltage transients, line noise, spikes, surges grade, user-input devices, such as mice and keyboards,
and fluctuations; is not acceptable in most situations. Instead, the Olfs
.have the ability to annunciate its status to the should be provided with waterproof membrane-style
DCICS by way of hard-wired va
or communications; keyboards and pointing devices. Touch-screen technology
and is also recommended whenever possible.
.be equipped with automatic maintenance bypass
capabilities to ensure continued power to the load- 8.11.4 Local OIT power requirements
side equipment in the event of battery failure or Thelocal Oflsshould be backedup by the sameemergency
battery replacement maintenance. generators and/or uninterruptible power supplies (UPS)
that back up their associated controllers.

8.12 Level 4 - Best Practices


The terminologies, hardware and software used by
different suppliers of Level 4 equipment vary greatly.
The sections that follow present best practice tips for
the design and deployment of the Level 4 equipment
depicted in the sample DCICS that was introduced in
8.11 Level 3 - Best Practices section 8.6. Although the terminology and components
may vary from one supplier to another, the principles
The sections that follow present some guidelines for
presented here can be applied across the board to Level
the local Level 3 operator interface terminals (Olls).
4 equipment from any supplier.

Local Olls are installed directly on the plant floors close


to the equipment they control and monitor. When a
district cooling provider does not use Level 4 equipment,
the local orrs provide the only means for personnel to
interface to the DCICS and serve as secondary
interfaces in the event that the link to the Level 4
equipment is lost.
Level4 equipment is typically comprised of server-class
computers, similar to those found in data centers
8.11.1 Connecting local OITs to around the world; personalcomputers, such asdesktops,
local controllers towers and laptops; network infrastructure equipment,
Local Level 3 orrs should be coupled as tightly to the
like hubs, switches, routers and firewalls; and the
local plant controller(s) as possible and should not rely
necessary software to allow these devices to perform
on Level4 equipment (servers, hubs, switches, routers,
their specified functions. Table 8-7 provides best prac-
etc.) to communicate to those controller(s}. This ensures
tice tips for the computer hardware and software
that the plant can continue to operate in the event of
aspects only. Best practice tips for network infrastruc-
a loss of connectivity to the Level 4 equipment.
ture equipment are discussed in section 8.13.

8.11.2 Displaying metering data on


10calOlTs 8.13 Networking Best Practice
If a controller is collecting metering data (i.e., an ETS Considerations
controller), the local OlIts) connected to that controller
should display the metering data in a tabular format so 8.13.1 DCICS network categories
that readings can be taken manually in the event of an The networks that facilitate communications between
extended down time with the Level 4 equipment. the different district cooling instrumentation and con-
trol system components can be categorized as shown
A well-designed DClCS should permit manual readings in Table 8-8.
to be entered into the historical data such that automatic
and manual readings can be queried together to gen- Levell networks are used to interface Levell equip-
erate concise usage reports. ment to their associated Level 2 controller(s}. These net-
works are usually self-contained within a single plant,
8.11.3 Environment are high-speed and are secure by nature. Section 8.8.8
Local Olls are typically installed in harsh environments, provides some best practices to consider when design-
directly on the plant floors, near the equipment that ing and deploying Levell networks.
they control and monitor; The local Olls and the enclosures
in which they are mounted must be rated for these Level 2+ controller networks are used to connect Level
types of environments. The use of standard office- 2 controllers together and to connect Level2 controllers

125
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008lntemiftionifl D/5lrict Energy Associiftion. All rightsreserved.

level 4
Topic Best Practice Tips
Component

Data Server(s) Hardware The role of the data server implies its criticality. If its hardware is improperly
specified, it can become a single point of failure that prevents personnel
from interfacing with their equipment and can result in loss of data. A
well-designed data server will
• be a server class machine, running a server-class operating system;
• have large amounts of random access memory (RAM);
• have multiple processors (if the operating system and application
softwarecan exploitthem);
• incorporate hard-drive fault tolerance (minimum RAID Level 1);
• have redundantpower supplies;
• have redundantcooling fans; and
• have a minimum of two network interfacecards (NIC):
eone to communicate with its associated controllers over the
controller network.
eone to communicate with the balance of the Level 4 equipment
over the data network.
eone to communicate with the balance of the Level 4 equipment
overthe data network.
Redundancy To further decrease the likelihood of a data server becoming a single
point of failure, multiple data servers should be installed in redundant
and highly available configurations. In thesetypes of configurations, at
least two data servers are used. One is designated as the master and
the otherts) is designated asthe backup(s). Normally, all of the other
Level 4 servers and workstations communicate with the master data
server for their data. However, if the masterdata server should fail, all
of the other Level 4 servers and workstations should automatically
switch to the backupdata server for their data. Fallback to the master
data server upon its recovery can be automatic or manual, depending
on the district cooling provider's preference.

How historical data collection is handled when redundant data servers


are used is also a key design conceptto consider. Normally, only the
master data server should log historical data to the historical server, not
the backup(s). This prevents duplicate data from being written. When
the backup data server detects that the masterdata server is down, it
must automatically pick up the data logging responsibilities and begin
to log historical data to the historical server. Whenthe master data
server is restored, normal data logging should resume automatically.
Every record written to the historical server shouldbe date- and time-
stamped and should be flagged with the nameof the data server that
logged the record.
Historical data - If the data server that is currently logging to the historical server is
"store and feed operating properly, but loses its connection to the historical server, it
forward" should beginto storedata to its local hard drive. This iswhy fault-
tolerant RAID drives are recommended for data servers. When the
connection to the historical server is restored, the data that was logged
locally on the data server should be automatically copied to the historical
server. When it is confirmed that the data has been copied successfully
to the historical server, it should be removed from the data server so
that duplicate records do not existin the system.
Power All data server(s) should be powered by an uninterruptible power supply
(UPS) that is in turn backed up by an emergency generator.
Software The software that runs on a typical data server varies greatly from one
supplier to another, and any attempt to specify bestpractices for it is
beyond the scope of this chapter. However, some typical software
applications that run on data servers are listed below:
.1/0 drivers - programs that communicate to the Level 2 controllers
andserve the data accessed up to other applications that arerunning
on the data server. OPC servers arethe most common type.
• real-time process-variable database management applications
(scanning, scaling, alarming, etc).
• visualization software- graphical user interface screens
ealarm handling software

Table 8-7. Level 4 componentry best practice tips. Continued


126
DISTRICT (aaUNG BEST PRACTICE GUIDE
02008 /nf2ma~Ona/ Di5tridEnergy AssooiwOn. N/ nghll'reserved.

Level 4
Topic Best Practice Tips
Component
Data Server(s) • historical data collection software
(continued) • historical data trend display software
• reporting software
Historical Server Hardware The criticality of the historical server depends on the "value" that the
provider places on the data beingcollected and stored. The following
criteriashould be addressed when determining the "value" of the data:
• Why isthe databeing collected and stored? Formaintenance and
troubleshooting? To determine plantefficiencies? For customer invoicing?
.What is the required data collection rate?
• How long mustthe databe retained?

A historical server that is collecting and storing "critical" data should


• be a server-class machine, running a server-class operating system;
• have largeamounts of random access memory (RAM);
• have multiple processors [if the operating system and historical data
acquisition (HDA) software can exploit them];
• incorporate hard-drive fault tolerance (minimum RAID Level 1);
• have ample hard drive space to storethe large amount of data that
is required by a typical DCICS;
• have redundant power supplies;
• have redundant coolingfans; and
• have a minimumof two network intetface cards (N1C), with both
connected to the associated data network for communicationfault
. tolerance and increased bandwidth.
Redundancy As long as the following criteria are met, historical server redundancy is
not required:
• Fault tolerant hardware is specified for the historical server (see
above).
• Redundant data servers are deployed, and they log data to the
historical server as described above.
• The data servers utilize a "store-and-feed-forward" data collection
approach when logging to the historical server (see data server
section above), ensuring that data will not be lost if the connection
to the historical server is lost for any reason.
• Thedata being logged to the historical server is backed up periodically
and taken off site.
Power All historical serverts) should be poweredby an uninterruptible power
supply(UPS) that is in turn backed up by an emergency generator.
Software The storage file format built into most historical data acquisition (HDA)
applications is proprietary andcan vary from supplier to supplier. However,
most modern HDAsoftware packages supportinterfacingto third-party,
non proprietary relational database server applications aswell. This is
the recommended storage file format for a DClCS.

The selection of storage file format is veryimportant since the data that
the file stores will not only be accessed by other DCICS applications, but
also by third-party, Level 5 systems (i.e., accounting, maintenance and
billing systems). Most Level 5 systems should support issuing SQL queries
againstrelational databases that will makeaccessing the data much
easier than if proprietary filesare used.

Proper initial design of the storage file format and how the LevelS
applications will access the stored data can make integration much
easier downthe road, andcan lead to ongoing savings in datamaintenance.

The relational database server application selected should be enterprise


class, supportmanysimultaneous connections and users, provide audit
trailsof ali database activities andallow easy access to databy third-party
applications using SQL queries. It should be capable of handling the
large numberof records that a typical DCICS will generate quickly and
efficiently. Some acceptable relational database server applications
include MicrosoftSQL Server, Oracle RDBMS and OSlsoft PI.

Table 8-7. Level 4 componentry best practice tips. Continued

127
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 Inremariona! Disrncr EnergyAssociarion. All right5reserved.

level 4
Topic Best Practice Tips
Component
Historical Server Logging rates and data retention requirements should be defined dur-
(continued) ing the detailed design of the DCICS. Thiswill determine the size of the
mass storage device(s) that the historical server requires.
Data security, backup Data security, backupand restoration activities are also important factors
and restoration to consider when specifying and implementing a historicalserverfor a
DClCS. Depending on the "value" of the data, backups should be
performed at regular intervals and stored off site. Following are examples
of robust backup procedures:
.Automated backupto tape or other removable media performed
locallyat the historical server's location. Maintained by the owners
of the DCICS.
• Automated backupto corporate backup servers, which in turn are
backed up by other systems. Requires ongoing coordination with
the IT department that owns the backup equipment, but otherwise
should be transparentto the owners of the DCICS.

Regardless of how the datais backed up, detailed restoration procedures


must be in place that allow backed-up data to be restored and analyzed
while the DCICS continues to collect historical data, real-time.
Terminal Server Hardware Terminal servers host applications for users who connect to them
remotely. The applications are started and manipulated by the remote
users, but the applications actuallyrun on the terminal server. This
allowsthe remote users to access the applications without having to
install them locallyon their computers. All that istypically needed is a
standard Web browser and proper security credentials in order to access
the applications on the terminal server. Due to the fact that many
applications may be running on the terminal server at the sametime,
one of its most important specifications is the RAM it has. The more
simultaneous applications that are run, the more RAM that is needed.
Following are characteristics of a well-designed terminal server:
els a server-class machine, running a server-class operating system.
• Has large amounts of RAM. Themaximum amount available for the
computer being specified should be considered for a terminal server
if many remote users will access it simultaneously.
• Has multiple processors (if the operating system and application
software can exploit them).
• Uses standard hard drives (l.e., fault-tolerant RAID drives are
typicallynot a requirement).
• Isequippedwith standard power supplies and cooling fans (redun-
dant power supplies and fans are not typically required).
• Has a minimum of two network interface cards (NIC), with both
connected to the associated data network for communication fault
tolerance and increased bandwidth.
Redundancy Redundancy is not typicallya requirementfor a terminal serverunless it
is critical to the provider's business activitiesthat remote users be able
to access the DCICS at all times. Data server, historical server and DClCS
workstation operation should not be impacted by the loss of a terminal
server. Only remote useraccess should be affected.
Power All terminal server(s) should be powered by a UPS, which is in turn
backed up by an emergency generator.
Software Most software manufacturers who write software that can be run on
a terminal server license it based on the number of concurrent users.
Licensing must be thought about carefully. If there are not enough
concurrentlicenses available, then everyone who needs remote access
to the system will not be ableto get it. If therearetoo many concurrent
licenses then the first-time cost of the terminal server software will be
unnecessarily high.

Table 8-7. Level 4 componentry best practice tips.

128
DISTRICT (aGUNG BEST PRACTICE GUIDE
02008 International oanaEnergy Association. Allright> re~.

to their Level 3 OITs and Level 4 data servers. Level 2+ disastrous. However, if the provider depends on the
data networks are used to connect Level 4 data servers communication backbone to control equipment and
to other Level 4 servers and workstations and to tie all the connection is lost, then the impact might not be
of the local controller networks in a provider's district known until it is too late to do anything about it. It
together. Level 2+ networks can span multiple plants should be noted that control is actually done at the
and sites, and in the case of the central data network local plant controller - Level 2. Even when a satellite
presented in the sample Deles in section 8.6, may plant is "controlled" remotely, the remote input is to
extend to all of the plants and command centers. issue requeststo control equipment and to change set-
points. The actual control and setpoint mainte-
Network Example networks introduced nance is done by the local controller.
Category sample DClCS in section 8.6
Fiber optics
Level 1 Networks Remote 110 networks
Energy monitoring networks
Chiller controller networks From the reliabilitylsecurity perspective. the bestso-
VFD networks lution would be to install a fiber-optic system
"Smart" transmitter networks dedicated to and controlled by the provider. Fiber
Level 2+ Networks Controller networks optics is the best backbone for speed, flexibility
Data networks and maintainability, but it has the disadvantage
Level 5 Networks Corporate networks (notinthe scope of higher first cost. If a fiber-optic system is(or will
of this chapter) be)alreadyin place in the district cooling provider's
district, then sharing bandwidth might be a fea-
Table 8-8. DClCS network categories.
sible alternative. However, the provider should
The sections that follow provide some best practices to assume somesecurityand privacy will be lost.Alternatively,
consider concerning the specification, design and the provider could install the fiber-optic system and then
installation of Level 2+ networks. lease bandwidth to others. That way the provider could
exert greater control over its operation, at leastin theory.
Generally, fiber-optic systems will be more expensive
than wireless and Internetoptions. However, costs can
be reduced if the fiber can be installed with the district
cooling piping in new installations.

8.13.2 Level 2+ network infrastructure


Level 2+ network design and deployment will depend
strongly on the infrastructure already in place. Options
applicable to an existing (expanding) system will be dif- Although fiber is the most secure of the options, it canstill
ferent than options for a brand-new system. The fol- be "hacked." Unlike the other options, hacking into a
lowing addresses a brand-new district cooling system fiber system requiresthe intruder to be physically present
where there isthe flexibility to createa grassroots Level 2+ at some location where the fiber can be tapped into.
network infrastructure. This infrastructure could take
one or more of the following forms: Wireless
.dedicated fiber optics
.shared fiber optics Wireless is one alternative to fiber optics. Before
.wireless (radio frequency) proceeding with wireless technology, it would be ad-
• World Wide Web through Internet service provider visable to confirm government regulations concerning
.World Wide Web through leased line (dial up licensing of radio frequencies. The financial benefit of
telephone line connection) using wireless technology could be lost if franchise fees
become excessive or if government approval becomes
When selecting the infrastructure the two most signif- bogged down by an inexperienced bureaucracy.
icant parameters are reliability and security. Although Although most utility companies usewireless technology
cost is an important element, it needs to be considered in some form to monitor meter readings, it is not
in terms of satisfying reliability and security. commonly used for control. Wireless connections are
limited to 1 or 2 km unless repeater stations are
Monitoring requires less reliability and security than installed. Antennas require line of sight; that is, a clear
does control. If a connection for monitoring an energy shot without hills or buildings. It is important to
meter is lost, then the data will have to be retrieved lo- remember that installation of antennas will require
cally from the meter. Although inconvenient, it is not approval from the building owner if the building is not

129
DISTRICT COQUNGBEST PRACTICE GUIDE
C2008 Inremab'onal Dlsfna Energy Association. AI/lightsreserved.

owned by the district cooling provider. The key element to the success of remote control is
having a fairly sophisticated DClCS Level 2+ network
Wireless systems can be hacked from the curbside infrastructure in place.
using a laptop, making it a much less desirable option
then fiber optics, but it is still acceptable provided the 8.13.4 Sophistication
appropriate security measures are put in place. When controlling from remote locations, it is critical
that process variables be available to the remote
Internet operators on a timely basis. When the plant is locally
manned, an operator may detect a problem developing
Monitoring and control through Internet connections simply by the sound a machine is making, an unusual
is also fairly common. Service through an Internet odor or any symptom that can be physically sensed.
provider's high-speed infrastructure should be much These human senses are impossible to replicate with
quicker than through a leased line and would be the sensors and computers. Thus, any time a plant is
better Internet choice. Regardless, the connectivity to operated remotely, the provider is putting itself at a
the satellite plants will depend on the quality of the potentia I risk.
Internet connection. If the Internet connection is weak,
these options should not be considered. The extent of the risk depends on the plant'scomplexity.
On the complex side, a diesel electric generation plant
Hacking through the Internet is extremely convenient as with steam heat-recovery generators and absorption
the intruder can do it any time from any place in the chillers would be a difficult plant to control safely from
world, making it a much less desirableoption than fiber a remote location. On the simple side, an electric
optics, but it is still acceptable provided the appropriate centrifugal chiller plant could be safely controlled from
security measures are put in place. a remote location (this is often done). Since the most
complex procedure isstarting up a system, if the startup

8.13.3 Remote control vs. manning


individual plants is to be initiated remotely, then the controls will have to
The preceding discussions assumed a brand-new be appropriately sophisticated. For example, if a steam
system into which the DCICS Level 2+ network turbine drive isto be started remotely, then the procedures
infrastructure would be deployed. The reason the Level for draining and warming must be available to the
2 + network infrastructure is needed at all is so the remote operator.
district cooling provider can remotely monitor and
control any or all of their plants from a central location. It is also important to point out that local government
The question then is why it would be desirable to code and regulations may require staffed operation for
control multiple plants from a central location. The two plants that use certain types of refrigerants.
most common reasons are staff cost and staff competence.
If competent operators are availableat reasonable labor 8.13.5 Performance
rates, then it might be best to staff each plant with op- Once the plant complexity is determined, then the task
erators for all or significant parts of the day. If operators is to develop a district cooling instrumentation and
are also mechanics and electricians, then job duties control system Level 2+ network infrastructure that is
could be shared, with obvious benefits in cost and time. economical and meets acceptable risk levels. The term
However, if there is not a sufficient pool of competent "acceptable risk level" is deliberately ambiguous, as the
operators, it may be beneficial for the provider to district cooling provider must define this term based on
control and monitor many plants from a central location. its specific conditions and aversion to risk. Performance
criteria to consider whenspecifying a Level 2+ network
Controlling from a central location removes significant infrastructure are
portions of the staffing problems. By having a small .data throughput,
group of qualified operators in one location, several .reliability and
plants can be controlled and the labor cost can be .security.
spread over more units of production. Additionally,
methods and procedures can be standardized within a 8.13.6 Security
smaller group of people in a central location. Training Security on any type of distributedsystem, likea large-scale
operators is also more convenient. DCICS, needs to be implemented at the hardware and

130
DISTRICT COOLING BEST PRACTICE GUIDE
e2008lnrem~tionaJ Di5tTid Energy Association. Ailnghl5 re~.

software levelsand needs to be as robust as possible to port network monitoring via OPC (OLE for process con-
prevent unauthorized access, either accidental ormalicious. trol). Some of the data typically available includes
• device status,
On the hardware side, securelintelligent hubs, switches, .Iink status and
routers and firewalls that can be configured to limit .network statistics.
access to authorized people andlor computers should
be used extensively. The ability to read this information using an OPC server
allows it to be incorporated into most modern HMI ap-
On the software side, security should be implemented plications where it can be trended, alarmed and dis-
at the operating system level using the most modern, played along with all of the other process data being
robust security schemes available. Items such as unique accessed. Separate applications (other than the appro-
and complex user names and passwords and password priate OPC server) are not required to access this data.
expiration should be considered. In general, all of the It can be embedded into the same HMI application that
security-related recommendationsmade by the operating is used to control and monitor the rest of the equip-
system's manufacturer should be followed closely. ment in the district cooling provider's plants.

8.13.9 Network bridging and


controller pass-through
Network bridging and controller pass-through are two
concepts that should be supported by a well-designed
and deployed DCICS.

Network bridging involves 'hopping' from one network


(or network segment) to another network (or network
The operating system must provide a means of auditing
segment) through a network bridge. The network
who logged into the system and when. It should
bridges used should be intelligent devices that can be
support multiple user levels and have the ability to
configured to limit access to authorized personnel
assign users to groups. A user assigned to a particular
andlor authorized computers only.
group should inherit all of that group's privileges.
Controller pass-through technology allows authorized
On a large, highly distributed DCICS, it is important that
users to connect to one communications port in a
the security information for the entire system be stored
controller's rack, 'pass through' the rack's back-plane,
at a central location that is accessible remotely by au-
and go out through another port to access devices on
thorized administrators. This allows users to be added,
a completely different network. Proper pass-through
removed or have their privileges modified from one lo-
technology allows seamless connectivity between two
cation instead of physically traveling to all of the plants
dissimilar networks that may usedifferent media andlor
and command centers to do it.
protocols, aswell as between two similar networks.
Modern virus protection software should be deployed An example of network bridging and controller pass-
and updated regularly on every applicable DClCS com- through will further clarify these points. Referring to
ponent to detect, prevent and remove threats posed by the sample DCICS presented in section 8.6, let's say
external sources. that an authorized user whose computer resides on the
provider's corporate network needs to access an energy
8.13.7 Physical network topologies meter in order to reconfigure it. The energy meter
Multi-drop and trunkline-type network topologies resides on the energy monitoring network at the ETS in
should be avoided since a single break in the network Plant-F2. Users would log on to their computers,
cabling or a failure in a single network interface device 'bridge' from the corporate network to the DClCS
has the potential to affect communications to large central data network, 'bridge' again to the DClCS local
portions of the network. controller network that services PlanH2 and connect to
a port on one of the communication modules in the
Instead, ring-type topologies should be used. This style ETS controller's rack. From there the user would 'pass
of network topology provides two paths of communi- through' the controller's back plane and go out through
cations from any point to any point, so if a cable does
break or a single network interface device doesfail, net-
work operation will be minimally affected.

8.13.8 Network monitoring via ope


Many of the network interface devices (hubs, switches
and routers) that are available in today's market sup-

131
DISTRICT COOLING BEST PRACTICE GUIDE
e2008 /ntema~On.lIDi>trict Energy As5rxia~'on. Allriglll5 reserved.

a different port to access the energy monitoring It should be pointed out that the data being generated
network in Plant-F2. Finally, the user would access the by a typical DClCS needsto be made availableto systems
energy meter needed to configure over the Plant-F2 that run on the provider's corporate network, such as
energy metering network. billing and accounting systems. For this reason the two
departments (DCICS and IT) will need to interface
The example above illustrates the power of network regularly and a high level of cooperation needs to be
bridging and controller pass through from a serviceability maintained between the two.
point of view. Personnel do not need to travel to the
individual plants to service the equipment in them. With
this power also comes the potential for malfeasance by
unauthorized personnel, so robust security measures
must be put in place if network bridging and controller
pass through are implemented.

8,13,10 DClCS network and Level 4


equipment ownership
Most large providers have internal Information
Technology (IT)departments that operate and maintain Another example of DClCS equipment interfacing to IT
the networking equipment, servers and workstations equipment has to do with archiving critical data. Some
on the district cooling provider's corporate network. providers may elect to back up DCICS generated data
to corporate backup servers, which themselves are
While IT departments provide an invaluable service to automatically backed up to removable media and taken
the provider's overall operation, they should not be the off site for permanent storage. This automatic backup
department that 'owns' the DCICS network equipment, function is a service that most IT departments provide
servers, or workstations unless they are made aware of and if available should be taken advantage of by the
the criticality of this equipment and agree to modify DCICS because it will eliminate the first-time and
their standard operating procedures where this equipment ongoing costs of installing and operating a backup
is concerned. Most IT departments have procedures in system solely for the district cooling instrumentation
place that if applied to an operational district cooling and control system. However, it further stresses the
instrumentation and control system could render it need for cooperation between the two departments
inoperable. (DCICS and IT).

For instance, a typical task that IT departments perform 8.13.11 DClCS Level 2+ network
on a regular basis is to shut down network hubs for component power requirements
maintenance. This is fine on the corporate network DCICS Level 2+ networks allow large portions of the
where the shutdown can be scheduled during off hours DCICS to communicate with each other. Without
and the impact to theprovider's operation is minimized. proper thought, a failure of a single Level 2+ network
However, shutting down a DCICS hub, regardless of component can result in a substantial lossof visibility to
the time of day, can have disastrous consequences, the provider's plants. One of the first things to consider
resulting in loss of visibility to one or more plants. is how this equipment will be powered.

Another typical IT function is to automatically download It is highly recommended that all Level 2+ network
patches and updates to the servers and workstations equipment be backed up by emergency generators
on the corporate network. Thisis a valuable service that and/or uninterruptible power supplies (UPS).
IT departments provide. It helps to keep the provider's
corporate computers up to date with the most recent Emergency generators require the use of an automatic
versions of software and free of viruses. However, the transfer switch (ATS) to automatically toggle between
software implemented in a typical DCICS is designed, normal power and the emergency power generator
deployed and tested using certain revision levels of that is started when normal power is lost. The automatic
operating systems and other software. If this software starting of an emergency generator and the activation
is updated without first testing the updates in a con- of the ATS takes time (<30 seconds typically). A UPS is
trolled environment, the entire DCICS may stop working. needed to keep the Level 2+ networking equipment
energized for the short amount of time required to start
The choice of what department owns and operates the the generator and transfer to emergency power. The
DCICS network infrastructure is left up to the individual UPS should be sized to keep the equipment energized
provider, but it is important to emphasize that special during this short power transitional period.
care must be taken when servicing any piece of DCICS
network equipment. There may also be situations where an emergency
generator is not available at a particular plant. In these

132
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 inlemalionalDistrictEnergy As5Odalion. Allrightsreser.ro.

situations a UPS is required and should be sized to keep _heat exchanger customer-side pump control
the Level 2+ networking equipment energized for a (depending on customer)
much longer period of time. The length of time is _energy monitoring
dependent on the individual provider's requirements.
8.15 Human-Machine
8.14 Control Functions Interface Functionality
This section presents an overview of the types of control The provider's staff can interface to the DCICS in many
algorithms that a well-designed and implemented different ways from many different locations:
DCICS should be able to support. Details on these .Local to plants
control schemes are beyond the scope of this chapter .Iocal Level 3 OITs
and would typically be defined by the DClCScontractor elocal Level 4 workstations
during detailed design. .Command centers
• data servers
In general, a well-designed and implemented DCICS • historical data servers
should be able to perform all of the control functions .command center Level 4 workstations
necessary to meet the provider's main objective of .Indirectly from Level 5 applications by accessing
providing chilled-water energy to its customers in the the data stored in the relational database(s) on
most cost-effective manner possible. This includes, but the historical server(s).
is not limited to, the following: • Remotely from anywhere in the world, with the
proper security credentials, using standard Web
browsers via the terminal server(s) that are
installed in the command centers.

Some of the HMI functions that a DCICS must support


are listed below:
• Present the status of the equipment in all of the
.Schemes provider's plants to the user on graphical user
• primary-secondary systems interface screens.
_preferential loading systems .Allow users with the proper security credentials to
-sidestream systems operate equipment, modify setpoints and change
_variable::primary systems operating modes.
• Chiller-water plants • Provide alarm annunciation .
-cooling tower staging • Provide access to historically stored data via
_condenser-water pump control graphs and spreadsheets.
-condenser loop control .Generate reports from historical and real-time data.
-head pressure control .Automatically issue pages, emails, phone calls and
.chiller staging other types of notifications when critical alarms
• primary pump control occur in any of the provider's plants .
.secondary pump control
-energy monitoring 8.16 Standardization
• TES plants
_cooling tower staging Standardization is essential to the successful imple-
-condenser water pump control mentation of any new DCICS. Time spent during the
-condenser loopcontrol early stages of the DCICS design developing standards
.chiller staging will result in a DCICS that is maintainable and service-
.TES pump control able for years to come .
• TES heat exchanger staging
• TES heat exchanger dischargetemperature control At a minimum, standards should be developed for the
• TES heat exchanger discharge pump control following:
-energy monitoring .HMI standards
.Pumping (lift) stations -located well downstream
of the chilled-water production plants .
• pump control
_energy monitoring
• Energy transfer stations
.heat exchanger staging
-heat exchanger customer-side temperature control

133
DISTRICT COQUNG BEST PRACTICE GUIDE
ClOO8lnlematiooal Disrriet Energy Association. Ail righ~ reserved.

• Graphical user interface (GUI) screen standards. +end field devices,


GUI screens should have the same "look and + P&IDs and other drawings,
feel" from one plant to another. This will result in • design specifications,
operators needing less training when working .variable names in the PLC,
across multiple plants. General screen layout, +tag names in the HMI application,
color codes, screen navigation and animation .tag names when an alarm is annunciated and
preferences should all be standardized. +tag nameswhen a point is historically logged .
• Standard objects. Real-world devicessuch as iso- .Communications addressing
lation valvesare found all over a typical provider's .Proper planning for how devices are addressed
various plants. If a standard HMI object is created (i.e., IP addresses) on the various networks
for an isolation valve, encompassing all of the at- upfront can make maintaining and expanding
tributes that are typical for an isolation valve, the networks easier in the future.
then the same object can be deployed over and
over again instead of creating a newobject every 8.17 Standard Design Documents
time an isolation valve is placed ona GUI screen.
This can save enormous amounts of time in pro-
gramming. The concept of object programming The following design documents should be provided by
should be used extensively. any contractor implementing a new or modified district
• Standards for historical data collection and display cooling instrumentation and control system:
should be developed and adhered to. Similar .Functional requirements specification (FRS). This
processvariables should be displayed in the same document describes what the system (or the
color (i.e., pressure = red, flow = blue, tempera- modifications to the system) is supposed to do.
ture = yellow, setpoints = black). It outlines the district cooling provider's requirements
• Alarming standards, such as common annunciation for the system.
methods, color codes, alarm descriptions, logging • Design specifications (DS). These documents
and acknowledgement, should be followed describe how the system (or the modifications to
across the entire DClCS so that alarms are the system) will be built to meet the requirements
consistent, easy-to-understand and can be stated in the FRS. There are typically two types of
responded to quickly, regardless of what plant design specifications required:
generated the alarm. • Hardware (HDS). Must include an instrument list,
.Controller programming standards detailed instrumentdata sheets andannotated man-
.General. Good controller programming standards ufacturer cut sheetsthat clearly indicate all of the
are key to the maintainability and ongoing options being specified for every field
operation of a DCICS. Service personnel should instrument being provided.
be able to be trained on one controller program .Software (SDS). Must describe the sequence of
in one plant and then be able to go to any operations, provide the HMI specifications, sum-
controller in any other plant and debug it with marize the alarm and trend requirements and
relative ease. specify any other software-related items neces-
• Standard modules. As is the case with standard sary.
objects in HMI applications, standard controller oComputer systems design specifications (CSDS).
modules should be deployed when there are In situations where there will be a large amount of
large numbers of the same type of device used Level 4 equipment being installed, such as servers,
repetitively. The module should be written once, workstations, hubs, switches, routers, printers and
tested, and libraried. The libraried module would the like, it may advantageous to break out the spec-
then be duplicated as needed, passing ification of these components, the cabinets and fur-
in the parameters that are particular to each niture they will be installed in, and their associated
individual call to the module. software, into a separate computer system design
.Documentation standards. The controller specification. Typically, the people who will review
programming standard must spell out the this document will be differentthen the people who
documentation standards that are expected will review the DS, so breaking it out may streamline
in all DCICS controller programs. Items such as the review process.
common memory maps, variable naming, variable oDrawings. The following drawings are typically
descriptions, code segment comments and mod- provided:
ule comments should be addressed. • processand instrumentation diagrams (P&IDs)
.Naming standards • panel layout drawings, bill of materials, terminal
.Standard tag naming and device description stan- block and label schedulesand power distribution
dards should be developed early on and schematics
adhered to from site to site. Tag names should .1/0 module wiring schematics
be consistent across .instrumentation riser diagrams

134
DISTRICTCOOUNG BEST PRACTICE GUIDE
02008lntemati01lil'Di5trid Energy Association. Ailnghl5 reserved.

_communication riser diagrams • Hardware factory acceptance testing (HFAT) pro-


_instrumentation loop diagrams tocols. Tests that any hardware that is
_instrumentation location diagrams pre-assembled by the contractor before it is sent
• installation details to the provider's site has been built according to
specifications (i.e., panels).
8.18 Standard Testing Documents .Software factory acceptance testing (SFAT)
protocols. Tests that all software has been
The following testing documents should be provided programmed according to specifications. Tests
by any contractor implementing a new or modified are performed at the contractor's factory, prior to
DCICS to prove that all of the requirements stated in installing the software at the provider's site.
the FRS have been met and that all of the design • Site acceptance testing (SAD protocols. The
specifications (HDS/SDS) were followed: procedures test that all of the hardware and software
.Factory acceptance testing (FAD protocols. Testing have been installed properly at the provider's site and
procedures executed at the contractor's factory, that they function properly. Successful completion of
prior to shipment to the district cooling provider's theseprotocolsare required before turning the system
site. There are typically two types of protocols gen- over to the provider.
erated and executed:

135
DISTRICT COOUNGBEST PRACTICE GUIDE
02008 International Dimid Energy A5sociation. Ailnghrs res€rved.

9. Procurement and Project Delivery


There are a variety of options for procurement of design large-diameter piping worldwide, especially steel, has
and construction services for district cooling systems. made it very difficult to procure with reasonable lead
Although there are many variations, these options can times. In some cases, district cooling companies have
be grouped into the following major categories: had to change distribution piping material type for
.design/bidlbuild (DBB) projects due to unacceptable lead times for their
.engineer/procurelconstruct (EPC) preferred pipe material. It is important for piping
.packaged plant procurement issues to be explored and accounted for
early in the planning and design stages to avoid
In the following discussion, it is useful to note that the unexpected surprises.
optimal procurement strategy may vary for different dis-
trict cooling system elements(plant, distribution and ITSs).

Choice of the appropriate procurement approach


depends on a range of factors. Major procurement
decision criteria include
• f rst cost,
.Iife cycle cost, Even prior to the recent increase in demand, lead times
.schedule, for fittings could impact the chilled-water distribution
.equipment quality, pipe material selection. For the large-sized piping used
.contractor qualifications and established owner- for chilled-water mains, fittings generally have a much
contractor relationship and longer lead time than the pipes themselves. Therefore,
• performance guarantees. for pipe routings where there is a risk of unknown
obstacles requiring unforeseen directional changes,
While EPC procurement can be an attractive option for steel piping may be preferable to a material like ductile
plants, it presents more challenges for distribution and iron. With steel piping, miters and custom fittings with
ETS systems. Design of these systems is highly site- required angles can be fabricated in the field by the
specific and it is difficult to benefit from many of the installation contractor. For pipe materials where fittings
advantages of the EPC approach. cannot be customized in the field, the owner must
either havea stock of fittings of various sizes and angles
ordered ahead of construction, at significant expense,
or accept delays when unexpected obstacles are
encountered.

9.1 Design/Bid/Build (DBB)


Because of long production cycles for large or specialized
districtcooling equipment, procurement of the equipment In this approach, also called "plan and spec," a
before completion of construction documents may be consulting engineer prepares a detailed design includ-
required. Equipment that may be affected includes ing plans and specifications that are put out to bid to
• chillers, qualified contractors.
.pumps,
.cooling towers, Designlbid/build is most frequently used for complex or
.water treatment and unique district cooling projects. The following are
• main electrical transformers, motor control centers, etc. primary advantages of DBB:
• The designer is looking out solely for the interests
One procurement-related issue that has become a of the owner and is in the best position to develop
primary concern is the availability of materials and a design that minimizes life-cycle costs instead of
equipment. In recent years the unprecedented first costs.
skyrocketing of global demand for commodities and elf a single consultant is designing all district cooling
equipment has stretched lead times for certain items system elements (plant, distribution, ITSs), it is
and, in some cases, effectively precluded use of certain more likely that a fully integrated system design will
materials due to unacceptably long lead times. For result with DBB procurement.
example, there was a period in 2005-2006 where • The owner has more control over the design and
titanium was so difficult to procure that some equipment the final product produced by the design, including
vendors were not able to fill orders for equipment with integrating consideration of ongoing operations
titanium components. and maintenance into the design.
.DBB can result in lower costs than other options as
Another area of concern with regard to availability in a result of competitive bidding on a clear and de-
recent years is distribution piping. High demand for tailed scope of work; there is less need for

136
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008In!emdtional DislTid EnergyAssociation. All ngh~ reserwd.

contractors to increase the price to cover • Large EPC contractors are executing many projects
contingencies. on an ongoing basis and normally have a project
organization with well-established methods and
routines in place. Since the owner executes large
projects less frequently than an EPC contractor, it
may lack up-to-date experience and staffing.

The following are key disadvantages of DBB:


.It is generally a more time-consuming option to
reach initiation of construction and to respond
to any redesign issues that may arise during
construction .
• The separation of design and construction create The following are major disadvantages of EPC
multiple sources of responsibility, resulting in a procurement:
"gray area" if problems occur, with the potential .A cursory or poorly developed ORD can result in a
for mutual finger-pointing between the designer fundamental tension between the owner's desire for
and contractor. high reliability and low life-cycle costs and the EPC
.DBB requires more staffing and coordination costs contractor's desire to minimize construction costs.
for the owner. .EPC procurement requires the owner to rely a great
.Changes in design, or delayscaused by one of many deal on the integrity, acumenand competence of the
contractors or authorities, will likely become the design-builder.
owner's responsibility. In these circumstances, or in .Changes may be expensive due to fast-tracking and
thecase of minor design errors, contractors have large increases in costs for items that are affected by
opportunities to use the situation to their advantage. changes, but are not competitively bid.
• The compressed schedule can conflict with regulatory
9.2 Engineer/ProcurelConstruct (EPC) review, resulting in costly change orders to bring
the project into compliance with regulatory
In this approach, also called "designlbuild," the design requirements once full review is performed.
and construction are contracted for with a single elt is difficult to clearly delineate the boundaries
entity, the EPC contractor. This approach is used to between the owner's and the contractor's respon-
minimize the owner's project risk and reduce the delivery sibilities and risks. A major category of risks relate
schedule by overlapping the design phase and to environmental issues and permits given by the
construction phase of a project. For the design phase, authorities. These issues are normally dealt with by
the EPC contractor mayuse a combination of in-house the owner and are impossible to transfer completely
engineers and consultants. to the contractor.

Typically, the owner's requirements are established in a There is a wide variation in the level of detail in ORDs,
document called the Owner's Requirements Document ranging from a brief summary of key performance
(ORD) or Owner's Project Requirements (OPR). specifications to a specific conceptual design. An
example table of contents for a detailed ORD for a
There are many variations in this procurement district cooling plant is presented in Table 9-1.
approach, e.g., the owner may directly procure major
equipment. It is important that the ORD clearlydistinguish between
the owner's requirements and the conceptual design.
The following are key advantages of EPC procurement: The EPC contractor must fulfill the project require-
elt has a single point of responsibility and there are ments, whereas the conceptual design represents one
likelyfewer contracts between the owner and others. possible way to do the design to meet the require-
• There is a reduction in time required, leading to an ments. In the end, the EPC contractor must take full
earlier online date. responsibility for the design.
• Determining the most cost-effective design can be
enhanced through the contractor's input during the 9.3 Packaged Plants
design phase.
• Cost savings can result from reduced coordination A third option for procurement of design and
costs, reduced time for carrying a construction loan construction of district cooling plants is purchase of
(which typically carries a higher interest rate than packaged or modular plants. With this approach, plant
permanent financing) and an earlier online date. modules are manufactured in a factory, including

137
DISTRICT COOLING BEST PRACTICE GUIDE
e2008ln!enlJ~ooJ/ DismdEnetgyAssociJtion. Al!rightsresr:<vro.

General Flanges
System Description Joints
Plant Design Description Valves
Definitions Insulation
Codes and Standards Plant air compressor
Design Overview and Concepts Control Equipment Requirements
System Design Requirements Instruments
Utility Cost Information Programmable logic controllers
Plant Phasing and Project Schedule Flow meters
Plant System Descriptions and Design Criteria Transmitters
Mechanical Electrical Equipment Requirements
Chilled-water system 66 kV substation
Condenser-water system 11 kV and 3,300-volt switchgear
Water makeup and treatment systems Dry-type transformers
Safety systems Plant power factor
Refrigeration storage and handling Safety switches
Ventilation Raceway system
Monitoring Wire and cable - 600 volts and below
Over-pressure protection Medium-voltage cable
Control Wiring devices
System control descriptions Substation earthing (grounding)
Architecture Ground and lightning protection system
Integrator Panelboards
Electrical Variable-speed drives (VSDs)
Utility power supply Lighting
Short-circuit protection systems UPS system
Voltage regulation systems Fire alarm and detection
Grounding systems Motors
Lighting and small power systems Distribution system controls
Building Services Building Service Equipment Requirements
Acoustics, sound and vibration Acoustics, sound and vibration
HVAC HVAC
Lighting Lighting
Plumbing Plumbing
Security Security
Plant Equipment Requirements Building Construction Requirements
Mechanical Equipment Requirements Arch ite ctu raI/civiI/structu raI descripti an
Centrifugal water chiller packages General
Cooling towers Design criteria for structure
Distribution pumps Space programming requirements
Chiller pumps Construction materials
Condenser-water pumps Environmental
Chilled-water expansion tanks Permits and approvals
Water treatment Owner's Review Process
Chilled water Preliminary design phase
Condenser water Final design phase
System Piping and Materials Construction/startup phase
Piping Commissioning
Fitting and branch connections Standards of Acceptance

Table 9-1. Example detailed outline of Owner's Requirements Documents (ORDs) for engineer/procurelconstruct (EPe)
procurement.

chillers, chilled-water pumps, condenser-water pumps, In a packaged plant, chiller/pump/motor control


motor control centers, digital controls, enclosure, center/cooling tower modules are factory-assembled as
cooling towers and cooling tower support structure. complete units for field installation as a standalone
The package is then shipped to the site, installed on a plant, usually with minimal field construction and with
foundation and connected to site utilities. or without facades. In a modular plant, equipment

138
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lnremarionalDi5tridEnergy Association. Allrights reserved.

modules are installed in a conventional building.

The following are key advantages of packaged plants:


oCosts tend to be lower than, or comparable to,
built-up plants, because
.vendors have already invested significantly in
design of optimized plant systems,
.fabrication labor can be used more efficiently The following are disadvantages of packaged plants:
oThe ability to integrate plant controls with the ETS
than in the field and
• volume procurement offers the opportunity control systems may be constrained.
for cost economies for some equipment and oArchitectural flexibility, including ability to minimize
components. plant site area, is constrained. The footprint of a
oSincethe modules can be fabricated in parallel with packaged plant is larger than for a multi-story built-
civil works, packaged plants can reduce construc- up plant.
tiontime, and revenue generation can startsooner. oThere are constraints on fitting standard modules
• Manufacturing occurs in controlled conditions into an oddly shaped plant or site.
where it is easier to achieve quality control. oThere can be potential challenges in creating cross-
oFabrication of the plant can proceed concurrently redundancy between chillers, towers and pumps.
with obtaining permits from the authorities. • Maintenance can be more difficult with compressed
o Packaged plant vendorstypicallyprovidesome type of plant configurations common in packaged plants.
oHistorically, packaged plants have put functionality
performance guarantee.
o Package and modular plants offer greater flexibility ahead of aesthetics, although vendors have signif-
compared to built-up plants, facilitating staged icantly upgraded facades to improve appearance.
addition of capacity to meet increasing customer oGenerally, packaged plants are designed around
demand. This has the beneficial effect of delaying electric centrifugal chillers using standard cooling
capital expenditures until they are needed. towers. Case-specific factors may require non-stan-
oSmalier packaged plants can be used as temporary dard design elements, such as engine-driven
plants for several years in advance of building a chillers, plants with seawater cooling towers or
full-scale plant. The packaged plant can then be once-through seawater heat rejection, or other
moved to the next development. technologies.
oAlternatively, packaged plants can be used as
temporary plants and then, if siting constraints
permit, be converted into permanent plants by
adding modules and facades.

139
DISTRICTCQOUNG BEST PRACTICE GUIDE
02008 International Dl5trict EnergyItisociation. All righ~ reserved.

10. Commissioning
Numerous definitions and opinions of commissioning the procurement and project delivery process. Because
exist, but ASHRAE's definition is especially noteworthy. the different major elements of a district cooling
ASHRAE defines commissioning as "a systematic system (plant, distribution, ETSs) are often procured in
process of ensuring that systems are designed, installed, separate packages, it is especially important that there
functionally tested and capable of being operated and be one entity that has the responsibility and authority
maintained to perform in conformity with design intent." to ensure that all elements are designed, installed and
operated as an integrated whole. To ASHRAE this entity
ASHRAE Guideline 0-2005 addresses the commission- is known as the commissioning authority (CA), but
ing process for an entire project, from initial concep- sometimes many of the same roles are discharged by
tion through operations. The process is organized as the owner's engineer (OE).
follows:
• Pre-design - Owner's Project Requirements (OPR)
are defined.
• Oesign - Based on the OPR, construction docu-
ments are prepared by the engineer.
• Construction - Based on the construction docu-
ments, bids are received. Equipment and systems
are installed, inspected, tested and placed into op-
eration to meet the OPR. Effective integrated commissioning of district cooling
• Occupancy and Operations - Starting at substantial systems is rarely achieved, with the result that the
completion, functional performance testing is district cooling provider's operations staff bear the
preformed and ongoing operations and mainte- burden of trying to make sure that all systems operate
nance are verified against the final OPR. effectively together, which may be difficult or impossi-
ble to achieve after the fact. Compressed schedules
Commissioning is frequently considered to focus on exacerbate this problem.
startup, testing, adjusting and balancing, and some
standards focus on these tasks. For example, the U.S. It is especially important for the commissioning process
National Environmental Balancing Bureau (NEBB) Stan- to address district cooling system design and perform-
dard emphasizes the performance of work identified in ance as it relates to delta T, energy use, available equip-
the following ASHRAE Construction and Occu- ment capacity and customer comfort. Chapter 5 details
pancy/Operations phases: metrics that may be used at the customer ETS to assess
• Testing, Adjusting and Balancing (TAB) - Traditional system performance at the interface with each
measuring and setting of balancing devices for customer. Performance metrics should also be provided
obtaining proper flows and performance. for the plant very early in the design and planning
• Field Installation Verification (FIV) - Are the equip- process. Tothe greatest extent possible, the CA must be
ment and system ready for startup? capable of broadly evaluating the chilled-water system,
• Operational Performance Testing (OPT) - Is the including details beyond the customer interface, to
equipment operating as intended? ensure that the chilled-water return temperature to the
• Functional Performance Testing (FPT)-Is the equip- plant meets or exceedssystem design at peak- and part-
ment operating as efficiently as intended? load conditions. It is equally important to ensure that the
supply-water temperature provided to customer buildings
Commissioning is much more than just these tasks. Test- is sufficient to meet contractual obligations and satisfy
ing, adjusting and balancing are a necessary first step be- customer cooling requirements. Poor delta T performance
fore dynamic operations are tested as a key part of the is a very common industry problem that has an adverse
commissioning process. However, in addition to making impact on equipment capacity and energy consumption
surethat all the individual equipment is installed correctly and may also affect customer comfort and chilled-water
and with the necessary safety and controls systems, com- revenue. The commissioning process should pay special
missioning focuses on ensuring that the entire system attention to this issue long before the system is in con-
works as designed through all conditions that will occur struction and operation.
during operations, including startup, part- and full-load,
shutdown and alarm conditions. Testing and balancing A project's implementation is driven by cost, time and
usually focuses on minimum and maximum conditions, quality. Constructionmanagerstypicallyconcentrate on the
whereas commissioning addresses sequence of equip- first two elements - cost and time - and commissioning
mentoperation and optimization of performance across authorities concentrate on the third element - quality.
a range of conditions.
The owner expresses the desired outcome through
Commissioning should be integrated into the design what ASHRAE calls the OPR and others call the Owner's
and construction processes and should be a key part of Requirements Document (ORD). Then it is the commis-

140
DISTRICT COOLING BEST PRACTICE GUIDE
102008 International District Energy A5sada~'Ot1. Ailrights reSlYW:d.

sioning authority's role to ensure that the owner's requirements can be achieved. The commissioning au-
requirements are achieved as the project is planned, thority updates the commissioning plan, prepares
designed, installed, tested, operated and maintained. checklists, witnesses tests and verifies that test reports
The CA brings value to the owner through focused are documented.
attention to quality, process and system performance
within the context of the district cooling provider'sbusi- It is important to require the contractor to provide a
nesscase. The CA should understand the nature of the comprehensive equipment list, full as-built drawings
district cooling business and the often complex and useful O&M manuals for all equipment and
relationships between customer load, capital invest- systems. For projects in the Middle East, oftentimes the
ment and annual operating expenses. O&M manuals supplied by the contractor are simply a
collection of vendor literature and not proper O&M
manuals, which makes it difficult for district cooling
system operating personnel to operate the district
cooling system efficiently.

Most of the testing and performance verification will


be completed during the construction phase. However,
full commissioning is not always possible until there is
As the design is developed, the CA develops commis- sufficient load to commission systems across an ade-
sioning process requirements for the construction quate range of loads. Also, sometimes initial commis-
documents, reviews essential portions of the specifica- sioning must take place using temporary generators
tions and drawings, defines training requirements and instead of grid power, resulting in incomplete commis-
prepares the scope and format for the Systems Manual. sioning. Consequently, re-commissioning must take
The Systems Manual is a comprehensive document that place once the proper conditions exist. Re-commis-
is focused on systems operation and thus will be an im- sioning throughout the plant's operating life will
portant tool during training aswell asongoing operations optimize system performance as equipment wears in
and maintenance.The Systems Manual goesbeyond the and will facilitate operator training.
compilation of operation and maintenance manuals typ-
ically collected by the construction contractor. A district cooling system represents a significant
investment, especially when life-cycle operating and
In the construction phase, the CA reviews essential maintenance expenses are included. These life-cycle
contractor submittals for compliance with the ORD and costs can be minimized through thoughtful planning,
verifies that systems are installed such that the owner's intelligent design and thorough commissioning.

141
DISTRICT COOUNG BEST PRACTICE GUIDE
C2008/nt.emaUonal tema EnergyAssociarion. Allrigh!5 reserved.

Appendix A - Abbreviations and Definitions


The list has been alphabetized by abbreviations, then check valve
by terms where abbreviations are not applicable. A valve that normally allows fluid to flow through it in
only one direction.
AISI
American Iron and Steel Institute CHP
combined heat and power (sometimes called
ARI "cogeneration")
Air-Conditioning and Refrigeration Institute A general term describing a number of energy tech-
nology configurations that produce both electricity and
ARTI thermal energy from one fuel source in an efficient
Air-Conditioning and Refrigeration TechnologyInstitute process; or a facility that recovers thermal energy for
productive use that is normally wasted in power-only
ASHRAE generating plants.
American Society of Heating, Refrigeration and
Air-Conditioning Engineers CHW
chilled water
ASME
American Society of Mechanical Engineers CHWRT
chilled-water return temperature
standard atmosphere
A unit of pressure equal to 101.325 kPa (14.696 psi) CHWST
chilled-water supply temperature
balancing valve
A valve used in a piping system for controlling fluid C02
flow; not usually used to shut off the flow. carbon dioxide
The most common greenhouse gas, emitted asa result
bar of combustion of fossil fuels.
A unit of pressure equal to 100 kPa (14.50 psi).
combined cyde
BAS A type of power plant that employs more than one
building automation system thermodynamic cycle, e.g., combined use of a com-
bustion turbine driving a generator to produce elec-
BOE tricity with a steam turbine generator driven with steam
barrel of oil equivalent produced to produce additional electricity with the hot
A unit of energy based on the approximate energy exhaust gases from the combustion turbine.
released by burning one barrel of crude oil, about
6.1 million KJ (5.8 million Btu). COP
coefficient of performance
Btu The ratio of useful energy output to energy input in an
British thermal unit energy conversion device.
A unit of energy approximately equal to the heat
required to raise a pound of water 1 degree F. crossover bridge (or decoupler)
A branch pipe connection between supply and return
butterfly valve that is intended to hydraulically decouple two inde-
A type of valve typically used for isolation. The pendently pumped water loops.
"butterfly" is a metal disc mounted on a rod.
CW
bypass valve condenser water
A valve that controls flow via a bypass pipe typically
between the supplyand return of a chilled-water system. DB
dry bulb
C
degree Celsius dBA
decibel
CFC Unit measurement of sound pressure level using the
chlorofluorocarbon "A" weighting filter.
A class of refrigerants for which production has been
banned worldwide due to their destructive impact on
stratospheric ozone.
A-1
DISTRICT COQUNGBEST PRACTICE GUIDE
02008 Intemalional oana Enef9Y A5wcia~on. Ail rightsfe:.erved.

DBB EFLH
designlbid/build equivalent full-load hours
A project delivery process in which a consulting engi- Ratio of total annual energy consumption to peak
neer prepares a detailed design including plans and hourly demand.
specifications that are put out to bid to qualified con-
tractors. EPe
eng ineer/procu relconstruct
De A project delivery process in which the design and con-
direct current struction are contracted for with a single entity.

ceres equalizer piping


district cooling instrumentation and controls system Piping connecting basins of multiple cooling towers or
cells to maintain a common water level.
DDe
direct digital controller ER
equity ratio
Des Ratio of equity to total capital.
distributed control system
ETS
debt ratio energy transfer station
Ratio of debt to total capital. The thermal energy transfer interface between the
district cooling provider and each customer, typically
decoupled consisting of metering, valves, piping, controls and in
Hydraulically independent. the case of indirect connections, a heat exchanger.

decoupler (or crossover bridge) expansion tank


A branch connection between supply and return that is A tank used in a closed-water system to accommodate
intended to hydraulically decouple two independently water volume changes due to thermal expansion and
pumped water loops. contraction.

delta P F
The pressure difference between supply and return. degree Fahrenheit

delta T FIV
The temperature difference between supply and return. field installation verification

DER FPT
debt-to-equity ratio functional performance testing

desalination FRP
Any of several processes that remove excess salt and fiberglass-reinforced plastic
other minerals from water.
fps
DIR feet per second
debt interest rate
gpm
DR gallons per minute
dimension ratio
The ratio of HDPE pipe outside diameter to pipe GHG
wall thickness. greenhouse gas
Gases present in the earth's atmosphere that warm
EeWT near-surface global temperatures through the green-
entering condenser-water temperature house effect.

EEMS globe valve


expert energy management systems A type of valve used for regulating flow in a pipeline
consisting of a movable disk-type element and a
EEPROM stationary ring seat in a generally spherical body.
electrically erasable programmable read-only memory
A-2
DISTRICT COOUNG BEST PRACTICE GUIDE
02008lnrema~'0flil1 Di5tricrEnergy AssodaMn.Ail nghf5 reS€M'd.

GRP HV
glass-reinforced plastic high voltage

GWP HVAC
global warming potential heating, ventilation and air conditioning
A measure of how much a given mass of greenhouse
gas is estimated to contribute to global warming. It is impeller
a relative scale that compares the gas in question to The rotating element in centrifugal pumps and
that of the same mass of carbon dioxide (whose GWP compressors that transfers energy from the motor to
is by definition 1). A GWP is calculated over a specific the fluid to create pressure head.
time interval. In this document the GWP figures reflect
the commonly used tuo-year interval. 1/0
input/output
HCFC
hyd rochlorofluorocarbon IEEE
A commonly used class of refrigerants. Institute of Electrical and Electronics Engineers

HDA I&C
historical data acquisition instrumentation and controls

heat rate IDEA


A measure of how efficiently a power generator uses International District Energy Association
fuel, expressed as the number of British thermal units
of fuel required to produce a kilowatt-hour of electricity, ISO
International Organization for Standardization
hermetic drive
A chiller arrangement in which the motor is contained isolation valves
within the same housing as the compressor and is in Valves that allow a piece of equipment to be isolated
direct contact with the refrigerant. from the rest of the system to facilitate maintenance,
equipment removal and shutdown.
HOPE
high-density polyethylene IT
information technology
HEX
heat exchanger jacket water
A device for transferring thermal energy between two Fluid circulated within a reciprocating engine for the
hydraulically separated systems. purpose of heat rejection.

HFC kPa
hydrofluorocarbon kilopascal
A commonly used class of refrigerants.
kVA
HMI kilovolt ampere
human-machine interface
kW
hot tapping kilowatt
An operation in which a branch connection is made to
a pipe main while the pipe remains in service or "hot." kWh
kilowatt-hour
hp
horsepower LCWT
leaving condenser-water temperature
HR5G
heat-recovery steam generator LNG
A boiler producing steam from recovered heat; often liquefied natural gas
used in a combined-cycle configuration to effectively
utilize thermal energy for power production or addi- m
tional heat uses. meter

A-3
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008Int;emalionaIDistrictEnergyA5wda~.on.Al!ngh~ reserved.

mADC ODP
milliamps DC ozone depletion potential
The relative amount of degradation to the ozone layer
mbar a given chemical can cause, with trichlorofluo-
millibar romethane (R-l1) being fixed at an ODP of 1.0.

MED OIP
multi-effect distillation operator interface terminal

micro-tunneling OLE
A trench less construction method for installing object linking and embedding
pipelines. A technology that supports the linking and embedding
of objects from one application seamlessly into another
MID meter application.
An electronic flow meter that measuresflow by induc-
tion of voltage in a conductor moving in a magnetic OPC
field. These devices are often called "magmeters." OLE for processcontrol
A standard that specifies communication of real-time
mm plant data between devices from different manufac-
millimeter turers.

MMBtu open-drive motor


million British thermal units A motor arrangement in which the motor is outside the
compressor housing.
MMBtu/hr
million British thermal units per hour OPR
Owner's Project Requirements
MSF
multi-stage flash distillation OPT
operational performance testing
MW
megawatt ORO
Owner's Requirements Document
MWh Documents establishing an owner's requirements for
megawatt-hour the purpose of soliciting engineer/procure/construct
bids.
mps
meters per second OSHA
Occupational Safety and Health Administration
I'S/cm
micro-Siemens per centimeter ozone-depleting refrigerant
A unit of specific conductivity. Refrigerants that contribute to depletion of the stratos-
pheric ozone layer.
NEBB
National Environmental Balancing Bureau part load
Operation of equipment at lessthan 100% load.
NFPA
National Fire Protection Agency PC
personal computer
NPV
net present value PE 80 or PE 100
Material classes for the resins used to construct
O&M polyethylene piping products.
operation and maintenance
PEX
cross-linked polyethylene

A-4
DISTRICT COOUNG BEST PRACTICE GUIDE
e2008lnlemationalDistri<:t EnetgyAswd"tiOll.All rightsreserved.

PLC 51
programmable logic controller Standard International

pneumatic control solenoid


Control devices that utilize compressed air signals to A type of actuator that operates in a two-position
control inputs and outputs. (open/closed) mode.

PPE SOP
personal protective equipment standard operating procedure

ppm standard atmosphere


parts per million A unit of pressure equal to 101.325 kPa (14.696 psi).
Denotes one part per 1,000,000 parts and a value of
1 x 10-6. T&D
transmission and distribution
provider
District cooling provider. An entity providing district TAB
cooling services, usually as a commercial enterprise. testing, adjusting and balancing

psi TCP/IP
pound per square inch transmission control protocol/internet protocol
A unit of pressure equal to 68.95 millibar. A protocol for communication between computers
used asa standard for transmitting data over networks
psig and as the basis for standard Internet protocols.
pounds per square inch gauge
Pressure above standard atmospheric pressure, TEAAC
measured in psi. totally enclosed air-to-air-cooled

PVC TEFC
polyvinyl chloride totally enclosed fan-cooled

RAM TES
random access memory thermal energy storage

RF TEWAC
radio frequency totally enclosed water-to-air-cooled

RO three-way valve
reverse osmosis A valve having either a single inlet and two outlets or
two inlets and a single outlet.
ROE
return on equity ton
A measure of cooling capacity or demand equal to
ROI removal of 12,000 8ritish thermal units (Btu) per hour;
return on investment sometimes the abbreviation TR is used, for "tons
refrigeration. "
RTTMS
real-time thermal modeling and simulation ton-hr
A measure of cooling energy consumption equal to one
SCADA ton over a one-hour period.
supervisory control and data acquisition
TSE
S/cm treated sewage effluent
Siemensper centimeter
A unit of specific conductivity. turbine meter
A device that measures the rate of flow in a pipe via a
shadow prices rotor that spins as the media passes.
An assumption of C02 emissions cost for the purpose
of comparing options.
A-5
DISTRICT COOLINGBEST PRACTICE GUIDE
01008 International tssuta Energy As5Odation. N/ nght>re:;ervro.

turndown VDC
The ratio between maximum and minimum flow or voltage DC
capacity for the controllable operating range of a piece
of equipment. VGD
variable geometry diffusers
two-way valve
A valve having two ports that can be open or closed, VSD
used for controlling flow to equipment. variable-speed drive
A system for controlling the rotational speed of
ultrasonic meter powered machinery(e.g., pump or fan) by controlling the
A device that measures flow by measuring the time frequency of the electrical power supplied to the ma-
between the transmission and reception of ultrasonic chinery; also known as variable-frequency drive (VFD).
signals over an exactly known distance.
WACC
UPS system weighted average cost of capital
un interruptible power supply system
A power supply system that includes a battery to main- WB
tain power in the eventof a poweroutage. wet bulb

US$ or USD V-strainer


United States dollar Filtration device that retains solids when a liquid passes
through it.
valve authority
The ratio between pressure drop across the control ZLD
valve and the total pressure drop across the circuit. zero liquid discharge

VAV
variable air volume

A-6
DISTRICT COOUNGBEST PRACTICE GUIDE
C2008lnlem<llional District EnergyAssodali'Oll. Allrightsreserved.

Appendix B - Conversion Factors


The following conversion factors can be used to convert between English (lP) and metric (51) units.

Multiply by to obtain
bar 100 kilopascal (kPa)
barrel [petroleum) 159.0 liter (I)
barrel [petroleum] 42 gallon (g)
Btu 1.055 kilojoule (kJ)
Btu 0.0002931 kilowatt-hour (kWh)
Btu/hr 0.2928 watt (W)
cubic feet (ft3; cu ft) 0.0283 cubic meter (m 3 ; cu m)
cubic feet/minute (dm) 0.4719 literlsecond (Ips; 115)
feet (ft) 0.3048 meter (m)
feet (ft) 304.8 millimeters (mm)
ft2/ton 0.09290 m2/ton
feet of water (ft) [head] 2.989 kilopascal (kPa)
feet/minute (fpm) 0.00508 meterlsecond (m/s)
feet/second (fps; ft/s) 0.3048 meterlsecond (m/s)
gallon (gal) [US] 0.003785 cubic meter (m 3 ; cu m)
gallon (gal) [US] 3.785 liter (I)
gallons/minute (gpm) 0.06309 liters/second (1/5)
horsepower (hp) 0.7457 kilowatt (kW)
inch (in) 25.4 millimeter (mm)
inch (in) 1000 mil
mile (mi) 1.609 kilometer (km)
mile/hour (mph) 1.609 kilometer/hour (km/h)
millibar (mB) 0.1 kilopascal (kPa)
ounce (oz) 28.35 gram (g)
pound (Ib) [mass] 0.4536 kilogram (kg)
Ib/in 2 (psi) 0.06895 bar
Ib/in 2 (psi) 2.307 feet of water (It) [head]
Ib/in 2 (psi) 6.895 kilopascal (kPa)
psi/l 00 ft 226.2 Pascal/meter (Palm)
square feet (ft2 ; sq ft) 0.09290 square meter (m 2)
therm 105.5 megajoule (MJ)
ton [refrigeration] 3.516 kiIowatts (kW)
ton [refrigeration] 12,000 Btu/hr
ton-hr 3.516 kilowatt-hour (kWh)
ton-hr 12,000 Btu
yard (yd) 0.9144 meter (m)
to obtain by Divide

NOTE; All approximate conversion factors above are presented with four significant digits.

Other useful conversions:


degree C ~ (degree F - 32) x 0.5556

degree F ~ (degree C x 1.8) + 32


kW/ton ~ 3.5161 coefficient 01 performance (COP)

Ib/in2 absolute (psia) ~ psig + 14.70

Ib/in' gauge (psig) ~ psia - 14.70

one year ~ 8760 hr

B-1
DISTRICT COOLING BEST PRAcrJCE GUIDE
C2008 International District Energy Association. Alltightsreserved.

Appendix C - Arc Flash


This appendix has been contributed by John pfeiffer' increasing in intensity as the pressure wave develops.
and is usedwith permission. ©Copyright2008. pfeiffer The challenge is to sensethe arc fault current and shut
Engineering Co. Inc. ALLRIGHTS RESERVED. off the voltage in a timely manner before it develops
into a serious arc flash condition.
Arc Flash: Do you understand the dangers?
Arc flash is the result of a rapid release of energy due Why the Focus on Arc Flash?
to an arcing fault between a phase bus bar and another In the early 1980s a paper by Ralph Lee, "The Other
phase bus bar, neutral or a ground. During an arc fault, Electrical Hazard: Electric Arc Blast Burns," was
the air is the conductor. Arc faults are generally limited published in the IEEE Transactions on Industrial
to systemswhere the bus voltage is in excess of 120 V. Applications. The effect of this paper was to realize the
need to protect people from the hazards of arc flash.
Four separate industry standards pertain to the
prevention of arc flash incidents:
• OSHA 29 Code of Federal Regulations (CFR) Part
1910 Subpart S
• NFPA 70-2002 National Electrical Code
• NFPA 70E-2000 Standard for Electrical Safety
Requirements for Employee Workplaces
• IEEE Standard 1584-2002 Guide for Performing Arc
Flash Hazard Calculations

Compliance with the U.S. Department of Labor's


Occupational Safety and Health Administration (OSHA)
involves adherence to a six-point plan:
1. A facility must provide, and be able to demonstrate,
a safety program with defined responsibilities.
2. Calculations for the degree of arc flash hazard.
3. Correct personal protective equipment for workers.
4. Training for workers on the hazards of arc flash.
5. Appropriate tools for safe working.
6. Warning labels on equipment. Note that the
labels are provided by the equipment owners, not
the manufacturers. It is expected that the next
Lower voltage levels normally will not sustain an arc. revision of the National Electric Code will require
An arc fault is similar to the arc obtained during electric that the labels contain the equipment's flash
welding; the fault has to be manually started by some- protection boundary, its incident energy level, and
thing creating the path of conduction or a failure such the required personal protective equipment.
as a breakdown in insulation.
Companies will be cited and fined for not complying
The causeof the short normally burns away during the with these standards.
initial flash, and the arc fault is then sustained by the
establishment of a highly conductive plasma. The Personal Protective Equipment
plasma will conduct as much energy as is available and Categories of personal protective equipment (PPE) as
is only limited by the impedance of the arc. This described in NFPA 70E are:
massive energy dischargeburns the bus bars,vaporizing
the copper and thus causing an explosive volumetric
increase - the arc blast, conservatively estimated as an Category Callem' Clothing
expansion of 40,000 to 1. This fiery explosion devastates
0 1.2 Untreated cotton
everything in its path, creating deadly shrapnel as it
1 5 Flame retardant (FR) shirt and
dissipates.
FR pants
The arcfault current is usually much less than the available 2 8 Cotton underwear, FR shirt and
bolted fault current and below the rating of circuit FR pants
breakers. Unless these devices have been selected to 3 25 Cotton underwear, FR shirt
handle the arc fault condition, they will not trip, and FR pants and FR coveralls
the full force of an arc flash will occur. The electrical 4 40 Cotton underwear, FR shirt,
equation for energy is volts x current x time. The FR pants and double-layer
transition from arc fault to arc flash takes a finite time, switchinq coat and pants

c-i
DISTRICT COOLINGBEST PRACTICE GUIDE
e2008 International District EnergyAssociation. AJInghts reserved.

Callem' are the units of incident energy that the PPE is adequately braced to handle the available fault
can withstand. Note that a hard hat with full-face shield current. Finally, the bolted fault currents are converted
and the appropriate gloves are required also. into arc fault currents for additional analysis.

Steps Required for a Flash Hazard Analysis Coordination Study


To perform an arcflash hazard analysis, data is collected A coordination study is the examination of the electrical
about the facility's power distribution system. The data system and available documentation with the goal of
includes the arrangement of components on a one-line ensuring thatover-current protection devices are properly
drawing with nameplate specifications of every device. designed and coordinated. Over-current protective
Also required are details of the lengths and cross- devices are rated, selected and adjusted so only the
section area of all cables. The utility should be fault- current-carrying device nearestthe fault opens to
contacted for information including the minimum and isolate a faulted circuit from the system. This permits
maximum fault currents that can be expected at the the rest of the system to remain in operation, providing
entrance to the facility. Once the data has been maximum service continuity. The study consists of time-
collected, a short-circuit analysis should be performed, current coordination curves that illustrate coordination
followed by a coordination study. The resultant data among the devices shown on the one-line diagram.
can then be fed into the equations described by either Note that protective devices are set or adjusted so
NFPA 70E-2000 or IEEE Standard 1584-2002. These pickup currents and operating times are short but
equations will produce the necessary flash protection
boundary distances and incident energy to determine
the minimum PPE requirement.

Flash Hazard Analysis - A New Approach


Once the data is prepared and a flash hazard analysis
has been performed, most likely it will be discovered
that Category 4 PPE will be required in most places.This
is most unfortunate as this type of PPE is very unwieldy
and could be costly in terms of time taken to perform
work and the potential for mistakes. Prior to the new
arc flash regulations, coordination studies were
targeted at reliability with all settings adjusted toward
the high side. Compliance with the new arc flash The above figure isa person in a full Category 4 suit. This
regulations means that not only does the coordination suit will provide the necessary protection, but it is
study need to be more accurate but it also needs to cumbersome to work in, ishot and providespoor visibility.
take into account the fact that the arc fault current is The suits will make many tasks very difficult, if not
impossible, to perform. Because of their restrictions to
less than the bolted fault current.
vision and movement, they may even make some tasks
more dangerous. There are definitely times when this
The data can be used to perform a sensitivity study to type of protection is both necessary and required, but
adjust breaker/fuse characteristics to lower the PPE being overly conservative will result in excessive stress
requirement. Toachieve this goal, the existing breakers for workers and require an unacceptably long time to
may need to be replaced, generally by more modern make repairs or adjustments.
counterparts. Old breakers have relatively slow reaction
times and will trip at too high a current. To limit the sufficient to override system transient overloads, such
flash hazard, the breakers are adjusted to trip earlier as inrush currents experienced when energizing
than before. It is expected that the outcome of this transformers or starting motors.
sensitivity study, when implemented, will result in most
Category 4 PPE requirements being decreased to The Problems
Category 1 or 2. Once the hazards associated with arc flash are under-
stood, the challenge becomes to eliminate or at least
Short-Circuit Study reduce them. The following section discusses some of
The short-circuit study is based on a review of one-line the problems and subtleties involved in implementing
drawings. The drawings must be created if they do not corrective action.
exist and field-verified if they do. Maximum available
fault current is calculated at each significant point in There are several problems in dealing with arc flash
the system. Each interrupting protective device is then analysis:
analyzed to determine whether it is appropriately
designed and sized to interrupt the circuit in the event 1. Being overly conservative inthe short-circuit analysis
of a bolted type of short circuit. Next, the associated may result in the required PPE category being set
equipment must be reviewed to insure that the bus bar at a level higher than necessary.

C-2
DISTRICT COOUNG BEST PRACTICE GUIDE
02008 /ntema~Onal DistrictEnergy A550da~'on. Allright!; re~.

2.Relying on quick analysis methods can result in Arc fault current (lfe) is derived from the available
exposure to unexpeded liabilities. Therearea number bolted short-circuit or fault current (I,,) and is always
of shortcuts being offered by individuals and substantially less than its corresponding short-circuit
companies that can have disastrous results. current. The Instituteof Electrical and Eledronics Engineers
Companies should be sure their methods will stand (IEEE) has established a formula for calculating (esti-
up to analysis and peer review. Cure-all solutions mating) the (lfe), and they provide a spreadsheet. The
are being promoted, such as the installation of following areexamples of results from using theirformula:
current-limiting fuses. Many firms rightfully believe
in the use of fuses, particularly current-limiting
types, but as will be shown below, they are not Bolted Fault Current Arc Fault Current
always the answer. They are definitely not a quick-
@480V
fix solution. 10 kA = 6.56 kA
20 kA = 11.85 kA
3. Being overly conservative when performing a 30 kA = 16.76kA
short-circuit analysis results in the misapplication
40 kA = 21.43 kA
of circuit protection equipment, which in turn has
the consequence of calculated arc flash levels
being higher than they actually are.
What is now important is to obtain?
1. The maximum expected (worse case) bolted short-
4. The calculated bolted fault or short-circuit current circuit current.
is a worst-case calculation that assumes very low 2. The minimum and maximum voltage to the facility.
short-circuit impedance. A bolted short-circuit 3. The minimum expected short-circuit current.
connection is based upon two conductors being
"bolted" together to form the short. In reality, Also needed are definitions of the operating modes of
most short circuits are less than ideal, resulting in the facility, such as
fault currents that are less than the calculated • the minimum and maximum motorloads expected
bolted short-circuit condition. during normal operation and off-hour operation;
and
5. On the other hand, the arc fault should be a more • variation in the sourcesof supply to the plant, such
predictable occurrence. The arc fault calculations as- as alternate feeders or cogeneration.
sume that there is a physical gap between conduc-
tors that was bridged by something resulting in the The data from the public utility and the determination
arc formation. Once the arc is formed and plasma is of the facility's modes of operation should be converted
produced,the arccurrent should closelyapproximate into the maximum and minimum arc fault current at
the calculated fault levels. The arc fault calculations various locations in the plant. These results are applied
are an approximation based upon research and test- to protective device coordination studies, where the
ing similarto the short-circuit analysis methods. They protective devices are evaluated, and adjusted if
are not exact, and therefore care needs to be taken necessary, allowing the proper PPE categories to be de-
when usingthe results. termined.

Solution The curveon the next page illustratesthe point.


The solution is to first perform, as accurately as practical,
a short-circuit analysis. The goal for most people This figure shows the coordination curve for the sec-
performing a short-circuit analysis has always been to ondary of a 1,000- kVA 480 V transformer. The curve
erron the conservative side. For example, whena cable shows two types of secondary protection, a fuse and a
length was needed, it is the practice to always use the circuit breaker, each selected based on the National
shortest practical value, which would result in higher Electrical Code requirements. The fuse is a KRP-C
calculated short-circuit current values. When the pub- 1600A and the circuit breaker is a Square D Master-
lic utility is contacted, it is the practice to only ask for pack breaker with a Digitrip.
the worse case short-circuit value.
All transformers limit the amount of fault current that
The overall result is that the short-circuit values are can pass through the transformer. This is a function of
always calculated on the high side. When doing a short- the transformer's impedance. The coordination curve
circuit analysis for sizing the interrupting capability of shows a line for the (I,,), the maximum short-circuit
protection equipment, this is the best practice. It is not current that can passthrough this transformer (24,056
the best practice, however, when evaluating equipment amps). The (lsc) value used assumes that there actually
for arc faults and establishing PPE requirements. This is is sufficient current available at the primary to provide
anextremely significant, and quite nonintuitive, situation. 24,056 amps on the secondary.

(-3
DISTRICT COOLING BEST PRACTICE GUIDE
e2008lntemab'ooal ()j~lJiet Energy Assodalion. All rights reserwd.


CURRENT INAMPERES
point for the fuse, which is approxi-
10
1000 1000 mately 28,000 amps. Thus, there is no
current-limit effect from using the fuse.
Current-limiting fuses often do provide
additional protection, and they are very
good devices, but they must be applied
100 100 properly. In this example, the circuit
breaker provides the best protection.

In this example, it can also be assumed


that the fuse and the circuit breaker
10 FUS 10 are at the main of a facility and that
BUSSMANN
the facility is served by a much larger
KR?-C, 600V CIIIU L
Trlp1600A transformer where the worse-case
bolted short-circuit current as reported
CIRCUIT BREAKE by the utility is 60,000 amps. Under
1 ~~~~NWLF,6.OPIH
this condition, the arc fault current
Trip1S00A
setting, Ph.. e would be 30,300 amps. In this case,
LTPlJILTD(AOA-1.O x S) 1 (1S00A);4
STPU (1.5-1Ox LTPU) 3 (4800A)
ShortCircuit Current
the fuse would open in quarter cycle
STD (INST-<I.4) INST(I'2 TOld)
INST(2.15x 5) 10 (16000.0.) and would limit the fault current.

0.10 The Emb would equal 1.15 cal/crn-,


which falls under a Category 0 PPE.

The figure on the next page involves a


fuse and a circuit breaker protecting a
0.01 0.D1 125 HPmotor. The fuse isa LLS-RK 200 A
0.5 10
and the circuit breaker is a Square D
Masterpackwith an electronictrip. There
are three arc fault currentsanalyzed.
TCC Name; Test CurrentScale x 100 Reference Voltage: 480
onejne:
September 8, 2008 2:01 PM
Prepazred By: PfeifferEngineerlng Co., Inc.Louisville, KY Point 1
• Arc fault current 1600 amps
• Bolted fault current 3200 amps
Based on the IEEE formula, the calculated arc fault
current (lfe) is 11,701 amps. Using these two currents • Results:
• Circuit breaker clears in 0.06 seconds 4.57
and the coordination curve, the time the circuit breaker
and the fuse will take to clear the fault can be estimated.
callcm' PPE Category 2
• Fuse clears in 0.02 seconds 1.45 callcm' PPE
Category 1
Bolted Fault Condition
• Fuse clears in 0.02 seconds Point 2
• Circuit breaker clears in 0.08 seconds • Arc fault current 1400 amps
Arc Fault Condition • Bolted fault current 2400 amps
• Fuse clears in 0.90 seconds • Results:
• Circuit breaker clears in 0.08 seconds • Circuit breaker clears in 0.06 seconds 4.57
callcm' PPE Category 2
From these current levels and clearing times, the PPE • Fuse clears in 0.1 seconds 7.62 callcm' PPE
category can be determined. Category 2
Point 3
Emb (maximum in cubic box incident energy) • Arc fault current 1100 amps
• Fuse 36 callcm' Category 4 PPE • Bolted fault current 1600 amps
• Circuit breaker 2.5 cal!em' Category 1 PPE • Results:
• Circuit breaker clears in 0.06 seconds 4.78
Clearly, in this example the circuit breaker outperforms callcm' PPE Category 2
the current-limiting fuse resulting ina minimal "worker- • Fuse clears in 1.0 seconds 79.8 call em' PPE
friendly" PPE requirement. Category >4

In the above example, both the arc fault current and At an arc fault current of 4000 amps the fuse will begin
the bolted fault current are less than the current-limiting to current limit and will open the circuit in quarter cycle,

C-4
DISTRICT COOLING BEST PRACTICE GUIDE
C2008lntemaUonal osuta Energy A5,:;ooaUon, All righrs ~.

CURRE~TINAMPERES
only 2.1 cal/em", however, many busses
1000 had quite high incident energy levels? :
1000: : ~
.24% of busses over 8 cal/em'
PPE Category 2
• 12 % of busses over 40 cal/em'
PPE Category 4
100 .5% of busses over 85 cal/ern'
deadly - no protection
• 1% of busses over 205 cal/ern"
deadly - no protection
Risks to personnel indude-'
10 =='-__" 10 • burns,
• damaging sound levels and
• high pressure (720 Iblft' eardrums
rupture; 1728 to 2160 Ib/ft'lung
damage).

Conclusions
1. Arc fault analysis is actually risk
management. There are basicallythree
SQUARED
Masklrpacl, NW LF.6.0PIH choices:
0.10 ~~~~ha'B '-~-'-l>
LTPUILTO (AO.4-1.0~ S) 0.6 (15QA); II 1- • Be very conservative and require
STPU (1.5.10~ LTPU) 6 (12OOA)
STO(INST'{)A) INST(lA2 T Oul) PPE Category 4, in most cases
INST (2.1S~ S}6 (lSOOA)
resulting in higher maintenance
cost.
• Do nothing and suffer the
0.01 0.01
0.5 10 ~ ~
consequences (pay later).
• Perform the necessary analysis and
make adjustments to reduce the
TCC Name; Motor Current Seale x 10 Reference Voltage: 480 arc fault conditions resulting in
Oneline:
September 8, 2008 2;02 PM reduced PPE requirements.
Prepazred By:PfeifferEngineering Co., Inc.Louisville. KY

2. A reduction in bolted fault current


and thus a reduction in arc fault current can actually
reducing the PPE category to O. result in a worse situation. Inthemotor example above,
an arc fault current reduction from 4000 amps to 1800
The three points analyzed show that a relatively small amps resulted in an increase in arc fault energy from
change in calculated bolted fault current has a major 0.6 cal/cm' to 78.8 callcm'. This is exactly the opposite
effect on the calculated arc fault current. This situation of what one would expect before doing the math. In
could easily lead to the misapplication of circuit terms of the above example coordination curves, this
protection equipment or inappropriate adjustment of occurs because the arc fault current moves from the
same. It should also be noted that asthe calculated arc instantaneous portion at the bottom of the coordination
fault current is reduced, the clearing time increases, curve to a point higher up, incurring a the time delay
resulting in the incident energy level increasing and before the device trips.
thus the PPE requirement increasing.
3. Overly conservative short-circuit analysiswill result in
In reality, the arc current is primarily affected by facility bolted short-circuit numbers that may well result in the
operating conditions, i.e., motor contribution and misapplication of circuit protection equipment.
changes in the fault current coming from the utility. The
examples illustrate that the accuracy required when 4. It is very important to obtain the minimum available
calculating short currents has to be improved over short-circuit current as well as the maximum short-
traditional methods. Both reliability and arc fault circuit current from the electricutility.Voltagefluctuations
conditions must now be considered when performing in the plant supplyshould be considered when developing
coordination studies. the short-circuit calculations. The arc fault calculations
need to be evaluated at more than just the worst-case
The Risk and the minimum-case conditions. In the example
In a study of 33 plants with 4892 busses or switch above, a reduction in the arc fault current actually
points under 600 V, the median incident energy was resulted in worse conditions. This represents a subtle,
(-5
DISTRICT COOUNG BEST PRACTICE GUIDE
C2OO8lntemarional DistrictEnergy A5soc!ilrion, All nghrsreserved.

but extremely significant, change in the methodology


of short-circuit analysis.

5. Apart from the fines, nominal compliance with the


regulations will cause workers to have to wear
cumbersome PPE. This will result in little or no
high-voltage maintenance being performed, eventually
compromising safety, equipment operation and
ultimately productivity. Arc flash isa riskmanagement issue.

1 "Arc Flash: Do You Understand the Dangers" ©Copyright


2008. Pfeiffer Engineering Inc. All rights reserved. John Pfeiffer,
president, Pfeiffer Engineering Co.Inc., www.pfeiffereng.com.
2 "A Summary of Arc-flash Hazard Calculations," D.R. Doan
& R.A. Sweigart.
3 "Arcing Flash/Blast Review with Safety Suggestions for
Design and Maintenance." TimCrnko & Steve Dyrnes.

(-6
DISTRICT COOLING BEST PRACTICE GUIDE
C2008 !nlernil~'onal DlillictEnergy AsIDdatioo. Ailrightsreservro.

Your comments are welcomed!

The authors and contributors of the District Cooling Best Practice Guide have made
their best effort to be accurate and inclusive, but in the end, some items may
inadvertently contain errors and/or there are additional topics that may be of interest
to you. IDEA welcomes your comments or notices of errors or omissions you deem
important. Please email us at bpg.idea@districtenergy.org with detailed information
on your comments, including the page number and location of any errors, plus your
suggestions for additional content for consideration for the Second Edition.

Along with your comments, please be sure to include your complete contact
information, as listed below, so IDEAstaff can contact you.

Name
Title
Organization
Mailing Address [street, city, state/province (asapplicable), country]
Phone (office and mobile)
Email address

Thank you for your interest and input.

INTERNATIONAL
DISTRICf ENERGY
• ASSOCIATION
24 Lyman Street, Suite 230
Westborough, MA 01581 USA
+ 1 508-366-9339 phone
+1 508-366-0019 fax
www.districtenergy.org

Anda mungkin juga menyukai