Anda di halaman 1dari 16

Electrical Power and Energy Systems 105 (2019) 454–469

Contents lists available at ScienceDirect

Electrical Power and Energy Systems


journal homepage: www.elsevier.com/locate/ijepes

A pilot-based distance protection scheme for meshed distribution systems T


with distributed generation

Aristotelis M. Tsimtsiosa, George N. Korresb, Vassilis C. Nikolaidisa,
a
Department of Electrical and Computer Engineering, Democritus University of Thrace, Xanthi 67100, Greece
b
School of Electrical and Computer Engineering, National Technical University of Athens, Iroon Polytechniou 9, 15780 Athens, Greece

A R T I C LE I N FO A B S T R A C T

Keywords: This paper proposes a pilot-based distance protection scheme for meshed distribution systems with a high pe-
Distance protection netration of distributed generation. The proposed scheme assumes distance relays installed at the opponent ends
Distributed generation of each main line segment. A forward distance element is enabled in each relay to protect the main line segment,
Meshed distribution system while, a reverse distance element is enabled in each relay for protecting adjacent buses and laterals. The relays
Pilot protection
protecting a main line segment or a bus/lateral communicate in a permissive logic, ensuring protection sensi-
tivity and security at the same time. The scheme provides efficient primary and backup protection against faults
of any type, even with a considerable fault resistance, and under weak-infeed conditions. It is also appropriate
for both the grid-connected and the islanded mode of system operation. Coordination of the distance protection
scheme with the lateral protection means is also addressed. Existing numerical distance relay technology is
considered, to enhance the applicability of the proposed scheme. Offline setting of the distance relays is required,
which has to be performed once. Only one setting group is ultimately extracted for each relay, suitable for
different fault/system conditions, avoiding the need for adaptive protection techniques. The proposed scheme is
applied to a test meshed distribution system and conclusions are drawn. Comparison with directional over-
current and differential protection shows the advantages of the designed distance-based protection scheme.

1. Introduction operators (DSOs) and DG producers [3]. In fact, such multi-relay


communication-assisted protection schemes have been considered for
The integration of distributed generation (DG) into distribution real-world applications, even for looped distribution systems without
systems imposes the reconsideration of conventional overcurrent pro- DG [4,5], to enhance their reliability.
tection techniques, due to several issues encountered under the pre- So far, multi-relay schemes using directional overcurrent relays
sence of DG [1]. This is further necessitated by the prospect of oper- have been mainly considered in the literature as a solution for looped/
ating distribution networks in a looped/meshed configuration, which meshed distribution systems. Within this context, optimization algo-
aims to enhance their reliability, but also to improve their voltage rithms are a promising tool for setting directional overcurrent relays
profile, to reduce power losses, and to increase their DG hosting ca- protecting such networks [6–9]. Communication-based adaptive di-
pacity [2]. rectional overcurrent protection is applied to deal either with DG-
In order to maximize the reliability of distribution networks, which connection and system-configuration changes [10,11], or with the
is the main purpose of looped/meshed operation, this concept requires transition from the grid-connected to the islanded mode of system op-
the installation of circuit breakers, operated by relays, at both ends of eration [11]. Pilot-based directional overcurrent protection schemes
each line segment, and, usually, the use of communication means to could also be applicable to actual looped distribution systems without
ensure protection efficiency under various conditions concerning the DG [4,5], or to looped microgrids [12].
mode of system operation (i.e. grid-connected vs. islanded), the DG Alternatively, advanced differential protection schemes have been
contribution and the faults occurring (e.g. fault type/position, fault considered for protecting each line segment in looped [13] or meshed
resistance etc.). Although this prospect requires a considerable invest- [14,15] distribution systems, while, communication-assisted multi-
ment, the latter can be considered justified, taking into account the relay schemes, applying alternative protection principles, are also
operational/maintenance benefits gained by the distribution system proposed for such applications [16–18].


Corresponding author.
E-mail address: vnikolai@ee.duth.gr (V.C. Nikolaidis).

https://doi.org/10.1016/j.ijepes.2018.08.022
Received 5 April 2018; Received in revised form 19 July 2018; Accepted 18 August 2018
0142-0615/ © 2018 Elsevier Ltd. All rights reserved.
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

The advantages of distance relays (e.g. inherent directionality and addressing several of the aforementioned issues. A pilot-based distance
non-direct dependency on short-circuit currents [19]) render them a protection scheme for a grid-connected/islanded microgrid is proposed
promising option for modern distribution systems, although their ap- in [35,36], which is, however, applicable only to a radial configuration.
plication is still challenging [20]. So far, distance protection schemes Moreover, specific guidelines for setting the impedance characteristics
proposed for distribution systems mainly regard radial networks. used against various fault/system conditions are not given. Faults with
Distance protection is applied to grid-connected radial distribution a considerable resistance are not simulated, thus, the effect of fault
systems without DG in [21,22]. The reach of the distance zones is resistance is not actually dealt with. Coordination of the distance relays
empirically set in these applications, which, in general, might prove with other protection means encountered in distribution systems (e.g.
unreliable if DG and various fault/system conditions are also con- fuses) is also not addressed. A permissive underreaching transfer trip
sidered. (PUTT) logic is applied as part of [37], but only for the sake of accel-
The presence of DG renders the application of distance protection erating the operation of one of the two distance relays protecting a line
more challenging. The authors of [23] consider a distance relay for segment in a radial microgrid, on condition that this relay has already
protecting a grid-connected radial feeder with DG, which coordinates detected the fault inside its second distance zone. Multiple setting
with other protection means. Moreover, the underreach effect of DG groups are stored for protection against various system conditions
infeed is dealt with through an overreaching distance zone. However, (adaptive logic), while, Mho-based distance zones are used, whose
the resistive reach of the distance zones is set based on a rule of thumb, settings are extracted based on a rule of thumb. The latter might prove
so, the actual effect of fault resistance is not taken into account. Dis- unreliable for various resistive faults. Moreover, the scheme is tested
tance-relaying applications for grid-connected radial feeders with DG only for low-resistance three-phase faults, while, coordination with
are also examined by the authors as part of [24,25]. Multiple distance lateral protection means is not addressed.
zones are applied, which are suitably extended to address the DG infeed Another concept considering a distance relay as a protection ele-
effect, while, coordination with lateral fuses is addressed. Nevertheless, ment in a grid-connected, radial distribution network has been recently
similarly to the abovementioned paper, the effect of fault resistance is proposed in [38]. However, in this work, the distance relay is only
still empirically considered. In [26], distance relays are intended to examined as the interconnection relay of a wind farm, while, the au-
replace the undervoltage relays of DG units and some of the feeder thors investigate the effect of wind power intermittency on the relay’s
overcurrent relays, in a grid-connected radial feeder. The issue of dis- performance, solely in terms of polarization using the pre-fault voltage.
tance relay coordination with lateral protection is also mentioned. Other impedance-based protection schemes for radial distribution fee-
However, the performance of the distance relays is adversely affected ders with DG have also been proposed, as part of a differential [39,40]
by infeed/outfeed currents and fault resistance. Distance protection is and an inverse-time-impedance [39] protection principle though;
applied to radial feeders with DG, as part of [27,28]. Mho-based dis- hence, actual/common distance protection is not examined in these
tance elements are used, which are empirically set, taking into account papers.
the infeed constants. Fault resistance effect is not actually dealt with, The advantages of distance protection could become more promi-
while, coordination with lateral protection is also not considered. In nent in looped/meshed distribution networks with DG, although their
[29], an adaptive distance protection scheme is applied to a grid-con- consideration for actual applications might still prove problematic [41].
nected radial feeder with DG. Only solid phase faults are considered, Despite the significant issues to be addressed in this direction, relevant
while, coordination with lateral protection is not addressed in this work research efforts are limited. In [35], a central distance-based protection
either. scheme is considered for an islanded, ring-type microgrid; however, the
Alternative techniques have also been proposed, intending to deal issues mentioned previously for the radial application of the same work
with the effect of DG infeed and/or fault resistance. In [30], a distance hold in this case as well. Distance protection is considered for a grid-
protection scheme, applied to a grid-connected/islanded radial feeder, connected ring-type network in [42], although intermediate DG infeed
is proposed, where the DG infeed effect is compensated by calculating is not taken into account. Coordination with lateral protection means is
the infeed error term through current measurements. However, this also not addressed. In [43] and [44], distance protection is, respec-
compensation would not be directly applicable under the effect of fault tively, applied to a meshed and a looped distribution system with DG,
resistance, which is not taken into account in this work. In addition, using multiple setting groups (adaptive logic) against different system
coordination of the distance relays with lateral protection means is not conditions. Fault resistance effect and coordination with lateral pro-
addressed. A measurement-based infeed-current compensation metho- tection means are not addressed in these papers. A preliminary attempt
dology is also used in [31]; however, fault resistance is not dealt with in by the authors to apply distance protection to a looped distribution
this case as well. Coordination of backup main line distance protection network with DG is also included in [25].
with primary main line overcurrent protection is also addressed, al- As part of [45,46], the authors also analyze the considerable effect
though the latter does not hold for coordination with lateral protection. of zero-sequence compensation, DG infeed and fault resistance speci-
In [32], the distance relays protecting a grid-connected radial feeder fically on distance relays protecting distribution systems. These factors
against single-line-ground faults are set through an optimization algo- might lead to severe impedance calculation errors, compromising pro-
rithm, considering a specific range of fault resistance values. Never- tection dependability and security if their concurrent effect is not
theless, the efficiency of this algorithm can be limited due to system properly considered during relay setting. However, the latter has not
changes and/or under the presence of DG, while, coordination with been sufficiently addressed in the literature so far. Note that, although
common lateral protection means is not taken into account. A pro- [45,46] refer to radial feeders, the aforementioned influencing factors
mising distance-based approach for a grid-connected radial distribution must be considered for setting distance relays in looped/meshed dis-
network with DG is presented in [33]. This approach is fault-location- tribution networks as well.
oriented, aiming to compensate for impedance calculation errors due to In this work, a distance-based protection scheme for meshed dis-
DG infeed and fault resistance. Communication means and multi-point tribution systems with DG is developed, intending to address all the
measurements are required for this purpose. However, the accuracy of aforementioned issues encountered in the literature, concerning the
this methodology can be limited when load and fault resistance are application of distance protection to distribution systems. For the sake
high, while, the methodology is not applicable against single-line- of enhancing the applicability of the proposed solution, existing dis-
ground faults (i.e. the most frequent faults). tance relay technology (i.e. tested by vendors in real-world applica-
Despite the fact that pilot-based distance protection has been tra- tions) is exploited, which is, however, properly adapted to the needs of
ditionally applied to transmission systems [34], its proper application/ the present application. The designed distance scheme is suitably set to
adaptation to modern distribution systems could be considered for provide efficient protection against solid and non-solid (with a

455
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

considerable fault resistance) faults of any type, under high DG pene- case of a solid short-circuit, the positive-sequence impedance up to
tration, while, weak-infeed conditions are also dealt with. Permissive point F, seen by DR, will be:
logic is applied to ensure protection speed, sensitivity and security at
Z = +Z
ZA B + 
(IB
/ )·Z
IA B
the same time. Coordination with lateral protection means is also ad-
ZF Zadd1 (3)
dressed. Moreover, the proposed scheme is efficient in both the grid-
connected and the islanded mode of system operation, without using where ZA is the positive-sequence impedance from the relay location up
any complex adaptive logic. to the DG connection point, ZB is the positive-sequence impedance from
The organization of this paper is as follows. Section 2 includes a the DG connection point up to the fault position F, IA is the short-circuit
brief theoretical analysis of the basic influencing factors affecting dis- current flowing from the external grid and IB is the infeed current
tance relay operation. In Section 3, the generic meshed distribution flowing from the DG unit.
system configuration adopted in this paper is briefly described, while, a To analyze the fault resistance effect solely, a fault with resistance
thorough description of the proposed protection philosophy is also RF is assumed at point F (Case 2 in Fig. 1a). For the sake of generality, it
given. The detailed setting procedure of the distance relays is addressed is assumed that the fault is also fed by a reverse current (IR ), which
in Section 4. Section 5 presents the simulation results obtained from the could flow from DG units downstream to point F and/or from the grid
application of the proposed scheme to a test system. In Section 6, the in case of a looped/meshed network topology. Note that the infeed
advantages of the proposed scheme compared to other distance-based effect is not examined now, since, in that case, DG units would be as-
schemes are described, while, a comparison with a directional-over- sumed connected between the relay and point F. The apparent positive-
current-based and a differential-based protection scheme is also in- sequence impedance up to point F will be:
cluded. Conclusions are drawn in Section 7.
Z = ZF + 
(IR
/
IF )·
RF
Zadd2 (4)
2. Factors affecting operation of distance relays
where ZF is the positive-sequence impedance from the relay location up
Distance relays calculate the positive-sequence impedance of the to the fault position F, and IF is the short-circuit current flowing from
protected circuit up to the fault position, based on local voltage and the grid.
current measurements. In fact, a distance relay calculates six impedance It is apparent that, in both cases (Case 1 and Case 2), the relay sees
values, three for phase fault loops (a-b, b-c, c-a) and three for ground an additional impedance (Zadd1 and Zadd2 , respectively), apart from the
fault loops (a-g, b-g, c-g). The calculated impedance for a phase (e.g. a- actual impedance ZF up to the fault position. Depending on the relation
b) and a ground (e.g. a-g) fault loop is, respectively, equal to [19]: between the phase angles of IB , IA for Case 1 and IR , IF for Case 2, the
Za − b = (Va−Vb) (Ia−Ib ) above phenomena can lead to underreach or overreach of the distance
Za − g = Va [Ia + K 0·(3·I0)] relay [46]. Fig. 1b shows the impedance seen by a distance relay on the
(1)
complex impedance (R-X) plane for a fault downstream or upstream to
where Va, Vb, Ia and Ib is the phase-a voltage, phase-b voltage, phase-a its location, in case of underreach (ZC1 and ZC1′, respectively) or over-
current and phase-b current, respectively, measured by the relay. K0 is reach (ZC2 and ZC2′, respectively). The underreach/overreach effect
the zero-sequence compensation factor, required to compensate for results from the additional calculated impedance Zadd due the separate
zero-sequence current (I0) during ground faults, and in that case is or even the combined effect of the above-described factors. It appears
calculated as [19]: that, for downstream faults (forward direction), the relay can see the
fault in the first or even in the fourth quadrant, in case of a very intense
K 0 = (Z0−Z1) (3·Z1) (2)
overreach (dashed arrow) [46]. Respectively, for upstream faults (re-
where Z0 and Z1 is the positive- and zero-sequence impedance, re- verse direction) the relay can see the fault in the third or the second
spectively, up to the fault position. quadrant. Such intense overreach effects may be encountered under
Major influencing factors for distance relays are the intermediate specific fault conditions (concerning fault type and fault position) if
infeed effect, which appears when power sources are connected be- fault resistance is considerable. The concurrent effect of K 0 during
tween the relay and the fault position, and the fault resistance effect. ground faults plays a crucial role in the appearance of these overreach
Both may result in inaccurate apparent impedance calculation by the phenomena, in distribution system applications of distance relaying
distance relay [34]. [46].
The latter is briefly explained with the help of Fig. 1a, which depicts It is obvious that if the above-described factors are not properly
a faulty part of a distribution feeder, protected by a distance relay (DR). taken into account when designing a distance protection scheme
In order to analyze the infeed effect solely, a DG unit is assumed con- (especially for distribution applications), the reliability of the latter will
nected between the DR and the fault position F (Case 1 in Fig. 1a). In be doubtful. These factors are addressed by the proposed protection

Fig. 1. (a) Infeed/fault resistance effect, (b) Impedance seen by the distance relay.

456
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Fig. 2. Examined system and proposed protection scheme.

scheme, described in the following. Through the above implementation, distance relays are never af-
fected by intermediate infeed during forward faults, since no DG units
3. Proposed distance protection scheme are connected between buses Bi and Bj . Note that, forward faults are
recognized by the relays as fault currents flowing into the corre-
3.1. Generic meshed distribution system sponding main line segment. Even if a DG unit was tapped at an in-
termediate point of a main line segment, the latter would be divided at
The proposed protection scheme is demonstrated with the help of the point of DG connection and distance relays would again be installed
the generic meshed overhead distribution system of Fig. 2. Two pairs of at the endpoints of the new segments formed, without any DG con-
crossed interconnection line segments are assumed to increase the nected between them. This practice is due to avoid unnecessary dis-
network’s complexity. This system can operate in both grid-connected connection of DG units during main line faults, which is critical to
and islanded mode. Inverter-interfaced generating units (photovoltaic motivate DG investments in distribution systems. However, inter-
plants PV1 and PV2 ), as well as conventional synchronous generators mediate DG infeed effect is encountered when designing bus and lateral
(SG1 and SG2 ), are assumed connected to the positions shown in Fig. 2. protection, and will be dealt with as part of the corresponding proposed
Fuses are assumed protecting laterals Li (i = 1, …, 10) . Fuses are con- protection scheme, described later.
sidered instead of overcurrent relays, as they are the most encountered Two forward distance elements (FDEs) are enabled in each distance
(low-cost) protection means for distribution system laterals, while, they relay, i.e. a phase forward distance element (PFDE) and a ground for-
are more difficult to coordinate with main feeder relay(s), due to their ward distance element (GFDE). PFDEi, j and PFDEj, i of distance relays
non-settable characteristic. DRi, j and DRj, i , respectively, are responsible for protecting line segment
Li, j against forward line-line-line (LLL) and double-line (LL) faults,
whereas, GFDEi, j and GFDEj, i of distance relays DRi, j and DRj, i respec-
3.2. Description of the proposed protection scheme tively, are assigned for forward single-line-ground (SLG) and double-
line-ground (LLG) faults. It has to be mentioned that in several com-
3.2.1. Dealing with faults occurring in the main line segments mercial distance relay models, LLG faults can be detected and cleared
Each main line segment Li, j (i, j = 0, …, 10, i ≠ j ) connecting buses by both phase and ground distance elements. However, from the
Bi and Bj is protected by a numerical distance relay DRi, j installed at Bi viewpoint of the methodology proposed here, this is not problematic,
and a numerical distance relay DRj, i installed at Bj (see Fig. 2).

457
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Fig. 3. Overall protection and communication logic of the proposed scheme.

since the concurrent trip of phase and ground distance elements does We assume that fault-confirmation and permission signals remain ac-
not affect the scheme’s efficiency. This will become clearer later in this tive for a proper time duration, to ensure correct operation of the
subsection, after the proposed protection philosophy is further de- protection scheme.
scribed. Unless necessary, we will not specifically refer to phase or Ultimately, FDEi, j trips circuit breaker CBi, j at DRi, j location if the
ground distance elements in the rest of this paper, as the proposed following conditions hold simultaneously:
methodology is equally applied to both.
The reach of FDEi, j (resp. FDEj, i ) is initially set to cover beyond Bj • FDE i, j confirms that a fault lies inside FDZi, j .
(resp. Bi ), meaning that both FDEs overreach the total line length of the • FDE i, j receives permission from FDEj, i .
protected segment (e.g. by 20% of this length), to compensate for any
relay calculation or measuring errors during faults in segment Li, j . Note Hence, for faults inside line segment Li, j , FDEi, j and FDEj, i trip CBi, j
that this reach extension is performed only for the latter reason and not and CBj, i , respectively, isolating only this segment. For faults outside
for detecting faults in the adjacent line segment (i.e. for backup pro- Li, j , at least one of the above FDEs does not sense the fault, thus un-
tection). The tripping direction of each FDE and its assigned main line desired trips are avoided.
part is shown with solid arrows in Fig. 2. A quadrilateral characteristic From the viewpoint of tripping time, FDEi, j and FDEj, i are set with
is applied to all distance elements. an instantaneous time delay (tFi, j and tFj, i , respectively), ensuring rapid
The previous paragraph (and Fig. 2) outlines just the basic setting fault clearance, as only this unintentional instantaneous time delay (i.e.
philosophy of the proposed scheme. In case of solid faults occurring in the response time of the relays), which is less than 50 ms for common
segment Li, j , both FDEi, j and FDEj, i will calculate the impedance up to relays, should elapse for a trip order to be issued. Note that commu-
the fault position accurately, as distance elements are not affected by nication latency is negligible (4.9 μs/km for fiber optic cable), thus it
any external changes (e.g. transmission grid changes, transition from does not practically affect the tripping time of the relays. Of course, the
grid-connected to islanded mode etc.), while, infeed/fault resistance overall fault clearing time (tC) is the sum of the tripping (response) time
effect is not present. Therefore, if we considered only solid faults, the of the relays, plus the interrupting time of the CBs (tCB).
above-described basic setting philosophy would be adequate, i.e. the It is worth mentioning that, after a distance relay DRi, j calculates the
reach of FDEi, j /FDEj, i would simply be set according to the positive- impedance of each fault loop during a fault (see Section 2), it has to
sequence impedance of Li, j (also considering 20% overreach for calcu- determine the type of the fault as well as the faulted phase. This is to
lation/measuring errors). Since, however, the proposed scheme deals take into account the correct impedance value for checking if the latter
with more realistic fault conditions, i.e. fault resistance is considered as is detected inside a distance zone or not, as well as to decide between
well, the additive term Zadd2 of (4) is taken into account for setting the single- or three-pole trip. This can be easily addressed, since most
distance elements properly. In particular, when needed, the reach of common commercial numerical distance relays include advanced phase
FDEi, j /FDEj, i is further extended to compensate for the effect of fault selection functions. The latter are based on several criteria, such as the
resistance, so that every possible resistive fault in Li, j is located inside impedance magnitude of each fault loop, the relation between the
the corresponding distance zones. The amount of the required extension phase angles of the current/voltage sequence components etc.
is determined through proper simulation study, as described later. Al- [34,47,48].
though reach extension (by 20% or more) can result in FDEi, j /FDEj, i The protection and communication logic of a FDEi, j (described
sensing faults occurring outside Li, j , permissive logic will prevent them previously) is included in Fig. 3. To sum up, after the relay calculates
from tripping undesirably, ensuring protection security. the impedance of the fault loop indicated by the phase selection func-
The aforementioned permissive logic is designed as follows. Once tion, it checks if it lies inside FDZi,j. In that case (and after the time
FDEi, j of a relay DRi, j confirms that a fault is detected inside its forward required for the relay to respond expires), a permission signal is sent to
distance zone (FDZi, j ), it sends a permission signal to FDEj, i of DRj, i and FDEj,i. If, at the same time, a permission signal is received from FDEj,i,
vice versa. The signal is transferred through a communication path (e.g. CBi,j is tripped and the breaker-failure function (described later) is in-
a fiber optic cable) linking opponent FDEs. Note that PFDEi, j (resp. itiated. Obviously, FDEj, i operates similarly.
GFDEi, j ) exchanges permission signals only with PFDEj, i , (resp. GFDEj, i ).

458
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

avoid increasing the scheme’s cost by installing dedicated relay(s) for


bus/lateral protection. Specifically, in each relay DRi, j adjacent to Bi/Li,
apart from the FDEi, j activated for main line protection, a reverse dis-
tance element RDEi, j is activated for bus and lateral protection. RDEi, j is
responsible for protecting from bus Bi up to the endpoint of Li . For
instance, RDE1,0 , RDE1,2 and RDE1,9 of distance relays DR1,0 , DR1,2 , and
DR1,9 , respectively, are used to protect bus B1 and lateral L1, up to its
endpoint. In fact, the reach of RDEi, j is initially set to cover beyond Li
Fig. 4. Pilot-based protection scheme for faults in the first line segment, under
endpoint (e.g. increased by 20%, as happens for FDEi,j) to compensate
weak-infeed conditions.
for possible relay calculation or measuring errors, during faults in Li .
The trip direction of each RDEi, j and its assigned line part is shown in
3.2.2. Special protection treatment of segments L0,1 and L0,10 Fig. 2 with dashed arrows. Note that, concerning DR1,0 and DR10,0 , the
A potential issue during the grid-connected mode of system opera- reverse blocking elements RDEb1,0 and RDEb10,0 , described in the pre-
tion, concerns faults occurring close to the main substation, i.e. in vious paragraph, are independent of RDE1,0 and RDE10,0 , protecting
segments L0,1 and L0,10 . In the general case where fault resistance is B1/L1 and B10 /L10 , respectively.
expected, and concerning only FDE1,0 (resp. FDE10,0 ), the term IR/IF of All the RDEs protecting Bi /Li form a group of adjacent RDEs, re-
(4) may become considerably large, due to the weak current IF flowing ferred as GARDEi . Permissive trip logic is applied, i.e. RDEi, j trips CBi, j
from bus B1 (resp. B10 ). This would subsequently result in a large re- only if:
quired extension of FDZ1,0 (resp. FDZ10,0 ) when setting the relay, which
may not be applicable with commercial relays, due to their limited
• It sees a fault between (and including) B and L endpoint.
i i
reach setting range. Although this issue could be addressed by the relay
vendors, a dedicated solution is proposed below, to keep up with
• It receives permission from the rest RDEs of GARDE . i

commercially-available relay specifications. As mentioned earlier, the reach of each RDEi, j is initially set to cover
As the operation of FDE1,0 and FDE10,0 is not reliable for faults close at least 120% of Li length; however, there might be cases where this
to the main substation, a combination of the directional comparison reach is further extended during the setting procedure. Now, such cases
blocking (DCB) principle with the permissive logic is proposed for may arise not only due to the fault resistance effect (as happens when
protecting segments L0,1 and L0,10 . This functional combination is illu- setting FDEs for the main line protection) but also due to intermediate
strated in Fig. 4, focusing on L0,1, while it is equally applied for pro- infeed currents (see Section 2) flowing from DG units and/or other
tecting L0,10 . In brief, FDE0,1 is set as all FDEs, with the exception of not feeders connected to Bi . Similarly to FDEs, the required additional reach
requiring permission to trip from the opponent distance element FDE1,0 , extension of RDEs, to compensate for the infeed/fault resistance effect,
which is kept disabled in DR1,0 . Instead, a reverse blocking distance is determined through proper simulation study, as described later.
element (RDEb1,0 ) is enabled in DR1,0 . This element supervises the RDEs should also coordinate with the lateral fuses. Therefore, the
feeder downstream to B1 (in the reverse direction of DR1,0 , as shown maximum total clearing time (tTC,max ) of the lateral fuses is critical for
with the solid arrow in Fig. 4) and blocks FDE0,1 whenever a fault oc- setting RDEs properly. This time depends on the fuse’s type and rated
curs inside this area. In this way, undesired trips of FDE0,1 due to the current and the fault/system conditions. As tTC,max of a fuse Fi can reach
extension of its reach beyond B1 (as explained before), are avoided. high values, it is up to the protection engineer to decide whether tRi of
The main particularity of the pilot-based protection solution pro- the RDEs constituting GARDEi will be set greater than tTC,max for the
posed here concerns the fact that, since FDE1,0 is disabled, RDEb1,0 is needs of relay-fuse coordination (as indicated later in Subsection 4.2),
also responsible for tripping CB1,0 in case of a fault inside L0,1 . For this or a lower tRi setting will be considered, to limit through-fault damage.
reason, RDEb1,0 receives a permission signal from FDE0,1, once the latter Note that in the latter case, relay-fuse coordination for a number of
confirms that a fault lies inside FDZ0,1 (i.e. after tF0,1), while it trips CB1,0 fault cases will be “sacrificed” for the sake of protection speed. Ob-
only if: viously, if fuse Fi fails to clear a fault in Li, the overall fault clearing time
(tC) will be equal to tRi plus the interrupting time of the CBs (tCB). It is
• ItIt has received permission from FDE . 0,1 worth mentioning that the replacement of lateral fuses with relays
• has not detected a fault inside its reverse blocking zone RDZb 1,0 . would make the protection design study much simpler. However, it is
here considered preferable to maintain fuses for lateral protection in
RDEb1,0 is set with instantaneous time delay (tR1,0 ), as FDE0,1. Hence, order not to increase the scheme’s cost and in order to consider the most
the overall fault clearing time (tC) in this case will be equal to the re- challenging scenario for setting the relays.
sponse time of the relay plus the interrupting time of the CB (tCB). The trip logic of a RDEi, j is similar to that of a FDEi, j and is also
The trip logic of FDE0,1 and RDEb1,0 is also shown in Fig. 3. To sum shown in Fig. 3. To sum up, after the relay calculates the impedance of
up, the respective relays initially calculate the impedance of the fault the fault loop indicated by the phase selection function, it checks if it
loop indicated by the phase selection function. If the impedance cal- lies inside RDZi,j. In that case (and after the time delay set for co-
culated by DR1,0 lies inside RDZb1,0, RDEb1,0 sends a blocking signal to ordination with the corresponding lateral fuse expires), a permission
FDE0,1. If the opposite happens, and RDEb1,0 receives a permission signal is sent to the rest relays of GARDEi. If a permission signal is also
signal from FDE0,1, then (after the unintentional time delay tR1,0 ex- received from the relays of GARDEi, CBi,j is tripped and the breaker-
pires), CB1,0 is tripped and the breaker-failure function (described later) failure function (described later) is initiated.
is initiated. Note that, in order for the aforementioned permission signal From what is described in this subsection, concerning both FDEs and
to be sent, FDE0,1 has in the meantime confirmed that the impedance RDEs, it is derived that the proposed scheme ensures protection sensi-
calculated by DR0,1 lies inside FDZ0,1 (after the expiration of the relay’s tivity and security at the same time. The latter is further clarified with
response time). In the latter case, FDE0,1 also trips CB0,1 and initiates the help of Fig. 5, which illustrates a main line segment Li,j (re-
the breaker-failure function (described later). presenting any main line segment of a meshed distribution system),
along with its adjacent buses, main line segments and laterals. For
3.2.3. Dealing with faults occurring in buses or laterals simplicity, in this example, we focus solely on the protection of segment
For the primary protection of each bus Bi and the backup protection Li,j, bus Bi and lateral Li. Fig. 5 also illustrates the communication paths
of the corresponding lateral Li (primarily protected by fuse Fi ), the, for permission signal exchange between the FDEs enabled in DRi,j, DRj,i
already installed, distance relays adjacent to bus Bi are exploited, to to protect Li,j, as well as the respective paths of the RDEs constituting

459
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Fig. 5. Explanation of the protection and communication philosophy of the proposed scheme.

GARDEi, enabled in DRi,j, DRi,h, DRi,l to protect Bi/Li. Let us assume fault remains closed after tBF expires, DRi, j trips the adjacent CBs. In the
SC1 occurring in Li,j. In that case, both FDEi,j and FDEj,i will see the fault, meantime, a re-trip command is issued to CBi, j , as a second attempt to
thus they will trip the CBs at their location, after they exchange per- trip this CB, in order to avoid opening the adjacent CBs. The re-trip time
mission signals. However, as explained before, the FDEs might need to delay (tRT ) is set to 1–2 cycles, just to avoid misoperation due to nui-
extend further than their opponent bus (by even more than the initial sance input (e.g. noise) [49]. Fig. 6 shows the designed BF trip logic of a
overreach of 20%), for sensitivity purposes. For instance, FDEi,j might relay DRi, j . Note that the proposed BF function discriminates between
erroneously see fault SC1 as if it occurred in Lj,k instead of Li,j (under- the BFI signal coming from FDEi, j (BFIFi, j ) or RDEi, j (BFIRi, j ), so as to trip
reach effect), due to the effect of fault resistance (see Section 2). By the proper adjacent CBs (CBFi, j and CBRi, j , respectively).
properly extending the reach of FDEi,j, the latter will be able to protect At this point, let us provide an example of the BF function. Once
against such fault cases in Li,j. Even if this extension can also lead to FDE1,2 issues a trip command to CB1,2 and a BFI signal is asserted, a trip
FDEi,j sensing a fault actually occurring further than Bj, e.g. fault SC2, command is re-issued to CB1,2 after tRT . If CB1,2 remains closed after
the permissive logic described previously will guarantee protection tBF > tRT , then DR1,2 trips CB1,0 and CB1,9 . In the special case where
security in that case. In other words, although FDEi,j will send permis- FDE0,1 (resp. FDE0,10 ) fails to trip CB0,1 (resp. CB0,10 ), CB0,10 (resp. CB0,1)
sion to FDEj,i, the opposite will not happen, as FDEj,i will not see the and the CB at the substation transformer secondary trip instead after tBF
fault. Hence, none of these distance elements will ultimately trip in- elapses. Since, tripping the CB at the substation transformer secondary
correctly. Remember that both the opponent FDEs must receive per- would lead to islanded operation, breaker redundancy could also be
mission signals from each other, in order for their CBs to be tripped. considered as an option just for CB0,1 (resp. CB0,10).
RDEs operate similarly, and, in fact, are also properly extended to In order to preserve their functionality, modern numerical relays
deal with underreach phenomena, due to the effect of fault resistance can continuously perform self-diagnosis in the form of watchdog cir-
and/or the effect of intermediate DG connected to bus Bi (see Section cuitry and check for internal failures [19]. Hence, it is anytime known
2). In case of fault SC3 occurring in lateral Li, all the RDEs of GARDEi whether each relay is able to provide primary/backup protection, or a
will see the fault and trip the CBs at their location, after they exchange reparation action is required. Moreover, the operability of commu-
permission signals. Note that protection security is ensured in this case nication channels can be checked through regular signal exchange be-
as well. For instance, fault SC1 can be sensed by RDEi,h and RDEi,l, as the tween the corresponding relays (e.g. through GOOSE messages).
latter are set to protect towards Bi/Li (i.e. in their reverse direction). In any case, the overcurrent element of the substation transformer’s
However, RDEi,j will not see this fault (since it has occurred in its op- differential relay can be set as an additional backup protection (besides
posite direction), thus it will not send permission signals to RDEi,h and BF) for the whole distribution system. The latter has to be set with a
RDEi,l. Remember that all the RDEs of a GARDE must exchange per- time delay greater than the greatest time delay of the FDEs and RDEs
mission signals in order for their CBs to be tripped. used, plus the tBF set in the distance relays. If the faulted network is
isolated from the external grid and, for any reason, both primary and BF

3.3. Backup protection

For the case where a CB fails to open, although a trip order has been
issued by the respective relay, a breaker-failure (BF) protection scheme
is designed. The latter ensures that if a CB fails to open after receiving a
trip signal by its corresponding relay, its adjacent CBs will be tripped by
the same relay. In general, BF protection functions are included in
several distance relay models [34]; however, the design of this logic is
here suitably adapted to the needs of the proposed protection scheme.
Specifically, as part of this work, BF is designed as follows: Once
FDEi, j or RDEi, j of DRi, j issues a trip order to CBi, j , a breaker-failure
initiation (BFI) signal is simultaneously asserted (see Fig. 3). We assume
that the BFI signal remains active for a proper time duration. After-
wards, the state of CBi, j is checked for a time period equal to tBF . Ty-
pically, tBF lasts for 7–15 cycles [49], to compensate for the CBi, j in-
terrupting time plus any other delays associated with the relay. If CBi, j Fig. 6. Breaker-failure trip logic of a distance relay DRi,j.

460
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

protection fail to clear the fault, the network will be de-energized after 4. Angle of the down zone blinder (θd, FDEi, j )
the protection means of the DG units (which are out of the scope of this 5. Angle of the right zone blinder (θr , FDEi, j )
work) disconnect the latter. 6. Angle of the left zone blinder (θl, FDEi, j )

4. Detailed setting procedure of distance relays Specifically, for determining settings 1–3 from the previous list, the
following maximum magnitudes, seen by each phase (resp. ground)
For setting distance elements as part of the proposed methodology, distance element during phase (resp. ground) faults, are extracted from
a proper fault-simulation study is conducted, taking into account all the the simulations:
possible combinations of expected marginal fault/system conditions. In
this way, the relay setting procedure considers any infeed/fault re- a. Maximum positive reactance + Xp,max (resp. + Xg,max ), being equal
sistance effect expected during the grid-connected/islanded mode of to:
system operation, as well as any other factor that could affect the relays’
+ Xp,max (resp. + Xg,max )
efficiency. A fixed setting group for each relay is finally determined,
protecting the system efficiently under any expected fault/system = max{ + XFDEi, j, FT , PL, RF , OM , + XFDEj, i, FT , PL, RF , OM } (5)
condition, while, adaptive or other complex setting strategies are
avoided. b. Maximum negative reactance |−X |p,max (resp. |−X |g,max ), being equal
to:
4.1. Setting FDEs for main line protection
|−X |p,max (resp. |−X |g,max ) = max{|−XFDEi, j, FT , PL, RF , OM |,
To set FDEi,j, faults of all common types (i.e. LLL, LL, LLG, SLG) are |−XFDEj, i, FT , PL, RF , OM |} (6)
simulated in front of DRi, j and at the opponent endpoint of the protected
main line segment, i.e. at the marginal points of the line part assigned to c. Maximum positive resistance + Rp,max (resp. + Rg,max ), being equal
FDEi,j. Assuming the grid-connected mode of system operation, all the to:
simulations are performed for both zero and maximum DG production,
as well as for zero and maximum fault resistance. Assuming the is- + Rp,max (resp. + Rg,max )
landed mode of system operation, all the simulations are performed for = max{ + RFDEi, j, FT , PL, RF , OM , + RFDEj, i, FT , PL, RF , OM } (7)
zero and maximum fault resistance, but only for a fixed DG penetration
level permitting the islanded operation. This procedure is further clar- In (5)–(7), FT stands for a LLL or LL (resp. LLG or SLG) fault.
ified with the help of Fig. 7a, which illustrates a main line segment Li,j The ultimate settings +XPFDEi,j/+XGFDEi,j, |−XPFDEi,j|/|−XGFDEi,j|,
and its adjacent lateral Li. For simplicity, only the protection means and + RPFDEi,j/+RGFDEi,j of phase/ground FDEi,j will be, respectively,
installed in Li,j and Li are shown. For setting FDEi,j, a number of fault- equal to:
simulation scenarios SFT,PL,RF,OM is considered for each position SCFDEi,j + XPFDEi, j = ( + Xp,max ) + ε , + XGFDEi, j = ( + Xg,max ) + ε
(i.e. in front of DRi,j) and SCFDEj,i (i.e. in front of DRj,i). FT stands for the
|− XPFDEi, j | = (|−X |p,max ) + ε , |−XGFDEi, j | = (|−X |g,max ) + ε
fault type (LLL, LL, LLG, or SLG), PL stands for the DG penetration level
(zero or maximum), RF stands for fault resistance (zero or maximum + RPFDEi, j = ( + Rp,max ) + ε , + RGFDEi, j = ( + Rg,max ) + ε (8)
expected) and OM stands for the operation mode of the examined where ε (ε > 0) is an optional safety margin, to further ensure fault
system (grid-connected or islanded). Remember that zero PL is not detection.
taken into account when OM is islanded. From the faults simulated at Note that, concerning GFDEs, K 0 is set based on the positive- and
each position, e.g. at position SCFDEi,j, a number of values (combina- zero-sequence impedance of the protected main line segment. Also note
tions) results for the positive reactance +XFDEi,j,FT,PL,RF,OM, the negative that, although only forward faults are of interest, −XFDEi, j and θd, FDEi, j
reactance −XFDEi,j,FT,PL,RF,OM, and the positive resistance should be set properly, as it is possible for a forward fault to be detected
+RFDEi,j,FT,PL,RF,OM, calculated by the relay. by FDEi, j in the fourth quadrant of the R-X plane (see Section 2). Angle
Fig. 7b depicts a generic quadrilateral FDEi, j protecting line segment θd, FDEi, j (setting 4) could a priori be set equal to 90° (i.e. on the −X
Li, j . Similar characteristic/settings also hold for RDEs/RDEbs, which are axis), to ensure fault detection. Since the + RFDEi, j setting alone pro-
set later. Setting each FDEi, j (and RDEi, j as explained later) is based on vides maximum fault resistance coverage, as it is based on the max-
the abovementioned simulation results and the determination of the imum resistance seen by the relay during the simulations, angle θr , FDEi, j
following settings: of the right blinder (setting 5) is set to 90°. The latter setting is here
disengaged from the traditional distance relay setting philosophy,
1. Positive reactance reach ( + XFDEi, j ) where the angle of the right zone blinder is set equal to the impedance
2. Negative reactance reach (−XFDEi, j ) angle of the protected conductor. In addition, since forward faults are
3. Positive resistive reach ( + RFDEi, j ) not expected to lie in the second quadrant of the R-X plane, angle θl, FDEi, j

Fig. 7. (a) Fault-simulation strategy for setting FDEi,j/RDEi,j, (b) Typical quadrilateral FDEi,j settings.

461
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

positions SCRDEi,j and SC′RDEi,j of Fig. 7a (marginal points of the line


part protected by RDEi,j). The reach settings of RDEi,j are based on
the maximum calculated values resulting from these simulations, as
described for setting FDEi,j.
• The time delay tRi of RDEi, j is set to coordinate with fuse Fi of Li (see
Subsection 3.2). For this purpose, tTC,max for every fuse Fi (resulting
from the lowest short-circuit current flowing through Fi) is de-
termined by simulating faults of all types at the remotest point of Li ,
considering all the DG-contribution and system-operation scenarios.
Then, tRi for all the RDEs of GARDEi is set as:

tRi ⩾ tTC,max + CTI (10)

where CTI is a proper Coordination Time Interval.


Note that DRi, j locates reverse faults in the second or the third
quadrant of the R-X plane, as they occur upstream to its location (see
Fig. 1b). Therefore, a fault is determined as reverse, if the following
holds for the angle θz of the calculated impedance:

90o < θZ < 270o (11)


Fig. 8. Generic quadrilateral phase/ground FDEi,j, after performing the pro-
posed setting procedure. Nevertheless, the impedance values opposite to the calculated ones
are determined to extract RDEi, j settings, since, in all common com-
mercial distance relays, reverse elements are set like being forward.
of the left blinder (setting 6) is set to zero. Based on the above angle- Compensation factor K 0 of GRDEi, j is set based on the impedance of
setting philosophy, a fault is determined as forward, if the following the conductor where DRi, j is installed. The impedance calculation error
holds for the angle θz of the calculated impedance: due to the effect of K 0 , accompanied with the effect of infeed currents
−90o < θZ < 90o (9) and fault resistance, is anyway compensated [45,46] by the distance
zone reach settings extracted from the above-described simulation
Finally, as mentioned in Section 3, no intentional time delay is set
study, since K0 is taken into account during the simulations, along with
for FDEs.
all the other influencing factors.
Fig. 8 illustrates the generic form of a quadrilateral phase/ground
Finally, undesired trips of phase RDEs under heavy normal load
FDEi,j, after being set according to the above-described philosophy. The
conditions must be avoided (FDEs are never affected as at least one of
dotted arrows stand for the impedance calculation errors during the
the opponent FDEs in a main line segment does not see the load current
specific faults, occurring at the marginal points of Li,j (SCFDEi,j and
in its trip direction). To deal with this issue, a load encroachment (LE)
SCFDEj,i), which give the maximum calculated positive reactance/re-
element is enabled for each phase RDE. This element, included in sev-
sistance and negative reactance. The final FDEi,j reach settings can re-
eral commercial distance relays [23], blocks trip command if the cur-
main equal to the respective maximum calculated values, or can be
rent flowing over the segment of interest is within its normal load va-
further extended by ε (dashed lines in Fig. 8), to enhance dependability.
lues. The latter are determined through pre-fault load-flow simulations,
Note that, in the example of Fig. 8, the choice of which fault gives each
considering all the possible DG-connection cases and line segment/
maximum value is indicative. Moreover, a single fault could determine
lateral configurations in the grid-connected/islanded mode. Note that
more than one reach settings of FDEi,j.
cases where LE elements prevent phase RDEs from clearing LLL faults
It is worth mentioning that the value of the calculated reach settings
are expected to be very rare.
depend on various factors concerning the specific system examined,
such as the length/cross-section of the protected conductors, the short-
circuit contribution of the utility (during the grid-connected mode) and
4.3. Setting distance relays in segments L0,1 and L0,10
the DG units, the system configuration etc. Moreover, the effect of
several influencing factors (e.g. fault resistance) is unpredictable.
As explained in Subsection 3.2, the reach settings of RDEb1,0 have to
Hence, a simulation study (as that proposed in this work) is a quite
be greater than the (over)reach settings of FDE0,1 (see Fig. 4). There-
reliable tool to take into account all the particularities of the specific
fore, the following must hold:
network under consideration. Note that simulation studies considering
marginal fault/system conditions constitute the common methodology + XRDEb1,0 > [(+ XFDE 0,1)−( + XL0,1)]
used by protection engineers for setting protective relays in real-world
+ RRDEb1,0 > [(+ RFDE 0,1)−( + RL0,1)]
applications. In addition, as mentioned before, by considering ε, it is
|− XRDEb1,0 | > |(−XFDE 0,1 )−( + XL0,1)| (12)
further ensured that all the expected faults will be detected by the ex-
amined distance element, compensating for possible calculation/mea-
suring errors. Since, at the same time, protection security is guaranteed where + XRDEb1,0 , + RRDEb1,0 and −XRDEb1,0 is the positive reactance
by the permissive logic described in Section 3, ε can be set as great as reach, positive resistive reach and negative reactance reach, respec-
desired, to ensure dependability. tively, of RDEb1,0 , + XFDE0,1, + RFDE0,1 and −XFDE0,1 is the positive re-
actance reach, positive resistive reach and negative reactance reach,
4.2. Setting RDEs for bus and lateral protection respectively, of FDE0,1 and + XL0,1, + RL0,1 is the positive-sequence
reactance and resistance, respectively, of L0,1 conductor. Similarly to
The same procedure as that described in Subsection 4.1 is followed FDEs/RDEs, the angle of RDEb1,0 left blinder is set equal to zero, the
for setting RDEi, j , meaning to determine settings 1–6 for this element. angle of RDEb1,0 right blinder is set equal to 90° and the angle of
The only differences here are that: RDEb1,0 down blinder is also set equal to 90°, to ensure fault detection.
RDEb10,0 is set similarly. No intentional time delay is set for RDEbs.

• Faults are simulated at bus B and at the endpoint of lateral L , i.e. at


i i

462
A.M. Tsimtsios et al.

Table 1
Maximum calculated reactance/resistance (in Ω pri) by FDE/RDE of each relay during phase-/ground-fault simulations.
Mode Distance Calculated value DR0,1, DR1,0, DR1,2, DR2,1, DR2,3, DR9,8 DR3,2, DR3,4, DR4,3, DR4,5, DR7,6 DR5,4, DR5,6, DR1,9, DR2,10, DR3,7, DR4,8,
element DR0,10 DR10,0 DR10,9 DR9,10 DR8,9 DR8,7 DR7,8 DR6,7 DR6,5 DR10,2 DR9,1 DR8,4 DR7,3

GC FDEi,j +Xp,max/+Xg,max 2.28/ 1.67/ 2.14/ 1.67/ 1.94/14.96 1.97/ 1.67/ 2.21/ 1.67/15.48 1.67/ 1.67/ 2.14/ 1.67/ 1.67/ 2.21/
13.58 66.73 20.00 47.54 63.26 20.79 44.85 67.33 24.61 20.00 47.54 20.79 44.85
|−X|p,max/|−X|g,max 0/11.40 46.16/ 0/13.48 0.32/ 0.01/7.86 1.15/ 0.05/8.77 0/22.54 0/5.64 0.02/ 0/11.10 0/13.48 0.32/ 0.05/8.77 0/22.54
4024 25.78 35.83 59.46 25.78
+Rp,max/+Rg,max 18.77/ 3001/ 27.49/ 59.67/ 21.78/ 79.45/ 29.43/ 53.35/ 17.00/ 82.59/ 27.66/ 27.49/ 59.67/ 29.43/ 53.35/
59.52 5717 74.71 141.66 78.02 189.06 123.03 126.36 39.24 286.35 64.52 74.71 141.66 123.03 126.36
RDEi,j +Xp,max/+Xg,max – 5.24/ 12.66/ 6.97/ 16.88/ 5.42/ 11.26/ 6.43/ 16.92/ 3.39/ 5.63/ 12.66/ 6.97/ 11.26/ 6.43/
17.03 66.74 26.19 88.98 18.76 61.85 27.02 93.55 19.30 32.11 66.74 26.19 61.85 27.02
|−X|p,max/|−X|g,max – 0/13.14 2.05/ 0.08/ 2.88/38.51 0.33/7.64 0.49/ 0.55/ 1.02/63.52 0/7.33 0.04/ 2.05/ 0.08/ 0.49/ 0.55/
28.23 15.32 24.78 11.83 12.85 28.23 15.32 24.78 11.83

463
+Rp,max/+Rg,max – 28.50/ 98.04/ 43.00/ 130.72/ 33.40/ 87.15/ 46.34/ 136.23/ 26.14/ 43.77/ 98.04/ 43.00/ 87.15/ 46.34/
69.38 165.34 88.00 220.46 89.70 147.00 144.93 353.35 44.12 73.54 165.34 88.00 147.00 144.93

ISL FDEi,j +Xp,max/+Xg,max 1.67/ 1.67/ 1.67/ 1.67/ 4.28/36.24 1.67/ 1.97/9.20 1.67/ 1.67/10.47 1.67/ 1.67/ 1.67/ 1.67/ 1.97/9.20 1.67/
36.29 13.92 31.36 15.64 11.09 13.88 14.06 15.56 31.36 15.64 13.88
|−X|p,max/|−X|g,max 0/25.36 0/7.46 0/22.41 0/9.26 0/28.59 0.11/5.97 0/35.07 0.01/9.00 0/5.46 0.02/ 0/11.10 0/22.41 0/9.26 0/35.07 0.01/9.00
59.46
+Rp,max/+Rg,max 59.89/ 20.93/ 53.51/ 24.84/ 56.74/ 18.79/ 49.03/ 25.13/ 16.96/ 82.59/ 27.70/ 53.51/ 24.84/ 49.03/ 25.13/
117.76 40.39 105.06 48.22 146.80 33.72 184.35 47.11 31.80 286.35 56.73 105.06 48.22 184.35 47.11
RDEi,j +Xp,max/+Xg,max – 12.66/ 5.07/ 11.24/ 3.50/15.40 16.30/ 4.97/ 10.84/ 16.92/ 3.39/ 5.63/ 5.07/ 11.24/ 4.97/ 10.84/
56.53 22.62 49.24 58.73 20.65 13.40 20.11 14.48 23.54 22.62 49.24 20.65 13.40
|−X|p,max/|−X|g,max – 0/27.56 0/11.01 0.11/ 0.34/7.65 0/30.76 0.25/ 0.15/ 1.02/63.52 0/7.14 0.04/ 0/11.01 0.11/ 0.25/ 0.15/
24.57 10.77 38.07 12.85 24.57 10.77 38.07
+Rp,max/+Rg,max – 98.04/ 39.22/ 87.54/ 28.83/ 91.71/ 39.74/ 79.77/ 136.23/ 26.07/ 43.77/ 39.22/ 87.54/ 39.74/ 79.77/
140.23 56.07 124.73 38.51 176.12 54.51 227.02 353.35 36.25 66.01 56.07 124.73 54.51 227.02
Electrical Power and Energy Systems 105 (2019) 454–469
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

5. Application to a test distribution system simplicity, a uniform maximum fault resistance of 10 Ω is con-
sidered for simulating phase faults in the present application.
5.1. Test system description • As for the simulation of ground (SLG and LLG) faults, we consider a
maximum fault resistance of 40 Ω, so as to test the applicability of
The proposed protection scheme is applied on a 20 kV, 50 Hz, me- the proposed protection scheme for greater fault resistance values
shed overhead distribution system, having exactly the same config- (as expected during ground faults). The latter fault resistance value
uration as that of Fig. 2. The system is modelled with DIgSILENT is considered as a standard value by several utilities in distribution
PowerFactory, based on realistic data provided by the Hellenic Elec- system protection design studies [50]. Note that the fault resistance
tricity Distribution Network Operator S.A (HEDNO S.A.). 5-km long 95- of 40 Ω is indicative, and is here considered during the simulations
mm2 and 5-km long 16-mm2 ACSR conductor is considered for all the as a representative fault resistance example, for the sake of de-
main line segments Li, j and all the line laterals Li , respectively. Each monstrating the setting procedure of the proposed scheme. The
lateral is protected by a 30 T-fuse Fi . proposed methodology can be similarly applied for higher fault re-
The external transmission grid is represented by an equivalent sistance values, without any modification or additional challenge,
source with a maximum short-circuit power of 2085.1 MVA at 150 kV. on condition that the relay model used is not restrictive concerning
The system is normally supplied from the transmission grid through a its reach setting range. As mentioned earlier, the latter is up to the
150/20 kV bulk distribution transformer but is also able to operate as relay designer.
an island. Two 2-MW-rated PV plants, PV1 and PV2 , operating with unity • The two feeders, connecting B0 to B5 and B0 to B6 are identical,
power factor, are connected through a step-up transformer to buses B2 while, the same holds for the interconnection line segments (e.g.
and B9 , respectively. The maximum steady-state short-circuit con- L1,9 , L2,10 etc.). This results in identical settings between symmetrical
tribution of each PV plant is limited to its nominal load current. Two distance relays (e.g. DR 0,1 and DR 0,10 , DR1,0 and DR10,0 etc.).
synchronous generators, SG1 and SG2 , are also considered connected Although this assumption is made to give a clearer illustration of the
through a step-up transformer to buses B4 and B7 , respectively. SGs have results, the proposed methodology can be similarly applied to non-
a maximum production of 2 MW (with unity power factor) in the grid- identical feeders. In any case, the required fault-simulations have
connected mode, whereas, their active and reactive output is suitably been performed in the whole network, to ensure the validity of the
adjusted to support the islanded operation. The total system load is 9.08 relay settings.
MVA (8.17 MW). A maximum DG penetration level (PL) of 98% is • The relay model assumed in this study (chosen from the database of
achieved in the grid-connected mode if all DG units are simultaneously the software used) provides independent phase and ground quad-
in operation, whereas, a PL of 103% is required for the islanded op- rilateral elements, settable as forward, reverse or non-directional.
eration.
5.3. Simulation results and resulting relay settings
5.2. Study procedure and assumptions
Table 1 summarizes the maximum values of list a-c in Subsection
The fault-simulation procedure described in Section 4 is performed 4.1, in both the grid-connected (GC) and the islanded (ISL) mode of
for the test system. That means that phase/ground faults of different system operation, as calculated by the assigned FDEs/RDEs of each pair
types are simulated at critical positions for setting FDE/RDE/RDEb of of symmetrical relays, after simulating all the phase-/ground-fault cases
each relay, taking into account fault resistance, DG infeed, and the indicated in Section 4. As described in Section 4, these cases refer to
mode of system operation, i.e. grid-connected vs. islanded mode. The different fault types, fault resistance, DG infeed, and mode of system
following assumptions additionally hold in the present application: operation (i.e. grid-connected/islanded). Note that, during the simula-
tions, it was also confirmed that the faults are detected by the relays in
• As for the simulation of phase (LLL and LL) faults, the maximum the correct direction. The bolded values in Table 1 correspond to the
fault resistance considered during the simulations is indicatively maximum values calculated by FDEs/RDEs in each column, i.e. the
taken equal to five times the initial (basic) positive reactance reach maximum values of list a-c calculated by FDEi, j /RDEi, j of each relay
of a distance element, based on the relevant assumption of [23]. DRi, j , considering all the simulated fault cases.
Based on Subsection 3.2, the minimum required positive reactance Based on the latter values, the final relay settings of Table 2 are
reach in primary ohms (Ω pri) of all FDEs and RDEs in the test extracted. Specifically, for each distance relay, settings 1–3 from the list
system (which might be further extended depending on the simu- of Subsection 4.1 are given for the corresponding phase/ground FDE
lation results) is 2 Ω and 2.53 Ω, respectively (i.e. 120% of the (PFDE/GFDE) and phase/ground RDE (PRDE/GRDE). Table 2 does not
protected conductor’s reactance). This results in a maximum fault include settings for FDE1,0 and FDE10,0 , as they will be individually
resistance of 10 Ω and 12.65 Ω, respectively. However, for determined later. To consider a safety margin ε for certain fault

Table 2
Reactance/resistance reach settings (in Ω pri) and time data of the phase/ground FDE/RDE of each relay.
Distance Settings/Time data DR0,1, DR1,0, DR1,2, DR2,1, DR2,3, DR3,2, DR3,4, DR4,3, DR4,5, DR5,4, DR5,6, DR1,9, DR2,10, DR3,7, DR4,8,
element DR0,10 DR10,0 DR10,9 DR9,10 DR9,8 DR8,9 DR8,7 DR7,8 DR7,6 DR6,7 DR6,5 DR10,2 DR9,1 DR8,4 DR7,3

FDEi,j +XPFDEi,j/+XGFDEi,j 3/37 – 3/32 2/48 5/37 2/64 2/21 3/45 2/16 2/68 2/25 3/32 2/48 2/21 3/45
|−XPFDEi,j|/|−XGFDEi,j| 0/26 – 0/23 1/26 1/29 2/36 1/36 1/23 0/6 1/60 0/12 0/23 1/26 1/36 1/23
+RPFDEi,j/+RGFDEi,j 60/ – 54/ 60/ 57/ 80/ 50/ 54/ 17/40 83/ 28/65 54/ 60/142 50/ 54/
118 106 142 147 190 185 127 287 106 185 127
tFi,j (s) 0.04 – 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04
tC = tFi,j + tCB (s) 0.1 – 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

RDEi,j +XPRDEi,j/+XGRDEi,j – 13/57 13/67 12/50 17/89 17/59 12/62 11/28 17/94 4/20 6/33 13/67 12/50 12/62 11/28
|−XPRDEi,j|/|−XGRDEi,j| – 0/28 3/29 1/25 3/39 1/31 1/25 1/39 2/64 0/8 1/13 3/29 1/25 1/25 1/39
+RPRDEi,j/+RGRDEi,j – 99/ 99/ 88/ 131/ 92/ 88/ 80/ 137/ 27/45 44/74 99/ 88/125 88/ 80/
141 166 125 221 177 147 228 354 166 147 228
tRi (s) – 0.58 0.58 0.60 0.60 0.63 0.63 0.65 0.65 0.69 0.69 0.58 0.60 0.63 0.65
tC = tRi + tCB (s) – 0.64 0.64 0.66 0.66 0.69 0.69 0.71 0.71 0.75 0.75 0.64 0.66 0.69 0.71

464
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Fig. 9. (a) Reactance calculated by DR0,1, (b) Resistance calculated by DR0,1.

detection (see Section 4), the settings of Table 2 result from the cor- be mentioned that the response time of a relay varies from model to
responding bolded values of Table 1, rounded up to the next integer. model and it could be even lower. The time delay tBF of the BF function
Note that a relatively low ε is considered here for illustration purposes, is set to 15 cycles in all the relays, to ensure correct BF operation (see
i.e. in order to keep discernible the correspondence of the bolded values Subsection 3.3).
of Table 1, to the respective settings of Table 2. Of course, a much Concerning settings 4–6 from the list of Subsection 4.1, they are
greater ε could be normally considered. equally adopted for all FDEs/RDEs, according to the angle-setting phi-
Furthermore, the offline fault-simulations that gave the ultimate losophy described in Section 4:
relay settings of Table 2 were repeated in the time-domain, in order to
further check the validity of the relay settings. It was found that the • The angle of the right/down zone blinder (θ /θ ) is set equal to 90°.
r d
magnitudes of the reactance/resistance values calculated by the relays • The angle of the left zone blinder (θ ) is set equal to zero.
l
(after their response time) were always below the corresponding reach
settings of Table 2, so the relays performed well. Two representative Focusing on FDE1,0 and FDE10,0 , a high negative reactance and po-
examples of time-domain relay calculations are given in Fig. 9a and sitive resistive reach setting is required, as realized from the italicized
Fig. 9b, which illustrate the reactance (X) and resistance (R), respec- values in Table 1. This is particularly due to the weak current flowing
tively (in secondary Ω), calculated by DR0,1 during a 40-Ω SLG fault in through DR1,0/DR10,0 during faults in L0,1/L0,10, in the grid-connected
front of DR1,0, in the islanded mode of system operation. The fault is mode, with PL = 0. Such great reach values are not settable, based on
assumed occurring at t = 0, while, a 2-cycle time-window is considered, the reach setting range of common commercial distance relays. Al-
equal to the response time of the relay used. This specific fault de- though, as mentioned before, this could be addressed by the relay de-
termined the −XGFDE0,1 and the +RGFDE0,1 setting of GFDE0,1 (shown signers, in order to take into account the most restrictive case, FDE1,0
with dashed line in Fig. 9a and Fig. 9b respectively). It appears that the and FDE10,0 are replaced by RDEb1,0 and RDEb10,0 , respectively (see
magnitudes of the reactance and resistance calculated by the relay are Subsection 3.2), set according to (12). The rest values of Table 1 are
slightly (due to the low ε considered previously) lower than the cor- settable in several commercial distance relays.
responding relay settings. Hence, the relay proves efficient against these Table 3 includes the positive reactance reach ( + XRDEb1,0 ), negative
marginal fault cases. Just to mention, as part of this study, the relay reactance reach magnitude, (|−X |RDEb1,0 ) and positive resistive reach
calculations were based on a sampling frequency of 1000 Hz, con- ( + RRDEb1,0 ) of phase and ground RDEb1,0 (PRDEb1,0 and GRDEb1,0 , re-
sidering 20 samples/cycle, and a full-cycle Discrete Fourier Transform spectively), set according to (12). Note that +XL0,1 and +RL0,1 of (12)
(DFT) filter. The current and voltage transformation ratio is 60 and 200, are equal to 1.67 Ω and 1.075 Ω, respectively. These settings are equally
respectively. applied to phase/ground RDEb10,0 , which is symmetrical to RDEb1,0 .
Table 2 also includes the tRi settings of all RDEs, as resulted ac- The rest RDEbs’ settings are determined according to Subsection 4.3 and
cording to Subsection 4.2 and considering a CTI of 0.3 s. An example of are listed below:
relay-fuse coordination is illustrated in Fig. 10a. Specifically, Fig. 10a
shows the minimum-melting and total-clearing curve of fuse F1 (30T- • The angle of the right/down zone blinder (θ /θ ) is set equal to 90°.
r d
fuse), as well as its tTC,max (0.275 s), which results from the less severe • The angle of the left zone blinder (θ ) is set equal to zero.
l
fault simulated at the endpoint of lateral L1 (leading to a short-circuit
current IL1,min of 623 A flowing through F1). In this particular case, this No intentional time delay is set for RDEb, i.e. it trips after 2 cycles
was a SLG fault at the endpoint of L1, in the grid-connected mode of (response time of the relay).
system operation, with PL = 0. By setting the time delay tR1 of GARDE1 Finally, Table 4 shows the maximum load current (IL,max ) flowing on
relays according to (10), i.e. equal to 0.58 s, we ensure that, in case of a each line segment Li, j , determined through a proper pre-fault load-flow
fault in L1, these relays will let F1 clear the fault first. simulation study (see Subsection 4.2). Specifically, for determining
Moreover, Table 2 gives the tripping (response) time tFi,j (uninten- IL,max values, load flow simulations were conducted in the grid-con-
tional time delay) of each FDEi,j, as well as the overall fault clearing nected/islanded mode of system operation, for a variety of cases. These
time (tC) corresponding to each FDE and RDE (see Subsection 3.2 for tC cases resulted from consecutively disconnecting main line segments or
explanation), during any fault in its assigned line part. Note that CBs laterals in the examined network. In addition, in each one of the re-
with an interrupting time (tCB) of 60 ms (3 cycles) are considered, sulting cases during the grid-connected mode of the system, sub-cases
while, as mentioned previously, the response time of the particular were formed by considering all the possible connections of the DG
relay model chosen for the simulation study is 40 ms (2 cycles). It has to units.

465
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Fig. 10. (a) Coordination between fuse F1 and the relays of GARDE1, (b) Phase and ground zone characteristics of DR1,2.

Table 3 regarding several influencing factors and proper relay setting are noted.
Settings of phase/ground reverse blocking elements. This work proposes a distance-based protection scheme for meshed
Distance elements +XRDEb1,0 (Ω pri) |−X|RDEb1,0 (Ω pri) +RRDEb1,0 (Ω pri)
distribution systems, intending to address all the protection issues that
could be encountered in practice.
PRDEb1,0/GRDEb1,0 2/36 2/28 59/117

6.1.2. All the factors affecting distance relay operation are addressed
The impedance setting ZLE of the LE element, enabled for the phase To ensure that the applied distance protection scheme is reliable
RDE of both relays installed at the opponent ends of each line segment under realistic system conditions, the concurrent effect of all the factors
Li,j, is also included in Table 4. This setting is calculated based on the influencing distance relay operation in distribution systems (e.g. DG
corresponding IL,max, increased by a safety margin of 25%. Note that, infeed, fault resistance and K0), must be properly considered [46] (also
since the same current magnitude IL,max flows in symmetrical line seg- see Section 2). So far, a complete solution in this direction has not been
ments, the corresponding relays have the same ZLE setting. Remember proposed as part of distance protection applications for distribution
that FDEs do not require a LE element, since, at least one of the oppo- systems. Several relevant research efforts intend to deal with the effect
nent FDEs in a main line segment does not see the load current in its trip of DG infeed, but they do not address (at least properly) the effect of
direction. Also note that in the cases where the resulting ZLE is greater fault resistance. The latter is critical, as the nature of its effect is un-
than the positive resistive reach of the corresponding phase RDE, a LE predictable and can lead to intense underreach or overreach phe-
element does not have to be ultimately enabled for this RDE. nomena. Especially in case of ground faults, due to the concurrent effect
The representative case of DR1,2 is chosen in Fig. 10b, to illustrate of K0, the overreach effect of fault resistance can be very intense, so, it
the resulting phase (solid lines)/ground (dashed lines) zone character- requires special attention [46]. On the other hand, a few proposed
istic of FDE1,2 and RDE1,2 , and the corresponding LE element. approaches which intend to deal with the fault resistance effect (non-
empirically), either display limited efficiency under the presence of DG
and various system changes [32], or they are not applicable against SLG
6. Advantages of the proposed protection scheme and comparison faults [33], which, besides they are the most frequent, they are the main
with other protection principles cause of intense overreach phenomena, as mentioned previously.
The proposed methodology takes into account the concurrent
6.1. Advantages of the proposed protection scheme compared to other (overall) effect of the aforementioned influencing factors, by con-
distance-based schemes ducting a proper simulation study, considering various combinations of
DG-production, fault-type, fault-resistance and system-operation sce-
This work intends to address all the issues encountered so far in the narios at the same time. Remember that protection sensitivity against
literature, concerning the application of distance protection to dis- all these factors is achieved by suitably setting (extending) distance
tribution systems with DG (see Section 1). In the following, the main zones, so that the most severe impedance calculation errors, observed
contributions of this paper, compared to relevant research efforts (as for each relay, are covered. At the same time, protection security is
those cited in Section 1), are summarized. ensured through the permissive logic applied. The above philosophy
constitutes the main difference of the proposed scheme compared to
6.1.1. An efficient distance protection scheme for meshed distribution other distance protection schemes which intend to subtract impedance
systems is proposed calculation errors from the calculated impedance [30,33]. Specifically,
So far, the vast majority of research efforts, dealing with the topic of although it seems a promising solution, such a compensation of im-
distance protection for distribution systems, regard radial network pedance calculation errors is difficult to be applied against all fault
configurations. There are limited papers applying distance protection to types and/or fault conditions. On the other hand, the proposed ap-
looped/meshed networks, but, even in these cases, significant issues proach “allows” the appearance of these errors, and deals with them

Table 4
Maximum load in each segment and load encroachment settings.
Line segment (Li,j) L0,1, L0,10 L1,2, L10,9 L2,3, L9,8 L3,4, L8,7 L4,5, L10,9 L5,6 L1,9, L2,10 L3,7, L4,8

IL,max (A) 279 126 167 70 55 28 126 70


ZLE (Ω pri) 33 73 55 132 168 330 73 132

466
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Table 5
Number of examined cases where DOCRs failed to trip.
DOCRi,j DOCR1,0, DOCR10,0 DOCR1,2, DOCR10,9 DOCR2,1, DOCR9,10 DOCR2,3, DOCR9,8 DOCR3,2, DOCR8,9 DOCR4,5, DOCR7,6 DOCR1,9, DOCR10,2 DOCR2,10, DOCR9,1

Ip,ph (A) 349 158 158 209 209 69 158 158


Ip,g (A) 84 38 38 50 50 17 38 38
TNOC 8 4 6 12 10 2 4 6

through a proper relay setting and communication logic. The methodology presented in this work uses existing distance relay
technology, so as to enhance the applicability of the proposed scheme.
6.1.3. A fixed setting group is determined for each relay At the same time, all the relevant issues concerning the application of
So far, several distance-relaying applications for distribution sys- distance protection to distribution systems are addressed. Note that the
tems, which consider both the grid-connected and the islanded mode of specifications (e.g. reach setting limitations) of commercially-available
system operation [27,30,31,35,36,43], have not extensively studied the distance relays are also taken into account in this work.
suitability of distance relay settings under a variety of system and fault
conditions (e.g. different fault types, different fault resistance values 6.2. Comparison with a directional overcurrent protection scheme
etc.). Furthermore, in some distance-based applications, multiple set-
ting groups are applied against different system conditions (adaptive A critical advantage of distance relays is that distance zones can be
logic) [29,37,43,44]. suitably extended to protect against faults with a considerable fault
As part of the proposed methodology, a single setting group is de- resistance, whereas, this is not always possible with directional over-
termined for each relay, suitable for all the expected system conditions. current relays, due to sensitivity limitations. Assume, for instance, that
Hence, an adaptive logic is avoided, maintaining protection simplicity. each DRi, j in Fig. 2 is replaced by a directional overcurrent relay
DOCRi, j . More specifically, assume that each (forward or reverse) phase
6.1.4. A solution against weak-infeed conditions is proposed distance element is replaced by a (forward or reverse, respectively)
Research efforts dealing with the application of distance protection definite-time phase overcurrent element, which picks-up for currents
to distribution systems have not provided a detailed solution against the larger than 125% of the corresponding line segment’s maximum load
problem of insufficient distance zone reach sensitivity due to weak-in- (see Table 4). In addition, assume that each (forward or reverse) ground
feed conditions so far. This problem is described in Subsection 3.2.2. A distance element is replaced by a (forward or reverse, respectively)
problem of the same nature is noted for a pilot-based directional definite-time ground overcurrent element, which picks-up for residual
overcurrent protection scheme in [12], even for a solid fault. However, currents larger than 30% of the corresponding line segment’s maximum
the solution proposed in this case leads to the disconnection of the load. After simulating exactly the same faults as those simulated for
whole distribution system. setting the distance relays (see Section 4), it was observed that some
In this work, the aforementioned issue is dealt with, while, at the DOCRs failed to trip, unlike the corresponding distance relays which
same time, selectivity is maintained; in other words, the fault is cleared performed well. Table 5 shows the pairs of symmetrical DOCRs which
by disconnecting only the faulted line segment (see Subsection 3.2.2). failed to trip, the total number of examined cases (TNOC) where this
happened for each DOCR pair, and the pick-up current of the phase and
6.1.5. Coordination with lateral protection is ensured, also providing ground element of each DOCR (Ip, ph and Ip, g , respectively). It has to be
backup protection for the laterals and maintaining maximum protection noted that, in several cases of Table 5, DOCRs failed to trip even for
speed for the main line solid faults.
It is a fact that many studies applying distance protection to dis-
tribution systems do not consider the coordination of distance relays 6.3. Comparison with a differential protection scheme
with other protection means encountered in distribution systems (as
overcurrent relays or fuses). Nevertheless, actual distribution networks It is a fact that differential protection could also be considered as a
include laterals protected by separate means (usually fuses). Normally, reliable solution for meshed distribution systems, providing sensitivity
main line protection should coordinate with lateral protection and and security. However, the main drawback of differential schemes is
serve as backup protection for the laterals. Furthermore, in other ap- their inability to inherently provide backup protection [51]. For in-
plications where coordination of distance zones with lateral protection stance, let us assume that the distance-based scheme protecting each
is addressed (e.g. [24–26]), the distance zones’ time delay has to be main line segment in Fig. 2 is replaced by a typical differential scheme.
properly adjusted for this purpose, also affecting protection speed Although the differential scheme protecting a segment Li,j is expected to
against main line faults. perform well against a variety of faults in Li,j, it cannot simultaneously
As part of the proposed scheme, separate distance elements are serve as primary protection for its adjacent buses Bi, Bj and backup
enabled in each relay for the primary protection of the main line (FDE) protection for its adjacent laterals Li, Lj. That means that separate
and the backup protection of its adjacent lateral (RDE). In this way, protection schemes (differential or other) would be required for bus/
FDEs can be set to operate instantaneously, while, RDEs can be set with lateral protection, which is not so practical. Instead, the proposed dis-
a proper time delay to coordinate with lateral fuses, without affecting tance-based scheme, protecting each segment Li,j (using FDEs), exploits
protection speed in the main line. the multiple distance elements provided by a common commercial
distance relay, settable in the forward or reverse direction, to protect
6.1.6. A solution applicable with existing distance relay technology is adjacent buses and laterals as well (using RDEs), without installing a
proposed separate relay.
It is a fact that most distance protection concepts addressed in the Also note that, every protection scheme (even a differential one)
literature apply common distance relay technology. However, as de- considered for protecting laterals, should coordinate with the corre-
scribed, significant issues are not dealt with. Some studies intend to sponding lateral fuse, thus it should be set with a proper time delay.
include alternative functions [30,31,33] or characteristics [32] in dis- Within this context, a differential scheme would not differ from the
tance relays, to improve their performance; however, significant issues proposed distance-based scheme in terms of protection speed. In other
are noted in those cases as well. words, both these schemes would trip instantaneously in case of a main

467
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

Table 6
Maximum fault resistance (in Ω) sensed by the distance and the differential scheme during SLG faults at the midpoint of main line segments.
Mode Applied scheme L0,1, L0,10 L1,2, L10,9 L2,3, L9,8 L3,4, L8,7 L4,5, L7,6 L5,6 L1,9 L2,10 L3,7 L4,8

GC Distance 242 400 274 306 186 452 400 400 306 306
Differential 217 216 216 216 216 215 216 216 216 216

ISL Distance 290 336 217 292 181 437 336 336 292 292
Differential 207 207 208 209 208 208 207 207 209 209

line fault, and with the same time delay in case of a lateral fault. takes into account specifications of commercially-available distance
Furthermore, since communication latency is negligible, it does not relays, its applicability is enhanced. The advantages of the designed
affect protection speed either in the distance-based or in the differential distance-based protection scheme, compared to a directional-over-
scheme. current-based and a differential-based protection scheme, as well as to
Despite the aforementioned drawback of the differential scheme other proposed distance protection schemes, are also addressed.
concerning bus/lateral protection, it would be interesting to compare To sum up, the main contributions of the proposed distance-based
the performance of the proposed distance scheme to that of a differ- protection scheme are that (i) it constitutes an efficient distance pro-
ential one, against faults in main line segments. It is true that the dif- tection solution for meshed distribution systems, (ii) it deals with the
ferential scheme is expected to perform well against all the main line concurrent effect of all the factors affecting distance relay operation,
faults simulated previously for setting the distance-based scheme, as it (iii) it applies a fixed setting group to each relay, suitable for different
can display adequate sensitivity. Hence, a substantial comparison of fault/system conditions, (iv) it deals with weak-infeed conditions, (v) it
these two schemes could be performed for (ground) faults with high coordinates with lateral protection means, maintaining maximum
resistance. For this comparison, actual relay sensitivity limits have been protection speed for the main line, and (vi) it is based on existing dis-
considered for both the distance and the differential element, based on tance relay technology and realistic relay specifications.
the specifications of a typical commercial multifunctional relay of a
well-established manufacturer. Specifically, the ground distance ele- Acknowledgements
ment applied has a maximum settable reactive and resistive reach of
500 secondary Ω, and a maximum measured phase and sequence cur- The authors would like to thank HEDNO S.A. (Xanthi area) and
rent sensitivity of 5%In, where In is the corresponding current trans- especially the Director V. Sarris for providing them with all the ne-
former’s (CT) nominal current. The differential element applied has a cessary data to model the test distribution system as part of this work.
minimum differential pick-up current of 20%In. Note that a current This work was supported by the General Secretariat for Research
transformation ratio of 60 is considered for all the distance/differential and Technology (GSRT)/Hellenic Foundation for Research and
relays and a voltage transformation ratio of 200 is considered for all the Innovation (HFRI).
distance relays.
Table 6 shows the maximum fault resistance accompanying a SLG References
fault at the midpoint of each main line segment of the system of Fig. 2,
which can be sensed by the distance and the differential scheme. Faults [1] Bollen MH, Hassan F. Integration of distributed generation in the power system.
were simulated in both the grid-connected (GC) and the islanded (ISL) New York: Wiley-IEEE Press; 2011.
[2] Celli G, Pilo F, Pisano G, Allegranza V, Cicoria R, Iaria A. Meshed vs. radial MV
mode of system operation, considering DG. Actually, Table 6 includes distribution network in presence of large amount of DG. In: IEEE PES PSCE, New
the maximum fault resistance sensed in each case, for which the cor- York; 2004. p. 709–14.
responding sensitivity limits of the previous paragraph are not violated. [3] Gellings C. Estimating the costs and benefits of the smart grid. A preliminary esti-
mate of the investment requirements and the resultant benefits of a fully functioning
It is apparent that the distance-based scheme can protect against faults smart grid. Electric Power Research Institute, Rep. 1022519, Palo Alto, CA; 2011.
with higher resistance in the vast majority (90%) of the simulated fault [4] Fairman JR, Zimmerman K, Gregory JW, Niemira JK. International drive distribu-
cases. Note, however, that this percentage might vary depending on the tion automation and protection. Pullman, WA: SEL Inc.
[5] Lauria S, Codino A, Calone R. Protection system studies for ENEL Distribuzione's MV
particular relay model installed (i.e. the sensitivity limits of the relay)
loop lines. In: PowerTech, Eindhoven, Netherlands; 2015. p. 1–6.
and the fault/system conditions. [6] Alam MN, Das B, Pant V. An interior point method based protection coordination
scheme for directional overcurrent relays in meshed networks. Int J Electric Power
Energy Syst 2016;81:153–64.
7. Conclusion [7] Yazdaninejadi A, Nazarpour D, Golshannavaz S. Dual-setting directional over-cur-
rent relays: an optimal coordination in multiple source meshed distribution net-
works. Int J Electric Power Energy Syst 2017;86:163–76.
This paper proposes a distance protection scheme for meshed dis- [8] Saleh KA, Zeineldin HH, Al-Hinai A, El-Saadany EF. Optimal coordination of di-
tribution systems with DG, aiming to disconnect only the faulted line rectional overcurrent relays using a new time-current-voltage characteristic. IEEE
part, avoiding unnecessary disconnection of consumers and/or DG Trans Power Del 2015;30(2):537–44.
[9] Ojaghi M, Mohammadi V. Use of clustering to reduce the number of different setting
units. Separate distance elements are enabled in each relay for main groups for adaptive coordination of overcurrent relays. IEEE Trans Power Del
line protection and bus/lateral protection, ensuring maximum protec- 2018;33(3):1204–12.
tion speed for main line faults and relay-fuse coordination for lateral [10] Papaspiliotopoulos VA, Korres GN, Kleftakis VA, Hatziargyriou ND. Hardware-in-
the-loop design and optimal setting of adaptive protection schemes for distribution
faults. Permissive pilot protection allows the extension of the distance systems with distributed generation. IEEE Trans Power Del 2017;32(1):393–400.
zones, in order to achieve efficient protection under the effect of DG [11] Liu Z, Su C, Høidalen HK, Chen Z. A multiagent system-based protection and control
and fault resistance, while, undesired trips due to overreach are scheme for distribution system with distributed-generation integration. IEEE Trans
Power Del 2017;32(1):536–45.
avoided; hence, the proposed protection scheme guarantees protection [12] Che L, Khodayar ME, Shahidehpour M. Adaptive protection system for microgrids:
sensitivity and security at the same time. An efficient solution against protection practices of a functional microgrid system. IEEE Electrific Mag
weak-infeed conditions, which normally affect relay sensitivity, is also 2014;2(1):66–80.
[13] Liu X, Shahidehpour M, Li Z, Liu X, Cao Y, Tian W. Protection scheme for loop-
proposed. The offline relay setting procedure is conducted only once,
based microgrids. IEEE Trans Smart Grid 2017;8(3):1340–9.
and the resulting settings are suitable for both the grid-connected and [14] Aghdam TS, Karegar HK, Zeineldin HH. Variable tripping time differential protec-
the islanded mode of system operation, as well as for all the expected tion for microgrids considering DG stability. IEEE Trans Smart Grid [in press].
[15] Kar S, Samantaray SR, Zadeh MD. Data-mining model based intelligent differential
fault/system conditions, avoiding the use of adaptive logic. Since the
microgrid protection scheme. IEEE Syst J 2017;11(2):1161–9.
proposed scheme is based on existing distance relay technology and

468
A.M. Tsimtsios et al. Electrical Power and Energy Systems 105 (2019) 454–469

[16] Li X, Dyśko A, Burt GM. Traveling wave-based protection scheme for inverter- p. 1–6.
dominated microgrid using mathematical morphology. IEEE Trans Smart Grid [34] Ziegler G. Numerical distance protection: principles and applications. Erlangen,
2014;5(5):2211–8. Germany: Publicis Publishing; 2011.
[17] Bukhari SBA, Zaman MSU, Haider R, Oh YS, Kim CH. A protection scheme for [35] Elkhatib M, Ellis A, Biswal M, Brahma S, Ranade S. Protection of renewable-
microgrid with multiple distributed generations using superimposed reactive en- dominated microgrids: challenges and potential solutions. Sandia National
ergy. Int J Electric Power Energy Syst 2017;92:156–66. Laboratories, Rep. SAND2016-11210, Albuquerque, NM; 2016.
[18] Zhang Z, Xu B, Crossley P, Li L. Positive-sequence-fault-component-based blocking [36] Elkhatib M, Ellis A. Communication-assisted impedance-based microgrid protection
pilot protection for closed-loop distribution network with underground cable. Int J scheme. In: IEEE PES General Meeting, Chicago, IL; 2017. p. 1–5.
Electric Power Energy Syst 2018;94:57–66. [37] Lin H, Guerrero JM, Vásquez JC, Liu C. Adaptive distance protection for microgrids.
[19] Gers JM, Holmes EJ. Protection of electricity distribution networks. London, UK: In: 41st Annu Conf IEEE Ind Electron Soc (IECON 2015), Yokohama, Japan; 2015.
IET; 2004. pp. 725–30.
[20] Hooshyar A, Iravani R. Microgrid protection. Proc IEEE 2017;105(7):1332–53. [38] El-Arroudi K, Joós G. Performance of interconnection protection based on distance
[21] Chang J, Gara L, Fong P, Kyosev Y. Application of a multifunctional distance pro- relaying for wind power distributed generation. IEEE Trans Power Del
tective IED in a 15KV distribution network. In: 66th Annu Conf Protective Relay 2018;33(2):620–9.
Engineers, College Station, TX; 2013. p. 150–71. [39] Huang W, Nengling T, Zheng X, Fan C, Yang X, Kirby BJ. An impedance protection
[22] Enayati A, Ortmeyer TH. A novel approach to provide relay coordination in dis- scheme for feeders of active distribution networks. IEEE Trans Power Del
tribution power systems with multiple reclosers. In: North Amer Power Symp, 2014;29(4):1591–602.
Charlotte, NC; 2015. p. 1–6. [40] Xu M, Zou G, Xu C, Sun W, Mu S. Positive sequence differential impedance pro-
[23] Sinclair A, Finney D, Martin D, Sharma P. Distance protection in distribution sys- tection for distribution network with IBDGs. In: POWERCON, Wollongong,
tems: how it assists with integrating distributed resources. IEEE Trans Ind Appl Australia; 2016. p. 1–5.
2014;50(3):2186–96. [41] Biller M, Jaeger J, Mladenovic I, Schacherer C, Wolter D, Stoetzel M. Protection
[24] Nikolaidis VC, Arsenopoulos C, Safigianni AS, Vournas CD. A distance based pro- systems in distribution grids with variable short-circuit conditions. In: DPSP 2016,
tection scheme for distribution systems with distributed generators. In: PSCC, Edinburgh, UK. p. 1–5.
Genoa, Italy; 2016. p. 1–7. [42] Chilvers I, Jenkins N, Crossley P. Distance relaying of 11kV circuits to increase the
[25] Tsimtsios AM, Nikolaidis VC. Application of distance protection in mixed overhead- installed capacity of distributed generation. IEE Proc – Gen Transm Distrib
underground distribution feeders with distributed generation. In: DPSP 2018, 2005;152(1):40–6.
Belfast, UK. p. 1–6. [43] El Naily N, Saad SM, Elsayed RE, Aomura SA, Mohamed FA. Planning & application
[26] Pandakov K, Høidalen HK, Marvik JI. Implementation of distance relaying in dis- of distance relays coordination for IEC microgrid considering intermediate in-feed
tribution network with distributed generation. In: DPSP 2016, Edinburgh, UK. factor. In: 9th Int Renewable Energy Congr, Hammamet, Tunisia; 2018. p. 1–6.
p. 1–7. [44] Liu Z, Høidalen HK, Saha MM. An intelligent coordinated protection and control
[27] Lin H, Liu C, Guerrero JM, Vásquez JC. Distance protection for microgrids in dis- strategy for distribution network with wind generation integration. CSEE J Power
tribution system. In: 41st Annu Conf IEEE Ind Electron Soc (IECON 2015), Energy Syst 2016;2(4):23–30.
Yokohama, Japan; 2015. p. 731–6. [45] Tsimtsios AM, Nikolaidis VC. Setting zero-sequence compensation factor in distance
[28] Uthitsunthorn D, Kulworawanichpong T. Distance protection of a renewable energy relays protecting distribution systems. IEEE Trans Power Del 2018;33(3):1236–46.
plant in electric power distribution systems. In: POWERCON, Hangzhou, China; [46] Nikolaidis VC, Tsimtsios AM, Safigianni AS. Investigating particularities of infeed
2010. p. 1–6. and fault resistance effect on distance relays protecting radial distribution feeders
[29] Ma J, Li J, Wang Z. An adaptive distance protection scheme for distribution system with DG. IEEE Access 2018;6:11301–12.
with distributed generation. In: 5th Int Conf Critical Infrastructure, Beijing, China; [47] Kasztenny B, Cambell B, Mazereeuw J. Phase selection for single-pole
2010. p. 1–4. tripping–Weak infeed conditions and cross-country faults. In: 27th Annu Western
[30] Biswas S, Centeno V. A communication based infeed correction method for distance Protective Relay Conf, Spokane, WA; 2000. p. 1–19.
protection in distribution systems. In: North Amer Power Symp, Morgantown, WV; [48] Costello D, Zimmerman K. Determining the faulted phase. In: 63rd Annu Conf
2017. p. 1–5. Protective Relay Engineers, College Station, TX; 2010. p. 1–20.
[31] Jin L, Jiang M, Yang G. Fault analysis of microgrid and adaptive distance protection [49] Xue Y, Thakhar M, Theron JC, Erwin DP. Review of the breaker failure protection
based on complex wavelet transform. In: PEAC, Shanghai, China; 2014. p. 360–4. practices in utilities. In: 65th Annu Conf Protective Relay Engineers, College
[32] Jecu C, Raison B, Caire R, Alibert P, Deschamps P, Chilard O, Grenard S. Protection Station, TX; 2012. p. 260–8.
scheme based on non communicating relays deployed on MV distribution grid. In: [50] Grigsby LL. Electric power generation, transmission and distribution. Boca Raton,
PowerTech, Grenoble, France; 2013. p. 1–6. FL: CRC Press; 2012.
[33] Pandakov K, Høidalen HK. Distance protection with fault impedance compensation [51] Ziegler G. Numerical differential protection: principles and applications. Erlangen,
for distribution network with DG. In: IEEE PES ISGT-Europe, Torino, Italy; 2017. Germany: Publicis Publishing; 2012.

469

Anda mungkin juga menyukai