- PREDIMENSIONAMIENTO DE COLUMNAS
DATOS Predimensionamie
f'c = 210 kg/cm2 fy = 4200kg/cm2
columna = 0.25 x 0.25 (asumido)
Vigas (XX=YY) = 0.25 x 0.45
losa maciza = e = 0.15m
(considerando losa maciza en todos los niveles)
Tab. Equival. = 220 kg/m2
s/c (último nivel) = 100 kg/m2 PLANO DISTRIBUID
s/c = 200 kg/m2
Muros Per im. = e = 0.15m
ep = 0.05 m
P.e. conc. Armado = 2400 kg/m3
P.e. conc. Simple = 2000 kg/m3
P.e. Ladrillo = 1600 kg/m3
P. vigas = 6512.40kg
P. columnas = 1560.00kg
P. losa maciza = 8703.55kg
P. muro perim. = 10508.16kg Pm =34.17ton
P. tab. equiv. = 5983.69kg Pv =7.25ton
P. piso = 906.62kg
s/c (último nivel) = 1813.24kg
s/c (resto nivel) = 5439.72kg
SUMA = 41427.38kg =41.43ton
COLUMNA C-2
Lx = 4.95m L muro perim= 1.52m
Ly = 2.86m Área = 14.16m2
L col = 2.60m
P. vigas = 8434.80kg
P. columnas = 1560.00kg
P. losa maciza = 13590.72kg
P. muro perim. = 3793.92kg
P. tab. equiv. = 9343.62kg Pm =38.14ton
P. piso = 1415.70kg Pv =11.33ton
s/c (último nivel) = 2831.40kg
s/c (resto nivel) = 8494.20kg
SUMA = 49464.36kg =49.46ton
COLUMNA C-3
Lx = 1.87m L muro perim= 2.96m
Ly = 2.86m Área = 5.35m2
L col = 2.60m
6
P. vigas = 5108.40kg
P. columnas = 1560.00kg
P. losa maciza = 5134.27kg
P. muro perim. = 7388.16kg Pm =23.26ton
P. tab. equiv. = 3529.81kg Pv =4.28ton
P. piso = 534.82kg
s/c (último nivel) = 1069.64kg
s/c (resto nivel) = 3208.92kg
5
SUMA = 27534.02kg =27.53ton
COLUMNA C-4
Lx = 1.59m L muro perim= 4.26m
Ly = 4.26m Área = 6.77m2
L col = 2.60m
4
P. vigas = 6318.00kg
P. columnas = 1560.00kg
P. losa maciza = 6502.46kg
P. muro perim. = 10632.96kg Pm =30.16ton
3
P. tab. equiv. = 4470.44kg Pv =5.42ton
P. piso = 677.34kg
s/c (último nivel) = 1354.68kg
s/c (resto nivel) = 4064.04kg
SUMA = 35579.93kg =35.58ton
COLUMNA C-5 2
Lx = 3.13m L muro perim= 0.00m
Ly = 4.24m Área = 13.27m2
L col = 2.60m
P. vigas = 7959.60kg
P. columnas = 1560.00kg
P. losa maciza = 12740.35kg
P. muro perim. = 0.00kg Pm =32.35ton 1
P. tab. equiv. = 8758.99kg Pv =10.62ton
P. piso = 1327.12kg
1
COLUMNA C-6
Lx = 3.41m L muro perim= 0.00m
Ly = 4.24m Área = 14.46m2
L col = 2.60m
P. vigas = 8262.00kg
P. columnas = 1560.00kg
P. losa maciza = 13880.06kg
P. muro perim. = 0.00kg Pm =34.69ton
P. tab. equiv. = 9542.54kg Pv =11.57ton
P. piso = 1445.84kg
s/c (último nivel) = 2891.68kg
s/c (resto nivel) = 8675.04kg
SUMA = 46257.17kg =46.26ton
COLUMNA C-7
Lx = 1.87m L muro perim= 4.24m
Ly = 4.24m Área = 7.93m2
L col = 2.60m
P. vigas = 6598.80kg
P. columnas = 1560.00kg
P. losa maciza = 7611.65kg
P. muro perim. = 10583.04kg Pm =32.38ton
P. tab. equiv. = 5233.01kg Pv =6.34ton
P. piso = 792.88kg
s/c (último nivel) = 1585.76kg
s/c (resto nivel) = 4757.28kg
SUMA = 38722.42kg =38.72ton
COLUMNA C-8
Lx = 1.59m L muro perim= 3.20m
Ly = 3.20m Área = 5.09m2
L col = 2.60m
P. vigas = 5173.20kg
P. columnas = 1560.00kg
P. losa maciza = 4884.48kg
P. muro perim. = 7987.20kg Pm =23.47ton
P. tab. equiv. = 3358.08kg Pv =4.07ton
P. piso = 508.80kg
s/c (último nivel) = 1017.60kg
s/c (resto nivel) = 3052.80kg
SUMA = 27542.16kg =27.54ton
COLUMNA C-9
Lx = 3.13m L muro perim= 0.00m
Ly = 3.20m Área = 10.02m2
L col = 2.60m
P. vigas = 6836.40kg
P. columnas = 1560.00kg
P. losa maciza = 9615.36kg
P. muro perim. = 0.00kg Pm =25.62ton
P. tab. equiv. = 6610.56kg Pv =8.01ton
P. piso = 1001.60kg
s/c (último nivel) = 2003.20kg
s/c (resto nivel) = 6009.60kg
SUMA = 33636.72kg =33.64ton
COLUMNA C-10
Lx = 3.41m L muro perim= 0.00m
Ly = 3.20m Área = 10.91m2
L col = 2.60m
P. vigas = 7138.80kg
P. columnas = 1560.00kg
P. losa maciza = 10475.52kg
P. muro perim. = 0.00kg Pm =27.47ton
P. tab. equiv. = 7201.92kg Pv =8.73ton
P. piso = 1091.20kg
s/c (último nivel) = 2182.40kg
s/c (resto nivel) = 6547.20kg
SUMA = 36197.04kg =36.20ton
COLUMNA C-11
Lx = 1.87m L muro perim= 3.20m
Ly = 3.20m Área = 5.98m2
L col = 2.60m
P. vigas = 5475.60kg
P. columnas = 1560.00kg
P. losa maciza = 5744.64kg
P. muro perim. = 7987.20kg Pm =25.32ton
P. tab. equiv. = 3949.44kg Pv =4.79ton
P. piso = 598.40kg
s/c (último nivel) = 1196.80kg
s/c (resto nivel) = 3590.40kg
SUMA = 30102.48kg =30.10ton
COLUMNA C-12
Lx = 1.59m L muro perim= 3.23m
Ly = 3.23m Área = 5.14m2
L col = 2.60m
P. vigas = 5205.60kg
P. columnas = 1560.00kg
P. losa maciza = 4930.27kg
P. muro perim. = 8062.08kg Pm =23.66ton
P. tab. equiv. = 3389.56kg Pv =4.11ton
P. piso = 513.57kg
s/c (último nivel) = 1027.14kg
s/c (resto nivel) = 3081.42kg
SUMA = 27769.64kg =27.77ton
COLUMNA C-13
Lx = 3.13m L muro perim= 0.00m
Ly = 3.23m Área = 10.11m2
L col = 2.60m
P. vigas = 6868.80kg
P. columnas = 1560.00kg
P. losa maciza = 9705.50kg
P. muro perim. = 0.00kg Pm =25.82ton
P. tab. equiv. = 6672.53kg Pv =8.09ton
P. piso = 1010.99kg
s/c (último nivel) = 2021.98kg
s/c (resto nivel) = 6065.94kg
SUMA = 33905.75kg =33.91ton
COLUMNA C-14
Lx = 3.41m L muro perim= 0.00m
Ly = 3.23m Área = 11.01m2
L col = 2.60m
P. vigas = 7171.20kg
P. columnas = 1560.00kg
P. losa maciza = 10573.73kg
P. muro perim. = 0.00kg Pm =27.68ton
P. tab. equiv. = 7269.44kg Pv =8.81ton
P. piso = 1101.43kg
s/c (último nivel) = 2202.86kg
s/c (resto nivel) = 6608.58kg
SUMA = 36487.24kg =36.49ton
COLUMNA C-15
Lx = 1.80m L muro perim= 3.23m
Ly = 3.23m Área = 5.81m2
L col = 2.60m
P. vigas = 5432.40kg
P. columnas = 1560.00kg
P. losa maciza = 5581.44kg
P. muro perim. = 8062.08kg Pm =25.05ton
P. tab. equiv. = 3837.24kg Pv =4.65ton
P. piso = 581.40kg
s/c (último nivel) = 1162.80kg
s/c (resto nivel) = 3488.40kg
SUMA = 29705.76kg =29.71ton
COLUMNA C-16
Lx = 1.59m L muro perim= 4.44m
Ly = 4.44m Área = 7.06m2
L col = 2.60m
P. vigas = 6512.40kg
P. columnas = 1560.00kg
P. losa maciza = 6777.22kg
P. muro perim. = 11082.24kg Pm =31.30ton
P. tab. equiv. = 4659.34kg Pv =5.65ton
P. piso = 705.96kg
s/c (último nivel) = 1411.92kg
s/c (resto nivel) = 4235.76kg
SUMA = 36944.83kg =36.94ton
COLUMNA C-17
Lx = 3.10m L muro perim= 0.00m
Ly = 4.44m Área = 13.76m2
L col = 2.60m
P. vigas = 8143.20kg
P. columnas = 1560.00kg
P. losa maciza = 13213.44kg
P. muro perim. = 0.00kg Pm =33.38ton
P. tab. equiv. = 9084.24kg Pv =11.01ton
P. piso = 1376.40kg
s/c (último nivel) = 2752.80kg
s/c (resto nivel) = 8258.40kg
SUMA = 44388.48kg =44.39ton
COLUMNA C-18
Lx = 3.41m L muro perim= 0.00m
Ly = 4.44m Área = 15.14m2
L col = 2.60m
P. vigas = 8478.00kg
P. columnas = 1560.00kg
P. losa maciza = 14534.78kg
P. muro perim. = 0.00kg Pm =36.08ton
P. tab. equiv. = 9992.66kg Pv =12.11ton
P. piso = 1514.04kg
s/c (último nivel) = 3028.08kg
s/c (resto nivel) = 9084.24kg
SUMA = 48191.81kg =48.19ton
COLUMNA C-19
Lx = 1.87m L muro perim= 4.44m
Ly = 4.44m Área = 8.30m2
L col = 2.60m
P. vigas = 6814.80kg
P. columnas = 1560.00kg
P. losa maciza = 7970.69kg
P. muro perim. = 11082.24kg Pm =33.74ton
P. tab. equiv. = 5479.85kg Pv =6.64ton
P. piso = 830.28kg
s/c (último nivel) = 1660.56kg
s/c (resto nivel) = 4981.68kg
SUMA = 40380.10kg =40.38ton
COLUMNA C20
Lx = 1.59m L muro perim= 3.98m
Ly = 2.54m Área = 4.04m2
L col = 2.60m
P. vigas = 4460.40kg
P. columnas = 1560.00kg
P. losa maciza = 3877.06kg
P. muro perim. = 9934.08kg Pm =22.90ton
P. tab. equiv. = 2665.48kg Pv =3.23ton
P. piso = 403.86kg
s/c (último nivel) = 807.72kg
s/c (resto nivel) = 2423.16kg
SUMA = 26131.75kg =26.13ton
COLUMNA C-21
Lx = 3.13m L muro perim= 3.13m
Ly = 2.54m Área = 7.95m2
L col = 2.60m
P. vigas = 6123.60kg
P. columnas = 1560.00kg
P. losa maciza = 7632.19kg Nº COL.
P. muro perim. = 7812.48kg Pm =29.17ton 1
P. tab. equiv. = 5247.13kg Pv =6.36ton 2
P. piso = 795.02kg 3
s/c (último nivel) = 1590.04kg 4
s/c (resto nivel) = 4770.12kg 5
SUMA = 35530.58kg =35.53ton 6
7
8
COLUMNA C-22 9
Lx = 3.41m L muro perim= 3.41m 10
Ly = 2.54m Área = 8.66m2 11
L col = 2.60m 12
13
14
P. vigas = 6426.00kg 15
P. columnas = 1560.00kg 16
P. losa maciza = 8314.94kg 17
P. muro perim. = 8511.36kg Pm =31.39ton 18
P. tab. equiv. = 5716.52kg Pv =6.93ton 19
P. piso = 866.14kg 20
s/c (último nivel) = 1732.28kg 21
s/c (resto nivel) = 5196.84kg 22
SUMA = 38324.09kg =38.32ton 23
COLUMNA C-23
Lx = 1.87m L muro perim= 4.16m
Ly = 2.54m Área = 4.75m2
L col = 2.60m
P. vigas = 4762.80kg
P. columnas = 1560.00kg
P. losa maciza = 4559.81kg
P. muro perim. = 10383.36kg Pm =24.88ton
P. tab. equiv. = 3134.87kg Pv =3.80ton
P. piso = 474.98kg
s/c (último nivel) = 949.96kg
s/c (resto nivel) = 2849.88kg
SUMA = 28675.66kg =28.68ton
C - 18 Pn = 101.57ton t= 29.32cm
3
Por reglamento b >= 25cm, por lo tanto obtengo como dimensionamiento de
columnas:
Columnas en esquinas b x t = 0,30m x 0,30m
Columnas perimetrales b x t = 0,30m x 0,30m
2
Columnas interiores b x t = 0,30m x 0,30m
1
1.- PREDIMENSIONAMIENTO DE LOSA
Predimensionamiento:
Lado largo/lado corto= 1.68 < 2 (Losa armada en 2 direcciones)
Espesor de la losa:
h>= Ln/40= 0.15 m
h>= Perímetro/180= 0.12 m
h = 0.15
PLANO DISTRIBUIDO POR PAÑOS PARA LOSAS
C - 20 C - 21 C - 22 C - 23
I II
C - 16 C - 17 C - 18 C - 19
III IV V
C - 12 C - 13 C - 14 C - 15
VI
C-8 C-9 C - 10 C - 11
VII VII IX
X XI
A B C D
6 6
C - 20 C - 21 C - 22 C - 23
5 5
C - 16 C - 17 C - 18 C - 19
4 4
C - 12 C - 13 C - 14 C - 15
3 3
C-8 C-9 C - 10 C - 11
2 2
C-4 C-5 C-6 C-7
A B C D
C-1 C-2 C-3
1 1
A B C D
Nº COL. Pm (ton) Pv (ton) ∑ Ps (ton) PU (ton)
31.6 6.06 37.68 54.573
49.2 10.1 59.36 86.139
21.5 3.46 25 35.974
27.3 4.49 31.82 45.898
43.2 9.05 52.29 75.916
49.2 10.1 59.36 86.139
28.8 5.34 34.15 49.416
23.1 3.39 26.46 38.055
34.6 6.83 41.45 60.076
39 7.48 46.43 67.244
23.7 4.03 27.77 40.083
23.2 3.41 26.59 38.244
34.8 6.89 41.71 60.456
39.2 7.54 46.73 67.681
41.6 5.8 47.39 68.091
27.9 4.62 32.47 46.843
44.3 9.31 53.57 77.797
49.5 10.2 59.7 86.637
29.4 5.5 34.92 50.54
16.6 2.61 19.16 27.611
28.4 5.26 33.61 48.637
30.6 5.75 36.33 52.583
18.8 3.1 21.9 31.589
IDENTIFICACION DE COLUMNAS:
A B´ C D
6 6
C - 20 C - 21 C - 22 C - 23
I II III IV
5
V VI VII VIII 5
C - 16 C - 17 C - 18 C - 19
4 IX X XI XII 4
C - 12 C - 13 C - 14 C - 15
XIII XVI
3 3
C-8 XIV C-9 XV C - 10 C - 11
2
XVII XVIII
C-4 C-5
XIV C-6
XX
C-7
2
XIII
C-8 XIV C-9 XV C - 10 XVI
C - 11
2
XVII XVIII
C-4 C-5
XIV C-6
XX
C-7
2
C-1
XXI XXII C-2
XXIII
C-3
1 1
A B C D
2.- PREDIMENSIONAMIENTO DE VIGAS
DATOS:
Lnx= 5.88
Lny= 4.70
EJE X-X:
PERALTE "h"
Lnx
h=
12
h= 5.88 = 0.490
12
h= 0.50 (Elegir)
ANCHO "b"
b ≥ 0.25 ó b ≥ 0.30 h
b= 0.25 (Elegir)
EJE Y-Y:
PERALTE "h"
Lny
h=
12
h= 4.70 = 0.392
12
h= 0.40 (Elegir)
ANCHO "b"
b ≥ 0.25 ó b ≥ 0.30 h
b= 0.25 (Elegir)
1
1
6
2
2
1
4.- ANALISIS ESTATICO DE UNA VIVIENDA
F4
F3
F2
F1
AREA EN PLANTA= 66.91 m2
DESCRIPCION
CATEGORIA DE LAS EDIFICACIONES ( U )
A Edificaciones Esenciales
B Edificaciones Importantes
C Edificaciones Comunes
SISTEMA ESTRUCTURAL
1 Pórticos
2 Dual
3 Muros estructurales
4 Muros de ductilidad limitada
5 Albañileria Armada o confinada
6 Madera
REGULARIDAD
R Regular
I Irregular
TIPO DE ESTRUCTURA
1 Sólo pórticos
2 Pórticos más ascensor (Duales )
3 Albañilería confinada o armada y sólo muros de corte
1 Concreto Armado
2 Albañileria
3 Madera
Zona 4 Z = 0.45
Categoría C U = 1
S/C = 0.25
Tipo de suelo 1 S = 1
Tp = 0.4
Sistema estructural 1 R = 8
Regularidad R Ri = 0.9
Tipo de Estructura (Periodo T=hn/Ct) 1 Ct = 35
Distorsión máxima de entrepiso Di ≤ 0.007
DATOS
f'c = 210 kg/cm2 fy = 4200kg/cm2
columna = 0.40 x 0.40
Vigas XX 0.25 x 0.45
Vigas yy 0.25 x 0.45
losa aligerado = e = 0.20m
Tab. Equival. = 100 kg/m2
s/c (último nivel) = 100 kg/m2
s/c = 200 kg/m2
ep = 0.05 m
P.e. conc. Armado = 2400 kg/m3
3º nivel
Peso Area (m2) Longitud (m) Nº de elementos Peso (Kg)
P.losa 300 kg/m2 66.9100 1.00 20073.00
P. cieloraso 100 kg/m2 66.9100 1.00 6691.00
2400 kg/m3 0.1125 2.24 2.00 1209.60
2400 kg/m3 0.1125 3.78 2.00 2041.20
P. en vigas eje x
2400 kg/m3 0.1125 1.14 1.00 307.80
2400 kg/m3 0.1125 3.10 4.00 3348.00
2400 kg/m3 0.1125 2.38 3.00 1927.80
P. en vigas eje y 2400 kg/m3 0.1125 2.55 3.00 2065.50
2400 kg/m3 0.1125 3.33 3.00 2697.30
P. de columnas 2400 kg/m3 0.1600 1.50 13.00 7488.00
47849.20
2º nivel
Peso Area (m2) Longitud (m) Nº de elementos Peso (Kg)
P.losa 300 kg/m2 66.9100 1.00 20073.00
P. cieloraso 100 kg/m2 66.9100 1.00 6691.00
2400 kg/m3 0.1125 2.24 2.00 1209.60
2400 kg/m3 0.1125 3.78 2.00 2041.20
P. en vigas eje x
2400 kg/m3 0.1125 1.14 1.00 307.80
2400 kg/m3 0.1125 3.10 4.00 3348.00
2400 kg/m3 0.1125 2.38 3.00 1927.80
P. en vigas eje y 2400 kg/m3 0.1125 2.55 3.00 2065.50
2400 kg/m3 0.1125 3.33 3.00 2697.30
P. de columnas 2400 kg/m3 0.1600 3.00 13.00 14976.00
P. Tabiqueria 100 kg/m2 66.9100 1.00 6691.00
62028.20
1º nivel
Peso Area (m2) Longitud (m) Nº de elementos Peso (Kg)
P.losa 300 kg/m2 66.9100 1.00 20073.00
P. cieloraso 100 kg/m2 66.9100 1.00 6691.00
2400 kg/m3 0.1125 2.24 2.00 1209.60
2400 kg/m3 0.1125 3.78 2.00 2041.20
P. en vigas eje x
2400 kg/m3 0.1125 1.14 1.00 307.80
2400 kg/m3 0.1125 3.10 4.00 3348.00
2400 kg/m3 0.1125 2.38 3.00 1927.80
P. en vigas eje y 2400 kg/m3 0.1125 2.55 3.00 2065.50
2400 kg/m3 0.1125 3.33 3.00 2697.30
P. de columnas 2400 kg/m3 0.1600 3.75 13.00 18720.00
P. Tabiqueria 100 kg/m2 66.9100 1.00 6691.00
65772.20
SISTEMA APORTICADO
Ubicación CHICLAYO
Factor zona ( Z ) 0.45
Factor suelo ( S ) 1
Factor uso ( U ) 1
Fator de reducción de fuerza sísmica ( R ) 8
Factor predominante del suelo ( Tp ) 0.4
Sistema estructural ( Ct ) 35
Altura de terreno a partir del suelo ( hn ) 10.5
Período de vibración de la estructura ( T ) 0.3
Coeficiente de amplificación sísmica ( C ) 3.33 2.5
Pesos totales
hn
Niveles Pesos (kg) Pesos (tn)
T
Ct
3º 49521.95 49.52195
2º 68719.20 68.7192 Tp
C 2 .5 x 2 .5
1º 72463.20 72.4632 T
ZUSC
Peso total (Kg) 190704.35
190.70
V
R
P
Peso total (ton)
Fuerza Sismica =
F1 = 6.42 Ton
F2 = 10.15 Ton
2º CALCULO DE LAS FUERZAS DE SISMO F3 = 10.24 Ton
Ic 40x40 = 213333.33 cm
Ivxx 25x40 = 189843.75 cm
Ivyy 25x40 = 189843.75 cm
Rigidez de columnas:
Rigidez de vigas:
DIRECCION EN EL EJE Y -Y
PORTICO A y D
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc 3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc 4 Kt 3 Kt 4
R = 8
E = 217.37065119 ton/cm2
DIRECCION EN EL EJE Y -Y
PORTICO C
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc4 Kt3 Kt 4
R = 8
E = 217.37065119 ton/cm2
DIRECCION EN EL EJE Y -Y
286.74 341.88 533.33 337.55 ∑Kt4 =
PORTICO B
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc 4 Kt 3 Kt 4
R = 8
E = 217.37065119 ton/cm2
DIRECCION EN EL EJE X -X
PORTICO 2,3,4 y 5
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h 3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc4 Kt3 Kt 4
DIRECCION EN EL EJE X -X
PORTICO 6
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc3 Kt 2
12
PARA EL ULTIMO ENTREPISO :
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc4 Kt3 Kt 4
R = 8
E = 217.37065119 ton/cm2
DIRECCION EN EL EJE X -X
PORTICO 1
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc4 Kt3 Kt 4
R = 8
E = 217.37065119 ton/cm2
PORTICO EN LA DIRECCION Y - Y
USANDO LAS FORMULAS DE WILBUR
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc 3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc 4 Kt 3 Kt 4
R = 8
E = 217.37065119 ton/cm2
PORTICO EN LA DRECCION X - X
48E
R2 48E
R3
4h 2 h1 h 2 h 2 h3 4 h3 h 2 h3 h3 h 4
h 3
Kt 3
h2
K c2 Kt1 Kc1 Kt2 Kc 3 Kt 2
12
4 8E
R4
4h 4 2 h3 h 4 h4
h4
Kc4 Kt3 Kt 4
R = 8
E = 217.37065119 ton/cm2
Qi (ton)
#REF!
10.24
20.40
26.82 #REF!
#REF! #REF!
10.24 #REF!
20.40 #REF!
26.82 #REF!
APLICANDO EL PERIODO DE RAYLEIGH
DIRECCION Y-Y
PixDi 2
T 2 #REF! segundos
gx FixDi
hn
T 0.300 segundos
Ct
DIRECCION X-X
PixDi 2
T 2 #REF! segundos
gx FixDi
hn
T 0.300 segundos
Ct
A B C D
6 6
C - 20 C - 21 C - 22 C - 23
A1
5 5
C - 16 C - 17 C - 18 C - 19
4 4
A2 A3
C - 12 C - 13 C - 14 C - 15
3 3
C-8 C-9 C - 10 C - 11
2 2
C-4 C-5 C-6 C-7
Y C-1 C-3
1 1
A B C D
X
NIVEL FUERZA LONGITUD EN PLANTA MOMENTOS DE TORSION
( ton ) L(x-x) L(y-y) Mxx( t-m ) Myy( t-m )
4 #REF! 20.00 10.00 #REF! #REF!
2 10.24 20.00 10.00 5.12 10.24
3 10.15 20.00 10.00 5.08 10.15
1 6.42 20.00 10.00 3.21 6.42
2514.72
#REF!
2514.72
#REF!
2514.72
#REF!
2514.72
#REF!
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF! #REF!
#REF! #REF!
#REF! #REF!
#REF! #REF!
2514.72
#REF!
2514.72
#REF!
2514.72
#REF!
2514.72
2844.44
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
0.0093
1499.50
#REF!
1499.50
#REF!
1499.50
#REF!
1499.50
1896.30
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
0.0145
1719.97
#REF!
1719.97
#REF!
1719.97
#REF!
1719.97
#REF!
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
#REF!
1719.97
#REF!
2359.36
#REF!
2359.36
#REF!
2359.36
#REF!
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
#REF!
828.06
#REF!
828.06
#REF!
828.06
#REF!
828.06
#REF!
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
#REF!
DRECCION Y-Y
9043.68
#REF!
9043.68
#REF!
9043.68
#REF!
9043.68
#REF!
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
#REF!
#REF!
DRECCION X-X
9427.91
#REF!
10067.29
#REF!
10067.29
#REF!
10067.29
#REF!
h3 h3 h 4
2 Kt 3
Di < 0.007
#REF!
#REF!
#REF!
#REF!
#REF!
δti (cm)
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
#REF!
D
6
C - 23
5
C - 19
3
C - 15
3
C - 11
2
C-7
C-3
D
PREDIMENSIONAMIENTO DE PLACAS
1) METRADO
4º nivel
1er nivel
Total :
Total :
Datos :
Ubicación : Chiclayo - Lambayeque
Uso : Vivenda
htotal(m): 12.40
Z 0.4 ZUSC
ec
r ia
es a U 1.0 V
R
P
S 1.4
R 7
Ct 45
Tp 0.9
Donde :
C 8.165 C<=2.5 C=
V(ton) 209.01445
SISTEMA DUAL
Ubicación CHICLAYO
Factor zona 0.4
Factor suelo 1.4
Factor uso 1
Fator de reducción de fuerza sísmica 7
Factor predominante del suelo (Tp) 0.9
Sistema estructural 45
Altura de terreno a partir del suelo 12.4
Período de vibración de la estructura 0.28
Coeficiente de amplificación sísmica 8.04 2.5
Niveles Pesos
1 303373.5 303.3735
2.3 325395.9 325.3959
4 224107.0 224.10695
Nivel W H WH WH/SUMA(W/H)
4 325.40 12.4 4034.909 0.3812
3 325.40 9.6 3123.801 0.2951
2 325.40 6.8 2212.692 0.2090
1 303.37 4.0 1213.494 0.1146
SUMA 10584.89592
COLS 0.3 0.3
VIGAS XX 0.25 0.4
VIGAS YY 0.25 0.45
Peso (Kg)
74897.28
5201.2
16648.8
21465
41609.6
6350.4
Peso (Kg)
10402.4
215706.95 176574.68 18.141404345
Peso (Kg)
74897.28
20804.8
16648.8
21465
41609.6
12700.8
Peso (Kg)
10402.4
274995.9 198528.68 27.80667639
Peso (Kg)
68489.28
19024.8
15304.8
21465
41609.6
13154.4
Peso (Kg)
10402.4
279373.5 189450.28 32.187455145
1045072.25
1045.072
2.5
1.4V
EAnecesaria
Vc
Longitud (m)
2.5 0.625
2.5 0.625
25000 50000
2.5
F(ton) Q(ton)
89.829 89.829
69.545 159.373
49.261 208.634
27.016 235.650