TESCO TRAINING
DEPARTMENT
• INTERLOCKS
• MAIN POWER
• MD-500 DRIVE SYSTEM
• COOLING SYSTEM
• PLC CONTROLLER
INTERLOCKS
This following interlocks exist and should be considered
when operating, maintaining or troubleshooting the system.
Precharge:
• Coolant flow must be verified.
• The ENABLE switch must be in the OFF position.
• The ESD button must be pulled out.
• Control power must be present at each SCM.
• Cabinet humidity must be less than 90% RH.
• Communication must be verified between the SCM.
© 2013 Tesco Corporation. All rights reserved. 3
TROUBLESHOOTING
INTERLOCKS
MR-8
INTERLOCKS
INTERLOCKS DRW-98XXX113
INTERLOCKS
INTERLOCKS DRW-98XXX202
INTERLOCKS
INTERLOCKS DRW-98XXX109
INTERLOCKS
INTERLOCKS DRW-98XXX202
INTERLOCKS
INTERLOCKS
INTERLOCKS
Valve Open:
• When the VALVE switch is set to OPEN, the auxiliary pump
starts automatically and interlocks prevent quill rotation.
The valve-open circuit is programmed to operate on a 5-
second timer, which means the circuit remains energized for
5 seconds from the moment the switch is released. This is to
ensure full opening of the valve even if the switch is only
briefly selected.
INTERLOCKS
Valve Close:
• In drill-forward mode, interlocks prevent quill rotation until
the 5-second timed sequence is completed. Set SPEED
switch to INCR to re-start rotation.
• In drill-reverse mode, interlocks prevent quill rotation until
the 5-second timed sequence is completed. Set TORQUE
switch to INCR to re-start rotation.
• In connect mode, interlocks prevent quill rotation until the
5-second timed sequence is completed, after which the quill
will resume rotation at the pre-set speed.
INTERLOCKS
INTERLOCKS
Grabber Open:
• The GRABBER OPEN switch activates an 8-second operating
period timed from the moment the switch is released.
Grabber Close:
• The grabber will not close unless quill rotation is less than 5
rpm.
INTERLOCKS
INTERLOCKS
Mud Pump:
• Relay DR-1 is energized by the PLC whenever the VALVE
switch is set to CLOSE. One set of n/o contacts of DR-1 is
used to energize an air valve (mud pump) using Cord “D”
from the driller’s panel.
Drawwork:
• The PLC energizes relay DR-2, located within the driller’s
panel, whenever the grabber is closed. The contacts of this
relay are wired to the drawwork control circuits or air valve
and prevent the drawwork from being hoisted.
INTERLOCKS DRW-98XXX213
INTERLOCKS
Resolver Failure
Resolver failure can include failure of any of the following:
• Resolver.
• Resolver circuitry within the CCB.
• Resolver signal cables.
• Resolver isolation board (Resolver Protection Package).
MAIN POWER
TVSS
TVSS DRW-98581107
000.00 000.00
600.00
000.00 000.00
120.00
Yes No
Ensure:
- 120 VAC is present in all SCM’s. Check the “blown fuse”
- SCM’s switches are in ON position. indication light (F3).
-All Precharge interlock relays (MR-5, MR-6)
are receiving 120 VAC to pin 8 & 7, and NO
contacts 5 & 3 are closing.
Yes
Is the fuse
Replace the fuse
indicator light ON
No
Check:
- 120 VAC is present before
and after fuse.
- If the light bulb is funtional.
No
Yes
Yes
Yes Confirm:
- The corresponding brake over-temperature
Is either B2or B3 - 24 VDC at pins 10&2 on MR-8.
B light OFF
thermostat is malfunctioning, or
- NO contacts 1&3 are closing.
- Brake is over-heating
- Replace relay if necessary.
No
Yes
Is it 24 VDC
Confirm that the High Humidity present on MR-8
interlock (SSR-9) is not engaged.
No
Check:
- Output card light A9 on PLC.
- Loos termination.
- Card and terminal block are properly
seated.
- Replace output card if necessary.
© 2013 Tesco Corporation. All rights reserved. 40
TROUBLESHOOTING
MR-5
MR-10
MR-8
MR-7
MR-9
Start
Check:
- Confirm 120 VAC in terminals A1 and A2 of the No
relay, if so, confirm that NO contact 11-14 is Yes Reconfirm the drive
closing, if not replace the relay. Is the light ON is Precharged. Raw
- If NO contact is closing, the breaker might have Bus ≈ 830 VDC
a faulty UV trip coil or the breaker itself is faulty.
- Check for loose connection.
No
No
Check:
- Drive’s HVCB (lose connections).
- Confirm HVCB CB Interlock relay
(U1) is closing (Term J4, pins 1 and 4).
5. Unit precharges to 830 VDC on all drives, all breakers set, DRW-98XXX113
but after two minutes all drive breakers trip. 98XXX114
If the auxiliary contacts of all breakers do not make contact when the
corresponding breaker is closed, after approximately two minutes the
precharge timer relay will time-out and all breakers will trip through the
ESD Interlock Relay.
a. Confirm that all breakers’ auxiliary contacts (set 2) are closing.
b. If all auxiliary contacts are closing, confirm blocking Diode D1, which
is mounted on MPP terminal strip.
5. Unit precharges to 830 VDC on all drives, all breakers set, DRW-98XXX113
but after two minutes all drive breakers trip. 98XXX114
• Tracking
• Top drive will not enable
• Top drive will not rotate
• Top drive disables during rotation
• One DRS drive is unstable
• Top drive increases to and/or remains at rated speed
• Power connector problems
• Top drive function problems
• Expanded DRS troubleshooting procedures
© 2013 Tesco Corporation. All rights reserved. 54
TROUBLESHOOTING
TRACKING
TRACKING
TRACKING
Half Tracking
TRACKING
Full Tracking
TRACKING
Conditions:
- Trip the drive breakers.
- System in precharge mode. What to do..?
- Ensure breakers are NOT set.
- Drive is disabled.
Start - Drive breakers ARE NOT set, or
- Disconnect the service loop from power
module.
- Drive breakers ARE set. Voltage WAS NOT
- Precharge the system. Check for tracking.
present before the breakers were set.
Yes
Fault might be in the
Vbus still track?
drive
No
TRACKING
Probable Causes and Recommended Actions
TRACKING
Probable Causes and Recommended Actions
or Buck choke shorted to Lock out the power and confirm buck chokes with a
Multimeter.
Minor Track ground Meter buck chokes in reference to ground.
signal to IGBT)
© 2013 Tesco Corporation. All rights reserved. 61
TROUBLESHOOTING
TRACKING
Buck Gate Driver board Test points (715-106374)
TRACKING
Test points IGBT 1: TP6 (gate), TP10 (emitter)
Test points
TRACKING
Buck Gate Driver board Test points (101164-X)
TRACKING
Test points IGBT 1: TP1(gate), TP2 (emitter)
Check:
- Quill direction switch is in neutral.
Start - Module ON light is illuminated.
- Lab View for any fault.
Yes
Ready light
Module light
© 2013 Tesco Corporation. All rights reserved. 68
TROUBLESHOOTING
Mud saver
interlock
relay
If none of the above checks isolate the Run each drive individually from LabView (not
greater than 10rpm).
problem, run each drive (motor) This will confirm if the problem is isolated to a
separately from LabView. single drive or an external input signal problem.
No
No
Replace Resolver
For timing:
Test points on
CCB: TP-54/JP-29
Noisy:
CONNECT FORWARD/REVERSE
CONNECT FORWARD/REVERSE
PreReg or Inverter Temperatures.
PLC Interlocks.
• PLC will disable rotation If the mudsaver VALVE
switch is set to OPEN or CLOSE.
Mud saver
interlock
relay
BREAKOUT
Yes
System Components.
• Heat pump, controlled by:
electronic thermostat.
heat pump humidistat.
• Building heater, controlled by electronic thermostat.
• Dehumidifier.
• System monitoring (MODULE ON light on driller’s panel
flashes)
© 2013 Tesco Corporation. All rights reserved. 114
TROUBLESHOOTING
Start
Power module
Module ON light Relative Humidity
ambient
flashing (1/10 a level is greater than
temperature is
second) 80-90%
greater than 68°F
Yes Yes
Yes Close the door or
Is the power module Is the power module Is the power module
Close the door check sensor and
building door open building door open building door open
circuit.
No No No
No
Check the following:
- Confirm heat pump breaker is in the ON position. Yes
- Confirm heat pump ON/OFF switch is in the ON position.
Yes - Heat pump shut down on low head pressure.
Heat pump cut out or - Confirm chiller is operational.
is turned OFF - Faulty humidistat.
- Faulty electronic thermostat.
- Heat pump fan not operating.
- Heat pump compressor failure.
- Check heat pump diagnostic lights.
© 2013 Tesco Corporation. All rights reserved. 119
TROUBLESHOOTING
Heat Cool
Symptom Probable cause (s) ing ing
Correction
Contactors
Compressor
Blower motor
Control Tx
High pressure inadequate air flow X check, clean, blower the coil
Freeze
protection
switch
© 2013 Tesco Corporation. All rights reserved. 125
TROUBLESHOOTING
PLC TROUBLESHOOTING
Considerations:
• Stand clear of controlled equipment when power is applied.
• Never reach into a machine to operate a switch since
unexpected motion could occur, causing injury.
• Remove all electrical power at the Main Power Disconnect
to ensure total power removal.
• Always remove power before inserting or removing
modules, or before connecting I/O cabling.
PLC TROUBLESHOOTING
PROFICY
Fuse for 24
VDC to PLC
PLC TROUBLESHOOTING
Fuse to PLC
PLC TROUBLESHOOTING
PLC TROUBLESHOOTING
PROFICY
PROFICY
PROFICY
PLC TROUBLESHOOTING
PLC TROUBLESHOOTING
PLC TROUBLESHOOTING
PROFICY
PLC TROUBLESHOOTING
PROFICY
PLC TROUBLESHOOTING
PROFICY
PROFICY
PROFICY
PROFICY
PLC TROUBLESHOOTING
PROFICY
PROFICY
PLC TROUBLESHOOTING
PROFICY
QUESTIONS