• Current monitoring
This is normally done by a current transformer (CT): a
very low impedance transformer which acts as a
current source to a protection timing relay (the CT
burden).
• Timing of operation
This requires a specific current-time (I-t) operating
characteristic – this may be a protection relay or a
microprocessor controller. It provides the tripping
signal to a circuit breaker after a suitable pre-
programmed time delay, i.e. short for high currents and
longer for low currents.
A fuse has a rudimentary timing system as part of its
pre-arcing I 2t characteristic.
• A circuit interrupter
This is either a fuse or a circuit breaker which is
actuated by the relay after some appropriate time.
2. Zones of Protection
• Transformers
These need high-speed differential protection with 6
CTs, three on each side to monitor input and output.
• Motors/generators
Need high speed differential protection, again with 6
CTs.
• Overhead lines
These need high speed “pilot wire” protection with
6 CTs. The pilot wires are relatively long cable
connections from the ends of the line to the
4. Protection Relays
Function
Auxiliary
Protection
Monitoring
Control
Type
Electromagnetic
Electronic/Computer-based
Non-electric (e.g. thermal, pressure, mechanical etc.)
ELEC9713: Industrial and Commercial Power Systems p. 6
Parameters sensed
Current
Voltage
Frequency
Power
Temperature
Pressure
Velocity
For large scale systems and circuits where there are many
radial lines with a number of fault current protective
devices located in series, the time discrimination of the
operation to a through-fault becomes of great importance
in achieving optimum performance with minimal
disruption.
The use of two CTs for unit protection systems, where the
outputs are compared and subtracted, relies on the two
CTs being identical in their characteristics. This is not
always the case even for the same design. Such
differences may be a limitation of the sensitivity of the
differential protection scheme. In the case of transformer
unit protection schemes, where the input and output
currents are quite different, because of the transformer
ratio, the CT design and choice is thus of paramount
importance.
3
Standard t= t = 3s at M = 10
log10 M
1.6
Very Inverse t= t = 1.6s at M = 10
( log10 M )
2
0.6
Extremely Inverse t = t = 0.6s at M = 10
( log10 M )
3
Time variation
Operating
by TMS
Time, t
Operating current
variation by PS
Current (PSM)
The plug setting allows tappings of the relay coil (or the
equivalent in electronic relays) to give seven discrete
settings in terms of the rated trip current. These are:
20%, 30%, 40%, 50%, 60%, 70% and 80% of the rated
tripping current.
Similarly, a PSM value which is just less than 1.0 may not
always guarantee non-operation of the relay: nuisance or
non-fault generated operation may occur at a PSM of
about 0.95 in some cases. Thus a value of PSM which is
less than about 0.8 is generally used in the normal
operational phase design to ensure non-operation of the
relay under normal operational conditions.
Transformer
33/11kV 20MVA
Transformer
IDMT relay current transformer
[1000/5]
circuit
11kV breaker
busbar
CT
Feeder
[400/5]
IDMT relay
PS=125%
TMS=0.3 feeders
Feeder relay:
I = 1050 A
A B C D
CT CT CT
Supply 800:1 500:1 250:1
X X X
At Maximum Fault
loads levels
D 180A 6000A
C 200A 7000A
B 220A 8000A
ELEC9713: Industrial and Commercial Power Systems p. 24
The motor at D is 15kW. Its full-load current is 28A and
the starting current is 6 times the full-load current during
the starting period of 5 seconds. The fuses shown are the
largest rating at each busbar (i.e. the longest operating
times).
1. Relay RC at C
I Fault = 6000A at D.
6000
∴ PSM = = 19.2 during fault
312.5
7000
PSM = = 22.4
312.5
Top = 2.22 s
380
Thus: = 0.76 so PS = 100% is OK
500
520
Start: = 1.04 OK PS = 100% is OK
500
600
Thus steady-state: = 0.75 PS = 100% is OK
800
740
Start: = 0.93 OK
800
Use PS = 100%
I F = 8000A
8000
PSM = = 10 ⇒ top = 3.0s
800
Thus:
Example:
Single circuit connected to 15A socket outlet. Cable is
2.5mm2 Cu conductor, 2 core & earth V75 TPS, nominal
ambient temperature not exceeding 40oC.
ELEC9713: Industrial and Commercial Power Systems p. 31
Option 1: Install cable on a surface partially surrounded
by thermal installation
Table 9 of AS3008.1 → I Z = 18A
Nominal commercial current rating of protection
device I N = 16A
(a) Coordination requirement:
I B (15A ) ≤ I N (16A ) ≤ I Z (18A ) O.K
(b) Overload protection requirement:
I 2 ≤ 1.45 I Z = 1.45 × 18 = 26.1A
For MCB: I N = I Z = 18A
For HRC fuse: I N = 0.9 I Z = 16.2A
Thus, both coordination and protection requirements
are met by using either 16A MCB or 16A HRC fuse.
Ring core of N
N L magnetic material L1
Load L2
Load L 3
Under healthy conditions the currents in the conductors
passing through the toroidal transformer are balanced,
there is no flux induced in the core and no voltage induced
in the secondary coil of the transformer.