Anda di halaman 1dari 5

Protection, maintenance and testing of capacitor units 26/963

This inherent time delay may be too long to protect the purpose by providing necessary protection to the
capacitors during a fault. To overcome this, a spark gap capacitors, on the one hand, and restoring the line natural
is additionally provided across the capacitors, which will impedance (i.e. the original fault level) by short-circuiting
spark-over instantaneously at the preset value and limit the capacitors, on the other.
the fault current to the required level during a fault Rapid reinsertion of the capacitors as soon as the
condition and bypass the capacitors as illustrated in Figure fault conditions are removed is an important requirement
26.11. Extinction of the arc is achieved by the bypass to retain the stability of the system. This can be achieved
breaker, which closes soon after (3 to 5 cycles from with the use of an additional ZnO, non-linear resistance
initiation of the fault). (ZnO being the latest in this field compared to SiC, which
The excessive line current results in a high voltage was being used earlier), across the capacitor banks (Figure
drop across the capacitors (ISC · XC), which sparks over 26.12). Generally, the ZnO resistor will be adequate to
the gap generally set at about 2.5 to 3 times the nominal damp the fault current without initiating the spark gap,
voltage of the capacitors. This high voltage for an and will limit the over-voltage across the capacitors. It
extremely short duration will economize on the cost of will also permit automatic reinsertion of the capacitors
capacitors. The arc will be sustained only until the fault as soon as the fault conditions are removed without causing
clears or the line de-energizes or the bypass breaker closes, a delay. The spark gap will serve as a backup to the ZnO
whichever occurs first. The arc will extinguish at every resistor in the event of very severe faults.
current zero and attempt to insert the capacitors back The above bypass facility can also be achieved with
into the line. The arc will reappear until the over-voltage the use of a thyristor switch, which may be made current
attenuates to less than the spark-over-voltage, or the line sensing or voltage sensing.
de-energizes or the bypass breaker closes. The capacitors
must therefore be suitable to withstand repeated transient
voltages developed during each arcing. 26.2 Installation and maintenance of
A CT is provided in series with the spark gap to sense capacitor units
its operation during a line fault. As soon as there is arcing,
it provides an instantaneous command to a short-circuit The following are suggestions for the successful operation
relay. The relay, in turn, closes the bypass breaker, within of the capacitor units installed on an LV or an HV system:
3 to 5 cycles, leaving only the natural line impedance in
the faulty circuit. Now XC = 0, which limits the fault 1 Over-heating shortens the life of a capacitor. Adequate
current to the natural level of the system, as if the capacitors ventilation and cooling facilities, through convection
were not connected. The shorting device is restored to its and radiation, must be made available at the place of
original status as soon as the fault condition is cleared. installation. When housed inside a cubicle, as in a
The device must be capable of interrupting the line fault capacitor control panel and in a tier formation, sufficient
current without a restrike. The scheme serves a dual space must be provided between each unit. Adequate

1 1
G1 G2 G1 G2

3 3
2
2 Xc
Xc

5 4 5 4

6 6

1 5 Short circuit protection relay 1 5 Short circuit protection relay

6 Bypass or shorting breaker 2 Isolators 6 Bypass or shorting breaker (a


2 Isolators normal interrupter or a thyristor
(a normal interrupter or a
thyristor switch), to short 3 switch), to short circuit the
3 capacitors
circuit the capacitors
4 Spark gap 4 Spark gap 7 Non linear ZnO–resistor

Figure 26.11 Over-voltage protection with the help of a spark Figure 26.12 Over-voltage protection with the help of a ZnO
gap and a shorting switch resistor, spark gap and a shorting switch
26/964 Electrical Power Engineering Reference & Applications Handbook

ventilation facilities should also be provided, either • Avoid any spillovers, leakage or vaporization of liquid
through louvres, exhaust fans or by providing an or disposal of a waste unit. One can use Araldite,
expanded metal enclosure, for the capacitors to ensure solder or any other means to stop a leakage. If this is
a free air circulation around each capacitor unit (Figure not possible, collect carefully all the chemical PCB
23.32). and carefully dispose it of.
2 Concentration of capacitor banks at one point in a • Soaked rags, cloth or papers, must be destroyed in an
system may cause amplification of harmonics, self- incineration plant at 1000∞C. Disposal at a landfill
excitation of machines, over-voltages due to switching area is not advisable for during rain they may be
and unsatisfactory working of audio frequency remote carried by storm drains into rivers, canals or ponds.
control apparatus. To overcome this, concentration of • Old units should not be sold to a scrap dealer for
capacitor banks at one point must be avoided as far as similar reasons.
possible. These may be installed at different locations
in the system.
3 A loose contact within the circuit, producing sparks, 26.3 Test requirements
will generate high-frequency oscillations (harmonics).
However small these oscillations are, they may raise
the system voltage and frequency. High-frequency Below we discuss briefly recommended tests on a finished
oscillations will also reduce the impedance of the capacitor unit based on various IEC recommendations.
1 For Standards refer to the list provided at the end of the
capacitors x ch a and cause high currents, leading chapter.
fh
to premature failure of the capacitors. Loose contacts
must therefore be thoroughly checked. It is recom- 26.3.1 Routine tests
mended that a capacitor circuit particularly be checked
periodically for loose connections or sparkings. Routine tests are carried out on each capacitor unit.
4 When the reactive control is not automatic, then during
off-peak periods (such as during the night) it is important (1) Capacitance measurement
that some of the banks are dropped manually to avoid
an over-compensation and a consequent over-voltage. This is to be determined at rated voltage and frequency
5 It is advisable to periodically check the condition and can be carried out between 0.9 to 1.1 times the rated
(i.e. the capacitance value C) of each capacitor unit voltage and 0.8 to 1.2 times the rated frequency.
to detect failure of one or more of them and the Permissible tolerances in capacitance from the declared
consequent over-voltage across the healthy units. This values can be as follows:
can be measured by any of the methods discussed in
Section 26.3.1(1). The capacitance value of each unit • For LV capacitor units up to 1000 V For both self-
must fall within the permissible limits as indicated healing and non-self-healing types:
in that section. The failed units, if any, must be –5% to +10% for units and banks up to 100 kVAr
replaced promptly with units of the same rating and –5% to +5% for units and banks above 100 kVAr.
brand to avoid any performance variation. If this is • For HV capacitors
not possible then the banks must be balanced by –5% to +15% for capacitor units or banks containing
readjusting the units. When the banks are connected one unit per phase
through a series reactor, the value of the reactor must –5% to +10% for capacitor banks less than 3 MVAr
also be readjusted to match changed parameters. 0% to +10% for capacitor banks from 3 MVAr to 30
Otherwise the reactor may resonate with the fifth or MVAr
the seventh harmonic, for which it is designed, and 0% to +5% for capacitor banks above 30 MVAr.
cause an over-voltage. • For series capacitors
These are usually HV capacitor units/banks:
±7.5% for capacitor units or banks containing one
26.2.1 Precautions in handling a capacitor unit unit per phase
with PCB ±5% for capacitor banks less than 30 MVAr
±3% for capacitor banks 30 MVAr and above.
Although the manufacture of PCB-filled capacitor units
has been discontinued, for older installations some may still
be used. For the benefit of their users we give below the Methods to determine the capacitance of a
precautions that they must take when handling these units: capacitor unit
• Do not inhale the vapour of this chemical. Two common methods to determine this are:
• Avoid its contact with eyes and skin.
• Avoid its contact with birds and animals. • Voltage method and
• Avoid its contact with animal feed. • Bridge method.
• Do not re-use contaminated paper and cloth. In the voltage method the normal voltage is applied across
• In the event of contact with the human body, wash the capacitor terminals and line current, Ic, is measured.
the skin with soap and water and the eyes with clean The value of capacitance, C, can be determined from the
running water. equations provided in Section 23.5.2(A). In the bridge
Protection, maintenance and testing of capacitor units 26/965

Table 26.3 Power frequency test voltages and their duration for voltage tests on a power capacitor unit or bank

LV capacitors up to 1000 V HV capacitors above 1000 V


Description Routine test Type test Routine test Type test
Test Duration Test Duration Test Duration Test Duration
voltage voltage voltage voltage

(i) Voltage test between 2.15 Vra 2s 2.15 Vra 10 s 2.15 Vra 10 s – –
terminals

(ii) Voltage test between


terminals and container For lightning impulse withstand voltage
(a) for rated voltage £ 660 V 3 kV 10 s 3 kV 1 min refer to Table 26.4
(b) for rated voltage > 660 V 6 kV 10 s 6 kV 1 min
a
Vr = rated voltage
Notes
1 For a repeat test, only 75% of the test voltage must be applied.
2 The above tests refer to dry power frequency voltage withstand tests for indoor units. Outdoor capacitor units will be subjected to a wet
test as in IEC 60060-1.

method the capacitance is measured directly through a (5) *Test for the internal discharge device
capacitance meter without disconnecting the unit from
the circuit. This is required to determine the suitability of the
resistance of the discharge device to ensure that it
Note
discharges a charged capacitor unit or bank at 2 Vr to
The values thus obtained will be accurate when the system is free 50 V or less in 1 minute in LV and in 10 minutes in HV
from harmonics. If harmonics are present in the system correction shunt capacitor units or banks and in 5 minutes in series
will be necessary for both V and f, as in Equation (23.5). capacitors. The arrangements of discharge devices are
illustrated in Figure 25.8.
(2) Measurement of capacitor loss in
terms of tan d (6) Scaling test
Tan d is a measure of dielectric loss in a capacitor unit This is required to check the leakage of the capacitor
and is represented by the ratio of equivalent series dielectric during long operations. It is carried out by
resistance and capacitive reactance of a capacitor unit at heating the unit uniformly on all sides, at least 20∞C
the rated voltage and frequency (Figure 9.7), i.e. higher than the maximum ambient temperature of the
capacitor unit, for at least 2 hours. There should be no
tan d = R leakage.
Xc
where equivalent series resistance, R, is the virtual
resistance which, if connected in series with an ideal 26.3.2 Type tests
capacitor unit of capacitive value equal to that of the (1) Thermal stability test
capacitor under reference, will have a power loss equal
to the active power dissipated in that capacitor under This is another name for a heat run test. A voltage sufficient
specified operating conditions. to cause an output of the capacitor unit equal to 1.5
The test can be performed at voltages and frequencies, times the rated output is applied at the rated frequency
as noted in (1) above. The value of tan d should not and test conducted for at least 48 hours. During the last
exceed the declared value. six hours of the test the temperature rise and tan d are
measured at least four times. The temperature rise during
(3) Voltage test between terminals the last six hours should not exceed 1∞C, otherwise the
test duration must be extended until the temperature
Every capacitor unit will be subject to an a.c. test at a stabilizes to a rise of only 1∞C. The final test results
voltage specified in Table 26.3 at a frequency between 15
and 100 Hz, preferably as close to the rated as possible.
During the test no permanent puncture or flashover should *These figures are only indicative, as different countries may specify
occur. different discharge voltages and discharge times. For instance, various
IEC Standards mentioned at the end of the chapter specify the
(4) Voltage test between terminals and container discharge voltage as 75 V, reached in 3 minutes in LV and 10
minutes in HV shunt as well as series capacitors. When required
The test procedure and test performance should be the for fast switching operations, special discharge devices are sometimes
same as noted in (3) above except the test voltages, which employed to achieve a faster discharge, as discussed in Section
will be as specified in Table 26.3. 25.7.
26/966 Electrical Power Engineering Reference & Applications Handbook

compared to the measurement taken at the start of the • For LV units: Three impulses should be applied of
test should not vary by more than the following: positive polarity followed by three of negative between
the terminals joined together and the container.
• For capacitance value • For HV units: Fifteen impulses should be applied of
For LV units: 2% of its capacitance value positive polarity followed by fifteen of negative
For HV units: The two test values should be corrected between the bushings joined together and the container.
to the same reference of dielectric temperature, say,
20∞C or as agreed. The difference between the two The value of the first peak of the test wave is specified
test values should be less than an amount corresponding in Table 26.4. During the test there should be no rupture
to either breakdown of an element or operation of an or flashover at any part of the unit, which should be verified
internal fuse. by a cathode ray oscillograph. An oscillograph should
• For tan d value also be used to record the voltage and check the wave shape.
For LV units: 2 ¥ 10–4
For HV units: 1 ¥ 10–4 or as agreed between the (6) Short-circuit discharge test
manufacturer and the user.
The unit should be first charged by d.c. and then discharged
(2) Measurement of capacitor loss in through a gap situated nearby. The test voltages should
terms of tan d be as follows.

This is the same as for the routine test (2) For LV units

(3) Voltage test between terminals • Star-connected units Test voltage 4 Vr / 3. The test
should be carried out between any two terminals,
This is similar to the routine test (3) except the duration leaving the third open.
of the test, which should be as specified in Table 26.4. • Delta-connected units Test voltage 2Vr. Any two
terminals of the unit should be shorted and the test
(4) Voltage test between terminals and container conducted between the third and the shorted terminal.

This is similar to the routine test (4) except the duration For HV units
of the test, which would be as specified in Table 26.4.
The test voltage should be 2.5 Vr, irrespective of star- or
(5) Lightning impulse voltage test between delta-connected units. The capacitor unit should be charged
terminals and container with the test voltage and discharged five times within 10
minutes. Within 5 minutes after the test the unit may be
The test should be conducted generally with a wave of subjected to voltage test (3) between the terminals. The
1.2 to 5/50 ms as illustrated below: capacitance of the test unit may be measured before the

Table 26.4 Insulation levels for power capacitor units

Highest voltage for Rated lightning impulse withstand Rated power-frequency short-duration withstand voltage for
equipment voltage voltage test
List 1 List 2 Duration
kVr.m.s. kVpeak kVpeak kVr.m.s. Routine test Type test
æææææÆ
æææææÆ

up to 0.66 – 15 ¸
Ô
0.66 to 1.0 – 25 ˝ (Refer to Table 26.3)
Ô
˛
1.2 – 25 6
2.4 – 35 8
3.6 20 40 10
7.2 40 60 20 10 s 1 min
¨ææææ
¨ææææ

12 60 75 28
17.5 75 95 38
24 95 125 50
36 145 170 70

Notes
1 For a repeat test only 75% of the test voltage must be applied.
2 The power frequency voltage test refers to indoor units. The outdoor capacitor units must be subjected to a wet test as in IEC 60060-1.
3 The choice between list 1 and list 2 will depend upon the extent of exposure of the units to the internal and external voltage surges and
the amount of surge protection, if provided.
4 It will also depend upon the condition of system grounding, i.e. whether effectively grounded, non-effectively grounded or isolated
neutral etc. For systems other than effectively grounded, list 2 must be preferred.
5 For higher voltage systems, refer to the relevant Standards noted in the table of Standards provided at the end of the chapter.
Protection, maintenance and testing of capacitor units 26/967

discharge test and after the voltage test. The capacitance (c) After test (b), the test in (a) is repeated.
values thus measured should not be exceeded by more
than 2% or breakdown of an element or blowing of an On conclusion of the test no permanent breakdown
internal fuse. or flashover should be observed. The variation in the
capacitance value as measured before and at the end of
the test should not vary by more than 3%. The capacitor
(7) Partial discharge test (applicable to HV units) unit should withstand the voltage test between the
There are invariably voids that will appear in an insulating terminals and the container as stated in test (4) above
system as a matter of process, irrespective of the type and the scaling test as in test (6) under routine tests.
and procedure of impregnation adopted, as discussed in
Section 9.6.1. For all practical purposes, a dielectric system (10) Self-healing test
may therefore be considered to be an imperfect capacitor.
This test is applicable to LV capacitors only, which are
All such voids may cause internal discharges and lead to
the self-healing type. The capacitor is subjected to a
erosion and ultimate failure of the dielectric under the
effect of the applied voltage. The applied voltage may voltage of 2.15 Vr, for 10 seconds. If fewer than five
be fluctuating too, aggravating the situation. This test is breakdowns occur during this time, the voltage may be
conducted to check the condition and suitability of the increased slowly until it reaches 3.5 times its rated value,
dielectric used to perform the required duties in service or five breakdowns, whichever happens first. If five
without causing an undue discharge (ionization). It is a breakdowns have still not occurred, the test is continued
means of detecting defects in the insulating system of until they do. The capacitance measured before and
a capacitor unit and is complementary to a dielectric after the test should show no significant change.
test.
To perform this test, the rated voltage may be applied (11) Destruction test
long enough for thermal equilibrium to be achieved. Then This test is also applicable to LV capacitor units only.
a test voltage of twice the rated voltage is applied only The basic objective is to establish that the failure of a
once for one second. The voltage is then reduced to 1.2 unit is within a safe zone and is not accompanied by the
times the rated voltage and maintained for 10 minutes risk of a violent explosion or fire.
and then it is raised again to 1.5 times the rated voltage
for 30 minutes. During the last 10 minutes, the discharge
under such conditions should be less than 50 pc Concluding
(picocoulombs). The capacitance should be measured These are only brief descriptions of the recommended
both before and after the test. The change in capacitance tests and their procedures on a completed capacitor unit.
should not exceed 2%. For more details refer to the table of Standards provided
One will appreciate that such tests are no guarantee at the end of the chapter.
of the minimum life of a capacitor unit. Moreover, it is
not expected that such tests can predict the future of the
capacitor units. They can, at best, suggest the compliance 26.3.3 Checking field operating conditions
of the test requirements which should ensure a reasonably On larger installations, particularly, it is recommended
prolonged operating life of the capacitors, as envisaged. that the actual operating conditions be checked and
These tests do provide feedback to the manufacturer on compared with the assumed conditions for which the
the quality of the dielectric and the process of insulation capacitor units were designed to ensure that they do not
adopted and if any improvements are required. differ by more than the permissible limits. This is because
a capacitor is highly susceptible to some operating
(8) Endurance test (process test for HV conditions such as fluctuations in voltage and harmonic
capacitors) contents in the system. An excess of any of these or
both V and Vh may shorten the life of the capacitor
This is an alternative to the ageing test and is applicable units and cause frequent failures of individual units. It
for shunt capacitors of 1000 V and above. It is an in- may also lead to over-voltages across the units and
house process test and is carried out on the capacitor increase harmonic contents. All this may cause failure
elements before they are assembled into a capacitor unit of the capacitor units, leading to even a cascade failure,
to ascertain their dielectric stability against repeated over- increasing the unbalance in voltage and kVAr across
voltages. For the test procedure refer to IEC 60871-2. each phase and destabilize the entire capacitor network.
The effect of voltage and voltage fluctuations can be
(9) Ageing test (applicable to LV units) checked through the capacitor line current, Ic, which is
a measure of the capacitance C of the capacitor units.
This test is conducted to estimate the working life of a The capacitor current must correspond to the designed
capacitor. Briefly, the test can be conducted in three (rated) current plus the permissible variation. A higher
stages as follows: current than this would mean a voltage variation or the
(a) The capacitor is energized at 1.25 times the rated presence of harmonics in the system or both. While the
voltage for 750 hours. voltage may be measured through a voltmeter and the
(b) It is then subjected to 1000 discharges. current through an ammeter in the three lines, the

Anda mungkin juga menyukai