RELA-EOL

End-of-Line Relay

Product description Installation instructions


WARNINGS
• Disconnect power before installing or removing
components. Failure to do so may result in serious injury
or loss of life.
• This device will not operate without electrical power. As
fires frequently cause power interruption, we suggest you
discuss further safeguards with your local fire protection
specialist.
To install the RELA-EOL:

1. Verify that all field wiring is free of opens, shorts, and


END-OF-LINE RELAY ground faults.
FOR
EXTINGUISHING SYSTEM 2. Make the wiring connections shown in the wiring diagram.
3. Mount the relay and faceplate to the electrical box with the
6-32 screws provided.

Compatible electrical box

The End-of-Line Relay facilitates the connection of a


nonpolarized releasing solenoid to a supervised, polarized
releasing circuit. Faceplate

Specifications
Operating voltage: 18.4 to 27.4 VDC
Operating current: 26 mA
Supervisory current: 0.2 mA
Solenoid current: 2 A max. End-of-Line Relay
6-32 screw
Construction: Metal faceplate
Maximum wire size: 12 AWG
Mounting
North American 2.5 in. (64 mm) deep 1-gang box
Standard 4 in. square box, 1.5 in. (38 mm) deep box with Figure 1: Installing the RELA-EOL
1-gang cover

© 2017 United Technologies Corporation 1/2 P/N 3100160 • REV 03 • ISS 16MAR17
Wiring diagram

To nonpolarized solenoid valve [1]

3
(–)
UL/ULC listed 47 k End-of-line resistor or next relay
(+)
2
1

(–)
From SIGA-REL
(+)

Figure 2: Rear view of the RELA-EOL showing wiring

Notes
[1] Must be in conduit and within 20 feet.
2. Polarity shown is for release active.
3. All circuits are supervised and Class B.

© 2017 United Technologies Corporation 2/2 P/N 3100160 • REV 03 • ISS 16MAR17