Technical Specifications of Distance relays for 66 KV Lines

Sl No Particulars Specifications
Make, Type, Designation To be specified by the firm
1 Type of distance measuring element Numerical
2 Type of scheme Numerical
3 No. of measuring element or comparators with details Six ( Non-Switched)

Min 4 Zones with at least one zone having


4 No. of Zones reverse(menu selectable) direction

5 Setting range of distance measurement 0.1 to 200 Ohms


6 Overall range of all zones R-0.1 to 200 Ohms, X-0.1 to 200 Ohms
7 Reach setting range at rated current: Zone-1 forward R-0.1 to 200 Ohms, X-0.1 to 200 Ohms
8 Reach setting range at rated current: Zone-2 forward R-0.1 to 200 Ohms, X-0.1 to 200 Ohms
9 Reach setting range at rated current: Zone-3 forward R-0.1 to 200 Ohms, X-0.1 to 200 Ohms
10 Reach setting range at rated current: Zone-3 reverse(Offset) R-0.1 to 200 Ohms, X-0.1 to 200 Ohms
11 zone extentions if any To be specified by the firm
Characteristics of each zone
12 Characteristics of each zone -1for Phase fault unit Polygonal or circular- Menu selectable
13 Characteristics of each zone -1for Earth fault unit Polygonal or circular- Menu selectable
14 Characteristics of each zone -2 for Phase fault unit Polygonal or circular- Menu selectable
15 Characteristics of each zone -2 for Earth fault unit Polygonal or circular- Menu selectable
16 Characteristics of each zone -3 for Phase fault unit Polygonal or circular- Menu selectable
17 Characteristics of each zone -3 for Earth fault unit Polygonal or circular- Menu selectable
18 Characteristics of each zone -3(Offset) for Phase fault unit Polygonal or circular- Menu selectable
19 Characteristics of each zone -3(Offset) for Earth fault unit Polygonal or circular- Menu selectable
Zone -1 Reach of the relay along with the characteristic angle at
20 0.1 to 200 Ohms
rated current and voltage

21 Zone -1 Reach of the relay in resistive direction at rated current 0.1 to 200 Ohms
and voltage

22 Zone -1 Reach of the relay in reactive direction at rated current 0.1 to 200 Ohms
and voltage

23 Zone -2 Reach of the relay along with the characteristic angle at 0.1 to 200 Ohms
rated current and voltage

24 Zone -2 Reach of the relay in resistive direction at rated current 0.1 to 200 Ohms
and voltage

25 Zone -2 Reach of the relay in reactive direction at rated current 0.1 to 200 Ohms
and voltage

26 Zone -3 Reach of the relay along with the characteristic angle at 0.1 to 200 Ohms
rated current and voltage

27 Zone -3 Reach of the relay in resistive direction at rated current 0.1 to 200 Ohms
and voltage

28 Zone -3 Reach of the relay in reactive direction at rated current 0.1 to 200 Ohms
and voltage

29 Zone -3 (Reverse) Reach of the relay along with the characteristic 0.1 to 200 Ohms
angle at rated current and voltage

30 Zone -3 (Reverse) Reach of the relay in resistive direction at rated 0.1 to 200 Ohms
current and voltage

31 Zone -3 (Reverse) Reach of the relay in reactive direction at rated 0.1 to 200 Ohms
current and voltage
32 Powerswing block setting- Forward reach 0.1 to 200 Ohms
33 Powerswing block setting- Reverse reach 0.1 to 200 Ohms
34 Setting range of residual compensation 0 to 8
35 Setting range of mutuall compensation 0 to 8
36 Operating time of Zone -1 ≤ 35 msec
Sl No Particulars Specifications
37 Time setting range of Zone-2 0 to 10 sec- Menu selectable
38 Time setting range of Zone-3 0 to 10 sec- Menu selectable
39 Time setting range of Zone-3 reverse 0 to 10 sec- Menu selectable
Blocking time 0 to 10 sec - Menu
40 Time setting range of Power swing blocking selectable
41 Accuracy Zone-1 reach 5%
42 Accuracy Zone-2 reach 5%
43 Accuracy Zone-3 reach 5%
44 Polarisating scheme Memory Polarised/Phase polarised
Additional features
45 Fault Locator Available
Facilities avalable for Fault Locator
Rating and setting avalability Inbuilt
Rated VA ≤ 0.5 VA
Power consumption Voltage and current element ≤ 0.5 VA
Minimum 5 fault records on the event of
Memory capacity with details fault
Triggering metod Digital
Accuracy ≤ 5%
Method of Accuracy
46 Carrier adided tripping scheme Available
47 Power swing blocking Available
48 Broken cunductor dectection Available
49 Switch onto fault Available
50 Fuse failure supervision Available
51 Weakend infeed Available
52 Synchronours check Available
53 Directional Over current with IDMTL characteristic Available
54 Non-Directional Over current with IDMTL/DTL characteristic Available
55 Over Voltage supervision/Protection Available
56 Under Voltage supervision/Protection Available
Other details
57 Analog inputs - current elements 4 Nos-1 Aps
i) Operative range 0-100 A
ii)Permissive over load 4A cont, 100 A for 1 sec
58 Analog inputs - Voltage elements 4Nos-110 V/root 3
i) Operative range 0-340 V
ii)Permissive over load 420 V cont, 450 for 1 sec
59 Aux voltage- 80 to 245 V AC or DC
Min 8 Nos with contact burden rating of
60 Digital out puts (Programmable) for trip signals 1250 VA with max of 5 amps 300 V
contineous rating
61 Digital out puts (Programmable) for Alarm signals Min 8 Nos
62 Digital In puts (Programmable) Min 8 Nos
There shall be provision for add/
63 Provisional for additional modules remove IO Module at site
Communications
Front serial port -1 No
Rear Optic fiber port-1No
Rear Ethernet port-1No
674 Communication port supporting IEC 61850 -8-1 protocol
including Goose messaging and
68870-5-103 ,DNP 3.0 , SPA Protocols
to be specified by the firm with necessaary
65 Communication software and cable usb o serial port convertor
Technical Specifications of Diffrential relays for 66/11Kv Transformers

Sl
Particulars Specifications
No

Make, Type, Designation To be specified by the firm

1 Type of differntial measuring element Numerical

2 Type of scheme Numerical

3 Display Advanced HMI with LCD screen

24V-250V DC
If the auxiliary supply drifts, 2 alarms may be
4 Aux voltage- triggered:
. High set point and low set point alarm
(Min 20 V to max 275 V)

Differential Protection ( for T-87 relay)

Earth fault / Sensitive earth fault


Breaker Failure
Negative sequence / unbalance
5 Protection Thermal overload
Restricted Earth Fault
Phase over current
Over fluxing(V/Hz)
Under voltage(L-L or L-N)
Over voltage(L-L or L-N)
Over frequency
Under frequency
SIT, LTI, VIT, EIT, UIT (1)
RI
6
IEC: SIT/A, LTI/B, VIT/B, EIT/C
IEEE: MI (D), VI (E), EI (F)
Phase current I1, I2, I3 RMS
Measured residual current I0, calculated I0Σ
Demand current I1, I2, I3
Peak demand current IM1, IM2, IM3
Voltage U21, U32, U13, V1, V2, V3
Residual voltage V0
Frequency
7 Metering Active power P, P1, P2, P3

Reactive power Q, Q1, Q2, Q3

Apparent power S, S1, S2, S3


Peak demand power PM, QM
Sl
Particulars Specifications
No

Power factor
Tripping current Trip I1, Trip I2, Trip I3
Phase fault and earth fault trip counters
Unbalance ratio / negative sequence current
Harmonic distortion (THD), current and voltage
Ithd, Uthd
Phase displacement
Disturbance recording
Remaining operating time before overload tripping
Waiting time after overload tripping
8 Network and Machine diagnostics Running hours counter / operating time
Differential current Idiff1, Idiff2, Idiff3
Through current It1, It2, It3
CT / VT supervision
Trip circuit supervision
Auxiliary power supply monitoring
Cumulative breaking current

Watchdog function (The protection functions


are inhibited,)
Restraint on energization
Current threshold:1-10%
9 Diffrential relay setting
Time delay: 0to 300s
Choice of restraint:copnventional & Self Adapting
Set Point 1.03 to 2 pu
10 Setting of Over fluxing DET:0.1s to 2000s
IDMT :0.1 to 1250s
Set point 5 to 100% of Unp
11 Setting of Under Voltage
Time delay :0.05 to 300s
Set point 50 to 150% of Unp
Setting of Over Voltage
12 Time delay :0.05 to 300s
Over Frequency - Set point 50 to 55 Hz and time
delay 0.1 to 300 s
Setting of Over and Under frequency
Under Frequency-Set point 40 to 50 Hz and time
13 delay 0.1 to 300 s
Front serial port -1 No
Rear Optic fiber port-1No
Rear Ethernet port-1No
Communication supporting IEC 61850 -8-1 protocol including Goose
messaging and
14 68870-5-103 ,DNP 3.0 , SPA Protocols
Digital out puts (Programmable) for trip Min 8 Nos with contact burden rating of 1250 VA
15 signals with max of 5 amps 300 V contineous rating
Digital out puts (Programmable) for Alarm
Min 8 Nos
16 signals
17 Digital In puts (Programmable) Min 8 Nos
There shall be provision for add/ remove IO
18 Provisional for additional modules Module at site
19 CT Connection Suitable for ring type lugs
to be suppliedby the firm with necessary usb to
20 Communication software and cable
serial port convertor