START-UP PROCEDURE OF SEPARATOR

1. First, verify the reason for shutdown.


2. Before startup check PSLL3051, LSLL3052 & LSHH3051 are normal. If any
tag numbers are Alarm status put MOS of corresponding tag no.

RESET HS-3051 FROM OPERATOR CONSOLE FACIA

1) CLOSE MOV 3070 FROM FIELD AND RESET ESDV 3083, ESDV 3170,
ESDV3080 OPEN FROM FIELD.

2) PUT AUTO MODE PIC 3052A SET POINT 52PSI, PIC 3052B SET POINT 60PSI AND
LIC 3051 SET PONIT 50%.

3) OPEN MOV 3070 SLOWLY FROM FIELD AND THEN CHECK SYTEM PRESSURE &
LEVEL.

4) SYSTEM PRESSURE & LEVEL NORMAL THEN OPEN MOV 3070 GRADUALLY. AND
MAKE IT NORMAL CONDITION.