FOUNDATIONS
Learning Outcomes
Contents
10.1 Introduction
The primary function of all structural elements is to transfer the applied dead and
imposed loadings to the foundation and subsequently to the ground. The type of
foundation required depends on the various factors namely:
Hj Roslan/CeDS/2017
d) the location and proximity of adjacent structures
Pad foundation normally support single column and can be either square or rectangular
in plan as shown in Figure 10.1
When only concentric vertical load loading is applied, square pads are used, assuming
a uniform pressure under the whole base area. If the loading is eccentric, or if a moment
is applied to the base then it is more efficient to adopt a rectangular base. In this case
the pressure under the base is assumed to vary linearly.
Hj Roslan/CeDS/2017
10.2.2 Combined Foundations
Normally adopted for two columns either when they are relatively close together or
when one of the columns is adjacent to an existing structure. The shape of a combined
is as shown in Figure 10.2.
These are normally adopted for lines of closely spaced columns or under walls, as
shown in Figure 10.3. The strips are designed as a continuous beams subjected to the
ground bearing pressures.
Hj Roslan/CeDS/2017
10.2.4 Raft Foundations
These are continuous slabs which cover the whole plan area of the structure as shown
in Figure 10.4. They are normally used under the following cases:
a) For lightly loaded structure on soft natural ground where it is necessary to spread
the load.
b) For heavier structures where the ground conditions are such that there are
unlikely to be significant differential settlements.
c) Where differential settlements are likely to be significant.
d) Where mining subsidence is likely to occur.
The construction of the raft can be a flat slab construction thickness, thickened locally
around column positions, or can be strengthened by beams to form a ribbed
construction.
Figure 10.4
These are used in situations where it is necessary to transfer the foundation loads
through strata which have low bearing capacity, to strata which have a higher capacity,
or to rock. Piles are essentially long, slender members, mostly subjected to
Hj Roslan/CeDS/2017
compression as shown in Figure 10.5. In general, pile groups are subjected to axial
load, moments and horizontal loads.
When a base is subject to an axial load only, in which the line of action of the applied
force passes through the centroid of the base as shown in Figure 10.6, the pressure
under the base is assumed to be uniform throughout and is equal to P where:
Hj Roslan/CeDS/2017
10.3.2 Case 2: Varying Pressure(compression throughout)
𝑁 𝑀
𝑝= ±
𝐵𝐷 𝐵𝐷2 /6
𝑁 6𝑀
𝑝= ±
𝐵𝐷 𝐵𝐷2
Hj Roslan/CeDS/2017
10.3.3 Case 3: Varying Pressure(Compression over part of the base)
In the case of compression over part of the base as shown in Figure 10.8, the
magnitude of the maximum pressure can be determined using simple elastic analysis
and is equal to:
2𝑁
𝑝= 𝐷
3𝐵( – 𝑒)
2
𝑀
Where e = 𝑁
In case 1: e = 0 No tension
This is normally regarded as the middle third rule: i.e if the eccentricity e of the load
lies within the middle third of the base length, then no tension will occur under the base.
Hj Roslan/CeDS/2017
10.4 Pad Foundations Reinforcement
Dowel(or starter) bars provide the continuity of the reinforcement between the column
and the base. A length of the column(e.g 75 mm) is often constructed in the same
concrete pour as the foundation to form a”kicker”(support) for the column shutters. In
these cases the dowel lap-length should be measured from the top of the kicker as
shown in Figure 10.10.
Hj Roslan/CeDS/2017
Figure 10.11: Categories of Structures
According to EC7 section 6 ‘Geotechnical Design’, three methods for the design of
simple foundations namely:
1. The ‘Direct Method’ in which calculations are required for each limit state using
partial factors of safety for actions and material properties as appropriate.
2. The ‘Indirect Method’ which allows for a simultaneous blending of ultimate limit
state and serviceability limit state procedures.
3. The ‘Prescriptive Method’ which involves conventional and generally
conservative rules in the design, and attention to specification and control of
materials, workmanship, protection and maintenance procedures. This may be
used in situations where the calculations of soil properties are not available or
necessary.
Hj Roslan/CeDS/2017
10.6 Design Procedure
Hj Roslan/CeDS/2017
Example 1: Axially Loaded Pad Foundation
A pad foundation is required to support a single column transferring an axial load only.
Using the data provided and designing suitable reinforcement where necessary:
Design data:
Assume the design to be carried out on the basis of Clause 2.5 of BS EN 1997-1:2004,
i.e. design by prescriptive measures and design approach 1.
Hj Roslan/CeDS/2017
(b) Base Reinforcement – using ultimate limit state
Design approach 1
Concrete cover:
Nominal cover:
Cmin - Minimum cover for concrete cast on prepared ground (including binding) is 40
mm and that for concrete cast directly against soil is 65 mm.
(Note: This is the mean effective depth since the main reinforcement runs in both
directions)
Bending Reinforcement:
Hj Roslan/CeDS/2017
Design bending moment
Crack control:
Hj Roslan/CeDS/2017
From Table 8.1, ρ1 = As/bd = 1135/1000 x 480 = 0.24%,
and,
αcc = 0.85 for compression in flexure and axial loading and 1.0 for other
phenomnena. In this case use 1.
Hj Roslan/CeDS/2017
fcd = 1.0 x 35/1.5 = 23.33 MPa
bw = 4 x 375 = 1500 mm
Equation 6.48
Equation 6.49 vEd = VEd,red/u1d = 341.0 x 103 /7532 x 480 = 0.09 MPa
Hj Roslan/CeDS/2017
Equation 6.50
Design data:
Geotechnic category 1
Hj Roslan/CeDS/2017
Solution
Serviceability limit state loads are used to check the bearing pressure under the
base.
Clause 2.5 Design axial load for serviceability NEd = (1.0 Gk + 1.0 Qk)
The pressure diagram does not extend under the full length of the base.
The length of the pressure diagram can be found from the equivalent load
Hj Roslan/CeDS/2017
Diagram as follows:
In the case of compression over part of the base the magnitude of the
Column design moment MEd = 1.35 x 125 + 1.5 x 175 = 431.25 kNm
y = 2054 mm
In the case pf compression over part of the base the magnitude of the
Hj Roslan/CeDS/2017
Earth pressure due to ultimate loads pg = 1335.0/2.054 x 1.75
= 371.4 kN/m2
Base thickness
length)
Concrete cover
Nominal cover:
Cmin - Minimum cover for concrete cast on prepared ground (including binding)
is 40 mm and that for concrete cast directly against soil is 65 mm.
Effective depth:
(Note: This is the mean effective depth since the main reinforcement runs in both
directions)
Hj Roslan/CeDS/2017
Design bending moment:
Select 16 mm diameter bars @ 150 mm centres providing 1340 mm2/m at the bottom in
both direction.
Hj Roslan/CeDS/2017
Design shear force VEd = (371.4 x 1.75 x 0.620) = 403 kN
Hj Roslan/CeDS/2017
VEd ≤ 0,5 bwdνfcd ( Equation 6.5 , EC2)
and,
αcc = 0.85 for compression in flexure and axial loading and 1.0 for other
phenomnena. In this case use 1.
Since the critical perimeter lies outside the column base, the check above at 1.0d from
the column face is adequate.
Hj Roslan/CeDS/2017
Problems
Determine:
(a) size of base,
(b) tension reinforcement and
(c) any shear reinforcement.
K = M/bd2fck= ______
z = ____d = ____ x ____= ____mm
As = MEd/0.87fykz= _____mm2
Provide H__ @ ____ c/c (_____mm2)
Hj Roslan/CeDS/2017
For C__/__ concrete As,min = ____ \ OK/not OK
Beam shear
Check critical section d away from column face
VEd = ___ x _____= _____kN/m
vEd = VEd / d = _____MPa
vRd,c (from table) = ____MPa therefore beam shear OK/not OK.
Punching shear
Basic control perimeter at 2d from face of column
vEd = βVEd / uid < vRd,c
β = 1, ui = = _____mm
VEd = load minus net upward force within the area of the control perimeter)
= _____ – ____ x ( )
= _____kN
vEd = _____MPa; vRd,c = ______ (as before) => ok/not ok
2. Design a square pad footing for a 350 × 350 mm column carrying G k = 600 kN
and Qk = 505 kN. The presumed allowable bearing pressure of the non-
aggressive soil is 200 kN/m2. Use concrete C30/37 .
(a) Determine the size of the footing.
(b) Determine the reinforcement require.
(c) Check critical section d away from column face.
(d) Check punching shear
Hj Roslan/CeDS/2017