MODEL: FJF

Space-saving Plug-in Signal Conditioners F-UNIT [2] OUTPUT


Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
2-input MATH FUNCTION MODULE
Voltage
(field-programmable)
6: 1 – 5 V DC (Load resistance 500 Ω min.)
Functions & Features
• Providing temperature or pressure compensation for a gas
flow, and other arithmetic operations [3] POWER INPUT
• Microprocessor based AC Power
• Equation and parameters K: 85 – 132 V AC
selectable on site via hand-held programmer PU-2x (Operational voltage range 85 – 132 V, 47 – 66 Hz)
• Loop testing L: 170 – 264 V AC
• High-density mounting (Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
Typical Applications R: 24 V DC
• Various flowmeters (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
• Adding two flows P: 110 V DC
• Ratio calculation (Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
• Calculating average temperature

[4] OPTIONS (multiple selections)


26 (1.02) Equation (Refer to the EQUATION table)
/1: Temperature compensation for DP flowmeter (ideal gas)
/2: Pressure compensation for DP flowmeter (ideal gas)
100 /3: Addition/subtraction
(3.94)
/4: Multiplication
/5: Division
Other Options
137
(5.39)
mm (inch)
blank: none
/Q: Option other than the above (specify the specification)

MODEL: FJF–[1][2]-[3][4] SPECIFICATIONS OF OPTION: Q (multiple selections)


COATING (For the detail, refer to M-System's web site.)
ORDERING INFORMATION /C01: Silicone coating
• Code number: FJF-[1][2]-[3][4] /C02: Polyurethane coating
Specify a code from below for each [1] through [4]. /C03: Rubber coating
(e.g. FJF-6A-K/3/Q) TERMINAL SCREW MATERIAL
• Parameters /S01: Stainless steel
Use Ordering Information Sheet (No. ESU 1980). Default
setting will be used if not otherwise specified.
(K0 = 1, K1 = 1, K2 = 1, A0 = 0 %, A1 = 0 %, A2 = 0 %)
• Specify the specification for option code /Q
(e.g. /C01/S01)

[1] INPUT
Current
A: 4 – 20 mA DC (Input resistance 100 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)

http://www.m-system.co.jp/ FJF SPECIFICATIONS ES-1480 Rev.11 Page 1/3


MODEL: FJF
EQUATION INPUT SPECIFICATIONS
Equation parameters ■ DC Current: Input resistor incorporated
X0: output (%)
X1 to X2: input (%)
INSTALLATION
K0 to K2: gain ±29.999
Power input
A0 to A2: bias (%) ±299.99 %
EQUATION •AC: Approx. 4.5 VA
/1: Temperature compensation for DP flowmeter (ideal gas) •DC: 24 V approx. 70 mA
110 V approx. 20 mA
K1X1
X0 = K X +A Operating temperature: -5 to +55°C (23 to 131°F)
2 2 2
Operating humidity: 30 to 90 %RH (non-condensing)
where X0 : compensated flow (linear characteristic)
Mounting: Surface or DIN rail; Standard Rack Mounting
X1 : uncompensated flow (square root extraction available)
X2 : temperature
Frame BX-16H available
/2: Pressure compensation for DP flowmeter (ideal gas) Weight: 220 g (0.49 lb)
X0 = K1X1 K2X2+A2
where X0 : compensated flow (linear characteristic)
X1 : uncompensated flow (square root extraction available)
PERFORMANCE in percentage of span
X2 : pressure Accuracy: Input accuracy + output accuracy
/3: Addition/subtraction Input accuracy: ±0.2 % (gain ≤ 1)
X 0 = K0 {K1 (X1+A1) + K2 (X2+A2)} + A0 [±0.2 % × gain] with gain > 1
/4: Multiplication Output accuracy: ±0.2 %
X 0 = K0 (K1X1+A1) (K2X2+A2) + A0 Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
/5:Division Response time: ≤ 0.8 sec. (0 – 90 %)
X0 =
K0 (K1X1+A1)
+ A0 Line voltage effect: ±0.1 % over voltage range
(K2X2+A2) Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength
Power input code R:
1000 V AC @ 1 minute (input to output)
RELATED PRODUCTS
2000 V AC @ 1 minute (input or output or power to ground)
• Programming Unit (model: PU-2x)
500 V AC @ 1 minute (I/O to power)
• PC configurator software (model: JXCON)
Power input code K, L, P:
Downloadable at M-System’s web site.
1000 V AC @ 1 minute (input to output)
A dedicated cable is required to connect the module to the
2000 V AC @ 1 minute (input or output or power to ground)
PC. Please refer to the internet software download site or
1500 V AC @ 1 minute (I/O to power)
the users manual for the PC configurator for applicable
cable types.

GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless
steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power (non-isolated between
inputs)
Overrange input: Approx. -25 to +125 %
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Adjustments: Programming Unit (model: PU-2x); equation
and parameters, square root extraction, zero and span, etc.
(Refer to the users manual of JXCON for the adjustments
configurable with JXCON.)

http://www.m-system.co.jp/ FJF SPECIFICATIONS ES-1480 Rev.11 Page 2/3


MODEL: FJF
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
CLAMP
(top & bottom) 7.8 (.31)

1 2
DIN RAIL 15 3 4
35mm wide (.59)
100 (3.94)

93 (3.66)
2–4.5 (.18)
HOLE
15 (.59) deep

5 6
8–M3.5 7 8
SCREW
26 (1.02) 107 (4.21) 26 (1.02)
137 (5.39) [3.3 (.13)]

•When mounting, no extra space is needed between units.

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

Isolation
Digital Output
+ 1 Multiplexer 5 +
* Computation Driver
INPUT 1 OUTPUT
– 2 6 –

+ 3 7 U(+)
INPUT 2 * POWER
– 4 8 V(–)

PU-2x MODULAR JACK


SERIAL TRANSMISSION LINE
Base Socket

*Input shunt resistor incorporated for current inputs.

Specifications are subject to change without notice.

http://www.m-system.co.jp/ FJF SPECIFICATIONS ES-1480 Rev.11 Page 3/3