Wind power plant is a type of power plant that utilizes electric energy by the use of wind energy. It
transforms kinetic energy of wind into kinetic energy (rotational force) with wind turbine and mobilize
generator with the force to gain electric energy. A wind power plant is one of the designs considered
in the proposed development of the 35 MW power requirement of the client. The wind turbine will be
an alternative source for the area of western part of Batangas specifically Balayan and Nasugbu as
the two towns are expected to bloom into a full blown cities in the province in the years to come.
Based on the location of the client, a wind power plant will be a suitable option because of the weather
on the town of Calatagan in Batangas. Last year, an average of 8.9 meter per second wind speed
measured at 10 meters above the ground in Calatagan, a neighbor town of Balayan and Nasugbu.
The highest wind speed measured is 9.88 meter per second and the direction of the wind is West.
Another reason why Calatagan is considered to be the location of the wind power plant is because
of few natural obstacles that will block the path of wind.
Figure 3.1 shows the design options of the wind power plant. The design will revolve on the which
orientation is the best suitable for the location. Horizontal – axis wind turbine is further divided into
two which is the free standing type and the lattice type. Vertical – axis wind turbine has savonius and
darrieus types.
Design Options of Wind Power Plant
The diagram above shows the different wind turbine design options. There are two types of wind
turbines according to the rotor axis orientation-horizontal and vertical. Under each category fall more
subtypes. In this design project, two horizontal axis wind turbine and two vertical axis wind turbines.
Wind turbines use the energy of the wind to drive a generator which generates the electricity. Wind
power can be extracted with the use of wind turbines. They could be grouped together on a wind
farm to produce a desired output. Oftentimes they are on land but now, there are also offshore wind
turbines. Wind turbine generators differ in size from small ones which generate enough power for a
small application or establishment to utility size ones which can generate power for hundreds of
users.
The AC voltage output from the wind farm shall be step-up by a transformer before transmitting it via
a transmission line to the substation. Then from the substation, the voltage shall be stepped down
to a suitable voltage for consumer loads supplied by feeders. Different turbines have different
efficiency. Specifically, this refers to the ability of the blades to capture the mechanical power from
the wind referred to as the coefficient of power. Almost all generators have similar gearbox and
generator efficiencies. The formula for power coefficient is:
P
Cp = IEC 61400-12-1 Sec. 8.4 Power
1
ρAV3 coefficient of Wind Turbines
2
where,
Cp = power coefficient
P = mechanical power harnessed by the blades from the wind
ρ = 1.225 density of air (kg/m3)
A = area swept by the blades (m2)
V = 9.88 in the Calatagan wind farm site velocity of wind (m/s)
From the above equation, the general formula for estimating the power in watts that can be
harnessed by the blades from wind energy can be obtained:
In the above formula, the air density, area swept by the blades, and the wind speed in the locality
would be considered in the selection of the wind turbine rating to be selected by the designer.
Figure 3.3 Power coefficient versus advance ratio for different wind turbine configurations.
The figure above shows the Glauert ideal Cp which is the result of a more detailed analysis that
explicitly involves the advance ratio. Lying below and to the right of the Glauert ideal are the
expected Cp values for different wind turbine configurations.
To make the selection process of wind turbines easier, IEC has provided a standardized means of
describing the output power characteristics of wind turbines. This is through the provisions of power
curves on the turbine datasheets. These power curves are created manufactured based on careful
measurements as prescribed in IEC 61400-12-1 Sec. 8.1.
Figure 3.3 Power Curve Power Wind Turbine
By only having the wind speed as an input, the designer can easily determine if a wind turbine fits
the air conditions in the locality. In the site where the wind farm is to be situated in Calatagan, the
average annual wind speed is 9.88 m/s. It is a high wind area thus it is a great spot for harnessing
wind energy.
The Figure 3.3 shows the single line diagram of the power system and the stages where each component is
designed.
34.944 MW
PF =
3
PF = 11.648 MW
Rating
10,000 kVA, 3-phase, 69/13.8 kV
At Primary Side
MVA Rating
I=
√3 × V IEEE Standard C57.12.00-2010,
10 MVA Standard General Requirements for
I=
√3 (69 kV) Power and Regulation Transformers.
I = 83.6739 A
Primary Winding Conductor
The size of conductor for primary winding should be
167.3479 A. As indicated that the 80% ampacity of
the conductor shall be the full load current.
At Secondary Side
MVA Rating
I= IEEE Standard C57.12.00-2010,
√3 × V
10 MVA Standard General Requirements for
I= Power and Regulation Transformers.
√3 (13.8 kV)
I = 418.3698A
Circuit Breaker
Primary Circuit Breaker NEC Section 450.3 – Computation for
16.7348 A × 3 = 50.2043 A
Overcurrent Protection of Transformer
Use: 60AT CB
Grounding Conductor
Primary Grounding Conductor
1 PEC Part 2, Article 1.4.4.3(b) or
IGROUNDING = (Current) System Grounding Conductors for
5
1 Multi-Grounded Alternating Current
IGROUNDING = (83.6739) Systems.
5
IGROUNDING = 16.7348 A
Use: Turkey 6 (KCM or AWG)
The size of conductor should be 16.7348 A as indicated that the 80% ampacity of the conductor
shall be the full load current.
Secondary Grounding Conductor
1
IGROUNDING = (Current) PEC Part 2, Article 1.4.4.3(b) or
5
1 System Grounding Conductors for
IGROUNDING = (418.3698 A)
5 Multi-Grounded Alternating Current
IGROUNDING = 83.6740 A Systems.
Use: Raven 1/0 (KCM or AWG)
The size of conductor should be 83.6740 A as indicated that the 80% ampacity of the conductor
shall be the full load current.
Neutral Conductor
INEUTRAL = (IFLSecondary) PEC Part I(2009), Sec. 2.20.3.22 page
INEUTRAL = 522.9622 A 320: Feeder or Service Neutral Ground
Use: Finch 1113.0 (KCM or AWG)
IEC standards assume that peak value of making current disconnectors is to be 2.5 times the RMS
value of rated short circuit current for MV (13.8 kV) switches and between 1.7-2.2 times for LV
switches.
Use: 12 – 100 A – Medium Split-Core 1.25” (32mm) Opening
Disconnector Rating
Voltage Transformer IEC 62271-102(2001) High-voltage
69 kV switchgear and control gear - Part
VT- Primary Voltage = 102: Alternating current disconnectors
√3
VT- Primary Voltage = 39.8372 kV and earthing switches
Current Transformer
IGROUNDING = 43. 7386 A
Use: Primary Current = 100 A IEC 60099-8(2011) Part 8/IEEE C62.22
Secondary Current = 5 A page 8 – 16; Standard for Lightning
Accuracy Power = 30 VA Arrester and Ground Voltage Fault
Accuracy Class = 0.5
Lighting Arrester
Voltage ×1.05
VLA =
√3
Highest Voltage NEC (2001) Article 310, Table 310.60
69 kV × 1.05
VLA = (C) (67) and 310.60(C) (69), page 226;
√3 Conductor for general wiring
VLA = 41.829 kV
Use: RP1 Primary Side Normal Duty Distribution Class (ZnO)
Nominal Voltage Philippine Grid Code PP. (32) Section 3.2.3 – the
13.8 kV × 1.05 system owner must ensure that the voltage variation
VLA = must be not more or less than +-5% of the nominal
√3 voltage at any point during normal operation.
VLA = 11.9512 kV
Use: RP1 Load Side Normal Duty Distribution Class (ZnO)
Impedance
ZBUS = [√ (3 9875×10−9) × (5 9376×10−2)]
ZBUS = 2.5209 × 10-16 Ω/m Copper Development Association
(2014), Article 5.2, page 79: Conductor
1.5042×10-9 ×5.9376×10-2
Φ = tan -6
for general wiring.
7.5825×10
Φ = 90∘
ZTOTAL = 2.5209 × 10-6 Ω/m × (10 m)
ZTOTAL = 2.5209 × 10-15∠-90
Use: Dimensions in meter: 6.35 mm × 152 mm IEEE Std Gray Book C8.3.3 page 231:
Basic insulating materials are either
Skin Effect Ratio at 70℃: 1.18
Area in CM: 1910CM organic or inorganic.
Derating Factor
Stated under IEEE Std 80 (2000), Guide for safety in AC substation grounding
100
0.09 (1 - 100 ×100) IEEE Std 80 (2000), Guide for safety
CD = 1 - in AC substation grounding:
2 × 0.1 + 0.09
CD = 0.6928 Calculation of Potential Difference
Decrement Factor
Stated under IEEE Std 80 (2000), Guide for safety in AC substation grounding
X 1
Ta = × ( ) IEEE Std 80 (2000), Guide for safety
R 2 TF
1 in AC substation grounding:
Ta = 15 × ( ) Calculation of Potential Difference
2 T(60)
Ta = 0.0398
-2 × Tf
Ta
DF = √1+ ( Tf ) (1 - e Ta ) IEEE Std 80 (2000), Guide for safety
Ta -2 × 0.15 in AC substation grounding:
DF = √1+ ( Tf ) (1 - e 0.0398 ) Calculation of Potential Difference
DF = 1.1248
Buried Length
Lr
L = LC+ [1.55 + 1.22 ( )] LR
√L2X + L2Y
IEEE Std 80 (2000), Guide for safety
in AC substation grounding:
3
L = LC+ [1.55 + 1.22 ( )] LR Calculation of Potential Difference
√902 + 502
L = 994 m
1 1 1 1
KS = π [2h + D+h + D (1 – 0.5n-2)] IEEE Std 80 (2000), Guide for safety
1 1 1 1
KS = π [2 (0.6) + 12.5+0.6 + 12.5 (1 – 0.5n-2)] in AC substation grounding:
Calculation of Potential Difference
KS = 0.314
Power Losses
NLL = 11.6 kW IEEEC.57.12.00-2010 IEEE Standard
LL = 47.6 kW General Requirements for Liquid-
Immersed Distribution, Power, and
where: Regulating Transformers
NLL = No Load Losses
LL = Load Loss
where:
TLF = Total Loss in the Transformer per Feeder
TL = Total Loss for the Two Transformers
NLL = No Load Losses
LL = Load Loss
*Note: Transformer rating, losses, and short-circuit impedance are according to manufacturer
specifications: https://www.alibaba.com/product-detail/69kv-10mva-Power-Transformer-for-
Electric_60696507750.html?spm=a2700.7724857.normalList.30.18a4f9d2RWOnFO
New Substation Layout
The location of the Wind Power Plant is at Calatagan, Batangas. The power generated is to be
transmitted on two feeders namely Balayan and Nasugbu. To distances of the two feeders from the
generation to substation is 9.8 km and 16.4 km respectively.
Conductor Specification
At Balayan = 9.8 km
Calculation for Total Resistance of Conductor
Ω IEC 60287-1-1 Calculation of Current
R = (0.06712 ) 9.8km Ratings, Section 2.4.3, Table 2, Page
km 31, 2006
R = 0.6578 Ω
where:
Deq = Equivalent spacing of conductors or Geometric Mean Distance(GMD) of conductors
GMR = Geometric Mean Radius of conductor
L = Inductance of the conductor
Considering the transmission system is completely
National Electrical Code (NEC),
transposed,
GMR = 0.7788 (r) Rated 60-Hz withstand voltage, Article
370, page 461, 2011
where:
r = Radius of The Conductor
.680 in
r= = 0.34 in = 0.008636 m
2
GMR = 0.7788 (0.008636 m)
GMR = 6.7257 × 10-3
The figure above shows the appearance of a single circuit tower for a transmission line.
3
Deq = √(7.7492m)(8.4119m)(5.2469m) BULLETIN 1724E-2003 Horizontal
Deq = 6.9933 m Separation Recommendations
Section 6.b.(2), page 6-1
6.9933 1000m
L = 2 x 10-7 ln ( -3
)( ) ( 9.8km )
6.7257 x 10 1km
L = 13.6157 mH
ZT = ZCONDUCTOR × 3 phase
ZT = (0.6578+ j5.133 Ω/phase) × 3 phase
ZT = 1.9734 + j6.9147 Ω
At Nasugbu = 16.4 km
Calculation for Total Resistance of Conductor
IEC 60287-1-1 Calculation of Current
Ω Ratings, Section 2.4.3, Table 2, Page
R = (0.06712 ) 10.34km 31, 2006
km
R = 0.6940 Ω
where:
Deq = Equivalent spacing of conductors or Geometric Mean Distance(GMD) of conductors
GMR = Geometric Mean Radius of conductor
L = Inductance of the conductor
0.680 in
r= = 0.34 in = 0.008636 m
2
GMR = 0.7788 (0.008636m)
GMR = 6.7257 × 10-3 m
3
Deq = √(7.7492 m)(8.4119 m)(5.2469 m) BULLETIN 1724E-2003 Horizontal
Deq = 6.9933 m Separation Recommendations
Section 6.b.(2), page 6-1
6.9933 1000 m
L = 2 x 10-7 ln ( -3
) ( ) (10.34 km)
6.7257 x 10 1 km
L = 14.3659 mH
ZT = ZCONDUCTOR × 3 phase
ZT = (0.5262 + j5.4158 Ω/phase) × 3 phase
ZT = 1.5786 + j16.2474 Ω
11.648 MW + 177.6 kW
IL =
√3 69 kV
IL = 97.9588 A
Conductor Specifications
The size of conductor 97.9588 × 1.25 = 122.4485 A
PEC Part I (2009) Sec 4.30.2.4 page
As indicated that the 80% ampacity of the conductor
580: General Requirements for Full
shall be the full load current.
Load Branch Circuit, Feeder and Other
Use: ACSR Turkey, AWG 6
Conductors.
For the grounding conductor,
1
IGROUNDING CONDUCTOR = ( ) (IL ) Philippine Electrical Code Part 2
5
1 Article 1.4.4.3 (b): “System Grounding
IGROUNDING CONDUCTOR = ( ) (97.9588 ) Conductors for Multi-Grounded
5
IGROUNDING CONDUCTOR = 19.5918 A Alternating Current Systems”
Use: ACSR Turkey, AWG 6
RF2 = LF2 x R
RF2 = 16.4 km x 0.641Ω⁄0.3048 km
RF2 = 34.4895 Ω
Rating
25,000 kVA, 3-phase, 13.8 kV/69 kV
Primary Winding
MVA Rating
I=
√3 × V
20 MVA
I=
√3 (11 kV)
I = 836.7395 A
IF = 836.7395 A x 1.25
IF = 1045.9244 A
Use: Waxwing 266.8 (KCM or AWG)
At Secondary Winding
MVA Rating IEEE Standard C57.12.00-2010,
I=
√3 × V Standard General Requirements for
20 MVA Power and Regulation Transformers.
I=
√3 (69 V)
I = 167.3479 A
IF = 167.3479 A x 1.25
IF = 209.1849 A
Use: Finch 1113.0 (KCM or AWG)
Circuit Breaker
NEC Section 450.3 – Computation for
Primary Circuit Breaker
167.3479 A x 3 = 502.0437 A Overcurrent Protection of Transformer
Use: 600 AT CB
Grounding Conductor
PEC Part 2, Article 1.4.4.3(b) or
Primary Grounding Conductor
1
System Grounding Conductors for
IGROUNDING CONDUCTOR = (Current) Multi-Grounded Alternating Current
5
1 Systems.
IGROUNDING CONDUCTOR = (836.7395 A)
5
IGROUNDING CONDUCTOR = 167.3479 A
Use: Turkey 6 (KCM or AWG)
The size of conductor should be 167.3479 A as indicated that the 80% ampacity of the conductor
shall be the full load current.
Neutral Conductor
INEUTRAL = (IFLSecondary) PEC Part I(2009), Sec. 2.20.3.22 page
INEUTRAL = 522.9622 A 320: Feeder or Service Neutral Ground
Use: Finch 1113.0 (KCM or AWG)
IEC standards assume that peak value of making current disconnectors is to be 2.5 times the RMS
value of rated short circuit current for MV (13.8 kV) switches and between 1.7-2.2 times for LV
switches.
Use: 12 – 100 A – Medium Split-Core 1.25” (32mm) Opening
Disconnector Rating
Voltage Transformer IEC 62271-102(2001) High-voltage
69 kV switchgear and control gear - Part
VT- Primary Voltage = 102: Alternating current disconnectors
√3
VT- Primary Voltage = 39.8372 kV and earthing switches
13.8 kV
VT-Secondary Voltage = IEC 60099-8(2011) Part 8/IEEE C62.22
√3 page 8 – 16; Standard for Lightning
VT- Secondary Voltage = 7.9674 kV
Arrester and Ground Voltage Fault
Type: Disconnector Material: Porcelain
Rated Voltage: 13.2 kV Application
Current Transformer
IGROUNDING = 43. 7386 A
Use: Primary Current = 100 A IEC 60099-8(2011) Part 8/IEEE C62.22
Secondary Current = 5 A page 8 – 16; Standard for Lightning
Accuracy Power = 30 VA Arrester and Ground Voltage Fault
Accuracy Class = 0.5
Lighting Arrester
Voltage ×1.05
VLA =
√3
Highest Voltage NEC (2001) Article 310, Table 310.60
69 kV × 1.05
VLA = (C) (67) and 310.60(C) (69), page 226;
√3 Conductor for general wiring
VLA = 41.829 kV
Use: RP1 Primary Side Normal Duty Distribution Class (ZnO)
Nominal Voltage Philippine Grid Code PP. (32) Section 3.2.3 – the
13.8 kV × 1.05 system owner must ensure that the voltage variation
VLA = must be not more or less than +-5% of the nominal
√3 voltage at any point during normal operation.
VLA = 11.9512 kV
Use: RP1 Load Side Normal Duty Distribution Class (ZnO)
The voltage drop is passing because under National Electric Code (1999), Article 210, page 19 the
voltage drop should not exceed 5%.
Derating Factor
Stated under IEEE Std 80 (2000), Guide for safety in AC substation grounding
100
0.09 (1 - 100 ×100) IEEE Std 80 (2000), Guide for safety
CD = 1 - in AC substation grounding:
2 × 0.1 + 0.09
CD = 0.6928 Calculation of Potential Difference
Decrement Factor
Stated under IEEE Std 80 (2000), Guide for safety in AC substation grounding
X 1
Ta = × ( ) IEEE Std 80 (2000), Guide for safety
R 2 TF
1 in AC substation grounding:
Ta = 15 × ( ) Calculation of Potential Difference
2 T(60)
Ta = 0.0398
-2 × Tf
Ta
DF = √1+ ( ) (1 - e Ta ) IEEE Std 80 (2000), Guide for safety
Tf
Ta -2 × 0.15 in AC substation grounding:
DF = √1+ ( Tf ) (1 - e 0.0398 ) Calculation of Potential Difference
DF = 1.1248
Buried Length
Lr
L = LC+ [1.55 + 1.22 ( )] LR
√L2X + L2Y
IEEE Std 80 (2000), Guide for safety
in AC substation grounding:
3 Calculation of Potential Difference
L = LC+ [1.55 + 1.22 ( )] LR
√90 + 502
2
L = 994 m
1 1 1 1
KS = π [2h + D+h + D (1 – 0.5n-2)] IEEE Std 80 (2000), Guide for safety
1 1 1 1 in AC substation grounding:
KS = π [2 (0.6) + 12.5+0.6 + 12.5 (1 – 0.5n-2)] Calculation of Potential Difference
KS = 0.314
Power Losses
NLL = 19.2 kW IEEEC.57.12.00-2010 IEEE Standard
LL = 84.2 kW General Requirements for Liquid-
Immersed Distribution, Power, and
where: Regulating Transformers
NLL = No Load Losses
LL = Load Loss
where:
TL = Total Loss for the Step-up Transformer
NLL = No Load Losses
LL = Load Loss
TL = 103.4 kW
*Note: Transformer rating, losses, and short-circuit impedance are according to manufacturer
specifications: https://www.alibaba.com/product-detail/69kv-10mva-Power-Transformer-for-
Electric_60696507750.html?spm=a2700.7724857.normalList.30.18a4f9d2RWOnFO
Switchyard Layout
A switchyard, consisting of large breakers and towers, is usually located in an area close to the plant.
The substation is used as the distribution center where electrical power is supplied to the plant from
the outside, and electrical power is sent from the plant
The figure above shows the sections and details of the wind farm switchyard.
Stage 5: Wind Power Plant Design
The site in Calatagan has a flat terrain and does not have any tall structures in the vicinity, which
may have a significant effect on the wind farm layout.
Required kW Output
2
where:
Pout = Required kW Output of the Transformer
PDeficient = Power Deficiency in Balayan & Nasugbu in the year 2028
PTL = Total Losses in the Transformers
2
This wind turbine is characterized by blades which are perpendicular to the ground. Most of them
which are built nowadays are two or three-bladed. Meanwhile, there are some which use single blade
only or even more than three. The following is the wind turbine to be used.
Horizontal-axis wind turbines (HAWT) have the main rotor shaft and electrical generator at the top
of a tower, and may be pointed into or out of the wind. Small turbines are pointed by a simple wind
vane, while large turbines generally use a wind sensor coupled with a servo motor. Most have a
gearbox, which turns the slow rotation of the blades into a quicker rotation that is more suitable to
drive an electrical generator. HAWT in free standing configuration was made by steel pipe with a free
standing design. It was used for 1 kW to 50 kW wind turbines. The height of mono tower is usually
from 12m to 36m. It has less vibration and more reliable.
General Data
Manufacturer: Vestas (Denmark)
Model: V117
Nominal power: 4.2 MW
Rotor diameter: 57.2 m
Number of blades: 3
Start-up wind speed: 4 m/s
Maximum wind speed: 25 m/s
Generator output voltage: 690 V
Power Available in the Wind
To compute the available power in the wind we use the formula:
1
PAVAIL = 2 ρAV3
IEEE Trans Power Apparatus Syst
where: PAS-102(12):3791–3795. Stability
D
Swept area = π ( 2 )2 Simulation of Wind Turbine Systems.
Air Density = 1. 225 kg / m3
Wind Velocity = 9.88 m / s
Rotor Diameter = 52 Dm
52
PAVAIL = Pin = (0.5) (1.225) (9.88)3 π ( )2
2
PAVAIL = Pin = 3.0359 MW
Note: Pin is the mechanical power produce by the rotational movement of the wind turbine.
57.2
PMAX = (0.5) (1.225) (9.88)3 (0.5926) π ( )2
2
PMAX = 1.7990 MW
Generator Efficiency
Efficiency Generator = (0.95 × 0.97) × 100% = 92.15%
Efficiency at The Generation Part = (0.9215 × 0.98) × 100% = 90.307%
Note: Considering that the nominal power that the generator served was 1000 kW and the generator
should only be loaded at 50% of its full load.
Note: To know the number of turbines needed to be constructed we have to consider the electrical
power needed in the area which is 34.944 MW:
Losses Calculation
Power Input - losses
Efficiency = IEEE Trans Power Apparatus Syst
Power Input PAS-102(12):3791–3795. Stability
1.5079 MW - losses
92.15 % = Simulation of Wind Turbine Systems.
1.5079 MW
Losses = 1.5079 MW – 0.9215 (1.5079 MW)
Losses = 118.3702 kW per turbine
Note: To compute for the losses in each turbine consider the amount of mechanical power in the
wind turbine and the efficiency of the generator.
IEEE Trans Power Apparatus Syst
Total Power Losses PAS-102(12):3791–3795. Stability
Total losses = Losses × Number of Wind Turbines Simulation of Wind Turbine Systems.
Total losses = 118.3702 kW x 23
Total losses = 2.7225 MW
Note: To compute for the total losses in the wind turbines, multiply the total losses in each turbine to
the number of turbines.
The figure above shows the layout of the wind farm consisting of 23 wind turbines with a distance of
286 m between each of them.
Horizontal-axis wind turbine in lattice configuration turbines are delivered with steel towers, which
are manufactured in sections of 20-30 meters with flanges at either end, and bolted together on the
site. The towers are conical (i.e. with their diameter increasing towards the base) in order to increase
their strength and to save materials at the same time.
General Data
Manufacturer: Siemens Gamesa
Model: SG 4.5-145 DD
Nominal power: 4.8 MW
Rotor diameter: 145 m
Number of blades: 3
Start-up wind speed: 3 m/s
Maximum wind speed: 34 m/s
Generator output voltage: 690 V
Note: Pin is the mechanical power produce by the rotational movement of the wind turbine.
52
PMAX = (0.5) (1.225) (9.88)3 (0.5926) π ( )2
2 IEC 61400-12-1 Power Performance
PMAX = 8.8688 MW per turbine Measurements of Electricity
Producing Wind Turbines
Reasonably Obtainable Wind Power
IEC 61400-12-1 Power Performance
POBT = Cp (PAVAIL)
Measurements of Electricity
POBT = (0.55) (2.5090 MW)
POBT = 8.2313 MW Producing Wind Turbines
Generator Efficiency
Efficiency Generator = (0.95 × 0.97) × 100% = 92.15%
Efficiency at The Generation Part = (0.9215 × 0.98) × 100% = 90.307%
Note: Considering that the nominal power that the generator served was 1000 kW and the generator
should only be loaded at 50% of its full load.
Note: The electrical power output will depend on the efficiency at the generator part and the
mechanical power.
Note: To know the number of turbines needed to be constructed we have to consider the electrical
power needed in the area which is 34.944 MW:
Losses Calculation
Power Input - losses
Efficiency = IEEE Trans Power Apparatus Syst
Power Input PAS-102(12):3791–3795. Stability
1.3799 MW - losses
92.15 % = Simulation of Wind Turbine Systems.
1.3799 MW
Losses = 1.3799 MW – 0.9215 (1.3799 MW)
Losses = 108.3222 kW per turbine
Note: To compute for the losses in each turbine consider the amount of mechanical power in the
wind turbine and the efficiency of the generator.
IEEE Trans Power Apparatus Syst
Total Power Losses PAS-102(12):3791–3795. Stability
Total losses = Losses × Number of Wind Turbines Simulation of Wind Turbine Systems.
Total losses = 108.3222 kW x 26
Total losses = 2.8164 MW
Note: To compute for the total losses in the wind turbines, multiply the total losses in each turbine to
the number of turbines.
A type of vertical axis wind turbine (VAWT) used to generate electricity from the energy carried in
the wind. The turbine consists of a number of curved aero foil blades mounted on a vertical rotating
shaft or framework. The curvature of the blades allows the blade to be stressed only in tension at
high rotating speeds. A Darrieus wind turbines appear to be more suitable in different fields such as
building integration, the extreme zones (mountain refuge, observatories) than the classic wind
turbines. It is less efficient compared with the three-bladed wind turbines, this kind of wind turbine
can overcome the limits due to the sizes of blades and their rotation speed. The main advantage of
this type of turbines is that the generator can be easily set up in the ground.
General data
Manufacturer: Ropatec (Italy)
Model: TS30pro
Nominal power: 30 kW
Rotor Diameter: 12 m
Number of blades: 3
Start-up wind speed: 4 m/s
Maximum wind speed: 17 m/s
Generator Output voltage: 400 V
Note: Pin is the mechanical power produce by the rotational movement of the wind turbine.
12
PMAX = (0.5) (1.225) (9.88)3 (0.5926) π ( )2
2
PMAX = 79.1809 kW
Generator Efficiency
Efficiency Generator = (0.95 × 0.97) × 100% = 92.15%
Efficiency at The Generation Part = (0.9215 × 0.98) × 100% = 90.307%
Note: Considering that the nominal power that the generator served was 1000 kW and the generator
should only be loaded at 50% of its full load.
Note: The electrical power output will depend on the efficiency at the generator part and the
mechanical power.
Note: To know the number of turbines needed to be constructed we have to consider the electrical
power needed in the area which is 34.944 MW:
Losses Calculation
Power Input - losses
Efficiency = IEEE Trans Power Apparatus Syst
Power Input PAS-102(12):3791–3795. Stability
32.1776 kW - losses
92.15 % = Simulation of Wind Turbine Systems.
32.1776 MW
Losses = 32.1776 kW – 0.9215 (32.1776 kW)
Losses = 2.5259 kW per turbine
Note: To compute for the losses in each turbine consider the amount of mechanical power in the
wind turbine and the efficiency of the generator.
IEEE Trans Power Apparatus Syst
Total Power Losses PAS-102(12):3791–3795. Stability
Total losses = Losses × Number of Wind Turbines Simulation of Wind Turbine Systems.
Total losses = 2.5259 kW x 26
Total losses = 2.7405 MW
Note: To compute for the total losses in the wind turbines, multiply the total losses in each turbine to
the number of turbines.
The figure above shows the layout of the wind farm consisting of 8 wind turbines with a distance of
276 m between each of them.
A Savonius vertical-axis wind turbine is a slow rotating, high torque machine with two or more scoops
and are used in high-reliability low-efficiency power turbines. Most wind turbines use lift generated
by airfoil-shaped blades to drive a rotor, the Savonius uses drag and therefore cannot rotate faster
than the approaching wind speed.
General Data:
Manufacturer: Arborwind (Michigan, USA)
Model: PT-180
Nominal power: 60 kW @10.9 m/s
Rotor Diameter: 18 m
Number of blades: 3
Start-up wind speed: 3.129 m/s
Maximum wind speed: 11.176 m/s
Generator Output voltage: 480 V
Note: Pin is the mechanical power produce by the rotational movement of the wind turbine.
12
PMAX = (0.5) (1.225) (9.88)3 (0.5926) π ( )2
2
PMAX = 178.1523 kW
Generator Efficiency
Efficiency Generator = (0.95 × 0.97) × 100% = 92.15%
Efficiency at The Generation Part = (0.9215 × 0.98) × 100% = 90.307%
Note: Considering that the nominal power that the generator served was 1000 kW and the generator
should only be loaded at 50% of its full load.
Note: The electrical power output will depend on the efficiency at the generator part and the
mechanical power.
Note: To know the number of turbines needed to be constructed we have to consider the electrical
power needed in the area which is 34.944 MW:
Losses Calculation
Power Input - losses
Efficiency = IEEE Trans Power Apparatus Syst
Power Input PAS-102(12):3791–3795. Stability
48.2665 kW - losses
92.15 % = Simulation of Wind Turbine Systems.
48.2665 kW
Losses = 48.2665 kW – 0.9215 (48.2665 kW)
Losses = 3.7889 kW per turbine
Note: To compute for the losses in each turbine consider the amount of mechanical power in the
wind turbine and the efficiency of the generator.
IEEE Trans Power Apparatus Syst
Total Power Losses PAS-102(12):3791–3795. Stability
Total losses = Losses × Number of Wind Turbines Simulation of Wind Turbine Systems.
Total losses = 3.7889 kW x 724
Total losses = 2.7432 MW
Note: To compute for the total losses in the wind turbines, multiply the total losses in each turbine to
the number of turbines.
The figure above shows the layout of the wind farm consisting of 8 wind turbines with a distance of
90 m between each of them.
Figure 3.17 shows the single line diagram of the wind farm. Wind turbines are connected to breakers
to collector bus and goes through the collector feeder breakers. The local wind turbine grid can be
AC or DC and is the grid connecting the wind turbines together and to the collecting point. It is then
connected to switch gear or open substation which converts the voltage to a desired output. The
collecting point is the substation, including the transformer and power electronics used for the
respective transmission technology that is chosen. The transmission system is the connection to
shore, where the power is transmitted to the wind farm grid interface.