Anda di halaman 1dari 11

ASHIDA Numerical 3OC + 1EF Type: ADR241C

( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

Protection Features:  IEC60870-5-103 Protocol for


 4 Element (3 Phase + EF) Non Directional communication
Over current IDMT/DMT. Relay Design Features:
 Selection of Curve: Five selectable curve  16 x2 LCD Backlit display for Parameter
(Normal Inverse1 (C1), Normal Inverse2, and setting display
(C2) Very inverse (C3), Extremely inverse  Online display of CB status and other digital
(C4), Long time inverse (C5)) and Define and logical status.
Time (C6)  Continuous monitoring of module’s internal
 Instantaneous Over-Current Protection with hardware and alarm generation in case of
adjustable timer. failure of any critical components.
 Breaker Failure detection  4 Digital Output contacts for local alarm as
 In-built CB Trip Circuit Supervision function Trip
during pre closing and post closing of CB.  2 dedicated status input for Trip Circuit
 On site CT Secondary selection 1A or 5A. Monitoring
 Internal calculation of zero seq. current  5 nos of Fault data stored with keypad
(3Io) for Earth fault interface and time stamping.
 Wide range Power supply input 18V to
Description:
250V AC/DC
ADR241C is second generation Numerical 3OC
 Cold Load Pickup
+ 1EF Over Current Relay. It consist all the
 RS 485 communication port (at rear
side) for remote SCADA.

No t e : D u e t o o u r p o l i c y t o u p g r a d e o u r p r o d u c t s c o n s t a n t l y , we r e s e rv e t h e r i g h t t o
s u p p l y p r o d u c t s wh i c h m a y v a r y s l i g h tl y f ro m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 1 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

necessary protection and monitoring functions voltage supply for relay electronics and control
required for Normal feeder It consist of circuit. It also provides necessary isolation from
1. High Speed Digital DSP Controller station battery. The power supply module is
2. Analog Measuring Module design using very advance PWM controller
3. Power supply Module which allow very wide input supply variation i.e
4. Digital Input output module. 18V to 250VAC/DC covering 24Vdc, 30Vdc,
110Vdc and 220Vdc station battery
The High speed Digital Signal Controller (DSC)
requirement.
continuously monitors phase, E/F current along
with different optical isolated status The relay is having total 4 nos of high intensity
connections. The high-speed micro-controller dual LED for easy identification of type of fault
samples these current signals through a A/D for easy user interface. All LEDs and control
converter. The Digital Signal performs powerful output R1 to R4 are fully programmable via
Numerical Algorithms to find out RMS of keypad interface
fundamental & harmonic contents of the current
Main Functions
then this value is used for protection and
The ADR241C are having following protection
metering function. All measurement is tuned to
functions.
fundamental frequency i.e 50Hz, thus relay
1. Non Directional phase over current
remain stable during distorted waveform
element. (Ip>, and Ip>> )
generated electronics loco-motive. All these
2. Non Directional 3Io (Internally derived EF)
measure values are then used for different
(3Io> and 3Io>>).
protection function such as IDMT/DMT Over
3. Trip Circuit Super vision.
current protection, Instantaneous Over current
4. Breaker Failure Detection.
protection, Earth Fault protection, etc. These
5. Cold Load Pickup.
measured values are also displayed on large
6. Monitoring Functions.
16 x 2 LCD display for metering purpose. The
Each of these functions is independently
DSC also monitors different digital input through
programmable and can be enable or disable by
optical isolator and perform some monitoring
user depending upon requirement.
function such trip circuit supervision, and
control potential free contact for control CB and
Over Current & EF Element:
generate ALARM and Tele-signalling
The ADR241C is member of Ashida Numerical
Relay family design for protection general
The power supply module is basically DC – DC
feeder. The relay has one stage of IDMT/DMT
converted designed using modern PWM based
setting and one stage of instantaneous setting.
Switching mode technique to convert station
(Ip>, IP>>, 3Io>, 3Io>>). All major international
battery supply to the 12V and 24Vdc low

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 2 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

B+
IDMT curves are available. Range for IDMT TCCOM
1

6 To Relay CPU
stage is 10% to 250% and 50% to 3000% for 2

CB NO
instantaneous stage for both phase and 3Io.
B-
1
Although the curves tend towards infinite when 6 To Relay CPU
2
TC
the current approaches Is (general threshold), CB NC

the minimum guaranteed value of the operating Fig. Trip Circuit Logic
current for all the curves with the inverse time Relay monitor Trip coil continuity through CB
characteristic is 1.1Is (with a tolerance of ± NO during close condition and through CB NC
0.05Is). during Trip condition. If any discontinuity
Inverse Time Curves :- observed it generate Alarm signal.
The each stage thresholds for phase (earth) The output can be assigned to any of 4 relay
over current can be selected with an Inverse RL1 to RL4, The Trip circuit supervision logic
Definite Minimum Time (IDMT) characteristic. set reset PROTH (Protection healthy) bit, it
The time delay is calculated with a normally ON and become OFF at following
mathematical formula condition
 When DC supply is not sufficient (DC fail)
K * a
t= b  When CB NO and CB NC both active or
I
1 both inactive (CB NO as well as CB NC are
Iref
both close or open).
 Relay detects any internal hard ware Error.
Curve Description a b
Type Breaker Failure Detection:-
C1 Standard 0.14 0.02
Normally after tripping current should become
Inverse_1
Zero within 100 – 200ms time depend upon
C2 Standard 0.06 0.02
Inverse_2 type of fault and breaker mechanism. After
C3 Very Inverse 13.5 1 Fault ADR241C trigger internal timer (settable
C4 Extremely inverse 80 2 from 50ms to 800ms) if fault is not cleared
C5 Long Time Inverse 120 1 during this time then relay declare as Breaker
C6 Define Time - -
fail (LBB function) and set BF bit. This bit can

Trip circuit Supervision:- be assigned to any of the output relay.

The ADR241C is having 2 separate digital opto- Cold Load pickup:-

coupler status input which can be used to While closing the Circuit breaker on load, a load

continuously monitor continuity of trip-circuit. current takes sudden inrush current. This inrush
The general scheme is as shown in fig. current may be more than 4 to 5 times of rated
load current. The duration can be as high as
200ms. Due to this inrush current many times

No t e : D u e t o o u r p o l i c y t o u p g r a d e o u r p r o d u c t s c o n s t a n t l y , we r e s e rv e t h e r i g h t t o
s u p p l y p r o d u c t s wh i c h m a y v a r y s l i g h tl y f ro m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 3 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

relay get operate which is undesirable. General Programmable DI/DO and LED:-
practice is to keep normal setting to such high The ADR241C has 4 digital outputs, 2 opto-
value so that it will not mal operate at initial isolated input and 8 general purpose LEDs.
closing, which result increase in fault clearance These can be programmed by local key board.
time. To avoid such problem relay is equipped Any logical of physical status can be assigned to
with special features known as clod load any relay contact The logic of digital status input
pickup. Whenever a circuit breaker is turn on as well as logical status can be formed and
relay sense through CB auxiliary contact and assigned to any of the relay output. The RL1
start internal timer known as CL timer. During relay is by default assign to TRIPING CB.
this time it takes separate set of setting, so that
relay will not mal operate on inrush current

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 4 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

W hile O rde r i ng Spec if y t h e f ol lo wi n g I nfo r mat ion fo r AD R2 41 C R e la y

Definition of Model No of Aditya Series of Relays

AM XXX–XX – X – X – XX – X

Reserved for Future Use

Auxiliary Supply
PT Secondary 01 = 18 – 52 V dc 04 = 30 V dc
0 = NO PT 02 = 77 – 250 V dc 05 = 48 V dc
03 = 24 V dc 06 = 18 – 250 V dc

CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable

AM XXX XX X
Over Current Earth Fault Relay
For Aditya-V2 series start from 201. For V1 series refer respective document
201 01 Obsolete Version CSE – H – 150 3
201 02 Relay with standard Back Connection CSF – H – 136 3

O rd e ri n g i n f o r m a t i o n :

A D R 2 4 1 C - A M - X X X - X X - X - X - X X - X

E xa m p l e
A D R 2 4 1 C – AM - 2 0 1 -0 2 - 3 - 0 -0 6 -0
T yp e : A D R 2 4 1 C
S t. B a c k te r m i n a l l a yo u t
C a b i n e t T y p e : C SF -1 5 0 H
A u xi l i a r y S u p p l y : 1 8 -2 5 0 V d c
C T s e c : 1 Amp. / 5 Amp selectable

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 5 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

Technical Specifications:

General specifications
Sr. No. Specification Particulars
I. Current Input : Suitable for CT secondary 5Amp. Or 1Amp site selectable
II. Aux. Supply : 18 - 250VDC (Wide Range).
III. VA burden on CT : Less than 0.2VA
IV. VA burden on Aux. : Less than 10 Watts
V. Operating Temp. range : -10 deg. To + 65 deg.
VI. Continuous carrying : 2 x of rated for CT
capacity
VII. Pick up : Within 1.1 times of set value.
VIII. Reset Value : 95% to 90% of pick up.
IX. Output Contact : 4 Trip duty user assignable
X. Contact Rating : Continuous: 5A
: Make & carry for 0.5 sec : 30A
: Make carry for 3 sec : 15A
XI. Opto Isolated input : 1 for CB NO & 1 for CB NC
XII. Thermal With stand for CT : 20 x of rated for 3.0 sec.
General Settings
XIII. General setting : New PassWord 0 – 99 in steps of 1
: Unit Id 0 – 250 in steps of 1
: CT Sec 1A or 5A
: CT Primary 10 - 2000in steps of 10
: Test Block 01: YES, 02: NO
: Trip Ckt. 01: YES, 02: NO
:BF Enable 01: YES, 02: NO
: BF Delay 50-800 mS steps of 50ms
Relay Settings
XIV. Phase Section (Ip) : IP> Settings 10% – 250% in steps of 1%.
: IP> Time Multiplier (TMS) x0.01 – x1.00 in steps of 0.01
: IP> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6 )
: IP> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IP>> Settings 00% – 3000% insteps of 50% 00 means
block
: IP>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
XV. Earth Fault Section (3Io) : 3Io> Settings 10% – 250% insteps of 1%
: 3Io> Time Multiplier (TMS) x0.01 – x1.00 in step of 0.01.
: IE> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6 )
: 3IO> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 6 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

: 3IO>> Settings 00% – 3000% insteps of 50% 00 means


block
: 3IO>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
Cold Load settings
XVI. Phase Section (Ip) :CL Enable 01: YES, 02: NO
: CL Timer 0-2.00S in steps of 0.01 sec
: IP> Settings 10% – 250% in steps of 1%.
: IP> Time Multiplier (TMS) x0.01 – x1.00 in steps of 0.01
: IP> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6 )
: IP> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: IP>> Settings 00% – 3000% insteps of 50% 00 means
block
: IP>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
XVII. Earth Fault Section (3Io) : 3Io> Settings 10% – 250% insteps of 1%
: 3Io> Time Multiplier (TMS) x0.01 – x1.00 in step of 0.01.
: IE> Curve C1 – C6
(Operating Time) ( IDMT curve C1 – C5 or Define Time C6 )
: 3IO> C6 Delay 0 – 99.9 Sec in steps of 0.1Sec.
: 3IO>> Settings 00% – 3000% insteps of 50% 00 means
block
: 3IO>> Delay 0 – 2.00 Sec in steps of 0.01Sec.
Operational Indicators (Flags) 4 user assignable bicolour output LED Default assignment
XVIII. LED1 - PROT.H /ON : Green LED indicates Relay OK (Protection Healthy)
: Red LED indicates Fault in following conditions.
1. Problem in relay Hardware.
2. Trip Circuit Fault
LED 2 - PICK-UP : Red LED indicate Start of timer Self Reset (SR) Type
LED 3 - FAULT : Red LED indicate Relay Operated Flag (HR)
LED 4 - TRIP : Red LED indicates Output TRIP relay contact closer (SR) Type
XIX. Drawing References : For Typical External connection - ADV02702
: For Cabinet Type - MAC01501 (CSF)

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 7 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

The Relay Confirm to following standard


Sr. No. Title Standard no.
Electromagnetic Compatibility Type Test:
1. High Frequency Test : IEC 60255-22-1, class – III
: Frequency : 1MHz Damped Oscillatory
: Longitudinal :5 KV (peak)
: Duration: sec duration 2 sec.
: Between input current Terminal
2. Electrostatic : IEC 60255-22-2 Class III and IEC 61000-4-2 class III.
Discharge Direct : Contact discharge: 6kV,
Application : Air discharge: 8KV
: Polarity: both +ve and –Ve polarities.
3. Indirect Application : IEC-61000-4-2, Class-III
: IEC 60255-22-4 and IEC 61000-4-4, class A
Fast Transient
4. : 1.2KV; 5/50ns; 5KHz burst duration = 15ms.
Disturbance
: Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min.
: IEC 60255-22-5 / IEC 61000-4-6 class 4
: Differential Mode = 2kV
5. Surge Immunity Test
: Common Mode = 4kV
: 1.2/50uS , 5 surges of each polarity
6. Power Frequency : IEC-61000-4-8, Class-V
Magnetic Field Test
7. Radiated : IEC- 60255-22-3
Electromagnetic Field : EN-61000-4-3
Disturbance : Frequency 80MHz – 1GHz
8. Conducted Disturbance : IEC 60255-22-6 / IEC 61000-4-6: 1996.
Induced By Radio : Freq. 150kHz – 80MHz, Amplitude 10 V, Modulation 80% AM
Frequency Field @ 1 KHz
9. AC Ripple In DC : IEC 60255-11
Supply Test
10. Radiated Emission : IEC 60255-25
Insulation Tests:
11. High Voltage Test : IEC 60255-5. class – III
: At 2.5kV 50Hz between all terminal connected together and
earth for 1 minutes
12. Impulse Voltage Test : IEC 60255-5. class – III
: Test voltage: 5KV (peak) 1.2 / 50us,
: Energy :0.5 J,
: Polarity : + ve and – Ve
: Nos. of impulses : 3 positive and 3 negative impulse
: Duration between Impulses : 5 sec.
Environmental tests:
13. Cold test Storage test : IEC 60068-2-1
14. Dry heat test : IEC 60068-2-2
Damp heat test,
15. : IEC 60068-2-3
steady state

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 8 / 9
ASHIDA Numerical 3OC + 1EF Type: ADR241C
( AD I T Y AS e r i e s )
Protection Relay ( P r e l i m i n a r y)

16. Damp heat test, cyclic : IEC 60068-2-30


Mechanical tests
: IEC 60255-21-1 class 1
: Frequency Range = 10Hz – 150Hz , acceleration. = 1gn (9.8
17. Vibration
m/s2)
: Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis.
18. Bump Test : IEC 60255-21-2 Class-1
: 1000 bumps of 10gn peak acceleration and 16ms pulse
duration in each of the two opposite direction per axis as per
IEC 60255-21-2 class 1 No. of axes . 3.
19. Shock Withstand : IEC 60255-21-2 Clas-1
: 3 shocks of 15gn peak acceleration and 11ms pulse in each of
two opposite direction . No. of axis : 3
20. Seismic Test : IEC 60255-21-3
: In single axis sine sweep in X-axis
sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 3.5mm or 1.0gn
(whichever is less)
: In single axis sine sweep in Y-axis
- sweep (@a sweep rate of 1 octave/minute) vibration in the
frequency range (5-40 Hz) at amplitude of 1.5mm or 0.5gn
(whichever is less)

Revision Note

Rev. No. Date Description


01 26.04.10 Original specifications

N o t e : D u e t o o u r p o l i c y t o u p g ra d e o u r p r o d u c t s c o n s t a n t l y , w e r e s e r v e t h e r i g h t t o
s u p p l y p r o d u c ts w h i c h m a y v a r y s l i g h t l y f r o m t h a t i n d i c a t e d a b o v e .

ASHIDA ELECTRONICS PVT LTD.


ASHIDA HOUSE, Plot No. A-308, Road No. 21, Ref.:ADR241C

A
Wagle Industrial Estate,Thane (W)-400 604. INDIA.
E-mail: sales@ashidaelectronics.com Issue: 01 26.04.10
Web: www.ashidaelectronics.com Page 9 / 9

Anda mungkin juga menyukai