1 Select the PV module you will be using
2 Select the Morningstar controller you will be using
3 Result is the quantity of PV modules that may be used in series and parallel to safely operate within the charge controller ratings.
Maximum Power Rating (Pmax) 275.00
Open Circuit Voltage (Voc) 38.80
Maximum Power Voltage (Vmp) 30.90
Short Circuit Current (Isc) 9.47
Maximum Power Current (Imp) 8.91
TriStarMPPT60
Maximum Battery Current 60.00 A
Supported Nominal Battery Voltages 12V, 24V, 36V, 48V
Fields marked with an asterisk * are required
Calculate
Calculation Results
PV Module: Yingli Green Energy Holding Co., Ltd. PANDA 60 Cell YL275C
30b
Morningstar Product: TriStarMPPT60
PV Module Specifications Module Operation
http://stringcalculator.morningstarcorp.com/#manufacturer=1277&module=34491&product=23&vmin=46&vmax=58.8&tmin=10&tmax=35&tminunits=c&t… 1/2
3/10/2017 String Calculator » Morningstar Corporation
Name YL275C30b
Max. Operating Voc (record low temp.) 37.48 V
Pmax 275.00 W
Max. Voc (record low Temp., morning) 40.60 V
Voc 38.80 V
Minimum Vmp (average high temp.) 26.57 V
Isc 9.47 A
Maximum Vmp (record low temp.) 29.58 V
Vmp 30.90 V
Imp 8.91 A
NOCT 46.0 °C
Morningstar Product Specifications
Product Name TriStarMPPT60
Maximum Battery Current 60.00 A
Supported Nominal Battery Voltages 12V, 24V, 36V, 48V
Interactive String Results Array Information
1 String 2 Strings 3 Strings 4 Strings 5 Strings 6 Strings Max. Voc Max. Vin Min. Vmp Vb Max. Max. Vmp
2 Modules 550 1100 1650 2200 2750 3300 81.21 150.00 53.14 58.80 59.15
3 Modules 825 1650 2475 3300 4125 4950 121.81 150.00 79.71 58.80 88.73
Point to a cell in the table for more info. Click a cell to select and display with more information on new printable page.
String Results Legend
Optimal Configuration
Marginal performance in hot ambient temperature.
Maximum input voltage exceeded on or near record cold mornings.
Array Voc is close to Max. Input Voltage on record cold mornings.
Maximum Nominal Solar Input Power exceeded for this controller.
Exceeds maximum controller current rating.
Exceeds maximum operating input current rating.
Maximum Operational Input Voltage may be exceeded on near record cold mornings.
Invalid Configuration. Insufficient array voltage.