The aim of this project report is to estimate and calculate the approximate design of a 1MW solar PV
power plant (utility scale) so that we can come out with an approximate design of a 100MW solar PV
power Plant.
The total number of solar panel required and the different parameters of the solar panel estimated
using the solar intensity for Zimbabwe.
Also the brief details of the materials /equipments (solar panels, inverters, protective gears,
transformer, SCADA etc) used to set up a 100MW power plant are to be highlighted in this paper.
A financial overview with possible income datasheet is also to be included in the report.
TECHNICAL CALCULATION/ESTIMATION & SPECIFICATION
Divide this figure by the Wp of the chosen solar panel 3068.92 ~ 3069
to obtain the number of solar panels (here 290Wp)
By calculation and the demand of the plant, the total number of PV panels to be used = 3069
From 3069, total 3072 panels are considered to generate the required energy-1MW. For better
efficiency and to utilize the inverter and other components.
CONFIGURATION DETAILS:
3072 Panels are divided into 2 groups - each group containing 1536 solar panels. In each group,
1536 panels are further divided into 64 strings (parallel connection). Each string contains 24 solar
panels (series connection). So we will be having 100 groups of this configuration to generate a total
power of 100MW so the total number of PV modules required is 307200.
ELECTRICAL CALCULATION
The 100 MW solar power plant will be having a DC Output power of 104.96 MW as per this design.
The above specifications are available with Aelo Modules. Their module spec AELO S19 mono-crystalline Si
(High efficiency) has been used as a reference. The datasheet/spec. sheet of Aero S19 mono-crystalline has
been provided in this report.
INVERTER DETAILS AND SPECIFICATION; TYPE OF THE INVERTER CONSIDERED; SOLIVIA CL 600
Recommended specification
Input (DC)
OUTPUT (AC)
To meet the above stated criteria, SOLIVIA CL 600 Inverter manufactured by Delta Energy Systems
(India) PVT Ltd
Total of 2 inverters of SOLIVIA CL 600 inverter type required to generate the 1MW power, so we
need 200 inverters for the 100MW Solar PV Power Plant.
The system inverters typically provides power output of order 480VAC. Electricity grids operate at
much higher voltages of the order of tens or hundreds of thousands of volts, so transformers are
incorporated to deliver the required output of the grid.
Recon’s Oil Cooled Distribution Transformers were used as reference. Recon covers a wide range Oil
Cooled Transformers with Off Circuit Tap Changer? On Load Tap Changer (up to 5000 KVA in 11 KV &
33 KV) conforming to the international standards of quality and safety for industries and commercial
set-ups.
24pcs Solar panels are connected in series and totally we can get 64 groups solar panel lines
The 64 groups solar panel lines are connected with PV lightning protection combining box
(16 lines input and 1 line output)
The output line from PV lightning protection combining box is connected with 600KW in grid
Inverter.
Finally 2pcs 600KW in-grid Inverters are parallel and connected with utility grid.
DC SIDE PROTECTION
FUSES
FUSE HOLDERS
DC SWITCH
COOLING DEVICES
GROUNDING-FAULT PROTECTION
AC SIDE PROTECTION
1. Circuit breaker
2. Bar contractor
3. Insulation monitoring device
The safety and protection of the modules and plant equipments, protective gears from Schneider
Electric have been considered for maximum benefits and used as reference in this paper.
In a solar plant , data acquisition system is very important because we have to monitor the overall
system condition including Input/output condition, temperature, solar Insolation, Weather
condition, voltage/ current fluctuation, output power condition, surge effect, load dispatch etc.
SOLIVIA has to provide the monitoring facility/ SCADA for the power plant and the SOLIVIA CL 600
inverter itself has an In-built SCADA system.
So, for the monitoring and controlling of the over all power system of the plant, SOLIVIA SOLAR
SCADA system is recommended here.
FINANCIAL ANALYSIS & FEASIBILITY
Total expenses over the year for plant O&M and staffing = $ 4 000 000.00 ,this expense is considered
for regular maintenance cleaning of PV array, checking the status of inverter, cable-faulty,
emergency maintenance & replacement of components and annual salaries of O&M team of the
plant.