PROJECT:

22 TOWER STREET , BEDFORD ROW & JOCKEYS FIELD


& 49-51 FARRINGDON
OFFICE BUILDING SPACE
COOLING & VENTILATION LOAD CALCULATIONS

EXTERNAL & INTERNAL DESIGN CONDITIONS

EXTERNAL DESIGN CONDITIONS Reference

1 CITY LONDON
2 LOCATION UNITED KINGDOM
3 LATITUDE 51.48°N
4 LONGITUDE 0.45°W
5 SUMMER DB 28 0C From 2005 ASHRAE Handbook - Fundamentals
6 SUMMER MCWB 18.60C (SI)Design conditions for LONDON/HEATHROW,
8 MONSOON WB 25.90C United Kingdom
7 MONSOON MCDB 19.70C
9 WINTER DB - 3.40C
10 SUMMER DAILY RANGE 9.20C
11 ALTITUDE 24 MTRS
INTERNAL DESIGN CONDITIONS
BSRIA ,TABLE 25: Internal Environment Design
1 SUMMER 24±2 °C Criteria for Different Types of Building.
Page No-66
2 WINTER 20±2 °C
PROJECT: UK PROJECT

NAME OF THE BUILDINGS : 22 TOWER STREET , BEDFORD ROW & JOCKEYS FILED & 49-51 FARRINGDON

BUILDING TYPE: OFFICE BUILDING

ASSUMPTION REGISTER
Element Description Input Data REFERENCE INTEC REMARKS CLIENT REMARKS

Solid brick walls-No cavity or 1.6 (W/m2.K) As per Client's Input Received Dated 28-08-2018
insulation/Door - Existing Building

Solid brick walls for New Extension 0.25 (W/m2.K) As per Client's Input Received Dated 28-08-2018
conservatory -U value

Existing glazing/Windows -U value 1.6 (W/m2.K) As per Client's Input Received Dated 28-08-2018

Glazing/Windows for New Extension 1.2 (W/m2.K) As per Client's Input Received Dated 28-08-2018
conservatory -U value
U Values

Shading co-efficient of glazing/glass 0.9 As per Client's Input Received Dated 28-08-2018

Solar Heat Gain co-efficient of SHGC = SC X 0.87 = 0.78 As per Client's Input Received Dated 28-08-2018
glazing/glass

From CIBSE guide A,Pg 183


Partition walls 1.6 (W/m2.K) Table 3.50 Thermal properties of typical internal
partitions.

Exposed Roofs (W/m2.K) Please suggest for the U value

Floors (W/m2.K) Please suggest for the U value

People (Watts) Sensible Heat - 90 (W) From CIBSE guide A,Pg 6-2
Latent Heat - 50 (W) Table 6.1 Heat emissions from an adult male body

Lighting (W/sqm) 12 From BSRIA ,Pg 53


Table 17 Internal Heat gains in offices

Small Power (W/sqm) 25 From BSRIA ,Pg 53


Table 17 Internal Heat gains in offices
Internal Heat Gains

Computers (Sensible Heat- 75(W)


Office Equipments Monitor (Sensible Heat- 80 (W) From ASHRAE Pocket Handbook,Pg 169-170
Printers (Sensible Heat-275(W) Working,125 (W) Idle Heat gain from Typical Computer & office Equipment
Microwave (Sensible Heat- 400 (W)
Coffee Machine (Sensible Heat- 1050(W),Latent Heat- 450(W), 150w per
meeting room for tv screen on the wall.

12-16 L/s/person From BSRIA ,Pg 66- 67


(Note - Shall consider 12 L/s/person) Table 25 Internal & external design criteria
Outdoor Air Fresh Air
10 L/s/person As per Client's Input Received Dated 28-08-2018 On
Excel calculation Sheet

0.8 ACH As per Client's Input Received Dated 28-08-2018

Infiltration Leaky Building


1 ACH From CIBSE guide A,Pg 4-10
Table 4.10 Empirical values for air infiltration rate.

Maximum design conditions for Summer - July From 2005 ASHRAE Handbook - Fundamentals
Solar Heat Gains based on Orientation Of the Building and Winter Occours In- January (SI)Design conditions for LONDON/HEATHROW, United
Month WALLS Monsoon Occours In- June
Kingdom
ROOFS/FLOORS &
GLASS

Weather Data Sheet Please Refer To the PDF Attached in the mail & confirm

Orientation Based on Google Maps and Autocad

RFI REGISTER
1 Please provide the Sections for elevations In AutoCad For Calculations.

2 Number of electrical Equipments used in Office ,Kitchen Space ,coffee machines, microwave, Laser printers, Fax machines