Anda di halaman 1dari 3

Distributed Power System

Introduction

Distributed Power System (DPS) is a new generation power solution,


specialized for compact site. It consists of DC module, AC module &
battery module. It supports pole-mounted and wall-mounted. DPS can
be widely used for macro site, small cell and remote RRU.
DPU30D : DC module, converts AC/HVDC to -48Vdc, supplies 3
branches of DC output and 1 branch for battery
DPU30A : AC module, supplies constant 3 branches of AC output and a DOU-DCD01
branch of DC output for battery unit or DC load
DPU30D
DBU20B : battery module, provides reliable power backup
DBU20B
DOU-DCD01: DC distribution unit

DC Load Scenarios
Features
 Simple Deployment

• Fast installation, 10mins by 1 people, flexible deployment

• Multiple input mode: AC/HVDC (DPU30D)

 Easy O&M
AC Load
• Mobile APP (based on Bluetooth), NetEco

• Fan-free design, 3-5 years routine maintenance free


DPU30A
 Reliable Power Supply
DBU20B
• Iron lithium battery, IP65, working temperature -40℃ to +55℃

Scenarios

 RRU/AAU remote site AC Load Scenarios

 Easy Macro Site

 LampSite

 AtomCell (hot-spot / blind-spot coverage)


Specifications
DPS Solution for DC Load Scenarios
Product Type DPU30D-N06A1 DBU20B-N12A2 DBU20B-N12A1 DOU-DCD01
Dimension 400 mm × 300 mm ×
400 mm × 300 mm × 50 mm 400 mm × 300 mm × 120 mm 400 mm × 300 mm × 120 mm
(H×W×D) 50 mm

Weight 7 kg 20 kg 18kg 6 kg

Installation Mode Wall-mounted, pole-mounted, tower installation

Rated Power 1500 W 2000 W / 20 Ah 1000 W / 20 Ah NA

Cabling Mode Bottom inlet and outlet


System
Protection Level IP65

−40℃ to +55℃
Working
−40℃ to +55℃ IF up to 45℃, solar protection −40℃ to +55℃
Temperature
devices are needed

Cooling Mode Natural heat dissipation

Application
Class D Class D Class C Class D
Environment

Storage
−40℃ to +70℃
Temperature
Environme
nt Operating Humidity 5% to 95% (non-condensing)

Altitude −60 to +4000 m (1℃ per 200m temperature derating from 2000-4000m) NA

220 Vac single-phase, 110 Vac


Power Input Mode -48 Vdc -48 Vdc -48 Vdc
dual-live wire, HVDC

AC: 85 - 300 Vac


Input Voltage -48 Vdc -48 Vdc -48 Vdc
HVDC: 85 - 400 Vdc
Power
Input Input Frequency 45 Hz - 65 Hz NA NA NA

AC Input 1×220 V/15 A NA NA NA

Difference mode: 20 KA ,
AC SPD NA NA NA
Common mode: 20 KA

Output Power 1500 W 2000W 1000W NA

Output Voltage 48 Vdc -48 Vdc -48 Vdc 48 Vdc

3×30 A (with exchangeable 5×30 A (with


DC Output NA NA
Load fuse ) exchangeable fuse )
Output
1×40 A (with exchangeable 2×40 A (with exchangeable 2×40 A (with
Battery Branch 2×30 A (with exchangeable fuse )
fuse ) fuse ) exchangeable fuse )

Difference mode: 10 KA , Difference mode: 10 KA , Difference mode: 10 KA , Common


DC SPD NA
Common mode: 20 KA Common mode: 20 KA mode: 20 KA

Efficiency ≥96% NA NA NA

Communic 1× DB9 ( CAN)


ation Interface Definition 1× DB15 ( CAN+ 4× DO+ 2× RJ45 ( CAN) 2× DB9 ( CAN) NA
Interface RS485*)

*Remark: RS485 interface supports telecom protocol / NetEco / U2000/M2000


Specifications
DPS Solution for AC Load Scenarios
Product Type DPU30A-N06A1 DBU20B-N12A2 DBU20B-N12A1
Dimension (H×W×D) 400 mm × 300 mm × 50 mm 400 mm × 300 mm × 120 mm 400 mm × 300 mm × 120 mm

Weight 7 kg 20 kg 18 kg

Installation Mode Wall-mounted, pole-mounted, tower installation

Rated Power 1500 W 2000 W / 20 Ah 1000 W / 20 Ah

Cabling Mode Bottom inlet and outlet


System
Protection Level IP65

−40℃ to +55℃
Working Temperature −40℃ to +55℃ IF up to 45℃, solar protection devices
are needed

Cooling Mode Natural heat dissipation

Application Environment Class D Class D Class C

Storage Temperature −40℃ to +70℃

Environment Operating Humidity 5% to 95% (non-condensing)

Altitude −60 to +4000 m (1℃ per 200m temperature derating from 2000-4000m)

20 Vac single-phase, 110 Vac


Power Input Mode -48 Vdc -48 Vdc
dual-live wire

Input Voltage AC: 85 to 300 Vac -48 Vdc -48 Vdc

Power Input Input Frequency 45 Hz - 65 Hz NA NA

AC Input 1×220 V/15 A NA NA

Difference mode: 20 KA ,
AC Input SPD NA NA
Common mode: 20 KA

Output Power 1500 W 2000 W 1000 W

Output Voltage 220 Vac -48 Vdc -48 Vdc

Difference mode: 20 KA ,
AC Output SPD NA NA
Common mode: 20 KA
Load Output
AC Output 3×16 A NA NA

1×40 A (with exchangeable


Battery Branch 2×40 A (with exchangeable fuse ) 2×30 A (with exchangeable fuse )
fuse )

Difference mode: 3 KA , Difference mode: 10 KA , Common Difference mode: 10 KA , Common


DC SPD
Common mode: 5 KA mode: 20 KA mode: 20 KA

Efficiency ≥98% Bypass NA NA

1× DB9 ( CAN)
Communicati
Interface Definition 1× DB15 ( CAN+ 4× DO+ 2× RJ45( CAN) 2× DB9( CAN)
on Interface RS485*)

*Remark: RS485 interface supports telecom protocol / NetEco / U2000/M2000

Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved. HUAWEI TECHNOLOGIES CO., LTD.
No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd. Huawei Industrial Base
General Disclaimer Bantian Longgang
The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating Shenzhen 518129, P.R. China
results, future product portfolio, new technology, etc. There are a number of factors that could cause actual results and developments to differ materially
from those expressed or implied in the predictive statements. Therefore, such information is provided for reference purpose only and constitutes neither an Tel: +86-755-28780808
offer nor an acceptance. Huawei may change the information at any time without notice.
www.huawei.com