ETAP Page: 1
12.6.0H
Location: Date: 08-11-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS 4 Config.: Normal
Short-Circuit Analysis
ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
1/2 Cycle Network
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
19 Buses Total
Ohms or Siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable Length
Grounding
Branch Connections
GRID 1 Bus1 200.000 20.000 10.00 4.97519 49.75186 Wye - Solid 10.00 4.975186 49.75186
GRID 2 Bus2 200.000 20.000 10.00 4.97519 49.75186 Wye - Solid 10.00 4.975186 49.75186
Induction Machine Rating (Base) Positive Seq. Imp. Grounding Zero Seq. Imp.
ID Type Qty kVA kV RPM X"/R %R % X" % X' Conn. Type Amp X/R % R0 % X0
Mtr1 Motor 1 157.75 5.500 1500 10.00 1.845 18.46 46.15 Wye Open 10.00 1.845 18.46
Mtr2 Motor 1 391.31 5.500 1500 16.52 1.117 18.46 46.15 Wye Open 16.52 1.117 18.46
Mtr3 Motor 1 157.75 5.500 1500 10.00 1.845 18.46 46.15 Wye Open 10.00 1.845 18.46
Mtr4 Motor 1 391.31 5.500 1500 16.52 1.117 18.46 46.15 Wye Open 16.52 1.117 18.46
Mtr5 Motor 1 157.75 5.500 1500 10.00 1.845 18.46 46.15 Wye Open 10.00 1.845 18.46
Mtr6 Motor 1 157.75 5.500 1500 10.00 1.845 18.46 46.15 Wye Open 10.00 1.845 18.46
Mtr7 Motor 1 157.75 5.500 1500 10.00 1.845 18.46 46.15 Wye Open 10.00 1.845 18.46
Bus3 Total 0.00 5.696 0.00 97.10 95.33 6.156 6.156 2.75E+001 1.82E+002 1.67E+001 1.42E+002
Bus5 Bus3 19.36 0.085 13.95 92.27 102.26 0.061 0.000 3.56E+003 1.18E+004
Bus8 Bus3 58.93 0.259 42.47 97.08 113.89 0.186 0.000 3.35E+003 2.29E+003
Bus1 Bus3 74.10 5.439 86.34 100.00 86.41 5.970 6.156 * 2.17E+001 1.92E+002 1.67E+001 1.42E+002
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 10
12.6.0H
Location: Date: 08-11-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS 4 Config.: Normal
Bus3 5.50 0.849 -5.632 5.696 0.863 -6.095 6.156 4.877 0.736 4.933 4.444 4.056 6.016
All fault currents are symmetrical momentary (1/2 Cycle network) values in rms kA
* LLG fault current is the larger of the two faulted line currents
Project:
ETAP Page: 11
12.6.0H
Location: Date: 08-11-2018
Contract: SN:
Engineer: Revision: Base
Study Case: SC
Filename: TUGAS 4 Config.: Normal
Bus Positive Sequence Imp. (ohm) Negative Sequence Imp. (ohm) Zero Sequence Imp. (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
Bus3 5.500 0.08314 0.55129 0.55752 0.08314 0.55129 0.55752 0.05054 0.42961 0.43258