GENERAL

General
Design Code & Reference
Design Method
Design Data
GEOTECHNICAL PILE CAPACITY
BH-01
BH-02
BH-03
SUMMARY
STRUCTURAL PILE DESIGN

TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE

Cast In Situ PILE ( Φ = 600, L = 15m ) Calculation


Cast In Situ PILE ( Φ = 600, L = 18m ) Calculation
Cast In Situ PILE ( Φ = 600, L = 20m ) Calculation
Cast In Situ PILE ( Φ = 600, L = 25m ) Calculation
CONCLUSIONS
ATTACHMENT
Attachment-1: Borehole Location
Attachment-2: Borehole Logs
Attachment-3: Pile Drawing

GENERAL
1.1 General
For the Olkaria Ⅳ Geothermal Power Plant Project, pile foundation will be needed to support the
buildings and concrete structures depending on sub-soil condition.
The allowable pile capacity was calculated base on soil investigation results which will be submitted
as separate report(Doc No. ZP00700-B2CE-ECG-RPT-0001).
In consideration of sub-soil condition, the various bored pile will be adopted.
1.2 Design Code & Reference
1 BS 8110 : Structural Use of Concrete
2 BS 8004 : Foundations
3 3) Principles of Foundation Engineering, 6th Edition, Braja M. Das, Thomson Learning, 2007
4 ZP00700-B2CE-ECG-DSC-0001: Design Criteria for Civil and Building Works
5 FHWA-IF-99-025: Drilled Shafts: Construction Procedures and Design Methods
1.3 Design Criteria
1 Factor of Safety for End Bearing, FSbearing 2 =
2 Factor of Safety for Skin Friction, FSfriction
2 =
3 Factor of Safety for Lateral Load, FSlateral2 =

TITLE : DESIGN CALCULATION - BORED CAST IN-SITU PILE


1.4 Design Data
1 Pile
Type : Bored Pile
Dimension : D mm 600 mm
Modulus of elasticity (Ep) : 25,000,000 kN/m²
2
Pile section (Ap) 282600 mm

2 Concrete
Concrete Strength (fcu) 25 N/mm²
Unit weight (γc) 24 kN/m²
Modulus of elasticity (Ec) 25,000,000 kN/m²

3 Reinforcement steel (BS 4449)

Minimum yield strength (fy) 460 N/mm²


Modulus of elasticity (Es) 2.00E+05 N/mm²
Minimum cover to reinforcement 60 mm