MAIN SUMMARY

DETAILS OF CONNECTED LOAD


Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMMODATION
FEED FROM: DEWA

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE ECC


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C SIZE
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM SQ.MM
INCOMER
TP
OUTGOING
MDB-1 4P 1600 BY DEWA 2X150

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at 0.9 D.F
N SUMMARY
NECTED LOAD PLOT NO:

UR ACCOMMODATION

CONNCETED LOAD KWHR METER REMARKS


RYB FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH

217.36 216.56 217.53 651.45 1 1600/5A CT METER

1
217.36 216.56 217.53
651.45 KW
586.31
PROVIDE CT METER ABOVE MAX DEMAND
SUMMARY OF M
DETAILS OF CONNECTE
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACC
FEED FROM: METER CABINET

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE


FEEDER ISO ACB MCCB SWA 2/4X1C
DB. NO SP TP DUTY
XLPE SQ.MM
INCOMER
INCOMER-1 4P 1600 65 BY DEWA
INCOMER-2 4P PROVISION FOR MOBILE GENERATOR W
1600 65

OUTGOING
SMDB GF TP 125 50 4c x 50sqmm (XLPE)
SMDB FF TP 100 50 4c x 35sqmm (XLPE)
SMDB SF TP 100 50 4c x 35sqmm (XLPE)
SMDB TF TP 100 50 4c x 35sqmm (XLPE)
SMDB 4F-1 TP 400 50 4c x 300 sqmm (XLPE)
SMDB 4F-2 TP 400 50 4c x 300 sqmm (XLPE)
FIRE PUMP TP 250 50 4c x 150 sqmm (XLPE)
DB SS TP 32 35 2c x 10 sqmm (XLPE)
CAP Bank TP 630 50 2x4c x 185 sqmm (XLPE)

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
SUMMARY OF MDB-1
AILS OF CONNECTED LOAD PLOT NO:

(G+4)LABOUR ACCOMMODATION

CABLE SIZE ECC CONNCETED LOAD KWHR METER


2/4X2C SIZE
RPH YPH BPH 1 2 3 CT
SQ.MM SQ.MM

BY DEWA 1Cx150 217.36 216.56 217.53 1


N FOR MOBILE GENERATOR WITH ELECTRICAL AND MECHANICAL INTERLOCK

50sqmm (XLPE) 25 19.10 18.10 20.95 58.15


35sqmm (XLPE) 25 15.25 15.40 14.95 45.60
35sqmm (XLPE) 25 15.25 15.60 15.15 46.00
35sqmm (XLPE) 25 14.25 14.60 14.15 43.00
300 sqmm (XLPE) 150 63.61 63.97 63.42 191.00
300 sqmm (XLPE) 150 57.90 57.89 57.91 173.70
150 sqmm (XLPE) 95 31.00 31.00 31.00 93.00
10 sqmm (XLPE) 10 1.00 1.00
185 sqmm (XLPE) 2x95 250 KVAR Cap Bank

1
D PER PHASE 217.36 216.56 217.53
D (KW) 651.45 KW
586.31
PROVIDE CT METER ABOVE MAX DEMAND
REMARKS
FULL LOAD
AMP/PH

1600/5A CT METER

ELR+ ALARM

KW
DEMAND
SUMMARY OF SMDB-G
DETAILS OF CONNECTED LOA
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMM
FEED FROM: MDB-1

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM
INCOMER
TP 125 4c x 50 sqmm (XLPE)
OUTGOING
DB GF L TP 40 25 4c x 10 sqmm (XLPE)
DB GF P TP 80 25 4c x 25 sqmm (XLPE)
Jockey pump TP 25 25 4c x 6 sqmm (XLPE)
TRANSFER PUMP TP 32 25 4c x 6 sqmm (XLPE)

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
MARY OF SMDB-GF
F CONNECTED LOAD PLOT NO:

LABOUR ACCOMMODATION

ECC CONNCETED LOAD KWHR METER REMARKS


SIZE FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH
SQ.MM

25 19.10 18.10 20.95

10 3.50 1.70 3.05 8.25


16 10.60 11.40 12.90 34.90
6 2.00 2.00 2.00 6.00 ELR+ ALARM
6 3.00 3.00 3.00 9.00 40A,30ma ELCB

1
R PHASE 19.10 18.10 20.95
W) 58.15 KW
52.34
PROVIDE CT METER ABOVE MAX DEMAND
SUMMARY OF SMDB-FF
DETAILS OF CONNECTED LOAD
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMMODATIO
FEED FROM: MDB

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE ECC


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C SIZE
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM SQ.MM
INCOMER
TP 100 4c x 35 sqmm (XLPE) 25
OUTGOING
DB FF L TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF P TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF AC TP 32 25 4c x 10 sqmm (XLPE) 10
SPARE TP 32 25

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
RY OF SMDB-FF
ECTED LOAD PLOT NO:

R ACCOMMODATION

CONNCETED LOAD KWHR METER REMARKS


FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH

15.25 15.40 14.95 45.60

3.65 4.10 4.55 12.30


6.60 6.20 5.30 18.10
1.00 1.10 1.10 3.20
4.00 4.00 4.00 12.00

15.25 15.40 14.95 45.60


45.60 KW
41.04
PROVIDE CT METER ABOVE MAX DEMAND
SUMMARY OF SMDB-SF
DETAILS OF CONNECTED LOAD
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMMODATIO
FEED FROM: MDB

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE ECC


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C SIZE
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM SQ.MM
INCOMER
TP 100 4c x 35 sqmm (XLPE) 25
OUTGOING
DB FF L TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF P TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF AC TP 32 25 4c x 10 sqmm (XLPE) 10
SPARE TP 40 25

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
RY OF SMDB-SF
ECTED LOAD PLOT NO:

R ACCOMMODATION

CONNCETED LOAD KWHR METER REMARKS


FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH

15.25 15.60 15.15

3.65 4.10 4.55 12.30


6.60 6.40 5.50 18.50
1.00 1.10 1.10 3.20
4.00 4.00 4.00 12.00

15.25 15.60 15.15


46.00 KW
41.40
PROVIDE CT METER ABOVE MAX DEMAND
SUMMARY OF SMDB-TF
DETAILS OF CONNECTED LOAD
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMMODATIO
FEED FROM: MDB

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE ECC


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C SIZE
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM SQ.MM
INCOMER
TP 100 4c x 35 sqmm (XLPE) 25
OUTGOING
DB FF L TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF P TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF AC TP 32 25 4c x 10 sqmm (XLPE) 10
SPARE TP 32 25

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
RY OF SMDB-TF
ECTED LOAD PLOT NO:

R ACCOMMODATION

CONNCETED LOAD KWHR METER REMARKS


FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH

14.25 14.60 14.15

3.65 4.10 4.55 12.30


6.60 6.40 5.50 18.50
1.00 1.10 1.10 3.20
3.00 3.00 3.00 9.00

14.25 14.60 14.15


43.00 KW
38.70
PROVIDE CT METER ABOVE MAX DEMAND
SUMMARY OF SMDB-4F-1
DETAILS OF CONNECTED LOAD
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMMODATIO
FEED FROM: MDB

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE ECC


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C SIZE
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM SQ.MM
INCOMER
TP 400 4c x 300 sqmm (XLPE) 150
OUTGOING
DB FF L TP 40 25 4c x 10 sqmm (XLPE) 10
DB FF P TP 40 25 4c x 10 sqmm (XLPE) 16
DB FF AC TP 32 25 4c x 10 sqmm (XLPE) 10
VRF-RF-1 TP 100 25 4c x 35 sqmm (XLPE) 25
VRF-RF-2 TP 125 25 4c x 50 sqmm (XLPE) 25
VRF-RF-3 TP 125 25 4c x 50 sqmm (XLPE) 25
LIFT-1 TP 40 25 4c x 16 sqmm (XLPE) 16

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
RY OF SMDB-4F-1
ECTED LOAD PLOT NO:

R ACCOMMODATION

CONNCETED LOAD KWHR METER REMARKS


FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH

63.61 63.97 63.42

3.65 4.10 4.55 12.30


6.60 6.40 5.50 18.50
1.00 1.10 1.10 3.20
13.60 13.60 13.60 40.80 100A,100ma ELCB
16.90 16.90 16.80 50.60 100A,100ma ELCB
17.86 17.87 17.87 53.60 ELR+SHUNT TRIP
4.00 4.00 4.00 12.00 40A,300ma ELCB

63.61 63.97 63.42


191.00 KW
171.90
PROVIDE CT METER ABOVE MAX DEMAND
SUMMARY OF SMDB-4F
DETAILS OF CONNECTED LOAD
Planned Completion Date:12-10-2018
PROPOSED (G+4)LABOUR ACCOMMODA
FEED FROM: MDB

CIRCUIT RATING IN AMPS FAULT PVC CABLE SIZE


FEEDER ISO ACB MCCB SWA 2/4X1C 2/4X2C
DB. NO SP TP DUTY
XLPE SQ.MM SQ.MM
INCOMER
TP 400 4c x 300 sqmm (XLPE)
OUTGOING
FAHU-1 TP 80 25 4c x 25 sqmm (XLPE)
FAHU-2 TP 63 25 4c x 25 sqmm (XLPE)
KEF 32 25 4c x 6 sqmm (XLPE)
ECOLOGY UNIT TP 32 25 4c x 10 sqmm (XLPE)
WATER HEATER TP 32 25 4c x 6 sqmm (XLPE)
WATER HEATER TP 32 25 4c x 6 sqmm (XLPE)
TEF TP 32 25 4c x 10 sqmm (XLPE)
GEF 20 25 4c x 4 sqmm (XLPE)
VRF-RF-4 TP 100 25 4c x 35 sqmm (XLPE)
VRF-RF-5 TP 63 25 4c x 16 sqmm (XLPE)

Ensure that F/S does allow TOTAL CONNECTED LOAD PER PHASE
replacement of fuse rated
TOTAL CONNECTED LOAD (KW)
higher than specified for the
circuit cable. Max Demand at .9 D.F
MMARY OF SMDB-4F-2
F CONNECTED LOAD PLOT NO:

LABOUR ACCOMMODATION

ECC CONNCETED LOAD KWHR METER REMARKS


SIZE FULL LOAD
RPH YPH BPH 1 2 3 CT AMP/PH
SQ.MM

150 57.90 57.89 57.91 173.70

16 11.63 11.63 11.64 34.90 80A,100ma ELCB


16 8.30 8.30 8.30 24.90 63A,100ma ELCB
6 3.00 3.00 3.00 9.00 40A,100ma ELCB
10 3.20 3.20 3.20 9.60 40A,100ma ELCB
6 3.00 3.00 3.00 9.00 40A,30ma ELCB
6 3.00 3.00 3.00 9.00 40A,30ma ELCB
10 3.00 3.00 3.00 9.00 40A,100ma ELCB
4 1.00 1.00 1.00 3.00 40A,100ma ELCB
25 15.20 15.20 15.20 45.60 100A,100ma ELCB
16 6.57 6.56 6.57 19.70 63A,100ma ELCB

HASE 57.90 57.89 57.91 173.70


173.70 KW
156.33
PROVIDE CT METER ABOVE MAX DEMAND
PROJECT: PROPOSED G+4 LABOUR ACCOMODATION LOAD DISTRIBUTION
FED FROM : SMDB-GF LOCATION: GF
SCHEDULE for D/B
DB GF L
Ratin
CCT
ECT Load Per
SEC NO:
Rating MCB Wire watt/ Circuit in watts
g of SL. Ckt. Wire Room location/
of Rtg Size
Inco- No. No. Size Area unit
ELCB in A mm Ind. Ex. Inse 13A 13A 15A Split
mer
2
mm2 LTG
Fan Fan ct Sso Dso Sso
ISO W/H
Ac R Y B
1 R1 10 2.5 2.5 DINING ROOM 9 50 450
40 A ELCB, 100ma

2 Y1 10 2.5 2.5 KITCHEN 10 50 500


SEC 1

3 B1 10 2.5 2.5 KITCHEN 5 50 250


4 R2 10 2.5 2.5 PRAYER ROOM 10 50 500
5 Y2 10 2.5 2.5 STEPS 2 50 100
6 B2 10 2.5 2.5 ISOLATION ROOM 4 50 200
7 R3 10 2.5 2.5 TOILET 6 50 300
40 A ELCB, 100ma

8 Y3 10 2.5 2.5 LV ROOM 4 50 200


SEC 2

9 B3 10 2.5 2.5 PARKING 2 50 100


10 R4 10 2.5 2.5 SUBSTATION 6 50 300
11 Y4 10 2.5 2.5 TELEPHONE ROOM 2 50 100
40 A TP ISOLATOR

12 B4 10 2.5 2.5 PARKING 4 50 200


13 R5 10 2.5 2.5 PARKING 3 50 150
40 A ELCB, 100ma

14 Y5 10 2.5 2.5 DINING ROOM 6 50 300


SEC 3

15 B5 10 2.5 2.5 DINING ROOM 12 50 600


16 R6 10 2.5 2.5 DINING ROOM 12 50 600
17 Y6 10 2.5 2.5 GARBAGE ROOM 4 50 200
18 B6 10 2.5 2.5 STAIRCASE 24 50 1,200
24 50 1,200
40 A ELCB,

19 R7 10 2.5 2.5 STAIRCASE


SEC 4

100ma

20 Y7 10 2.5 2.5 BOUNTARY LIGHT 6 50 300


21 B7 10 SPARE 500

3,500 1,700 3,050


8,250
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC Total Connected Load
ATION: GF

Re-mark
PROJECT: PROPOSED G+4 LABOUR ACCOMODATION LOAD DISTRIBUTION
FED FROM : SMDB-FF LOCATION: FF
SCHEDULE for D/B
DB FF L
Ratin MC CCT ECT
Load Per
g of SEC NO: Rating
SL. Ckt. B Wire Wire Room location/ watt/ Circuit in watts
of
Inco- No. No. Rtg Size Size Area unit
ELCB C. Ex. Inse 13A 13A 15A Split
mer in A mm2 mm2 LTG
Fan Fan ct Sso Dso Sso
ISO W/H
Ac R Y B
ROOM
1 R1 10 2.5 2.5 3 2 50,100 350
40 A ELCB, 100ma

Area
ROOM
2 Y1 10 2.5 2.5
Area
3 2 50,100 350
ROOM
SEC 1

3 B1 10 2.5 2.5
Area
3 2 50,100 350
4 R2 10 2.5 2.5 ROOM 3 2 50,100 350
5 Y2 10 2.5 2.5 CORRIDOR 13 50 650
6 B2 10 2.5 2.5 CORRIDOR 12 50 600
7 R3 10 2.5 2.5 CORRIDOR 12 50 600
40 A ELCB, 100ma

8 Y3 10 2.5 2.5 ROOM 3 2 50,100 350


SEC 2

9 B3 10 2.5 2.5 ROOM 3 2 50,100 350


10 R4 10 2.5 2.5 ROOM 3 2 50,100 350
11 Y4 10 2.5 2.5 ROOM 3 2 50,100 350
12 B4 10 2.5 2.5 ROOM 3 2 50,100 350
13 R5 10 2.5 2.5 ROOM 2 1 50,100 200
40 A ELCB, 100ma

14 Y5 10 2.5 2.5 ROOM 3 2 50,100 350


SEC 3

15 B5 10 2.5 2.5 ROOM 3 2 50,100 350


40 A TP ISOLATOR

16 R6 10 2.5 2.5 ROOM 2 1 50,100 200


17 Y6 10 2.5 2.5 TOILET 7 50 350
18 B6 10 2.5 2.5 TOILET 7 50 350
19 R7 10 2.5 2.5 TOILET 7 50 350
40 A ELCB, 100ma

20 Y7 10 2.5 2.5 TOILET 9 50 450


SEC 4

21 B7 10 2.5 2.5 TOILET 10 50 500


22 R8 10 2.5 2.5 TOILET 13 50 650
23 Y8 10 2.5 2.5 ROOM 3 2 50,100 350
24 B8 10 2.5 2.5 ROOM 3 2 50,100 350
25 R9 10 2.5 2.5 ROOM 4 2 50,100 400
40 A ELCB, 100ma

26 Y9 10 2.5 2.5 ROOM 4 2 50,100 400


SEC 5

27 B9 10 2.5 2.5 ROOM 3 2 50,100 350


28 R10 10 2.5 2.5 ROOM 2 1 50,100 200
29 Y10 10 SPARE 500
30 B10 10 SPARE 500

500
3,650 4,100 4,550
Total Connected Load 12,300
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC
ON: FF

Re-mark
PROJECT: PROPOSED G+4 LABOUR ACCOMODATION LOAD DISTRIBUTION
FED FROM : SMDB-TF
SCHEDULE for D/B LOCATION: TF

DB TF L

Rating SEC NO: CCT ECT


Load Per
MCB Circuit in watts
of Rating of SL. Ckt.
Rtg
Wire Wire Room location/ watt/
Inco- ELCB No. No. Size Size Area unit
in A C. Ex. Inse 13A 13A 15A Split
mer mm2 mm2 LTG
Fan Fan ct Sso Dso Sso
ISO W/H
Ac R
ROOM
1 R1 10 2.5 2.5 3 2 50,100 350
ROOM
40 A ELCB, 100ma

2 Y1 10 2.5 2.5 3 2 50,100


ROOM
SEC 1

3 B1 10 2.5 2.5 3 2 50,100


ROOM
4 R2 10 2.5 2.5 3 2 50,100 350
5 Y2 10 2.5 2.5 CORRIDOR 13 50
6 B2 10 2.5 2.5 CORRIDOR 12 50
7 R3 10 2.5 2.5 CORRIDOR 12 50 600
40 A ELCB, 100ma

8 Y3 10 2.5 2.5 ROOM 3 2 50,100


SEC 2

9 B3 10 2.5 2.5 ROOM 3 2 50,100


10 R4 10 2.5 2.5 ROOM 3 2 50,100 350
11 Y4 10 2.5 2.5 ROOM 3 2 50,100
12 B4 10 2.5 2.5 ROOM 3 2 50,100
13 R5 10 2.5 2.5 ROOM 2 1 50,100 200
40 A ELCB, 100ma

14 Y5 10 2.5 2.5 ROOM 3 2 50,100


ROOM 3 2 50,100
SEC 3

15 B5 10 2.5 2.5
40 A TP ISOLATOR

16 R6 10 2.5 2.5 ROOM 2 1 50,100 200


17 Y6 10 2.5 2.5 TOILET 7 50
18 B6 10 2.5 2.5 TOILET 7 50
19 R7 10 2.5 2.5 TOILET 7 50 350
40 A ELCB, 100ma

20 Y7 10 2.5 2.5 TOILET 9 50


SEC 4

21 B7 10 2.5 2.5 TOILET 10 50


22 R8 10 2.5 2.5 TOILET 13 50 650
23 Y8 10 2.5 2.5 ROOM 3 2 50,100
24 B8 10 2.5 2.5 ROOM 3 2 50,100
25 R9 10 2.5 2.5 ROOM 4 2 50,100 400
A ELCB, 100ma

26 Y9 10 2.5 2.5 ROOM 4 2 50,100


SEC 5

27 B9 10 2.5 2.5 ROOM 3 2 50,100


40 A ELCB,
SEC
28 R10 10 2.5 2.5 ROOM 2 1 50,100 200
29 Y10 10 SPARE
30 B10 10 SPARE

3,650
Total Connected Load 12,300
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC
LOCATION: TF

Load Per Re-mark


Circuit in watts

Y B

350
350

650
600

350
350

350
350

350
350

350

350

450
500

350
350

400
350
500
500

500
4,100 4,550
12,300
PROJECT: PROPOSED G+4 LABOUR ACCOMODATION LOAD DISTRIBUTION
FED FROM : SMDB-4F LOCATION: 4F
SCHEDULE for D/B
DB 4F L
Ratin MC CCT ECT
Load Per
g of SEC NO: Rating
SL. Ckt. B Wire Wire Room location/ watt/ Circuit in watts
of
Inco- No. No. Rtg Size Size Area unit
ELCB C. Ex. Inse 13A 13A 15A Split
mer in A mm2 mm2 LTG
Fan Fan ct Sso Dso Sso
ISO W/H
Ac R Y B
ROOM
1 R1 10 2.5 2.5 3 2 50,100 350
ROOM
40 A ELCB, 100ma

2 Y1 10 2.5 2.5 3 2 50,100 350


ROOM
3 B1 10 2.5 2.5 3 2 50,100 350
SEC 1

ROOM
4 R2 10 2.5 2.5 3 2 50,100 350
5 Y2 10 2.5 2.5 CORRIDOR 13 50 650
6 B2 10 2.5 2.5 CORRIDOR 12 50 600
7 R3 10 2.5 2.5 CORRIDOR 12 50 600
40 A ELCB, 100ma

8 Y3 10 2.5 2.5 ROOM 3 2 50,100 350


SEC 2

9 B3 10 2.5 2.5 ROOM 3 2 50,100 350


10 R4 10 2.5 2.5 ROOM 3 2 50,100 350
11 Y4 10 2.5 2.5 ROOM 3 2 50,100 350
12 B4 10 2.5 2.5 ROOM 3 2 50,100 350
13 R5 10 2.5 2.5 ROOM 2 1 50,100 200
40 A ELCB, 100ma

14 Y5 10 2.5 2.5 ROOM 3 2 50,100 350


SEC 3

15 B5 10 2.5 2.5 ROOM 3 2 50,100 350


40 A TP ISOLATOR

16 R6 10 2.5 2.5 ROOM 2 1 50,100 200


17 Y6 10 2.5 2.5 TOILET 7 50 350
18 B6 10 2.5 2.5 TOILET 7 50 350
19 R7 10 2.5 2.5 TOILET 7 50 350
40 A ELCB, 100ma

20 Y7 10 2.5 2.5 TOILET 9 50 450


SEC 4

21 B7 10 2.5 2.5 TOILET 10 50 500


22 R8 10 2.5 2.5 TOILET 13 50 650
23 Y8 10 2.5 2.5 ROOM 3 2 50,100 350
24 B8 10 2.5 2.5 ROOM 3 2 50,100 350
25 R9 10 2.5 2.5 ROOM 4 2 50,100 400
40 A ELCB, 100ma

26 Y9 10 2.5 2.5 ROOM 4 2 50,100 400


SEC 5

27 B9 10 2.5 2.5 ROOM 3 2 50,100 350


28 R10 10 2.5 2.5 ROOM 2 1 50,100 200
29 Y10 10 2.5 2.5 EXTERNAL 5 50 250
30 B10 10 2.5 2.5 EXTERNAL 6 50 300
31 R11 10 2.5 2.5 LIFT 2 50 100
40 A ELCB,
SEC 6

100ma

32 Y11 10 SPARE 500


33 B11 10 SPARE 500
500
3,750 4,350 4,850
Total Connected Load 12,950
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC
TION: 4F

Re-mark
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION
FED FROM :SMDB GF SCHEDULE for D/B
DB GF-P

Rating CCT ECT


SEC NO:

MCB
of Rating of SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Ind/so 13AS 13A
Inco- ELCB No. No. Size Size Area LTG
in A Fan Fan c so Dso
mer mm2 mm2

1 R1 20 4.0 4.0 KITCHEN 3


40 A ELCB, 30ma

2 Y1 20 4.0 4.0 KITCHEN 2


SEC 1

3 B1 20 4.0 4.0 KITCHEN 4


4 R2 20 4.0 4.0 PRAYER ROOM 1 1
5 Y2 20 4.0 4.0 FIRST AID ROOM 2
6 B2 20 4.0 4.0 LAUNDARY 2
7 R3 20 4.0 4.0 LAUNDARY 2
40 A ELCB, 30ma

8 Y3 20 4.0 4.0 ISOLATION ROOM 2


SEC 2

9 B3 20 4.0 4.0 GENERAL ROOM 2


10 R4 20 4.0 4.0 LV ROOM 1
11 Y4 20 4.0 4.0 SUBSTATION 2
12 B4 32 4.0 4.0 TELEPHONE ROOM 4
40 A ELCB, 40 A ELCB, 40 A ELCB, 40 A ELCB, 40 A ELCB, 40 A ELCB, 40 A ELCB, 40 A ELCB, 40 A ELCB,

13 R5 20 4.0 4.0 GUARD ROOM 2


SEC 3

30ma

14 Y5 32 4.0 4.0 KITCHEN 3


15 B5 32 4.0 4.0 KITCHEN 3
16 R6 20 4.0 4.0 GF -1A
SEC 4

100ma

17 Y6 20 4.0 4.0 GF -1B


80A TP ISOLATOR

18 B6 20 4.0 4.0 GF -2A


19 R7 20 4.0 4.0 GF -2B
SEC 5

100ma

20 Y7 20 4.0 4.0 GF -2C


21 B7 20 4.0 4.0 GF -2D
22 R8 20 4.0 4.0 GF -2E
SEC 6

100ma

23 Y8 20 4.0 4.0 GF -2F


24 B8 25 6.0 4.0 GF-03
25 R9 25 6.0 4.0 GF-04
SEC 7

100ma

26 Y9 25 6.0 4.0 GF-05


27 B9 25 6.0 4.0 GF-06
28 R10 25 6.0 4.0 GF-07
SEC 8

100ma

29 Y10 25 6.0 4.0 GF-08


30 B10 25 6.0 4.0 GF-09
31 R11 25 6.0 4.0 GF-10
SEC 9

100ma

32 Y11 20 4.0 4.0 SUMP PUMP


33 B11 20 4.0 4.0 DIESEL PUMP
34 R12 20 4.0 4.0 FACP
SEC 10

100ma

35 Y12 20 4.0 4.0 VECP


36 B12 20 4.0 4.0 ELCP
37 R13
SEC 11

100ma

38 Y13 20 4.0 4.0 TELEPHONE ROOM


40 A ELCB,
SEC 11

100ma
20 4.0 4.0 TELEPHONE ROOM
39 B13

Total Connected Load


CABLE SIZE: 4C X 25 SQ.MM.CU.XLPE/SWA/PVC +1C X 16 SQ.MM Y/G CU.PVC
DISTRIBUTION
LOCATION: GF
DULE for D/B
Load Per Re-mark
Circuit in watts
watt/
32A FC
Iso
ISO W/H
U
unit R Y B

200 600
200 400
200 800
400 600
400 800
200 400
200 400
400 800
400 800
400 400
400 800
400 1,600 RING
400 800
400 1,200 RING
400 1,200 RING
1 200 200
1 200 200
1 200 200
1 200 200
1 200 200
1 200 200
1 200 200
1 200 200
1 1900 1,900 UVR+T
1 1900 1,900
1 1900 1,900 UVR+T
1 1900 1,900
1 1900 1,900
1 1900 1,900 UVR+T
1 1900 1,900
1 1900 1,900 UVR+T
1 1500 1,500
1 500 500
1 500 500
1 500 500
1 500 500
1,000
1 3000 1,000
1 3000
1,000
10,600 11,400 12,900
l Connected Load
34,900
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION
FED FROM :SMDB FF SCHEDULE for D/B
DB FF P

Rating CCT ECT


SEC NO:

MCB
of Rating of SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Ind/so 13AS 13A
Inco- ELCB No. No. Size Size Area LTG
in A Fan Fan c so Dso
mer mm2 mm2

1 R1 20 4.0 4.0 ROOM 4


40 A ELCB, 30ma

2 Y1 20 4.0 4.0 ROOM 4


SEC 1

3 B1 20 4.0 4.0 ROOM 4


4 R2 20 4.0 4.0 ROOM 4
5 Y2 20 4.0 4.0 ROOM 3
6 B2 20 4.0 4.0 ROOM 4
7 R3 20 4.0 4.0 ROOM 4
40 A ELCB, 30ma

8 Y3 20 4.0 4.0 ROOM 4


SEC 2

9 B3 20 4.0 4.0 ROOM 4


10 R4 20 4.0 4.0 ROOM 4
11 Y4 20 4.0 4.0 ROOM 3
2
40A TP ISOLATOR

12 B4 20 4.0 4.0 ROOM


13 R5 20 4.0 4.0 ROOM 4
40 A ELCB, 30ma

14 Y5 20 4.0 4.0 ROOM 3


SEC 3

15 B5 20 4.0 4.0 ROOM 1


16 R6 32 4.0 4.0 CORRIDOR 3
17 Y6 32 4.0 4.0 CORRIDOR 3
18 B6 20 4.0 4.0 ROOM 4
19 R7 20 4.0 4.0 ROOM 4
40 A ELCB, 30ma

20 Y7 20 4.0 4.0 ROOM 4


SEC 4

21 B7 20 4.0 4.0 ROOM 4


22 R8 20 4.0 4.0 ROOM 3
23 Y8 20 4.0 4.0 ROOM 4
24 B8 20 SPARE

Total Connected Load


CABLE SIZE: 4C X 16 SQ.MM.CU.XLPE/SWA/PVC +1C X 16 SQ.MM Y/G CU.PVC
DISTRIBUTION
LOCATION: FF
DULE for D/B
Load Per Re-mark
Circuit in watts
watt/
32A
Iso
ISO W/H AC unit R Y B

200 800
200 800
200 800
200 800
200 600
200 800
200 800
200 800
200 800
200 800
200 600
200 400
200 800
200 600
400 400
400 1,200 RING
400 1,200 RING
200 800
200 800
200 800
200 800
200 600
200 800
500

6,600 6,200 5,300


l Connected Load
18,100
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION
FED FROM :SMDB TF SCHEDULE for D/B
DB TF P

Rating CCT ECT


SEC NO:

MCB
of Rating of SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Ind/so 13AS 13A
Inco- ELCB No. No. Size Size Area LTG
in A Fan Fan c so Dso
mer mm2 mm2

1 R1 20 4.0 4.0 ROOM 4


40 A ELCB, 30ma

2 Y1 20 4.0 4.0 ROOM 4


SEC 1

3 B1 20 4.0 4.0 ROOM 4


4 R2 20 4.0 4.0 ROOM 4
5 Y2 20 4.0 4.0 ROOM 3
6 B2 20 4.0 4.0 ROOM 4
7 R3 20 4.0 4.0 ROOM 4
40 A ELCB, 30ma

8 Y3 20 4.0 4.0 ROOM 4


SEC 2

9 B3 20 4.0 4.0 ROOM 4


10 R4 20 4.0 4.0 ROOM 4
11 Y4 20 4.0 4.0 ROOM 3
2
40A TP ISOLATOR

12 B4 20 4.0 4.0 ROOM


13 R5 20 4.0 4.0 ROOM 4
40 A ELCB, 30ma

14 Y5 20 4.0 4.0 ROOM 3


SEC 3

15 B5 20 4.0 4.0 ROOM 1


16 R6 32 4.0 4.0 CORRIDOR 3
17 Y6 32 4.0 4.0 CORRIDOR 3
18 B6 20 4.0 4.0 ROOM 4
19 R7 20 4.0 4.0 ROOM 4
40 A ELCB, 30ma

20 Y7 20 4.0 4.0 ROOM 4


SEC 4

21 B7 20 4.0 4.0 ROOM 4


22 R8 20 4.0 4.0 ROOM 3
23 Y8 20 4.0 4.0 ROOM 4
24 B8 20 SPARE

Total Connected Load


CABLE SIZE: 4C X 16 SQ.MM.CU.XLPE/SWA/PVC +1C X 16 SQ.MM Y/G CU.PVC

CABLE SIZE: 4C X 16 SQ.MM.CU.XLPE/SWA/PVC +1C X 16 SQ.MM Y/G CU.PVC


DISTRIBUTION
LOCATION: TF
DULE for D/B
Load Per Re-mark
Circuit in watts
watt/
32A
Iso
ISO W/H AC unit R Y B

200 800
200 800
200 800
200 800
200 600
200 800
200 800
200 800
200 800
200 800
200 600
200 400
200 800
200 600
400 400
400 1,200 RING
400 1,200 RING
200 800
200 800
200 800
200 800
200 600
200 800
500

6,600 6,200 5,300


l Connected Load 18,100
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION
FED FROM :SMDB 4F SCHEDULE for D/B
DB RF-P

Rating CCT ECT


SEC NO:

MCB
of Rating of SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Ind/so 13AS 13A
Inco- ELCB No. No. Size Size Area LTG
in A Fan Fan c so Dso
mer mm2 mm2

1 R1 20 4.0 4.0 ROOM 2 1


40 A ELCB, 30ma

2 Y1 20 4.0 4.0 ROOM 2 1


SEC 1

3 B1 20 4.0 4.0 ROOM 2 1


4 R2 20 4.0 4.0 ROOM 2 1
5 Y2 20 4.0 4.0 ROOM 2 1
6 B2 20 4.0 4.0 CORRIDOR 3
7 R3 20 4.0 4.0 ROOM 2 1
40 A ELCB, 30ma

8 Y3 20 4.0 4.0 SUPERVISOR ROOM 1 1


SEC 2

9 B3 20 4.0 4.0 SUPERVISOR ROOM 1 1


10 R4 20 4.0 4.0 ROOM 2 1
11 Y4 20 4.0 4.0 ROOM 2 1
12 B4 20 4.0 4.0 ROOM 2 1
40A TP ISOLATOR

13 R5 20 4.0 4.0 ROOM 2 1


40 A ELCB, 30ma

14 Y5 20 4.0 4.0 ROOM 2 1


SEC 3

15 B5 20 4.0 4.0 CORRIDOR 3


16 R6 20 4.0 4.0 ROOM 2 1
17 Y6 32 4.0 4.0 ROOM 3 1
18 B6 20 4.0 4.0 ROOM 2 1
19 R7 20 4.0 4.0 ROOM 2 1
40 A ELCB, 30ma

20 Y7 20 4.0 4.0 ROOM 2 1


SEC 4

21 B7 20 4.0 4.0 ROOM 2 1


22 R8 32 4.0 4.0 ROOM 3 1
23 Y8 20 4.0 4.0 ROOM 2 1
24 B8 20 SPARE

Total Connect
CABLE SIZE: 4C X 16 SQ.MM.CU.XLPE/SWA/PVC +1C X 16 SQ.MM Y/G CU.PVC
DISTRIBUTION
LOCATION:RF
DULE for D/B
Load Per Re-mark
Circuit in watts
watt/
15A FC
Sso
ISO W/H
U
unit R Y B

400 800
400 800
400 800
400 800
400 800
200 600
400 800
400 600
400 600
400 800
400 800
400 800
400 800
400 800
200 600
400 800
400 1,000 RING
400 800
400 800
400 800
400 800
400 1,000 RING
400 800
500

6,600 6,400 5,500


Total Connected Load 18,500
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION SCHEDUL
FED FROM :SMDB-FF D/B
DB FF AC
Rating CCT ECT
SEC NO:
MCB
of Rating SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Inse 13A 13A
Inco- of ELCB No. No. Size Size Area LTG
in A Fan Fan ct Sso Dso
mer mm2 mm2
40 A ELCB, 40 A ELCB, 40 A ELCB,

1 R1 20 4.0 2.5 FF-02


SEC 1

100ma

2 Y1 20 4.0 2.5 FF-03


3 B1 20 4.0 2.5 FF-11
4 R2 20 4.0 2.5 FF-12
SEC 2

100ma

5 Y2 20 4.0 2.5 FF-16


6 B2 20 4.0 2.5 FF-17
7 R3 20 4.0 2.5 FF-21
SEC 3

100ma

8 Y3 20 4.0 2.5 FF-22


9 B3 20 4.0 2.5 FF-23
10 R4 20 4.0 2.5 FF-08
40 A ELCB,
SEC 4

100ma

11 Y4 20 4.0 2.5 FF-7B


12 B4 20 4.0 2.5 FF-7A
FF-6B
40A TP ISOLATOR

13 R5 20 4.0 2.5
40 A ELCB,
SEC 5

100ma

14 Y5 20 4.0 2.5 FF-6A


15 B5 20 4.0 2.5 FF-04
16 R6 20 4.0 2.5 FF-05
40 A ELCB,
SEC 6

100ma

17 Y6 20 4.0 2.5 FF-13


18 B6 20 4.0 2.5 FF-14
19 R7 20 4.0 2.5 FF-18
40 A ELCB,
SEC 7

100ma

20 Y7 20 4.0 2.5 FF-19


21 B7 20 4.0 2.5 FF-24
22 R8 20 4.0 2.5 FF-09
40 A ELCB,
SEC 8

100ma

23 Y8 20 4.0 2.5 FF-10


24 B8 20 4.0 2.5 FF-20
25 R9 20 4.0 2.5 FF-01
40 A ELCB,
SEC 9

100ma

26 Y9 20 4.0 2.5 FF-15


27 B9 20 SPARE

Total Co
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC
BUTION SCHEDULE for
LOCATION: FF
D/B
Load Per Re-mark
watt/ Circuit in watts
AC ISO W/H FCU unit R Y B

1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 200 200
1 200 200
1 200 200
1 200 200
200

1,000 1,100 1,100


Total Connected Load 3,200
FF
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION SCHEDUL
FED FROM :SMDB-TF D/B
DB TF AC
Rating CCT ECT
SEC NO:
MCB
of Rating SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Inse 13A 13A
Inco- of ELCB No. No. Size Size Area LTG
in A Fan Fan ct Sso Dso
mer mm2 mm2
40 A ELCB, 40 A ELCB, 40 A ELCB,

1 R1 20 4.0 2.5 FF-02


SEC 1

100ma

2 Y1 20 4.0 2.5 FF-03


3 B1 20 4.0 2.5 FF-11
4 R2 20 4.0 2.5 FF-12
SEC 2

100ma

5 Y2 20 4.0 2.5 FF-16


6 B2 20 4.0 2.5 FF-17
7 R3 20 4.0 2.5 FF-21
SEC 3

100ma

8 Y3 20 4.0 2.5 FF-22


9 B3 20 4.0 2.5 FF-23
10 R4 20 4.0 2.5 FF-08
40 A ELCB,
SEC 4

100ma

11 Y4 20 4.0 2.5 FF-7B


12 B4 20 4.0 2.5 FF-7A
FF-6B
40A TP ISOLATOR

13 R5 20 4.0 2.5
40 A ELCB,
SEC 5

100ma

14 Y5 20 4.0 2.5 FF-6A


15 B5 20 4.0 2.5 FF-04
16 R6 20 4.0 2.5 FF-05
40 A ELCB,
SEC 6

100ma

17 Y6 20 4.0 2.5 FF-13


18 B6 20 4.0 2.5 FF-14
19 R7 20 4.0 2.5 FF-18
40 A ELCB,
SEC 7

100ma

20 Y7 20 4.0 2.5 FF-19


21 B7 20 4.0 2.5 FF-24
22 R8 20 4.0 2.5 FF-09
40 A ELCB,
SEC 8

100ma

23 Y8 20 4.0 2.5 FF-10


24 B8 20 4.0 2.5 FF-20
25 R9 20 4.0 2.5 FF-01
40 A ELCB,
SEC 9

100ma

26 Y9 20 4.0 2.5 FF-15


27 B9 20 SPARE

Total Co
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC
BUTION SCHEDULE for
LOCATION: TF
D/B
Load Per Re-mark
watt/ Circuit in watts
AC ISO W/H FCU unit R Y B

1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 200 200
1 200 200
1 200 200
1 200 200
200

1,000 1,100 1,100


Total Connected Load 3,200
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION SCHEDUL
FED FROM :SMDB-4F D/B
DB AC-1
Rating CCT ECT
SEC NO:
MCB
of Rating SL. Ckt. Wire Wire Room location/
Rtg Ind. Ex. Inse 13A 13A
Inco- of ELCB No. No. Size Size Area LTG
in A Fan Fan ct Sso Dso
mer mm2 mm2
40 A ELCB, 40 A ELCB, 40 A ELCB,

1 R1 20 4.0 2.5 FCU-1


SEC 1

100ma

2 Y1 20 4.0 2.5 FCU-2


3 B1 20 4.0 2.5 FCU-3
4 R2 20 4.0 2.5 FCU-4
SEC 2

100ma

5 Y2 20 4.0 2.5 FCU-5


6 B2 20 4.0 2.5 FCU-6
7 R3 20 4.0 2.5 FCU-7
SEC 3

100ma

8 Y3 20 4.0 2.5 FCU-8


9 B3 20 4.0 2.5 FCU-9
10 R4 20 4.0 2.5 FCU-10
40 A ELCB,
SEC 4

100ma

11 Y4 20 4.0 2.5 FCU-11


12 B4 20 4.0 2.5 FCU-12
FCU-13
40A TP ISOLATOR

13 R5 20 4.0 2.5
40 A ELCB,
SEC 5

100ma

14 Y5 20 4.0 2.5 FCU-14


15 B5 20 4.0 2.5 FCU-15
16 R6 20 4.0 2.5 FCU-16
40 A ELCB,
SEC 6

100ma

17 Y6 20 4.0 2.5 FCU-17


18 B6 20 4.0 2.5 FCU-18
19 R7 20 4.0 2.5 FCU-19
40 A ELCB,
SEC 7

100ma

20 Y7 20 4.0 2.5 FCU-20


21 B7 20 4.0 2.5 FCU-21
22 R8 20 4.0 2.5 CORRIDOR
40 A ELCB,
SEC 8

100ma

23 Y8 20 4.0 2.5 CORRIDOR


24 B8 20 4.0 2.5 CORRIDOR
25 R9 20 4.0 2.5 CORRIDOR
40 A ELCB,
SEC 9

100ma

26 Y9 20 SPARE
27 B9 20 SPARE

Total Co
CABLE SIZE: 4C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X 10 SQ.MM Y/G CU.PVC
BUTION SCHEDULE for
LOCATION: RF
D/B
Load Per Re-mark
watt/ Circuit in watts
AC ISO W/H FCU unit R Y B

1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 100 100
1 500 500
1 500 500
1 500 500
1 500 500
500
500

1,700 1,700 1,700


Total Connected Load 5,100
PROJECT: PROPOSED (G+4)LABOUR ACCOMMODATION LOAD DISTRIBUTION
FED FROM : MDB-1 SCHEDULE for D/B
DB-SS EC
CCT T
Ratin Ratin MC
SEC NO:

Wire Wir
g of g of SL. Ckt. B Room location/
Size e Ind. Ex. Inse 13A 13A 15A
Inco- ELC No. No. Rtg Area LTG ISO
mm Size Fan Fan ct Sso Dso Sso
mer B in A
2 mm
2
SEC 1

100ma
ELCB,
40 A

1 C1 10 2.5 2.5 SUBSTATION 6


SEC 2

ELCB,
30ma
40 A

2 C2 20 4.0 2.5 SUBSTATION 2


40 A DP ISOLATOR

Total Connected Loa


CABLE SIZE: 2C X 10 SQ.MM.CU.XLPE/SWA/PVC +1C X10 SQ.MM Y/G CU.PVC
IBUTION
LOCATION: SS
for D/B
Load Per Re-mark
Circuit in watts
watt/
W/H AC unit R Y B

100 600

200 400

1,000 0 0
otal Connected Load 1,000