Compressor
The Frick manufactured RWB II compressor has been designed utilizing
the latest technology to offer the most reliable and energy efficient unit
ROTARY SCREW currently available. All screw compressor casings are designed and tested
COMPRESSOR UNITS in accordance with the requirements of common standard for 24 barg
maximum discharge pressure. Rotors for models 60-270 are manufactured
from bar stock. Rotors for models 316-399 are manufactured from
forged steel. Both use the latest asymmetric profiles. The compressor
MODELS 60 - 399 incorporates a complete antifriction bearing design for reduced power
consumption and the bearings selected provide an L10 life in excess of
Refrigerant R717 100,000 hours at design conditions.
(Ammonia) Capacity Control
Capacity control is achieved by use of a slide valve which provides fully
modulating capacity control from 100% to approximately 10% of full load.

"Volumizer®" Variable Volume Ratio Control


The RWB II compressor includes a patented method of varying the internal
volume ratio to match the system pressure ratio, eliminating the power
penalty associated with over- or undercompression.

Lubrication System
The RWB II compressor is designed specifically for operation without an
oil pump under normal operating conditions. All oil required for main oil
injection and lubrication is provided by positive gas differential pressure.
All oil passes through a 15 micron filter furnished with isolation stop
valves and drain connections for ease of servicing. Booster and some low
pressure differential, high-stage applications will require the demand oil
pump option.

Oil Separator/Reservoir
The oil separator is a horizontal, three-stage design with integral sump.
The separator is designed and constructed in accordance with PED for
a maximum design working pressure of 20.4 barg (24 barg in option).
Replaceable coalescent separator elements are provided for final gas/oil
separation of particles down to less than 1 micron.
Designed for all refrigeration Oil Cooling
applications. Cooling the compressor oil may be achieved by either liquid-refrigerant-
injection oil cooling, water-cooled oil cooling, or thermosyphon oil cooling.
RWB II Rotary Screw Compressor Units Water-cooled and thermosyphon oil-cooled systems are supplied with
are engineered and manufactured to meet shell and tubes type heat exchangers mounted on the unit.
the exacting requirements of the Industrial
Refrigeration Market. All components have Quantum Control Center
been designed and arranged to assure The Quantum control panel is factory mounted, IP54 CE listed, and
reliability, accessibility, and servicing completely piped and wired with all the required safety and operating
convenience. Standard units are designed devices. A built-in telecommunications interface suitable for connection to
for booster or high-stage duty with a remote computer or control device is included. A 10.4 « Active Color VGA
ammonia, halocarbon, or hydrocarbon Graphics Display offers a high contrast, crisp clear display of compressor
refrigerants and are shipped completely information and status. Additional I/O can be easily installed in the field. This
assembled. feature provides flexibility for future engine room upgrades and changes.
Two field-selectable serial communication ports allow you to choose from
a combination of RS- 422, RS-485, or RS-232 port configurations for both
interpanel and external communications. Included in the microprocessor
is time-proportioning capacity control, firstout annunciation, prealarms,
volumizer control, real-time clock control, access code protection, lead-
lag sequencing, alternate suction pressure operation, trending, and more.
The operating conditions at the time of the compressor’s last ten alarms
or shutdowns are stored in memory, providing the ultimate in service and
troubleshooting convenience.

Valves
The unit has a combination suction shutoff and check
7
Rm7m1onia
valve with strainer multivalve. The unit’s discharge
has a mounted combination check and shutoff valve
A
Technical Data
Compressor Displacement Ratings Ammonia (R717) *
RWBII Model @ 2950 RPM Cooling Capacity Shaft Power
m3/h kW kW
60 445 363 91
76 560 456 115
100 751 613 147
134 1001 817 197
177 1355 1103 254
222 1706 1384 320
270 2108 1715 395
316 2455 1992 460
399 3091 2495 580
* Based on -6.7°C suction and 35°C condensing with 5.5°C liquid subcooling and 5.5°C suction superheat
Ratings with water cooled oil cooling

Overall Dimensions and Weights

A B
Dimensions (mm)
Max. Operating Weight (kg)
Model A B C
Liquid injection Oil cooler Liquid injection Oil cooler
60…RWB…05 3490 1210 1430 1985 2670 3260
76…RWB…05 3490 1210 1430 1955 2780 3360
100…RWB…05 3555 1210 1480 2130 3210 3790
134…RWB…05 3795 1245 1480 2230 3920 4500
100…RWB…06 3680 1235 1550 2095 3700 4280
134…RWB…06 3875 1270 1550 2195 4030 4610
177…RWB…06 3950 1320 1550 2300 4870 5450
222…RWB…06 4245 1425 1550 2430 5200 5780
177…RWB…07 4255 1350 1650 2355 5370 5960
222…RWB…07 4550 1455 1650 2485 5710 6290
270…RWB…07 4700 1550 1687 2685 7330 7995
316…RWB…07 4960 1550 1687 2885 7810 8475
399…RWB…07 5060 1550 1687 2885 8920 9585
316…RWB…09 5510 1765 1851 3255 9350 10020
399…RWB…09 5610 1765 1851 3255 9710 10375
399…RWB…10 5795 1695 1701 3355 10320 10980

RWBII FORM RWB.01 SLE 08.04


Subject to change without notice.