CENTRES
1. SCOPE...................................................................................................3
3. SITE CONDITIONS................................................................................4
3.1 General........................................................................................4
3.2 Special Design Conditions...........................................................4
3.3 Altitude ........................................................................................4
5. CONSTRUCTION REQUIREMENTS.....................................................5
5.1 Internal Arrangement...................................................................5
5.2 Enclosure ....................................................................................6
5.3 Interchangeability ........................................................................6
5.4 Anti-Condensation Precautions ...................................................6
5.5 Arcing Faults................................................................................7
5.6 Main and Neutral Busbar Systems ..............................................7
5.7 Panels .........................................................................................7
5.8 Terminals...................................................................................10
5.9 Isolating Facilities ......................................................................11
5.10 Protective Devices.....................................................................11
5.11 Wiring/Cabling ...........................................................................14
5.12 Earthing .....................................................................................15
5.13 Mimic Diagram...........................................................................16
5.14 Rating Plates and Nameplates ..................................................16
5.15 Finishing ....................................................................................16
5.16 Erection .....................................................................................17
5.17 Tools and Testing Equipment ....................................................17
5.18 Spare Parts ...............................................................................17
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
This specification covers the general requirements for design, manufacture, testing and
supply of L.V. Distribution Board and Motor Control Center.
In case of differences between this specification and the international standard specified in
clause 2 below, the more stringent requirements shall prevail.
The specific requirements and details of the board(s) required are given on the data sheet(s)
and drawing(s). In case of conflicting requirements between this general specification and the
specific requirements, the data sheets shall always rule.
2. APPLICABLE STANDARDS
Unless specified otherwise LV distribution boards and motor control centres shall conform in
design, material, construction and performance to the latest editions of the IEC standards and
in particular to the following publications:
Copy of any relevant standards other than specified above should be included in the vendor
documentation.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
When different standards, namely BS or VDE, are specified on the data sheets and/or
accompanying documents, the latest edition of the specified standards shall be applicable.
Further to the international standard LV boards and MCC's shall in any case comply to the
local standards and/or regulations (ADWEA) when these are higher, more stringent or of
special nature.
3. SITE CONDITIONS
3.1 General
For general climatic conditions applicable to the project installations, refer to Specification for
General Technical Requirements.
The switch board/mcc shall be designed for humidity 100% and an ambient temperature of 50
deg. C even if it is to be installed in airconditioned rooms.
3.3 Altitude
Altitude where boards will be installed shall not be more than 1000 metres above sea level.
4. DESIGN CONSIDERATIONS
4.1 General
The distribution boards and MCC's shall be of a standard, well tested and proven design
which ensures maximum safety to personnel, maximum service reliability and economic
operation for an operational lifetime of at least 30 years. Design and construction shall be
simple and well laid-out and shall provide good accessibility to components and parts.
Even under extreme conditions of major short circuit or maloperation there shall be no danger
to persons in the vicinity of the assembly.
The electrical system for all low voltage boards and MCC's shall be 3 phase and neutral, 4-
wire solidly earthed.
Unless otherwise specified the neutral conductor size shall be the same size as the phase
conductors.
All incomers, and buscoupler shall be mutually interlocked mechanically and electrically.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
Distribution boards and MCC's shall be rated on the basis of voltage, current, frequency and
the symmetrical breaking capacity of incorporated LV automatic switching devices as defined
in appropriate IEC publication.
For standard voltages, frequencies and currents reference is made to IEC 60038 and 60059.
Low voltage, current-carrying components shall furthermore be capable of carrying their rated
current continuously at rated voltage and under specified service conditions without
exceeding the permissible temperature limits when mounted in the completely assembled
boards.
Unless otherwise specified the switch board shall be natural air cooled.
All equipment and components of the LV distribution boards and MCC's shall be capable of
continuous operation at their full current and voltage ratings and without detriment or
malfunction at system continuous deviation of up to and including the following percentages
of the normal values.
- Voltage ± 10%
- Frequency ± 5%
All components shall be capable of withstanding the dynamic, thermal and dielectric stresses
resulting from prospective short-circuit currents without damage or injury of personnel.
The temperature rise of the LV distribution board and motor control centre shall not exceed
temperatures indicated in IEC 60947.
5. CONSTRUCTION REQUIREMENTS
The distribution board and MCC shall comprise a busbar system and consist of one or more
sections, each having one incoming feeder.
The current rating of the incoming feeders and the busbars shall in general be of equal value
for each part of a combined panel or as indicated on the data sheets or drawing.
All incoming switches and buscouplers shall be equipped with facilities for padlocking both in
the "in" and in the "out" position.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
Alphanumeric notation, generally in accordance with IEC 60445, shall be used for
identification and marking of phases, conductors and terminals.
The system of construction for the LV distribution boards and motor control centres shall be a
factory-built assembly of a standard, well tested design.
The operation of incoming circuit breakers, buscoupler, interlocks, indications etc. shall be
from a suitable control voltage supply system as indicated in the data sheets.
5.2 Enclosure
The LV distribution boards and motor control centres shall be of the floor mounting cubicle
type, shall have a complete metal enclosure of sufficient mechanical strength and be
equipped with lifting facilities (eye bolts). The materials of construction shall be properly
prepared and treated against rust or corrosion. The boards shall be self-supporting and
suitable for front entry and operation.
In case of cable cellar, adequate bottom plates shall be provided which at least prevent
access by rodents.
The degree of protection shall be IP 54, form 4 totally withdrawable in accordance with IEC
publication 60529 and shall be minimum as follows:
5.3 Interchangeability
Effective precautions shall be taken to prevent the formation of harmful condensation inside
the enclosure, under either operating or non-operating conditions and service conditions.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
The space heaters shall be controlled by a thermostatic switch and shall be wired to outgoing
terminals.
Measures shall be taken to prevent the occurrence of internal arcing faults in accordance with
the IEC requirements.
The design and construction of the LV distribution boards and motor control centres shall be
such as to provide the highest possible degree of personnel protection against radiation,
overpressure and hot gases.
Busbars shall be of tinplated high conductivity electrolytic copper with joints by means of non-
corrosive high tensile steel bolts, nuts and washers, and secured against loosening. Insulated
coloured busbars are preferred. Busbars shall be suitable for extension to the left or to the
right as required.
5.7 Panels
The incoming panel shall consist of a metal enclosed free-standing, vertical, vendor's
standard steel structure, suitable for joining to feeder panels or MCC panels.
The incoming panel shall be provided with hinged front door(s) and removable rear cover(s).
Barriers shall be provided between the control compartment and the power compartment.
The incoming panel shall contain busbars, hand operated air break switches or circuit
breakers, auxiliary control devices, transformers, protective relays, meters, control and meter
switches, fault indicators etc. as required to comply with this specification.
Incoming and sectionalizer units shall be provided with switches of air-break, hand operated
type or with circuit breakers. In any case the switches shall be provided with locking facilities
in the "off" positions and also in the isolated position, if applicable.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
5.7.2.1 General
The motor control centre parts of the switchboard shall consist of totally enclosed, vertical
sections joined together with the incoming panel to form a rigid, free-standing assembly. The
MCC panels shall contain busbars, combination motor starters, feeder circuit breakers and
control as required to comply with this specification.
Each panel shall have a separate vertical cable compartment, minimum width 300 mm. Each
cable compartment shall have its own hinged door. The earth busbar shall be located in the
cable compartment.
The vertical busbars shall be isolated so that with the compartment door open and the draw
out unit removed, personnel is protected against unintentional contact. Live parts shall be
protected by flexi glass or equivalent.
A motor starter will basically comprise a switched short circuit protective device and contactor
with thermal overload release. The preferred short circuit protective device is a fuse switch
combination.
Remote control devices shall be arranged to operate at line and neutral voltage derived from
incoming supply.
Motor starters rated in excess of 37 kW shall also be equipped with earth leakage protection
set at (see 5.10.2).
Each motor starter compartment shall contain all equipment. The motor kilowatt rating shall
be the design basis to size short circuit protective devices and contactors.
Contactors shall be sized for a minimum of 1 million operations duty (AC 3). Thermal overload
relays shall be adjustable, ambient temperature compensated, provided with single phasing
detection and shall have an internal manual reset.
Each combination motor starter shall have sufficient rated interrupting capacity to safely
interrupt the maximum fault current available.
Each motor starter compartment door shall be mechanically interlocked so that the door
cannot be opened unintentionally when the switch is in the "ON" position.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
The guidance details are given in the relevant data sheet and or drawings.
ADWEA/ENGINEER reserve the right to change or enhance the level of
protection/indication/control at the time of vendor design approval to meet project specific
requirements. This shall be binding on the SUPPLIER.
All motor feeders shall have emergency 'stop' pushbuttons provided in the relevant
compartment.
A feeder circuit breaker will basically consist of a circuit breaker with thermal and magnetic
type releases or load break switch fuse combination, unless stated otherwise.
Each feeder circuit breaker compartment door shall be mechanically interlocked with the
circuit breaker so that the door cannot be opened unintentionally when the breaker is in the
"ON" position.
Circuit breaker operating handles shall indicate "ON", "TRIPPED" and "OFF" positions with
the door closed, and shall have provisions for padlocking in the "OFF" position with the door
closed. Padlocks and keys shall be supplied, one per 10 compartments.
5.7.2.4 "Spaces"
Spare "spaces" for future use shall be equipped in such a way that installation of
compartment can take place safely, without de-energizing the switchboard.
Spare "spaces" shall have compartment doors (no equipment mounted to doors) and
horizontal separations.
If requested on the data sheets. In one of the MCC panel sections, preferably in the middle, a
bottom compartment shall be equipped with terminal strips serving as connection
compartment for the control signal connections to and from the control system.
On one side of the terminal strips the control wiring from the motor compartments will be
connected on the other side the control signal cables to the control system will be connected.
The number of terminals is the number of motor or feeder compartments times four terminals
or as shown on the control diagrams.
Each motor compartment will in this case be equipped with an auxiliary relay with DC power
supply.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
Each switching device shall be provided with at least 2 make and 2 break auxiliary contacts
directly driven by the switching mechanism.
This contacts shall be completely wired up to terminal blocks in the secondary terminal
compartment.
The rated making and thermal-breaking capacities of these contacts shall be:
> 16A at 500 V AC and power factor0.3 > 1A at 500 V AC and power factor 0.3
5.8 Terminals
5.8.1 General
Each panel shall be provided with appropriate facilities for the independent terminals to
connect the LV main cable and the auxiliary cables. Types and sizes will be specified in the
requisition and/or data sheets.
The terminals shall be so arranged that all connections can be made safely, even when the
assembly is energized.
Suitable terminating facilities of adequate dimensions and thermal rating shall be provided for
each conductor.
Inside the compartments separate terminals or bolts, one for each cable, are required for
earthing purposes.
Efficient means to prevent strain on the actual conductors and cable lugs shall be provided.
Terminal blocks fitted with tubular type contacts with non-loosening screws shall be provided
for termination of cables.
Within the panel compartments suitable clamping devices shall be provided for securing of
the cables.
Terminals in current measuring circuits shall be special purpose with suitable bridging links
and measuring facilities.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
Termination compartments for main and control cables shall have adequate dimensions, with
ample accommodation for the required number of terminals.
Two or more conductor terminations on one terminal are not acceptable unless the terminals
are designed for more than one conductor.
Cable glands suitable for the cables specified shall be included in the supply of the assembly.
The connection in the secondary circuits between the fixed and the moving parts of panels
shall be by means of self-aligning contact.
These connections shall be maintained when the moving portion of the equipment is in the
test position.
Suitable MCCBs or high rupturing capacity (HRC) type fuses shall be used for short circuit
protection of circuits except for the following:
- circuits of current rating 1000 A and above where quick acting relay type protective
devices are required.
- CT wiring.
Earth fault protection for distribution circuits shall only be provided if indicated on data sheets
or drawings, but motor circuits for motors of 37 kW and above may be provided with
instantaneous earth fault protection of sensitivity not exceeding 5% of full load motor current
or 10 A, whichever is lower.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
Overload protection shall be incorporated in all phases and shall include protection against
single phasing. The minimum range of setting shall be 70 – 110% of the rated current.
Protective devices of the magnetic, thermal or inductive type may be used, but dash pot type
overload protective devices are not acceptable.
All overload devices shall have an easily visible manual reset facility accessible from the front
of the board.
The protective device shall be mounted in such a way that settings can be read conveniently
and that adjustment can be made without the need for special tools.
Overloads for small rated circuits may be directly connected in the protected circuit, but for
higher ratings overload shall be operated via current transformers. Saturating CT's may be
used on drives with long run-up periods.
Direct temperature rise protection by use of thermistors or RTD's may be required and
specified on the data sheet(s), drawing(s) or accompanying documents for motors operating
under adverse conditions.
The need for this protection shall be indicated on the data sheet(s) or drawing(s). The drop
out voltage of delayed undervoltage protection shall be between 50% and 65%; the pick up
value shall be at not less than 85% of the system rated voltage. The time setting shall be
adjustable as per project requirements.
General
These relays shall be of the plug-in type. The type and make shall be subject to approval by
the principal.
- Memory: 4.5 s
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
- Delayed restart, adjustable between 0.1 s and 30 s, after voltage dips between 0.2 s and
4 s inclusive.
Elements with multiple functions such as tripping and alarm duties shall have separate
operating contacts for each function and be brought out to separate terminals.
5.10.7 Metering
Rated output capacity of the transformers shall be matched to cover the burden required
by the equipment connected, and preferably be selected from the range of standard
values.
Rated primary current shall preferably be selected from the range of standard values.
Where required, the current ratio will be stated on the data sheets.
Other means of remote indication may be considered and quoted for, e.g. transducer
systems, but shall be subject to approval by the principal.
When the electrical system value requires a time duration of 3 s, the current transformers
shall be rated accordingly.
- Class of accuracy
Generally, measuring current transformers shall be Class 3, except those for measuring
the supply of third parties, which shall be Class 1. If Class 1 is applicable this will be
stated on the data sheets.
The over current factor "n" shall be < 5 in order to prevent damage of instruments at
maximum fault current.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
The over current factor shall be > 10 in order to ensure the proper working of the
protective devices and shall be indicated as follows: Class 5 P 10 or 10 P 10.
5.10.7.2 Ammeters
Ammeters shall be flush-mounted, square type (96 x 96 mm) upto a current of 16 A they shall
be direct wired in one of the phases above 16 A they shall have an element rated at or 5
ampere.
5.10.7.3 Voltmeters
5.10.7.5 Accuracy
Ammeters and voltmeters shall be of Class 1.5 and watt-hour meters shall be of Class 2.5 as
specified in IEC publication 60051 and 60521.
5.11 Wiring/Cabling
Control wiring shall be minimum 1.5 sq mm, stranded, 750 V AC grade, colour grey. All power
wiring/cabling shall be minimum 2.5 sq mm, stranded, 1000 V AC grade.
Wiring to door mounted devices shall be suitable for hinge wire application.
Bundles of single-core cables shall be routed neatly in the vertical and/or horizontal plane.
Individual wires and bundles shall be secured with plastic wire ties, cable lacing or by
enclosing in plastic wiring trays.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
All terminal blocks shall be rated 20 A (minimum) at 500 V. All terminal blocks shall have a
white plastic marking strip over the length of the block.
All wiring shall be identified by permanent slip-on plastic sleeves at each terminal point in
addition to the marking on the terminal blocks.
Panels shall be provided with undrilled, metal gland plates, which shall be grounded to the
switchboard earth bus.
When mentioned in the requisition one of the MCC panel sections shall house a control signal
connection (bottom) compartment equipped with terminal strips.
The internal connections between "motor starter" compartment and this connection
compartment shall be executed as internal wiring in the MCC. These connections shall be
part of the delivery.
5.12 Earthing
A bare copper, adequate horizontal earthing bar shall be provided at the bottom of the
switchboard, along the entire length.
Similar size earthing bars shall be provided in each MCC cable compartment. These vertical
bars shall be connected to the horizontal earthing bar.
Joints in the earth bar shall be bare copper and bolted with galvanized steel bolts, nuts and
washers, secured against loosening.
For direct connection to the station earthing grid, earthing bolts (M12) with nuts and spring
washers shall be provided at both ends of the main earth bar.
In addition to ensure adequate electrical continuity between all metal parts of the switchboard
and its cables and the earth bar particular care shall be taken to ensure that:
- the earth connections of current transformers shall be made directly from the terminal
board to the earth bar.
Means shall be provided of ensuring that the earthing connection of each withdrawable
switching device to the main earth bar is made prior to its primary connections.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
A removable connection shall be provided between the main neutral busbar and the earthing
busbar (TN-S distribution system). This connection shall be located in the incoming panel.
The front of the LV distribution boards shall be provided with a plastic or equivalent line mimic
diagram illustrating the main circuit and its components.
Distribution boards shall have a rating plate permanently fixed in the front of the equipment
giving at least the following information:
- Year of manufacture.
- Weight.
All components (switching devices, contactors protection relays, instruments etc.) shall be
fitted with a rating plate in accordance with the relevant IEC requirements. All functional units
shall be clearly labelled to identify the service. All relays, meters, switches etc. shall be
labelled in accordance with the wiring diagrams. Labels inscribing "CAUTION LIVE PARTS
INSIDE" shall be fixed on the doors.
Rating plates shall be made of corrosion-resistant metallic material and have indelible
inscriptions in the language specified in the requisition.
Each panel shall be provided with nameplates, mounted on the front of a non-removable part.
The nameplates shall be of black non-deteriorating material (e.g. Resopal or Traffolite) and
shall permit inscriptions with characters in white in the language, specified in the requisition.
5.15 Finishing
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
5.16 Erection
Assemblies shipped in transport units shall have these units clearly marked to facilitate
assembly and erection at site. Drawings shall indicate maximum shipping lengths. Each
transport unit shall be provided with hoisting facilities. Foundation and erection drawings, in
the language as specified, bolts, foundation clamps, small material, etc., required for erection
at site shall be packed inside the transport unit.
Special tools and equipment required for erection, commissioning, maintenance and testing
shall form part of the order and be shipped together with the assembly.
Spare parts shall be adequate for start-up procedures only a priced spare part list for two
years of operation is required.
6.1 General
The complete assembly shall be inspected in detail on conformity with the order specifications
and tested for acceptance before leaving the works. The inspection and the tests will be
witnessed by the ENGINEER, ADWEA or his nominee. The manufacturer shall provide
facilities, equipment and personnel to perform the inspection and tests.
6.2 Testing
LV boards and MCC's shall be tested by the manufacturer to the requirements of the
specified standards. Some or all of the tests may be witnessed by the ADWEA/ENGINEER or
the inspector representing the ADWEA/ENGINEER.
The witnessed tests shall be indicated on the data sheets or accompanying documents and
the manufacturer has to inform the ADWEA/ENGINEER representative at least 3 weeks in
advance of the test dates as specified.
All LV boards and MCC's shall be subjected to the following routine tests:
- Dielectric tests of all electrical components of the board. These shall consist of applying
AC voltage test in accordance with IEC 60439 for one minute between poles, poles to
frame and poles connected to frame.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
- Performance tests of all mechanical and electrical equipment and components of the
board, including the operations of control and protection circuits, measuring devices,
CT's, etc.
The manufacturer shall carry out the following type tests if required on the data sheet(s) or
accompanying document(s), if not, evidence of such tests carried out on similar boards,
equipment or components of the board(s) will be accepted:
- Short circuit withstand capacibility for 1 sec. (or 3 sec.) of the incomer(s) busbar system
and buscoupler(s).
The above tests shall not withdraw Vendor responsibility to ensure that the delivered
equipment is in accordance with the requisition/purchase order.
"Type test" certificates as proof of compliance with requirements regarding short circuit
capacity and enclosure in accordance with respective IEC publications, shall be made
available for the switchboard and circuit breakers. "Type test", certificates shall show that
circuit breakers have been tested when mounted within the types of enclosures incorporated
in the switchboard.
LV distribution boards and MCC's shall be packed in wooden type seaworthy crates having
sufficient strength to withstand normal ship handling and transport or be fixed mounted in
containers.
The crates shall be marked with ADWEA's name and address, order number, type of
equipment, hoisting points, etc.
Enclosed with the board, the following documents shall be included in suitable wrapping:
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES
- Control drawing
- Foundation drawing(s)
- Outline drawing(s)
- Performance data/curve(s)
- One-line diagram(s)
- Elementary/control diagram(s)
- Connection/terminal - diagram(s)
- Transport/lifting instruction(s)
- Installation instruction(s)
- Operating instructions
- Maintenance instructions
- List of priced spare parts recommended to be on hand during plant start-up and in the
first two (2) years of operation.
Client ADWEA
Project: STANDARD SPECIFICATIONS FOR WATER WORKS
Title: SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD / MOTOR CONTROL CENTRES