●LA specification and composed (related) items
The discharge current measuring device is used to measure a peak value of discharging current and
polarity of a surge arrester. The discharge current measuring device is composed of the magnetic coil,
magnetic-link, magneto-meter and demagnetizing coil.
Part name Part number Purpose
One-turn Magnetic coil SCA-M1A Magnetize the magnetic-link. Apply to power distribution(over 30kV)
Two-turn Magnetic coil SCA-M2A Magnetize the magnetic-link. Apply to railway system.
Magnetic-link ML-1 Recording medium for the discharge current.
Magneto-meter MM-1 Measure the discharge current through the magnetic-link.
Demagnetizing coil DMC-1 Demagnetize the magnetic-link.
TOSHIBA’s LA Specification
― Magnetic coil
Magnetic coil has two-turn coil, and to identify its polarity, above side of coil is colored in red. When the
surge arrester discharges, the discharging current magnetizes a magnetic-link through a magnetizing
coil.
Red
of DC 1.5kV of AC 6kV
Fig.3 Magnetic coil
― Magnetic-link
The discharging current magnetizes the magnetic-link and remains in it as residual magnetization. The
strength of residual magnetization is a function of peak value of the discharging current.
For measuring the discharging current by using the magneto-meter, the peak value of the discharging
current is available.
As shown in Fig.4, magnetic-link has a laminated layer structure with multiple magnetic sheets and
positioned in the protector tube. It has water resistant.
To identify its polarity, one side of outer tube is colored in red. Insert the magnetic-link its red part
above and match the red part of the magnetizing coil. If not, the polarity undefined and fails to measure
correctly.
Fig.4 Magnetic-link
― Magneto meter
Magneto meter provides the magnetic needle with scale dial on the synthetic resins with two cylindrical
holes of (A) (upper side) and (B) (lower side) as shown in Fig.5. Hole(A) and (B) has different scale of
calibration curve.
Depending on the magnetizing strength of the magnetic-link, insert the magnetic-link into either of the
cylindrical holes and measure the deflection of the magnetic needle.
To identify its polarity, one side of hall is colored in red. Insert the magnetic-link its red part with the red
part of the magneto-meter. If not, the polarity undefined and fails to measure correctly.
Red
Hole (A)
Hole (B)
Fig.5 Magneto-meter
―Demagnetizing coil
Demagnetizing coil used for demagnetize the magnetic-link. The structure is shown in Fig.6.
The magnetic-link is inserted into the cylindrical hole on the synthetic resins built-in the hollow
cylindrical coil. Demagnetization is carried out by pulling out the magnetic-link gradually while adding
an alternating current (AC 110V) to the coil.
for AC 110V
1. To measure the discharge current, pull out the magnetic-link from the magnetizing coil and insert
into the lower hole(B) on the magneto-meter for matching each red part.
2. Before insert the magnetic-link into hole(B), adjust the magneto-meter position so that N polarity
side of the magnetic needle on the magneto-meter shows “0” on the scale dial.
3. Read the deflection angle and direction of the magnetic needle. If the deflection angle is too small to
read, reinsert the magnetic-link into the upper hole(A) and read the deflection of the magnetic
needle. The discharge current is obtained for using the deflection angle as follows.
There is an example of identifying the discharge current from the deflection angle.
Fig.7 shows the case of using hole(B), deflection angle indicates 20 degree correspond with
approximately 400A of peak value of discharge current. To see more accurate discharge current,
reinsert hole(A) as follows.
Red
Hall (A)
Hall (B)
Fig.8 shows the case of using hole(A), deflection angle indicates 60 degree correspond with 400A of
peak value of discharge current.
Red
Hole (A)
Hole (B)