Anda di halaman 1dari 28

SECTOS

Pole Mounted SF6 Load Break Switch


CONTENTS

1 General 1

2 Standards for reference 1

3 Basic switch configurations 2

4 Electrical performance data 3

5 Features 4

6 Accessories 5

7 Electrical and remote control 8

7.1 Electrical control 8

7.2 Remote control and automatic sectionalizer 9

7.2.1 Remote- function 9

7.2.2 DTU-111 and 131 type option 10

7.2.3 Automatic Sectionalizer 11

8 Main construction and mounting 12

8.1 Main construction 12

8.2 Mounting modes 13

8.2.1 Below the crossarm 13


8.2.2 Above the crossarm 15

8.2.3 Mounted on pole directly 16

9 Dimension drawings(unit:mm) 17

9.1 NXB Load Break Switch 17

9.2 NXBD Load Break Switch 17

9.3 NXA Load Break Switch 18

9.4 Crossarm NPTRN1T6 / J401464 18

9.5 Fixing clamp NXAM 1 / NXAM 2 19

9.6 Spacer plate NXBZ59 19

9.7 Fixing clamp NXAM 4 / NXZM5 19

10 Ordering type code 20

10.1 Type code of Sectos NXB and NXBD 20

10.2 Type code of Sectos NXA 21

10.3 CT, VT and Sensor 22

10.3.1 CT and VT 22

10.3.2 Sensor 23
SECTOS Pole Mounted SF6 Load Break Switch

1 General
Product family name “Sectos” is used, when the clause is applicable to all NXA_, NXB_, NXBD_ types.
The more specific type markings are given, when the clause is applicable to limited types only.

Sectos is an SF6-insulated, outdoor pole mounted load break switch family for overhead lines and
specifically designed for use in modern remote controlled distribution automation systems. The Sectos
offers reliable maintenance free operation even in the most demanding climatic conditions including salt
laden atmospheres, corrosive industrial pollution, snow and ice. It has excellent load breaking and fault
making capacity and satisfies the isolation requirements specified for load break switch. The earthed
metal tank prevents all possible leakage currents across an open switch. Sectos can be manually
operated or motor operated for local and remote electric control, and can be upgraded easily.

NXB is designed up to 24 kV rated voltages. The unique feature of this type is integrated earthing switch
option.

NXBD is a 3- way load break switch using NXB components. Two independent load break switch in one
enclosure with the third tapped way can be used for easy and reliable line branching in overhead, cable,
or mixed networks.

NXA is available for rated voltages 24kV and 36kV to IEC standards, and for rated maximum voltage
27kV and 38kV to ANSI standards.

2 Standards for reference


IEC60129 Alternating current disconnectors and earthing switches

IEC60265-1 High-voltage switches. Part 1 : High-voltage switches for rated voltages above 1 kV
and less than 52 kV

IEC60694 Common specification high-voltage switchgear and controlgear standards

ANSI/IEEE C37.63 IEEE Standard requirements for overhead, pad-mounted, dry-vault, and submersible
automatic line sectionalizers for AC systems

ANSI/IEEE C37.71 Three-phase, manually operated subsurface load-interrupting switches for


alternating-current systems

GB3804 A.C. high voltage switches for rated voltages from 3kV to 63kV

GB/T11022 Common specification for high voltage switchgear and controlgear standards

1
SECTOS Pole Mounted SF6 Load Break Switch

NXB NXBD NXA

3 Basic switch configurations

Two-position Load Break Switch are available for all NXA_ and
NXB_ types

Two-position switch

All NXB_ types are also available with an integrated earthing


switch for safe and reliable earthing of the downstream line.
This version is called a 3-position switch to differentiate from the
standard 2-position switch.

Three-position switch

switched switched switched switched


1 2 way no.1 1 2
way no.1 way no.2 way no.2

3 3

tapped way tapped way

Two-position 3-way Three-position 3-way


switch types NXBD__A_ switch types NXBD__C_

2
SECTOS Pole Mounted SF6 Load Break Switch

4 Electrical performance data


Insulation level NXB & NXBD NXA
Rated voltage kV 12 24 36
Power frequency withstand voltage, 50Hz
– to earth and between phases kV 28 50 70
– across the isolating distance kV 32 60 80
Lightning impulse withstand voltage
– to earth and between phases kV 75 125 170
– across the isolating distance kV 85 145 195

Current ratings
Rated normal current A 630 630 630
Mainly active load breaking current A 630 630 630/400
Number of breaking operations CO n 100 100 50/400
Line-charging breaking current A 1.5 1.5 40
Cable-charging breaking current A 50 50 40
Earth fault breaking current A 50 50 175
Cable charging breaking current
under earth fault conditions A 28 28 80
No-load transformer breaking current A 6.3 6.3 20
Short-circuit ratings
Short-time withstand current, Ik (3s) kA 20 20 12.5
Peak withstand current kA 50 50 31.5
Short-circuit making current kA 50 50 31.5
Number of making operations
– main switch 50 kA (CL E2) n 3 3
– main switch 31,5 kA (CL E3) n 10 10 5
– earthing switch 50 kA (CL E2) n 3 3
– earthing switch 31,5 kA (CL E3) n 5 5

*1
Creepage distance mm 620 620 960 /1440

Ambient air temperature limits –40 ℃...+60 ℃

Mechanical endurance (number of close-open operations)


– main switch n 5000
*2
– earthing switch n 2000

Filling pressure (+ 20 ℃) bar (abs) 1.5


Alarm pressure (+ 20 ℃)
– density switch bar (abs) 1.2
– density gauge bar (abs) 1.2
– low gas lock-out mechanism bar (abs) 1.1
Weight
NXB (manual operated type) kg 82
NXA (manual operated type) kg 96
NXBD(manual operated type) kg 138
Degree of protection of the mechanism box IP X7

3
*1, 960mm special for 24kV product.
*2, Not suitable for NXA type
SECTOS Pole Mounted SF6 Load Break Switch

5 Features
> The high quality 3mm stainless steel are used for tank, which is designed for its maximum robustness
and minimum welding line to minimize corrosion, and specifically to guarantee the safety of the
operation personnel even with the internal arc faults at the maximum fault capacity of the tank the
Sectos can withstands an internal fault without venting hot gases.

> The independent spring operation mechanism adopt ABB patent spiral spring, provides a guaranteed
load break fault make capability by ensuring the opening and closing speed of the switch.

> Standard SF6 gas density units with temperature compensated are provided by Sectos (density switch
is standard for electrical operated type; density gauge is standard for manual operated type), which
ensure no misguide to wrong operating or lock-out by reliable and stable gas pressure measuring.

> The Sectos is provided with light reflecting position indicator which are directly connected to the switch
operating shaft providing clear and unambiguous switch position indication. Indicator made of light
reflecting material, which is easily visible from ground level even at night in driving rain.

> Advanced and Integrated Helium leakage detecting and filling equipment are be adopted, which
ensuring SF6 leakage of each switch is less than 0.15% strictly per year, IEC standard is 1% per year.

> The NXB and NXBD type are available as 2-position(ON-OFF) or 3-position(ON-OFF-EARTH) switch.
When supplied as a 3-positions switch the unit has facility to earth the line on one side of the switch.
The earth position of the 3-positions switch is manually operated only.

> The combined and integrated sensors are optional for NXB and NXBD type, which ensure system
Safety(No effects of short-circuited or interrupted signal circuits; No risk for ferroresonance), Compact
design(voltage and current can be measured in one combi sensor ) and Wide dynamic range(Current
from rated continuous current to short-time withstand current 20kA, voltage rating is applicable from 7.2
to 24kV networks).

> The switch can be manually controlled or it can be provided with an integrated motor drive device for
both remote and/or local electrical control. The motor drive device can easily be retrofitted on site to
manually operated units.

> The control cabinet is fitted with an automatism option(equip with advanced FTU type REC523) which
makes the Sectos a automatic sectionalizer function. It can be current-counter scheme with current
detection or can be voltage-time scheme with voltage detection.

4
SECTOS Pole Mounted SF6 Load Break Switch

6 Accessories

Single spring mechanism A

Usually Sectos Load Break Switch is equipped with single


spring mechanism. This kind of spring mechanism is suitable
for most applications. It's ABB's patent spiral spring, have
stable and reliable characteristics. When the operating shaft
of the switch is turned by manual or motor drive device, the
spring charges during the first part of the movement,
releases in the last part of the movement, and turns the
switch abruptly to new position. Therefor the switch operates
for opening and for closing with the speed, which is
completely independent from the operator or from the
operating device. Normally, the motor operated switch close
or open between 1.5-2.5 seconds from the command signal
initiation.

Double spring mechanism B


Sectos Load Break Switch can be equipped with a double
spring mechanism for rapid opening from initiation. When
the operating shaft of the switch is turned from open position
towards the closed position, the closing spring charges
during the first part of the movement, releases in the last
part of the movement, and turns the switch to closed
position. The second spring(opening spring) remains in
charged position. If the operating shaft is then turned, just a
little, towards to the open position, the opening spring
releases and turns the switch to the open position. This
tripping to open can also be achieved by means of tripping
coil.

The tripping coil is installed in the factory to the double


spring mechanism, and the tripping circuit is connected to
the multi-pin terminal. The total opening time of the switch
with tripping coil is less than 0.1second.

The nominal voltage of tripping coil is same with motor drive


device, normally is 24VDC, optional voltage can be 12VDC,
48VDC, 60VDC, 110VDC, 125VDC or 220VDC.

5
SECTOS Pole Mounted SF6 Load Break Switch

Low pressure lock out device NXBZ4

As an option for sectos, there is available a blocking device,


which blocks the operation of the operating mechanism by
means of a mechanical latch, releases when the inside gas
pressure reduces to lock-out pressure. As the lock-out
mechanism operates, an indication sign(Gas Low) becomes
visible through the position indicator window.

The low pressure lock out device is installed in the factory, the
lock out device is equipped with an auxiliary contact, which
provide electrical lock out for electrical operated type switch.

The low pressure lock out device is recommended to be used


where the outside temperature never falls below -10℃ and the
altitude doesn't exceed 1000m above sea level.

Manual locking device NXBZ90

As an option for sectos, there is available a locking device,


which can lock switch at open or close position by hook stick
manual operated under the pole. As locking device operates,
an indication sign(Locked) becomes visible through the
position indicator window.

The manual locking device is installed in the factory, and is


equipped with an auxiliary contact, which provide electrical lock
out for electrical operated type switch.

The manual locking device can not be used together with


above Low pressure lock out device NXBZ4.

Density gauge NXAP3

For manual operated Sectos, Density gauge can be standard


accessory. Which indicat gas pressure inside tank.

The density gauge is temperature compensated, variation of


the outside air pressure does not affect the indication of the
gauge. Therefore is actually indicate the effective pressure of
the SF6 gas inside of the tank.

Density switch ELEGMD1/0

For electrical operated Sectos, Density switch is standard


accessory, Which indicate gas pressure state inside tank. The
alarm contact of the density switch is normally closed(NC) and
it opens if the gas pressure in the tank falls below
1.2bar(absolute) at 20℃ .

The density switch is temperature compensated, variation of


the outside air pressure does not affect the change over switch
contact. Therefore is actually showing the density state of the
SF6 gas inside of the tank.

6
SECTOS Pole Mounted SF6 Load Break Switch

Manual operated type1

The Sectos are usually operated manually by a insulated hook


stick pulled from ground through the hook stick lever in the up
mechanism box of switch. This hook stick lever can be pulled in
the left to open and the right to close. And it is the only way to
be operated for earthing switch when equipped.

Hook stick normally can be provided or be purchased locally


according to local requirement.

Manual operated type2*

As left picture, Sectos can be selected manual operated by


device which normally located near to the ground level, and the
mechanical movement is transferred to the switch by an
operating rod, which moves up and down.

Operating rods NPTOT_

Operating rod sets are available with rods of 2x4m and 3x3m
lengths, each set including rod supports and necessary joint
pieces.

Rod support NPAZL 9 Extension rods OJUP-ZY10

The set includes one rod of 3m, joint pieces and one rod
support with fitting screws. It's possible to install the Sectos up
to 20 meters height.
Protection insulator of the
operating rod NPSZJ30
Rod support NPAZL9

The operating rod is fitted to the pole with rod supports.


Normally at least 2 supports are needed. The extension rod
Rod support NPAZL 9
set(if necessary) includes 1 rod support.

Protection insulator of the operating rod NPSZJ30


Operating rod NPTOT_ The protection insulator is commonly used with wooden or
concrete poles. Its purpose is to increase the safety of the
operator.
Mannal operating device Manual operating device UEKE3
UEKE3
The manual operating device UEKE3 is suitable for use with
sectos Load Break Switch. It can be locked in open and in
closed positions with a padlock.

7 * These accessories are for wood pole mounted, accessories for concrete pole can be offered if required. And this
operated type can not be selected when inner earthing switch is needed.
SECTOS Pole Mounted SF6 Load Break Switch

7 Electrical and remote control


7.1 Electrical control
The Sectos can be electrical operated locally, which Motor device and Electrical control cabinet are
needed.

Motor drive device UEMC40K8-24VDC

Motor drive device is mounted inside Mechanism box of side of


switch which mounted on the pole. It's can be assembled
before leave factory, also can be retrofitted on site to manually
operated units when needed by experienced people easily.

24VDC is normal for this UEMC40K8 Motor drive device,


Motor drive device UEMC40K8-24VDC 12VDC, 48VDC, 60VDC, 110VDC, 125VDC, 220VDC are can
be ordered for other needs.

Electrical control cabinet UEMC-A2/A3

Electrical control cabinet is mounted under the pole, normally


2-3 meters above ground level on the pole.

Electrical control cabinet UEMC-_ is including relevant control


circuit and components (heater, protection MCB, push button,
operating circuit, and so on), which ensure electrical control
locally, and have enough space for relevant FTU(Feeder
Terminal Unit) communication device.

For 12VDC and 24VDC products, relevant Charge and


Batteries are equipped as backup power. Primary power should
be from Voltage Transformer on the pole or from close-by
substation.
Electrical control cabinet UEMC-_
There are 2 standard types of this electrical control cabinet,
UEMC-A2 and UEMC-A3.

UEMC-A2

Material: stainless steel AISI 304


Degree of protection: IP 55
Includes: - mounting plate
620

- self-regulating heater 45 W,
110...250 V AC/DC
- relay panel
400 330 - wooden pole fixing element
Space for: - batteries
- charger
- 1 or 2 operating circuits
- remote control equipment

8
SECTOS Pole Mounted SF6 Load Break Switch

UEMC-A3

Material: stainless steel AISI 304


Degree of protection: IP 55
Includes: - mounting plate

800
- self-regulating heater 45 W,
110...250 V AC/DC
- relay panel
330
- wooden pole fixing element
500
Space for: - batteries
- charger
- 1 or 4 operating circuits
- remote control equipment

7.2 Remote control and automatic sectionalizer


7.2.1 Remote- function

When equip FTU(ABB type are REC523 and REC501) in UEMC-_ electrical control cabinet, the type of
whole control cabinet then change to DTU-111 or 131(Type option see point7.2.2). Its can realize remote-
control, indicate, measurement function, and automatic sectionalizer function (only with REC523).

Functionality of REC501
> Control
- one or two objects - external heater
- integrated temperature compensated charger
> Measurement
- temperature - battery voltage
> Condition monitoring
- SF6 pressure of primary equipment
- battery condition monitoring
- battery deep discharge protection
- operation counter for primary equipment
- internal self-supervision
> Communication media
- serial cable - modem - conventional radio
- radio modem - DLC - cellular phones
- other RS232 adaptable devices
> Communication protocols
- SPA - LON with adapter - ANSI X3.28
- RP 570 - IEC870-5-101 - Modbus
- DNP 3.0
> Pulse counter
- programmable pulse counter inputs for energy meters

Functionality of REC523
> Control
- two to four objects
- external heater
- integrated temperature-compensated charger

9
SECTOS Pole Mounted SF6 Load Break Switch

> Measurement and data logging


- phase currents and phase-to-phase voltages
- residual current and voltage - active and reactive power
- active and reactive energy - demand values of current and power
- frequency - power factor - harmonics
- temperature - battery voltage - disturbance and event recording
> Condition monitoring
- control circuit supervision - circuit breaker / disconnector condition monitoring
- SF6 pressure of primary equipment - battery condition monitoring
- battery deep discharge protection - operation counter for primary equipment
- internal self-supervision of the unit
> Protection(fault indication purpose)
- Directional/Non-directional over current
- Directional/Non-directional earth fault current
- Under voltage - Phase discontinuity
- Inrush detector - Auto recloser, 5 steps
> IEC 1131 based tools used for configurating of
- I/Os - control functions - measurement functions - timers
- other functional elements of a logic functions library
> Local Automation Functions
- Current Based Sectionalizer
> Communication media
- serial cable - modem - conventional radio
- radio modem - DLC - cellular phones
- other RS232 adaptable devices
> Communication protocols
- SPA - LON - IEC870-5-101
- Modbus(RTU and ASCII) - DNP 3.0

7.2.2 DTU-111 and 131 type option


With REC501
DTU 111 - □□□□
1 = comm. protocol ANSI X3.28 HD
2 = comm. protocol RP 570
3 = comm. protocol IEC 870-5-101
4 = comm. protocol MODBUS
5 = comm. protocol DNP 3.0
A = no heater
B = heater resistor 45 W
1 = 1 pcs contactor logic with local control push buttons
2 = 2 pcs contactor logic with local control push buttons
A ≥ 17 Ah batteries
B ≥ 24 Ah long life batteries
C = no batteries

10
SECTOS Pole Mounted SF6 Load Break Switch

With REC523

DTU 131 - □□□□


1 = reserved for future use
2 = reserved for future use
3 = comm. protocol IEC870-5-101
4 = comm. protocol MODBUS ASCII & RTU format
5 = comm. protocol DNP 3.0
B = 9 pcs sensors (Voltage dividers/Rogovski coils) are in testing on NXB
switches
C= 3pcs current transformers (1A/5A) e.g KOKU 072G4 600/1A CTs
D= 3pcs current transformers (1A/5A) and 3 pcs voltage transformers (110V)
E= 4pcs current transformers (1A/5A) and 3 pcs voltage transformers (230V)
F = 6pcs current transformers (1A/5A) and 3 pcs voltage transformers (110V)
G= 3pcs current transformers (1A/5A) and 6 pcs voltage transformers (110V)
1 = Controls 1 pcs NXB..w. contactor logic and local control push buttons
2 = Controls 2 pcs NXB..w. contactor logic and local control push buttons
3 = Controls 3 pcs NXB..w. contactor logic and local control push buttons
4 = Controls 4 pcs NXB..w. contactor logic and local control push buttons
A ≥ 17 Ah batteries
B ≥ 24 Ah long life batteries
C = no batteries

7.2.3 Automatic Sectionalizer

Sectos Load Break Switch can as Automatic Sectionalizer with DTU-131xxxx control cabinet easily.
Which also includes all remote- function at the same time, don't need add any hardware components.

As the 80-90% of Medium Voltage overhead line faults are self clearing or transient by nature and last for
a few cycles or seconds. In coordination with the main circuit-breaker or reclosers, The Sectos Load
Break Switch is able to distinguish between transitory and permanent faults occurring in the section it is
installed in. Only in case of a permanent fault, it will isolate the line automatically.

From principle and application, the Sectos can as two kinds of sectionalizer, one is Current Based
sectionalizer(need Current detection), the other is Voltage Based sectionalizer(need Voltage detection).

Current Based Automatic sectionalizer


|>
> Automatic sectionalizers are selfcontained,
automatically controlled circuit-opening devices.
Recloser or CB
> Automatic sectionalizers counts the fault current
operations of a upstream reclosing device.
> Automatic sectionalizers operates after a
Sectionalizer preselected number of fault current operations.
> Automatic sectionalizers isolate the faulted
section of a distribution feeder after the feeder
Count Count Count
has been deenergized by e.g. a recloser or
reclosing CB.

11
SECTOS Pole Mounted SF6 Load Break Switch

Voltage Based Automatic sectionalizer


Typical circuit
> Automatic sectionalizers are selfcontained,
Recloser or CB
automatically controlled circuit-opening devices.
> Lose voltage to Open
If Switch detect lost voltage two side of switch, Switch
Sectionalizer open immediately.
(transient fault)
A-Time > Add Voltage to Close(A-Time)
Either side add Voltage and last A-Time Switch close.
> A-Time open lockout
Recloser or CB Either side add Voltage and lost it within A-Time,
Switch hold open and lockout.
> B-Time
Sectionalizer
(permanent fault) A-Time A-Time Switch close and Start B-Time, If no lost voltage till B-
Time time out, Switch hold close.
> B-Time open Lockout
Lock out
Switch close and Start B-Time, If lost voltage within
B-Time, Switch Open and Lockout ( Load side Fault );
> Apply to Loop and emanative circuits.

8 Main construction and mounting


8.1 Main construction

1.Tank 2. Mechanism box 3.Control cable


4.CT measure cable 5.CT junction box 6.Electric control cabinet
7.Control unit

12
SECTOS Pole Mounted SF6 Load Break Switch

Above Picture take example for NXB Load Break Switch

? Manual operated type including item1 and 2;


? Local electrical operated type including item1, 2, 3 and 6;
? Remote control or automatic sectionalizer(current based scheme)type including all items above.
? Voltage based scheme need Voltage detection only, CT relevant item4 and 5 are not necessary.

8.2 Mounting modes


Sectos Load Break Switch can be mounted below or above crossarm which mounted on single or double
poles easily.

8.2.1 Below the crossarm

Sectos can be mounted below the Crossarm easily.

Crossarm NPTRN1T6 / J401464

The standard crossarm is 80 x 80 square tube. There are two standardized lengths, 2000mm
(NPTRN1T6)and 2850mm(J401464). See dimension drawings at the point9.4

Fixing clamp NXAM 1 or 2

Sectos is easy to install below the crossarm using these 2 pieces fixing clamps.

See dimension drawings at the point9.5

NXAM1 is use for 80…100 x 80…100 crossarm. 2 pieces NXAM1 are included in the delivery as a
standard accessory for every type Sectos switch.

NXAM2 is use for 120…160 x 120…160 crossarm

Spacer plate NXBZ59

The Spacer plates are required, if a 3-position switch(with inner earthing switch)

The Spacer plates can be without, if a 2-position switch(without inner earthing switch)

The spacer plate is standard for NXBD type. See dimension drawings at the point9.6

Surge arresters MWK

To protect the Sectos against atmospheric overvoltages, it is often necessary to install surge arresters on
one or both sides of the switch. Normally. It can be purchased locally according to features of local power
network. Also silicon rubber insulated surge arresters of ABB, type MWK can be used, complete
information please go to website http: ABB.com.cn, it can be provided by ABB Hochspannungstechnik AG,
Switzerland or ABB High Voltage Switchgear Co., LTD, BeiJing, China.

13
SECTOS Pole Mounted SF6 Load Break Switch

1
2
3

1.Crossarm
2.Fixing clamp
3.Spacer plate
4.Surge arrester

Single pole (Suitable for NXA and NXB)

2 3 1

1.Crossarm
2.Fixing clamp
3.Spacer plate
4.Surge arrester

Double poles (Suitable for NXA and NXB)

14
SECTOS Pole Mounted SF6 Load Break Switch

1 3
2

1.Crossarm
2.Fixing clamp
3.Spacer plate
4.Surge arrester

NXBD mounted at Double poles normally

8.2.2 Above the crossarm

Sectos(except NXBD) can be mounted below the Crossarm easily.

Description of Crossarm and Surge arrester can be found above in point 8.2.1

Fixing clamp NXAM 4 or 5

NXB is easy to install above the crossarm using 2 pieces fixing clamps---NXAM1 or NXAM2.

NXA is easy to install above the crossarm using 2 pieces fixing clamps---NXAM4 or NXAM5.

See dimension drawings at the point9.7

NXAM1 is use for 80…100 x 80…100 crossarm. NXAM2 is use for 120…160 x 120…160 crossarm

15
SECTOS Pole Mounted SF6 Load Break Switch

1
3

2
1.Crossarm
2.Fixing clamp
3.Surge arrester

Above pole (for NXA and NXB)

8.2.3 Mounted on pole directly

Sectos(only NXB) can be mounted on pole (Diameter 180mm to 250mm) Directly (as right picture)

When this mounting type is selected, a set of fixing accessory (named NXBZ204) should be selected.

Diameter
180-250mm

16
SECTOS Pole Mounted SF6 Load Break Switch

9 Dimension drawings(unit:mm)
9.1 NXB Load Break Switch

792 910
680 (42) 397

39
177.5

56.5
508
25
240 240

23

26
397
372.5
342.5

317.5
278.5

257.5

9
163.5

143.5
12

78.,5
M12
28.5
0

9.2 NXBD Load Break Switch


1250
1120
1077
397
702.5
712
243

658
505

831

1 1

M16 3

23

240 240
26

12
M12
9
143
344
264
135
94

680

17
SECTOS Pole Mounted SF6 Load Break Switch

9.3 NXA Load Break Switch


955
1286 700

669

507
14

24
669
M16
23 44.5 50

3× 13

26
9 11

13 M8 M12 M12
67
47
114
264

94
174

13

9.4 Crossarm NPTRN1T6 / J401464


2000

900 27
27

25 27 25

50 1000

22 22 22 80*80*4

50 1900 50

Type NPTRN1T6

1425

50 712,5 712,5

22
3*22 80*80*4

50 2750

2850

Type J401464

18
SECTOS Pole Mounted SF6 Load Break Switch

9.5 Fixing clamp NXAM 1 / NXAM 2

9.6 Spacer plate NXBZ59

NXBZ 59

9.7 Fixing clamp NXAM 4 / NXZM5

19
SECTOS Pole Mounted SF6 Load Break Switch

10 Ordering type code


10.1 Type code of Sectos NXB and NXBD

The Pole Mounted Load Break Switch type NXB 24 C 630 A M 3 / 24VDC / 8M / UEMC-A2

Pole mounted load Break Switch NXB


3-way Pole mounted Load Break Switch NXBD
Single phase Pole mounted Load Break Switch NXBS

Rated voltage 12kV IEC 12


24kV IEC 24
Type of insulators
Silicone rubber insulators C
Silicone rubber insulators with sensors CS
Series 400 for underground cable bushings according to IEC E

Rated Current 630 A 630


Without earting switch A
Earting switch on one side when NXB C
Earting switches on both sides/disconnectors when NXBD C
Tripping coil but no earthing swithes (with Double spring mechanism) B
Tripping coil and earthing swithes (with Double spring mechanism) D

Motor operating device M


Only manual operating = BLANK -

Gas measuring accessories in operaing mechanism box


Manual operated type with NXAP3 gas density gauge, with temp.
compensated, for temp.-40℃...+60℃ 3
Motor or remote operated type with ELEGMD1/0 gas density
switch, with temp. compensated, for temp.-40℃...+60℃ 3
Mechanical Low pressure lock-out device possible-10℃...+40℃,
without temp. compensated 4

Motor and tripping coil voltage is 24VDC 24VDC


Other voltages, 12VDC, 48VDC, 60VDC, 110VDC, 125VDC, 220VDC can
be ordered for other needs

A control cable is always needed with motor operating device 8M


The alternatives are 8m, 12m, 16,xxM (max 25 m) xx to be specified

Medium control cabinet with relevant control circuit and


components, spare space ready for radio and ABB FTU UEMC-A2
Big control cabinet with relevant control circuit and components,
spare space ready for bigger size communication device and UEMC-A3
Control cabinet with relevant circuit and components, equip with FTU REC523 DTU131-xxxx
Control cabinet with relevant circuit and components, equip with FTU REC501 DTU111-xxxx

20
SECTOS Pole Mounted SF6 Load Break Switch

10.2 Type code of Sectos NXA

The Pole Mounted Load Break Switch type NXA 36 C 630 A M 3 / 24VDC / 8M / UEMC-A2

Pole mounted load break switch NXA

Rated voltage 24 kV IEC (*Creepage distance up


to 960mm) 24
36 kV IEC (*Creepage distance up
to 1440mm) 36

Type of insulators
Silicone rubber insulators C
Series 400 for underground cable bushings according to IEC E

Rated current 630 A 630


Without earting switch A
Tripping coil but no earthing swithes (with Double spring mechanism B

Motor operating device M


Only manual operating = BLANK -

Gas measuring accessories in operaing mechanism box


Manual operated type with NXAP3 gas density gauge, with
temp. compensated, for temp.-40℃...+60℃ 3
Motor or remote operated type with ELEGMD1/0 gas density
switch, with temp. compensated, for temp.-40℃...+60℃ 3
Mechanical Low pressure lock-out device possible -10℃...+40℃,
without temp. compensated 4

Motor and tripping coil voltage 24VDC


Other voltages, 12VDC, 48VDC, 60VDC, 110VDC, 125VDC, 220VDC can be
odered for other needs

A control cable is always needed with motor operating device 8M


The altematives are 8m, 12m, 16, xxM (max 25 m) xx to be specified

Medium control cabinet with relevant control circuit and


components, spare space ready for radio and ABB FTU UEMC-A2
Big control cabinet with relevant control circuit and components,
spare space ready for bigger size communication device and UEMC-A3
Control cabinet with relevant circuit and components, equip with FTU REC523 DTU131-xxxx
Control cabinet with relevant circuit and components, equip with FTU REC501 DTU111-xxxx

21
SECTOS Pole Mounted SF6 Load Break Switch

10.3 CT, VT and Sensor


10.3.1 CT and VT

CT and VT are option items when order Sectos

Ring type Current Transformer KOKU072G4 are standard type of Sectos, For some special application,
Applies to the fault indicator SPEF 3A2C, Current Transformer type KOKU072G3(same size with
KOKU072G4) can be used. The ratio of it is 400/0.1A, the CT of each phase are connected to the
shielded downlead cable KOHZ11 in the branching box SPEC4, which also includes an over voltage
protection.

> Installed around the bushings of Sectos


> Type: KOKU 072 G4
> Ratio: 400/1A, 600/1A
> Burden/Class 3 VA / 5P10 0.5 VA / 5P20

VT(Voltage Transformer) should be equipped as power or voltage measuring.

TDO 6 type can be provided, also local purchaseing according local requirement is available.

Outdoor voltage transformers TDO 6

Highest voltage for equipment [kV] 12, 17, 5, 24, 25


Power frequency test voltage, 1 min. [kV] 28, 38, 50
Lightning impulse test voltage [kV] 75, 95, 125
Max. rated burden, classes [VA/cl] 50/0.2 - 100/0.5 - 150/1

22
SECTOS Pole Mounted SF6 Load Break Switch

10.3.2 Sensors

Current, Voltage & Combi Sensors are a new solution for measuring currents and voltages for protection
and monitoring of Medium Voltage power systems. In the combi sensors, both the current and voltage
sensors are integrated in the same compact cast resin part.

Technical Specifications of Current, Voltage and Combi Sensors

Current Sensor Voltage Sensor


Principle Rogowski-coil Capacitive voltage divider
Rated primary value 80 A 20: 3kV
Rated primary current factor 10
Accuracy limit factor 60
Rated continuous thermal current 630 A
Rated secondary value 0, 150V (0,180V at 60Hz) 2,0: 3V
Accuracy Class 5 Class 6P
-using calibration factor Class 3/10P60

Type of Combi Sensor KEVCY 24 SA 2


Type of Voltage Sensor KEVCY 24 SB 3
System includes ! 3 combi sensors and 3 voltage sensors (NXB_) or 6
combi sensor (NXBD_)
! cables from the sensor to a junction box
! cable from the junction box control cabinet
Output Adapted to ABB's REC 523-relay
Sensor cable Double shielded, sensor end casted in, junction box end
provided with terminals suitable for direct connection to PCB
Down lead cable The length of the double shielded cable from the junction box
to control box is 10m. The control box end of the cable is
provided with Twin-BNC connectors for direct connection to
REC 523 inputs.

23
CNXEC-SECTOS-EN/01/3000/T-2005/08

209, Douxi Road, Xiamen, Fujian 361004, P.R.China


TEL:+86 592 2299100 2299199 2299270
FAX:+86 592 2276704
http://www.abb.com.cn/outdoor