CONTENTS
Ordering Information •06 HLB2 & HOKZE •29 HiMP •48
HiMC •10 Accessory •31 HME •73
HiTH •22 HiMS Diagram •34
HMX & HMT •27 HiMS Drawing •36
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

Ordering Information

Magnetic Contactor

HiMC 22 W 22 S / 220 X
Rated Current(440VAC) W AC Control 2 Number of NO Safety Cover Operational Blank X
Blank S Voltage
Type Current Type Current G DC Control 2 Number of NC
60 Hz 50 Hz
Without With W AC 24~600 V
9 9A 110 110 A F Free Voltage Cover Cover
G DC 24~250 V
12 12 A 130 130 A Free voltage type
is available from F AC/DC 220, 440 V
18 18 A 150 150 A HiMC 65 to 800
Please refer to the
22 22 A 180 180 A Technical Data,
page 14 & 15
32 32 A 220 220 A

40 40 A 260 260 A

50 50 A 300 300 A

65 65 A 400 400 A

80 80 A 500 500 A

90 90 A 630 630 A

800 800 A

Thermal Overload Relay

HiTH 22 K 22 S
Type Rated Current Safety Cover
Hyundai Type Applied MC
Name
H K Blank S
innovative
22 HiMC 9~22 2 Element 3 Element Please refer to the Without With
THermal (Option) (Standard) Technical Data Cover Cover
overload 40 HiMC 32~40 page 24 & 25
relay 50 HiMC 50

90 HiMC 65~90

130 HiMC 110~130

220 HiMC 150~220

300 HiMC 260~300

500 HiMC 400~500

800 HiMC 630~800


Control Relay Separate Mounting Unit for HiTH

HMX 22 / 220 X HiTHMB 22 S


Control Relay Number of Contacts Operational Blank X Applied Safety Cover
Type
22 31 40
Voltage TOR Blank S
AC: HMX
60 Hz 50 Hz Without With
DC: HMT AC 24~600 V 22 HiTH22
2a 2b 3a 1b 4a Cover Cover
DC 24~250 V 40 HiTH40

50 HiTH50

90 HiTH90

Mechanical Interlock Unit Aux. Contact Block

HiTL 50 HAB 22
Type Application M.C Mounting Application
Type 2 2
Mechanical 40 HiMC 9~40 Side M/C
Interlock Unit 50 HiMC 50 HiAB Top HiMC 9~50
Number Number
130 HiMC 65~130 HiAL 11 Left HiMC 9~22 of of
NO NC
200 HiMC 150~200 HiAC Top HMX, HMT

300 HiMC 260~300 HiAL 5S Left


HiMC 65~130
800 HiMC 400~800 HiAR 6S Right

HiAL 7S Left
Hi Series

HiMC 150~800
HiAR 8S Right
07
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMC

Auxiliary Contacts and Contact Blocks

Based on IEC 60947 Standard

Auxiliary Contacts Auxiliary Contact Blocks


Type HiMC HAB, HAC, HAS
HiAL, HiAR
9 ~ 50 65 ~ 800 Fixed Contacts Convertible Contacts
Rated Insulation Voltage V 750 750 750 750 750
Rated Thermal Current Ith A 16 16 16 16 16
110 V 10 10 10 10 10
Rated Current
AC-12 duty 220 V 8 8 8 8 8
A
(Resistive 440 V 6 6 6 6 6
heating loads)
690 V 2 2 2 2 2
110 V 6 6 6 6 6
Rated Current
220 V 6 6 6 6 6
AC-15 duty A
(Coil loads) 440 V 3 3 3 3 3
690 V 2 2 2 2 2
24 V 5 5 5 5 5
Rated Current
DC-12 duty 48 V 3 3 3 3 3
A
(Resistive 110 V 2.5 2.5 2.5 2.5 2.5
heating loads)
220 V 1 1 1 1 1
24 V 3 3 3 3 3
Rated Current
48 V 2 2 2 2 2
DC-13 duty A
(Coil loads) 110 V 1 1 1 1 1
220 V 0.6 0.6 0.6 0.6 0.6

UL & CSA Standard

Auxiliary Contacts 1) Auxiliary Contact blocks


Type HiMC HAB, HAC, HAS 2)
HiAL, HiAR 1)
9 ~ 50 65 ~ 800 Fixed Contacts Convertible Contacts
Rated Thermal Current Ith V 16 16 16 16 16
120 V 6 6 3 3 6
AC 240 V 3 3 1.5 1.5 3
A
Rated Current 480 V 1.5 1.5 0.75 0.75 1.5
600 V 1.2 1.2 0.6 0.6 1.2
DC 125 V 1.1 1.1 1.1 1.1 1.1
A
Rated Current 250 V 0.55 0.55 0.55 0.55 0.55
※ Contact rating code: 1) A600-P600 (Aux. contact & HiAL, HiAR)
2) B300-P300 (Aux. contact block)
HMX & HMT

Control Relays

Features

◆HMX is for AC, and HMT is for DC


◆The protection degree is IP20.
◆Screw and 35 mm DIN-Rail mounting is available.
◆Both HMX and HMT have three types of contact (2NO+2NC, 3NO+1NC, & 4NO).
◆These are proper for control circuit and factory automation.
◆The following auxiliary blocks can be attached by one-touch method.
•Aux. contact block •Timer •Latching Block •Surge absorber(RC-Unit)

Applicable Standard ◆ IEC 60947–5–1 ◆UL 508 ◆VDE 0660 ◆CENELEC–EN 50011

Technical Data

Contact
IEC 60947 750
Rated Insulation Voltage V
VDE0660 1000
Thermal Current Ith (AC-1) A 20
220 V 10
380 V 4
AC-15 440 V 3.5
500 V 3
690 V 2
24 V 5
Rated DC-12
48 V A 3
Operational (Resistance
110 V 2.5
Current Ie Load)
220 V 1
24 V 3
DC-13 48 V 2
(Coil Load) 110 V 1
220 V 0.6
AC Operated 10 … 25
Closing Time
DC Operated 20 … 50
ms
AC Operated 5 … 20
Opening Time
DC Operated 15 … 35
Mechanical Lifetime 10000 Times 1500
Wire Size mm2 2×0.75 … 2.5
Hi Series

Operation Frequency Times/Hours 3000


Plug-Fuse (Fast/Slow) 35/25
Applicable Max. Fuse MCB-C Features A 16
27

HRC Fuse (DIN/BS88) 25


Coil
Making VA/W 60/44
AC (60 Hz)
Consumption Power Normal VA/W 7.5/1.9
DC Making/Normal W 6.5
AC Operated kg 0.34
Weight
DC Operated kg 0.61

UL Standard
Rated Thermal Current A 20
120 VAC 6 120 VDC 1.1
Rated Current A Rated Current A
240 VAC 3 240 VDC -
※ Contact Rating Code: A300 ~ P150
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HMX & HMT

Mechanical Interlock Unit

◆The mechanical interlocking of two contactors for reversing contactors is


available with interlock unit.
A simultaneous closing of two contactors is prevented.

Type Contactors
HiTL 40 HiMC 9 ~ 40
HiTL 50 HiMC 50
HiTL 130 HiMC 65 ~ 130
HiTL 220 HiMC 150~220
HiTL 300 HiMC 260 ~ 300
HiTL 800 HiMC 400 ~ 800

◆Handling
•The electrical interlock should be applied via the“b”contact when
mechanical interlock is used.
•Horizontal installation is not allowed.
•Mechanical interlock shall be installed on HiMC 150-800 after removing
auxiliary contact blocks between two magnetic contactors.

◆Dimensions

Type A B C D E F G H Ф
HiMC 9, 12, 15, 18, 22 98 83 50~66 32~35 10 86.2 - 7.5 4.8
HiMC 32, 40 136 83 50~66 33.5~53.5 10 86.7 - 8 4.8
HiMC 50 149.2 85.8 57.6~70 53.8~60.8 10 99.2 - 8 4.8
HiMC 65, 80, 90 201.6 130 110~116 80 14 135.7 7.5 12 5.5
HiMC 110, 130 220 142 120~130 90 14 150.3 3.5 12 6.2
HiMC 150, 180, 220 316 189 161~171 120 40 168 3 15 9
HiMC 260, 300 340 202 180 120~130 40 187.4 3 15 11
HiMC 400, 500 398 251 196~225 154 40 235.5 3 20 11
HiMC 630, 800 592 280 230~250 226~250 40 272.3 3 24 12
HLB2 & HOKZE

Mechanical Latching Block

HLB2 Characteristics

◆Fast & Easy mounting to contactors and control relays.

◆HLB2 keeps the contactor mechanically latched.

Operation

◆How to OFF contactors or control relays


•Manually: Push the lever to the “O” position.
•Electrically: Put power to the coil.

◆Caution
•Do not excite the contactors (or control relays) and mechanical latching
blocks simultaneously.
•Refer to the right diagram for the control circuit.

Ratings and Characteristics

VA 25
Power Consumption
W 30
Pick-up Voltage V (0.85 - 1.1) x UC
Operating Cydes Cycle/h 1,200
24 V Fixed
AC and DC Controlled
AC / DC 110 V 110 ~ 125 V
Voltage
220 V 200 ~ 240 V
Mechanical Endurance 1,000 times 500
ex) HLB 2 / 220 (AC/DC)
※ Different voltage range shall be informed in advance.
Hi Series
29
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HLB2 & HOKZE

Electronic Timer Block

HOKZE Characteristics
◆Fast & Easy mounting.

◆Accurate and multi function through electronic method.

◆Wide voltage range is realized, and both AC & DC are applicable


on the block.

◆On-delay and Interval functions are furnished on the timer block at once.

Ratings & Characteristics

Mode HOKZE 1 HOKZE 2


Rated Voltage AC/DC V 90 ~ 240 24 ~ 60
Operating Voltage V (0.85 ~ 1.1) X Rated Voltage
Making Capacity VA 90
Maximum Load VA 15
Position A 10 ~ 220
Delay Time
Position B 0.15 ~ 15
Precision % ±5
% 0.1
Repeat Accuracy
sec 50ms

Function Charts
※ The timer needs a recovery time of at least 150ms between
operations to be reset for the next operation.

Position 1: ON-DELAY / t: adjustable delay time 0.15...220S Position 2: Interval Timer


Accessory

Auxiliary Contact Blocks

Type Consist Characteristics Application


HiAB 22 2NO + 2NC -
HiAB 13 1NO + 3NC -
HiAB 31 3NO + 1NC -
HiAB 04 0NO + 4NC -
HiMC 9 ~ 50
HiAB 40 4NO + 0NC -
HiAB 11 1NO + 1NC -
HiAB 02 0NO + 2NC -
HiAB 20 2NO + 0NC -
HiAL 11 ★
1NO + 1NC Left Hand Side HiMC 9 ~ 22
HiAC 13 1NO + 3NC -
HiAC 22 2NO + 2NC -
HiAC 40 4NO + 0NC -
HMX
HiAC 11 1NO + 1NC -
HMT
HiAC 02 0NO + 2NC -
HiAC 20 2NO + 0NC -
HiAL 5S 1NO + 1NC Left Hand Side
HiMC 65 ~ 130
HiAR 6S 1NO + 1NC Right Hand Side
HiAL 7S 1NO + 1NC Left Hand Side
HiMC 150 ~ 800
HiAR 8S 1NO + 1NC Right Hand Side

The side mounting Aux. contact block shall not be used with the top mounting Aux. contact block at the same time.

HiAC 22 HiAC 20 HiAL 11 HiAL 5S HiAR 6S


Hi Series
31
Hyundai innovative Magnetic Contactor / Thermal Overload Relay

Accessory

Surge Absorber

◆Surge Absorber drops surge voltage, which is 10~20 times of the rated voltage occurred at the
operation of the contactor or auxiliary switch, to below 3 times of rated voltage.

◆It is suitable for PLC control circuit.

◆Damage to electronic parts from high surge voltage is prevented by the use of surge absorber.

◆Applicable to 50 Hz and 60 Hz.

Item Type Voltage Application


HRC 40/48 28 ~ 48 V
HMX
HRC 40/220 110 ~ 220 V
HiMC 9W ~ 40W
HRC 40/380 240 ~ 380 V
HRC 90/48 28 ~ 48 V
HiMC 50W
RC - Unit HRC 90/220 110 ~ 220 V
HiMC 65W ~ 90W
HRC 90/380 240 ~ 380 V
HRC 300/48 28 ~ 48 V
HRC 300/220 110 ~ 220 V HiMC 110W ~ 300W
HRC 300/380 240 ~ 380 V
Clamping Diode HOKYZX 38 HMT, HiMC 9G ~ 300G

◆Diagram

RC-Unit
Spare Parts

Control Coil Main Contact


Type Applicable MC Type Contactors
HMCOL 22X HMX HiMCTIP 9 ★
HiMC 9
HMCOL 22T HMT HiMCTIP 12★ HiMC 12
HiMCOL 40W/G HiMC 9 ~ 40 HiMCTIP 18 ★
HiMC 18
HiMCOL 50W/G HiMC 50 HiMCTIP 22★ HiMC 22
HiMCOL 90W/G/F HiMC 65 ~ 90 HiMCTIP 32 ★
HiMC 32
HiMCOL 130W/G/F HiMC 110 ~ 130 HiMCTIP 40★ HiMC 40
HiMCOL 220W/G/F HiMC 150 ~ 220 HiMCTIP 50 ★
HiMC 50
HiMCOL 300W/G/F HiMC 260 ~ 300 HiMCTIP 65 ★
HiMC 65
HiMCOL 500W/G/F HiMC 400 ~ 500 HiMCTIP 80 ★
HiMC 80
HiMCOL 800W/G/F HiMC 630 ~ 800 HiMCTIP 90 ★
HiMC 90
※ Ordering method: ex) HiMCOL 40W / 220X (Blank: 60 Hz, X: 50 Hz) HiMCTIP 110★ HiMC 110
HiMCTIP 130 ★
HiMC 130

Arc Chute HiMCTIP 150★ HiMC 150


HiMCTIP 180 ★
HiMC 180
Type Contactors
HiMCTIP 220★ HiMC 220
HiMCHT 90 HiMC 65 ~ 90
HiMCTIP 260 ★
HiMC 260
HiMCHT 130 HiMC 110 ~ 130
HiMCTIP 300 ★
HiMC 300
HiMCHT 220 HiMC 150 ~ 220
HiMCTIP 400 ★
HiMC 400
HiMCHT 300 HiMC 260 ~ 300
HiMCTIP 500 ★
HiMC 500
HiMCHT 500 HiMC 400 ~ 500
HiMCTIP 630★★ HiMC 630
HiMCHT 800 HiMC 630 ~ 800
HiMCTIP 800 ★★
HiMC 800

One set consists of 3 moving contacts and 6 fixed contacts.
★★
One set consists of 6 moving contacts and 12 fixed contacts.
(Two contact elements make one contact set.)
Insulation Barrier Unit
Type Contactors
HiMCIB 130 HiMC 65 ~ 130
HiMCIB 300 HiMC 150 ~ 300
HiMCIB 500 HiMC 400 ~ 500
HiMCIB 800 HiMC 630 ~ 800
Hi Series
33

Coil Main Contact Arc Chute


Hyundai innovative Magnetic Contactor / Thermal Overload Relay

HiMS Diagram

Location of Contacts

Contactor Aux. Contact Block

HiMC 9W11 HiMC 9G11


HiMC 12W11 HiMC 12G11
HiMC 18W11 HiMC 18G11
HiMC 22W11 HiMC 22G11 HiAB 22 HiAB 11
2NO+2NC 1NO+1NC

HiAB 31 HiAB 02
HiMC 32W22 HiMC 32G22 3NO+1NC 0NO+2NC

HiMC 40W22 HiMC 40G22


HiMC 50W22

HiAB 13 HiAB 20
1NO+3NC 2NO+0NC

HiMC 50G21

HiAB 04 HiAL 5S
0NO+4NC HiAL 7S
1NO+1NC

HiMC 65W22 HiMC 220W22


HiMC 80W22 HiMC 260W22 HiAB 40 HiAR 6S
4NO+0NC HiAR 8S
HiMC 90W22 HiMC 300W22
1NO+1NC
HiMC 110W22 HiMC 400W22
HiMC 130W22 HiMC 500W22
HiMC 150W22 HiMC 630W22
HiMC 180W22 HiMC 800W22
Control Relay Aux. Contact Block

◆AC Operation Type

HiAC 13
HMX 22 1NO+3NC

HiAC 22
HMX 31 2NO+2NC

HiAC 31
HMX 40 3NO+0NC

HiAC 40
4NO+0NC

◆DC Operation Type

HiAC 11
HMT 22
1NO+1NC

HiAC 02
HMT 31
0NO+2NC
Hi Series
35

HMT 40 HiAC 20
2NO+0NC