Medium-Voltage

Switchgear

Switchgear Catalog HA 41.21


2005
Type SIMOSEC up to 24 kV,
Air-Insulated, Extendable
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Contents Application

Page Typical uses

Application, Requirements
Typical uses, features 2 and 3

R-HA41-082 eps
Technical Data
Electrical data, pressure values,
temperature 4 and 5
Switchgear installation 6
Shipping data 7

Product Range
Product range overview, equipment
features 8 and 9
Panels 10 to 15

Design
Panel design 16 and 17

Components
3AH vacuum circuit-breakers 18 to 20 Example
Three-position switches 21 4-panel transfer switchgear with
Busbars, HV HRC fuse assembly 22 and 23 integrated low-voltage niche
Operating mechanisms 24
Indicating and measuring equipment 25
Interlocking systems and locking devices 26
Transformers 27 to 29
Cable connection 30 and 31
Low-voltage equipment 32

Dimensions
Panels 33 to 39
Floor openings, fixing points 40

Standards
Standards, specifications, guidelines 41 to 43

Notes
43
R-HA41-055 eps

Utilities transfer substation


© Siemens AG 2005 for industrial plants

2 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Application, Requirements

Features
SIMOSEC switchgear is a Technical features Reliability • Mechanical switch position
factory-assembled, type- • Air-insulated indoor • Type and routine-tested * indications integrated in
tested, three-phase, metal- switchgear mimic diagram
enclosed, metal-clad indoor • Standardized and manu-
• Gas-insulated, maintenance- factured using numerically • Switchgear interlocking
switchgear according to system with logical
IEC 60 298 / VDE 0670-6 * free switching functions for controlled machines
the three-position switch mechanical interlocks
for single busbars. • Quality management system
• Three-pole primary enclosure according to DIN EN ISO 9001 Reavailability
Typical uses
• Phases arranged one behind • More than 350,000 switchgear • Three-position switch discon-
SIMOSEC switchgear is the other components in operation nector with gas-insulated,
used for power distribution in worldwide for many years maintenance-free quenching
• No cross-insulation between
distribution systems with principle
feeder currents up to 1250 A. phases • No cross-insulation between
• Busbar system at the top phases • Metal compartmentalization
Modular space-saving design between busbar compart-
allows use in • Air-insulated busbar and cable Personal safety ment, switching devices and
• Substations, customer trans-
connection system cable connection compart-
• All switching operations can
fer substations, distribution • Three-position switch, metal- be performed with closed ment
substations and switching enclosed, with air-insulated panel front • Separate pressure relief for
substations of power supply primary terminals and gas- each compartment
insulated switching functions • Metal-enclosed, cubicle-type
and public utilities
or metal-clad switchgear • Cable testing without the
• Public buildings, such as • Vacuum circuit-breaker 3AH5,
• HV HRC fuses and cable seal- need to isolate the busbar
high-rise buildings, railway metal-enclosed, up to 630 A,
stations, hospitals fixed-mounted in gas-insulated ing ends are only accessible • Mounting location of three-
switchgear vessel when the outgoing feeders are phase current transformer for
• Industrial plants earthed selective disconnection of
• Vacuum circuit-breaker 3AH6,
• Logical mechanical interlocking circuit-breaker feeders
Typical examples air-insulated, up to 1250 A,
• Wind power stations
easy to withdraw after loose- • Capacitive voltage detection
Cost-efficiency
ning the fixing bolts system for verification of safe
• High-rise buildings isolation from supply Extremely low life-cycle costs
• Hermetically-sealed by
• Airports and extremely high availability
welding, stainless-steel • Earthing of outgoing feeders
throughout the entire product
• Underground railway stations switchgear vessel, by means of make-proof service life cycle as a result of:
– For switching devices earthing switches
• Sewage treatment plants – With welded-in bushings • Three-position switch with
• Port facilities (for electrical connections and Security of operation gas-insulated quenching
mechanical components) principle
• Traction power supply • Components, e.g. operating
systems – With insulating gas SF6 mechanisms, three-position • 3AH vacuum circuit-breaker
• Automobile industry • Cubicle-type or metal-clad switches, vacuum circuit- • Minimum space requirement
panel design breakers proven for years
• Petroleum industry • Easy switchgear extension
• Pressure relief • Metal-clad panels (metal com-
• Chemical industry – To the rear and upwards partmentalization between • Standard protection relays,
– Separately for each busbar and switching device e.g. multifunction protection
• Unit-type heating power
compartment and between switching device SIPROTEC 4
stations
• Air-insulated cable connection and cable connection compart-
• Textile, paper and Electrical features
system for conventional cable ment)
food industry • Rated voltages up to 24 kV
sealing ends • Cubicle-type panels with
• Emergency power supply
• Three-phase current trans- metal compartmentalization • Rated short-time withstand
installations between switching device and current up to 25 kA
former, factory-assembled on
the feeder bushings busbar compartment • Rated normal current of
Modular design
• Integrated low-voltage niche • Three-position switch metal- feeders
• Individual panels, for free
(standard) for installation enclosed with gas-insulated – Up to 630 A, e.g. for
combination and extension switching functions ring-main, metering and
of, e.g.
• Option: Low-voltage com- – Welded sealed-for-life circuit-breaker panels
– Terminals, MCBs, push-
partments can be supplied in buttons switchgear vessel – Up to 1250 A, for
two overall heights – Protection devices – No cross-insulation between circuit-breaker and bus
phases sectionalizer panels
• Option: Top-mounted low- – With welded-in bushings for
voltage compartment • Rated normal current of
cable connection, busbar and busbar up to 1250 A
• Option: Panel heating for operating mechanism
severe ambient conditions, • Switch operating mechanisms
e.g. condensation outside switchgear vessel
• Maintenance-free operating
mechanism parts (IEC 60 694/
VDE 0670-1000 *)
* Standards see page 41

Siemens HA 41.21 · 2005 3


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Electrical data of panels, pressure values, temperature


Common details on electrical data, filling pressure and temperature
Rated insulation level Rated voltage Ur kV 7.2 12 15 17.5 24
Rated short-dur. power-freq. withstand voltage Ud kV 20 28 36 38 50
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr 50/60 Hz
Rated normal current Ir 1) Standard 630 A
of busbar Option 1250 A
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 16 20 25 16 20 25 16 20
withstand current Ik for switchgear with tk = 3 s up to kA 20 – 20 – – 20 – – 20 – – 20
Rated peak withstand current Ip up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated filling pressure pre 2) for insulation 1500 hPa (absolute) at 20 °C
Minimum operating pressure pme 2) for insulation 1300 hPa (absolute) at 20 °C
Ambient temperature T for panels without secondary equipment Class “Minus 25 indoor” (– 25 °C to +55 °C)
for panels with secondary equipment Class “Minus 5 indoor” (– 5 °C to +55 °C)

Ring-main panel type RK and cable connection panel type K, K-E


Rated normal current Ir 1) for feeder and transfer, panel type RK 630 A (standard), 400 A (on request)
for feeder, panel type K, K-E 630 A (standard), 400 A (on request)
for feeder, panel type K1, K1-E 630 A (standard), 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50

Transformer panel type TR


Rated normal current Ir 1) for feeder 3) 200 A
Rated peak withstand current Ip 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit making current Ima 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Reference dimension “e“ for HV HRC fuse links mm 292 4) 292 442 442 442

Circuit-breaker panel type LS for feeder for transfer with


Rated normal current Ir 1) f. panel type LS1 and LS1-U 3AH5 * 630 A
f. panel type LS11 and LS11-U 3AH6 * 630 A
f. panel type LS31, LS32 and LS31-U 3AH6 * 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit breaking current Isc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20

Busbar earthing panel type SE


Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50

Busbar voltage metering panels type ME3 and type ME31-F


Rated peak withstand current Ip 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit making current Ima 3) up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Reference dim. “e“ in panel type ME31-F for HV HRC fuse links 292 mm

Billing metering panels type ME1


Rated normal current Ir 1) for transfer, panel types ME1 and ME1-H 630 A, 1250 A
for feeder as cable-connection panel type ME1-K 630 A, 1250 A
for busbar connection, panel type ME1-S 630 A, 1250 A
for bus riser panel type HF 630 A, 1250 A

Bus sectionalizer panels type LT


Rated normal current Ir 1) for panel types LT10 and HF, with 3AH5 * 630 A
for panel type LT1, with 3AH5 *: On request 630 A
for panel types LT11 and HF, with 3AH6 * 630 A
for panel types LT2 and LT22 630 A
for panel types LT31 and HF, with 3AH6 * 1250 A
Rated short-circuit making current Ima up to kA 50 63 50 63 40 50 63 40 50 63 40 50
Rated short-circuit breaking current Isc for 3AH vacuum circuit-breaker up to kA 20 25 20 25 16 20 25 16 20 25 16 20
Electrical service life for 3AH vacuum circuit-breaker:
at rated normal current Ir 1) 10,000 operating cycles
at rated short-circuit breaking current Isc 50 breaking operations, 35 breaking operations on
3AH6 * with 25 kA

1) The rated normal currents apply to ambient tempera- 3) For panel types TR and ME31-F depending on the max. * Type designation
tures of 40 °C. The 24-hour-mean value is max. 35 °C cut-off current of the HV HRC fuse link (ID w 25 kA) of the vacuum
(according to IEC 60 694 / VDE 0670-1000) 4) With reference dimension e = 192 mm, an extension tube circuit-breaker
2) Pressure values for SF6-insulated vessels (100 mm long) is additionally required for fuse mounting 292 mm

4 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Electrical data * of the switching devices


Three-position switch-disconnector
Rated voltage Ur kV 7.2 12 15 17.5 24
Rated insulation Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
level
Rated lightning impulse withstand voltage Uw kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normal ring-main feeders Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
current for transformer feeders 1) Ir A 200 200 200 200 200
Rated short-time for switchgear with tk (ttk)**= 1 s Ik (Ith)** up to kA 25 25 25 25 20
withstand current for switchgear with t k (ttk)**= 3 s Ik (Ith)** kA 20 20 20 20 20
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit transformer feeders 2) Ima kA 25 25 25 25 25
making current for
ring-main feeders Ima up to kA 63 63 63 63 50
Mechanical stability (class M1) No. of operating cycles 1000 1000 1000 1000 1000

Switching capacity of general-purpose switches (class E3) according to IEC 60 265-1 / VDE 0670 Part 301 (Standards see page 41)
Test duty 1 Rated mainly active for 100 switching operations I1 A 630 630 630 630 630
load breaking current for 20 switching operations I1 A 31.5 31.5 31.5 31.5 31.5
Test duty 2a Rated closed-loop breaking current I2a A 630 630 630 630 630
Test duty 3 Rated transformer breaking current I3 A 40 40 40 40 40
Test duty 4a Rated cable-charging breaking current I4a (IC or I6)** A 68 68 68 68 68
Test duty 4b Rated line-charging breaking current I4b A 68 68 68 68 68
Test duty 5 Rated short-circuit making current Ima up to kA 63 63 63 63 50
Test duty 6a Rated earth-fault breaking current I6a (Ie)** A 60 60 60 60 60
Test duty 6b Rated cable-charging breaking current and line- I6b A 35 35 35 35 35
charging breaking current under earth-fault conditions (HJ3 v ICL)**

– Cable-charging breaking current under IL + HJ3 v ICL A 630+50 630+50 630+50 630+50 630+50
earth-fault conditions with superimposed load current

Switching capacity of switch-disconnector/fuse combination (Standards see page 41)


Rated transfer current I4 A 1150 1150 830 830 830

Earthing switch
Rated voltage Ur kV 7.2 12 15 17.5 24
Make-proof earth- Rated short-circuit making current Ima up to kA 63 63 63 63 50
ing function of
the three-position Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
switch-disconnector
Make-proof earth- Rated short-circuit making current up to kA 63 63 63 63 50
HA41-29a eps

Ima
ing function in fee-
der of panels LS11, Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
LS31 and LS32
Earthing function Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
of the three-position
disconnector

3AH5 and 3AH6 vacuum circuit-breakers


Rated voltage Ur kV 7.2 12 15 17.5 24
Rated insulation Rated short-duration power-frequency withstand volt. Ud kV 20 28 36 38 50
level
Rated lightning impulse withstand voltage Up kV 60 75 95 95 125
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60
Rated normal current of feeders for 3AH5 Ir A 400, 630 400, 630 400, 630 400, 630 400, 630
for 3AH6 Ir A 630, 1250 630, 1250 630, 1250 630, 1250 630,1250
Rated short-time withstand current Ik (Ith)** up to kA 25 25 25 25 20
Rated short-circuit duration tk (tth)** s 3 3 3 3 3
Rated peak withstand current Ip up to kA 63 63 63 63 50
Rated short-circuit breaking current Isc up to kA 25 25 25 25 20
Rated short-circuit making current Ima up to kA 63 63 63 63 50
Electrical service life at rated normal current – – 10,000 operating cycles

* Higher values of electrical data available on request 1) Depending on the HV HRC 2) Corresponds to the max. permissible
** Indications in parenthesis acc. to previous standards fuse links cut-off current of the HV HRC fuse

Siemens HA 41.21 · 2005 5


Technical Data

Switchgear installation

Room planning

Switchgear installation
Wall-standing arrangement
– Single row
– Double row (for face-to-face

arrangement)

Room dimensions
See opposite dimension
drawings

Door dimensions
The door dimensions
depend on the
– Number of panels in a
transport unit
– Design with or without
low-voltage compartment

Switchgear fastening
• For floor openings and
fixing points of the switch-
gear, see page 40
• Foundations:
– Steel structure
– Steel-reinforced concrete

Panel dimensions
See pages 33 to 39

Weight
The weight of a panel depends
on the extent to which it is
equipped (e.g. with motor
operating mechanism, voltage
transformer). For details,
please refer to page 7.

* Switchgear height 2100 mm


if height of low-voltage
compartment 350 mm;
switchgear height 2300 mm
if height of low-voltage
compartment 550 mm
** Depending on bending radius of

6
cable

Siemens HA 41.21 · 2005


19
20
21
2100*
10
1750

Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

HA41-2392c eps
Room planning

Switchgear room

60

150

Plan view
1080

1230

850

Cable basement

1 Relief opening

4 Room height
5 Individual panel depth
90
10
10

2 Direction of pressure relief


3 Pressure relief of switchgear

6 Panel depth including end wall


7 Control aisle
>1000

>1000

³50
³50
>2400
600**

Wall-standing arrangement (side view)

Control aisle of 800 mm width (= minimum


requirements according to IEC 61 936 and
VDE 0101) permissible. When extending
or replacing panels, it might be necessary –
depending on the room dimensions – to
disassemble the respective neighbouring
panels.
8 Option: Floor cover
9 Cable
7

5
6
7

8
9

10

11

12
13

14
3

15
16
HA41-2391c eps
Switchgear room

60

150

Plan view

10 Foundation
1080

1230

850

Cable basement
90

> 2400
>1000

Free-standing arrangement (side view)

600**

11Height of cable basement corresponding to


cable bending radius
12 Wall distance
13 Side wall distance
14 Installation flush with rear wall
15 Panel width
16 End wall
17 Depth of pressure relief duct
18 Option: For free-standing arrangement
pressure relief duct for each panel for rated
short-time withstand current Ik w 20 kA
19 Option: Front cover
20 Option: Low-voltage compartment
21 Option: High end wall
7

17

18
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Technical Data

Shipping data

Transport units Individual panel Panel Panel or panel Transport unit (including packing)
for shipping (plan view) or combinations type combination for standard panels (without pressure relief duct)
thereof for standard switchgear
Width Net Width Height Depth Volume Gross
(without pressure relief duct)
T2 B1 weight 1) B2 T2 weight 1)
T1 1 mm approx. kg m m m m3 approx. kg
3 with- / with with- / with with- / with with- / with
out out out out
LVC*/LVC* LVC*/LVC* LVC*/LVC* LVC*/LVC*
HA41-2284b eps

2
B1
B2

Transport of individual panels


Ring-main panel RK 375 190 / 250 1.08 1.95 / 2.3 1.40 2.95 / 3.48 250 / 310
RK1 500 210 / 270 1.08 270 / 330
With individual panel
Ring-main panel for panel combinations RK-U 375 260 / 320 1.08 320 / 380
Cable panel K, K-E 375 190 / 250 1.08 250 / 310
K1, K1-E 500 190 / 250 1.08 250 / 310
T2
1 Transformer panel TR 375 210 / 270 1.08 270 / 330
T1 TR1 500 230 / 290 1.08 290 / 350
Circuit-breaker panel 630 A LS1, -U 750 340 / 400 1.08 410 / 460
LS11, -U 750 340 / 400 1.08 410 / 460
3 Circuit-breaker panel 1250 A
– For connection of max. 2 cables LS31 750 400 / 460 1.08 470 / 520
2
B1

– For connection of 3 cables LS32 875 460 / 520 1.08 530 / 580
Bus sectionalizer panel 1250 A LT31 750 450 / 510 1.08 520 / 570
4 Bus sectionalizer panel 630 A LT10 750 320 / 380 1.08 390 / 440
with vacuum circuit-breaker LT11 750 320 / 380 1.08 390 / 440
B2
B3

2
B1

5 Bus sectionalizer panel with LT2 750 250 / 310 1.08 320 / 370
1 three-position switch-disconnector LT2-W 750 310 / 370 1.08 380 / 430
Bus sectionalizer panel with LT22 750 290 / 350 1.08 360 / 410
HA41-2285c eps

2 2 three-position switch-disconnectors LT22-W 750 350 / 410 1.08 420 / 470


B1

Billing metering panel ME1.... 750 270 / 330 1.08 340 / 390
ME1-H 750 330 / 390 1.08 400 / 450
With combinations of different Busbar ME3 375 210 / 270 1.08 270 / 330
individual panels voltage metering panel ME31-F 500 270 / 330 1.08 330 / 390
Bus riser without transformers HF 375 170 / 230 1.08 230 / 290
panel with transformers HF 375 260 / 320 1.08 320 / 380
1 T1 = Depth of individual panel Busbar SE1 375 190 / 250 1.08 250 / 310
earthing panel SE2 500 270 / 330 1.08 330 / 390
2 Individual panel
dimension B1 x T1
For individual panel Panel Additional
3 Transport unit, width weight
dimension B2 x T2 mm approx. kg
4 B3 = Overall width of Pressure relief duct 375 30
combination of different for free-standing arrangement 500 40
individual panels of switchgear
750 60
5 B2 = Width of the
transport unit 875 70

Transport of combinations of different individual panels


Transport unit: Overall width B3 B2 T2
–Standard: As individual panels arranged On request 0.70 1.95 / 2.3 1.40 1.91 / 2.25
side by side and not screwed together
–Option: As multi-panel transport unit, w 875 mm 1.08 1.95 / 2.3 1.40 2.95 / 3.48 2) + 70 **
panels screwed together w 1000 mm *** 1.20 1.95 / 2.3 1.40 3.28 / 3.86 2) + 80 **
w 1500 mm 1.78 1.95 / 2.3 1.40 4.64 / 5.47 2) + 100 **
Standard packing for:
– Truck w 2125 mm 2.33 1.95 / 2.3 1.40 6.36 / 7.50 2) + 120 **
– Seaworthy crate, air freight
Container packing w 875 mm 1.10 1.95 / 2.3 1.26 2.70 / 3.19 2) + 80 **
w 2000 mm 2.20 1.95 / 2.3 1.26 5.41 / 6.38 2) + 120 **

Packing, transport (examples)


Packing Version For supply Transport
Panels mounted on wooden floor Open In Europe Rail, truck
and covered with PE protection sheeting
For container Overseas Ship + truck

1) The net weight and the gross 2) Sum of the * Low-voltage compartment, ** Packing
weight depend on the extent net weights of 350 mm high, weight approx. weight
to which it is equipped individual panels 60 kg depending on the *** w 1125 mm
(e.g. current transformers, motor panel type and on the extent on request
operating mechanisms) and are to which it is equipped, or
therefore given as mean value optionally 550 mm high

Siemens HA 41.21 · 2005 7


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Product range overview

Panel designation Panel Panel


Standard panels type width
R-HA41-073 eps

R-HA41-076 eps

Column No.
Ring-main as RK 375 mm
panel 1) feeder RK1 500 mm
as RK-U 375 mm
transfer
Ring-main panel Circuit-breaker panel Transformer as TR 375 mm
type RK type LS1 panel 1) feeder TR1 500 mm
Cable panel as K 375 mm
feeder K1 500 mm
Cable panel 1) 2)
R-HA41-074 eps

R-HA41-077 eps

as K-E 375 mm
feeder K1-E 500 mm
Circuit-breaker panel 630 A 1) as LS1 750 mm
with 3AH5 3) feeder
as LS1-U 750 mm
transfer
Circuit-breaker panel 630 A as LS11 750 mm
with 3AH6 3) feeder
as LS11-U 750 mm
transfer
Circuit-breaker panel 1250 A as LS31 750 mm
with 3AH6 3) feeder LS32 875 mm
as LS31-U 750 mm
transfer
Bus sectionalizer panel 630 A 1) LT10 750 mm
with 3AH5 3), for panel type HF
Bus sectionalizer panel 630 A LT11 750 mm
with 3AH6 3), for panel type HF
Bus sectionalizer panel 1250 A LT31 750 mm
with 3AH6 3), for panel type HF
Transformer panel Circuit-breaker panel Bus sectionalizer panel 630 A 1) 4)
LT2 750 mm
type TR type LS11 LT2-W 750 mm
5)
LT22 750 mm
LT22-W 750 mm
R-HA41-075 eps

R-HA41-078 eps

Billing metering Standard ME1 750 mm


panel ME1-S 750 mm
as ME1-K 750 mm
end panel ME1-KS 750 mm
Billing metering panel ME1-H 750 mm
for additional current transformer
Busbar voltage metering ME3 375 mm
panel 1) ME31-F 500 mm
Busbar earthing SE1 375 mm
panel 1)
6)
SE2 500 mm

Bus riser panel HF 375 mm

1) Metal-clad
2) With additional make-proof earthing switch
3) Type designation of vacuum circuit-breaker
4) With 1 three-position switch-disconnector
Cable panel Billing metering panel
5) With 2 three-position switch-disconnectors
type K type ME1
6) With voltage transformer for busbar metering

8 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Equipment features

h 2)
• Basic equipment ac 1)
ch Ce c h
Additional equipment (option), it N it
° further additional itc
h sw O+
2
sw
er cu
um
ov
er
2) w ing 2N it ion k a c
equipment on request 1 ) s 2) th 2) s ea v t
h io
n 1) ar EN 1 ) po br 6 en er
– Not available itc sit h o f e OP tch e e- u it- 3 AH1 )2 ) h rtm eak
sw o it c ro an d i r c f itc a r
n -p
sw ke-p ED sw of t
h cir “ o itch sw com
p t-b
io ee 2) ui
sit nt thr ical ion a S tion ch. um SED sw 1 ) ng e irc ) 2)
o e r it i u i l c 1)
e-p r a ce t m r m O
fo ect os nd . CL -pos . me een va
c
L O tion tch rth /cab m H
3
h
l r r . i i a u tc
hr
e ve p pa to el e-p a :f ee erat etw H.. “C os sw of e ion r u 3A wi r
rt co d in m ca ote hre itch ING thr n -p t tte ac n s to
fo ent e co di t r p l b 3A itio ree tion -pro nec shu or v se i ion
k l in m r
re fo n s RT
w H fo r o e
an nd
s h i f t ica
sm rtm r lo
c
in
a e to po t os ake con t or sm elea osi ind
a ni a e r m e rvic for tion itio EA nism mo er p 2 ) a tch hed e-p m e e n ni r -p lt
ec
h p v
co et te eas r-se ) a os d a r
fo rea h1
k ) i rt re or n th tm cha ed ree -fau ent
m e co ent
m s l NO ic -p an ch sw ea r th ut f i r at h
g l a ck he a t re y-fo (1 ind ree ctor me itch it-b itc for ith f o -o w pa m
e
p er or t arth ipm 7)
r h ce w o f
tin ab
rtm b nic u n a d
it c i th e
. n ing s w rc u s c re w u t c k
in
d
c om ng
i t.-o e re qu 4 ) g le
era
o r c pa able ge s
sh
a l re
sw erv h f con rat ote n ci ition evi ake ck-o g lo w ge rat s c. evic it o ry e ver a tin cab
o p f m c t a a ic g r -s itc is p e i s d r e lo in o n ta p e a d cu d a o he d
l ck co as ol e n in o w -d o em ock -po g b th ti ol o e g cir con or c l te s
ua lo le il -v leas cha nall dy-f x. s itch tor lr rl e kin it- sin -ear pec
g -v or leas ckin ort- ne un mp
an nter ab ra w e g a o ca te re Loc ircu o s w ot Se Fl
o
Pa o
M I C C- Lo Re M Si re Au Sw M Lo In th c Cl De In Lo M Re Lo Sh – – – M cla

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Panel type

• • – • • – – – – – – RK
° ° ° ° ° ° ° ° ° ° ° ° ° ° RK1
– – – – – – – – – RK-U
• • •
° ° ° ° ° ° ° ° – ° • ° –

– – – – – – TR
• • • •
° ° ° ° ° ° ° •
° ° – ° ° ° ° TR1
• – • • • – – – – – – – – – – – – – K
° ° ° ° ° ° ° K1
– • – • • – – – – – – – K-E
° ° ° ° ° ° ° ° ° ° ° ° ° K1-E
• • – • • – – – LS1
° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° °
– – – – – LS1-U
• • •
° ° ° ° ° ° ° ° ° ° ° ° – ° • ° –
6) LS11
– –
°)
• • • • 5 ) 6
° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° °
– – – – LS11-U
• • •
° ° ° ° ° ° ° ° ° ° ° ° ° – ° • ° –

• )
5 6 LS31
• • – • • • – ) ) 6
° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° ° LS32
– – – – LS31-U
• • •
° ° ° ° ° ° • •
° ° ° ° ° – ° • ° –

– – – – LT10
° – ° • –
• • • 7
° ° ° ° ° ° ° ° ° °) ° ° °
– – – – LT11
° – ° • –
• • • • 7
° ° ° ° ° ° ° ° °) ° ° °
– – – – LT31
• • •
° ° ° ° ° ° • •
° ° 7) ° ° ° – ° • ° –

– – – – – – – – LT2
• • • •
° ° ° ° ° ° ° ° – ° • ° –
LT2-W
– – – – – – – – – LT22
• • •
° ° ° ° ° ° ° ° – ° • ° –
LT22-W
– – • – • – – – – – – – – – – – – – – – ME1
° ° ° • ° ME1-S
– – • • • – – – – – – – – – – – – – – ME1-K
° ° ° ° ° ° ME1-KS
– – • – • – – – – – – – – – – – – – – – ME1-H
° ° ° • °
– – ME3
– – – – – – – –
• • •
° ° ° ° ° ° ° ° ° – ° • ° –
ME31-F
– – – – – – – – – – – – SE1
• • •
° ° ° ° ° – ° • ° –

– – – – – – – – SE2
• • •
° ° ° ° – ° – –
° – ° • ° –

– – • – • – – – – – – – – – – – – – – – – HF
° ° • °

1) Three-position switch as three-position switch-disconnector 5) Not to be applied for versions with separate feeder earthing switch in
2) Three-position switch as three-position disconnector in panel panel types LS11, LS31 and LS32
types LS31, LS31-U, LS32 and LT31 6) Inspection window is a standard equipment in panel types LS11, LS31
3) Type designation of the vacuum circuit-breaker and LS32 for versions with separate earthing switch
4) In special cases, deeper floor cover for panels 7) Panel heating: wired on terminal (standard).
with cable feeder required Option: version with thermostat.

Siemens HA 41.21 · 2005 9


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Ring-main panels

Ring-main panels Ring-main panel 4)


as feeder panels as transfer panel for attachment
to panel types ME1... or ME1-H 3AH5 vacuum
Standard: circuit-breaker
Option Option transfer

HA41-2350a eps
HA41-2348b eps

to the 5)
right
Option *
Option: 3AH6 vacuum
Option * Option transfer circuit-breaker
to the
3) 3)
either-or

left
Option *
Option
Three-position
1)
switch-disconnector

Capacitive
Type RK Type RK-U voltage detection
375 mm wide 375 mm wide system

1)

Cable-type
current transformer
For other panel combinations e.g. 4MC703 . . .
Option Option
HA41-2465b eps

With 2)
Option Option 3AH5
Block-type
HA41-2349b eps

6) 8) vacuum
current transformer
either-or

Option Option circuit-


4MA,
4) breaker,
Option cast-resin insulated
3) 3) fixed-

either-or
mounted
2) Option Option 3)
P2 P2
either-or

Option Option Three-phase


P1 2) 2) P1 current transformer
4MC63 . . .
1) 3) Option ** Option
6) 6) 7) 6)

Voltage transformer
Type RK1 either: Type LT10 Type RK-U The ring-main transfer panel e.g. 4MR, 1-pole,
500 mm wide Version with 750 mm wide 375 mm wide RK-U can be attached on the cast-resin insulated
transformers Bus sectionalizer panel type LT10 with left or right of the bus
7)
ring-main transfer panel type RK-U sectionalizer panel LT10

Option Option Voltage transformer


HA41-2466b eps

With e.g. 4MR, 2-pole,


Option 3AH6 cast-resin insulated
HA41-2351b eps

vacuum
Option Option circuit- 8)
Option
breaker,
3) 3) with-
On request:
either-or

drawable
voltage transformer
Option
either-or

5)
e.g. 4MR, 2-pole,
Option P2 cast-resin insulated,
Option 2) P1 only up to 17.5 kV
1) Option
6) 7)

Cable (not
Type RK1 or: Type LT11 Type RK-U included in the
500 mm wide Version with 750 mm wide 375 mm wide scope of supply)
connection
HA41-2390c eps

Bus sectionalizer panel type LT11 with


fittings ring-main transfer panel type RK-U
(non-interchangeable arrangement)
2nd cable (not
included in the
scope of supply)

P1 and P2
are terminal Surge
* On request up to 12 kV ** On request: designations arrester
only 1 set of voltage of the current
transformers possible transformer

10 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Transformer and cable panels

Transformer panels Cable panels Cable panels


as feeder panels as feeder panels, 630 A as feeder panels, 630 A, with
make-proof earthing switch Three-position
switch-disconnector
Option Option Option
HA41-2353a eps

HA41-2356d eps

HA41-2358c eps
Option ** Option **
HV HRC fuse
Option Option ** Option

either-or

either-or
3)

optional
Option ** Option ** Capacitive
Option * Option Option voltage detection
system
1) 1) 1)

Earthing
switch
Type TR Type K Type K-E
375 mm wide 375 mm wide 375 mm wide

Make-proof
earthing switch

as feeder panels as feeder panels Fixed


630 A and 1250 A 630 A and 1250 A earthing point

1)
Option Option Option Option Option
HA41-2357d eps

HA41-2359c eps
HA41-2354a eps

Cable-type

either-or
either-or

current transformer,
e.g. 4MC703 . . .
Option Option Option Option
2)
2) 2)
Block-type

either-or
Option * Option Option Option current transformer
4MA,
1) 1) 1) 3) cast-resin insulated

3)

Type TR1 Type K1 either: Type K1-E either: Three-phase


500 mm wide 500 mm wide Version with 500 mm wide Version with current transformer
transformers transformers 4MC63 . . .
Option
Option Option
3)
HA41-2444b eps

HA41-2445c eps

Voltage transformer
Option e.g. 4MR, 1-pole,
Option **
cast-resin insulated
Option
either-or

either-or

Option Option
Option Option Cable (not
included in the
1) scope of supply)
1)

Type K1 or: Type K1-E or: 2nd cable (not


500 mm wide Version with 500 mm wide Version with included in the
connection connection scope of supply)
fittings fittings
HA41-2390c eps

Surge
arrester

* Current transformer
located partly
underneath the panel
** On request up to 12 kV

Siemens HA 41.21 · 2005 11


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Circuit-breaker panels

Circuit-breaker panels 630 A Circuit-breaker panels 1250 A 4)


as feeder panels as feeder panels
3AH5 vacuum
Option Option circuit-breaker
for

HA41-2467d eps
Option Option connection
6) 7)

either-or
HA41-2360c eps

of max. 5)
Option ** 2 cables

either-or
Option
4) 3AH6 vacuum
Option Option 3) circuit-breaker

3) Option 5) Option
either-or

Option 2)
P1 Option Option Three-position

either-or
either-or
switch-disconnector
P2 2) Option
1) 6) Option Option

1)
Type LS1 With 3AH5 vacuum circuit-breaker, Type LS31 With 3AH6 Three-position
750 mm wide fixed-mounted 750 mm wide vacuum circuit-breaker, withdrawable disconnector

Option Option Option Option


for 1)
HA41-2362c eps

HA41-2468b eps

connection
of max. Cable-type
either-or

either-or
current transformer
Option Option ** Option Option ** 3 cables
e.g. 4MC703 . . .
(4 cables *)
3) 3)
2)
Option 5) Option Option 5) Option Option Block-type
current transformer
2) 2) 1)
4MA,
either-or

cast-resin insulated
either-or

either-or
either-or

Option Option
6) Option Option 6) Option 3)

1) 1) Three-phase
Type LS11 With 3AH6 Type LS32 With 3AH6 current transformer
750 mm wide vacuum circuit-breaker, 875 mm wide vacuum circuit-breaker, 4MC63 . . .
withdrawable withdrawable 6)

as transfer panels for attachment as transfer panel for attachment Voltage transformer
to panel types ME1... or ME1-H to panel types ME1... or ME1-H e.g. 4MR, 1-pole,
cast-resin insulated
Option Option Standard: Option Option Transfer 7)
transfer
HA41-2361d eps

HA41-2364g eps

possible
3) to the 3) only to
right Voltage transformer
4) the right
e.g. 4MR, 2-pole,
Option Option Option: Option B Option
cast-resin insulated
P1 transfer P1
2) to the 2) 5)
P2 P2
either-or

left
Option Option
6) 7) 6) Cable (not
included in the
scope of supply)

Type LS1-U With 3AH5 Type LS31-U With 3AH6


750 mm wide vacuum circuit-breaker, fixed-mounted 750 mm wide vacuum circuit-breaker, withdrawable Addit. cables (not
included in the
scope of supply)

Option Option Transfer


HA41-2363e eps

possible
3) only to Surge arrester
the right
Option B Option
P1
2) 5) * On request Capacitive voltage
P2 detection system
either-or

Option
** Standard: Feeder earthing
via the 3AH6 vacuum circuit-breaker
6)
with interlocks (without earthing switch)
Make-proof
B Mounting position of the current
earthing switch
transformer with terminal P1 at the top only
HA41-2390c eps

Type LS11-U With 3AH6 P1 and P2 are terminal designations


750 mm wide vacuum circuit-breaker, withdrawable Fixed
of the current transformer
earthing point

12 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Bus sectionalizer panels

Bus sectionalizer panels 630 A Bus sectionalizer panels 630 A 4)


in combination with bus riser panel with 1 three-position switch-disconnector
3AH5 vacuum
Option Option circuit-breaker
With
HA41-2367c eps

3AH5 Option Option


vacuum 5)

HA41-2371a eps
Option circuit-
Panel type HF attached

Option
breaker, 3AH6 vacuum
4)
3) fixed- circuit-breaker
mounted
Option Option
on the left

P2 P1
P1 2) 2) P2
either-or

Three-position
Option Option switch-disconnector
6) 7) 6) 7)

Type HF Type LT10 Type LT2 corresponds to type RK-U Three-position


375 mm 750 mm wide 750 mm wide with type HF disconnector

Option Option Option


With 2)
HA41-2368c eps

3AH5 Option
vacuum Block-type
HA41-2372c eps

circuit- current transformer


Option Option Option 4MA,
Panel type HF attached

breaker,
4) cast-resin insulated
3) fixed- Option
mounted
Option Option 3) Option 3)
P1 P2 P2
on the right

2) 2) 2) Three-phase
P2 P1 P1
either-or

current transformer
Option Option Option 4MC63 . . .
6) 7) 6) 7) 6) 7) 6)

Type LT10 Type HF Type LT2-W corresponds to type RK-U Voltage transformer
750 mm wide 375 mm wide 750 mm wide with type HF e.g. 4MR, 1-pole,
cast-resin insulated
Option 7)
With
Option 3AH6
with 2 three-position switch-disconnectors Voltage transformer
HA41-2369e eps

vacuum
e.g. 4MR, 2-pole,
Option circuit-
cast-resin insulated
be attached on the right

Option Option
Panel type HF can only

breaker
Option
HA41-2373a eps

with-
drawable
3) 5) Option Capacitive
P2 Option voltage detection
Option 2) system
P1
Option
HA41-2390c eps

6) 7)
Fixed
earthing point
Type LT11 Type HF
750 mm wide 375 mm wide

Type LT22 corresponds to type RK-U


Bus sectionalizer panel 1250 A 750 mm wide with type RK-U
in combination with bus riser panel
Option Option
With
Option 3AH6 Option
vacuum
HA41-2365d eps

HA41-2374e eps

Option circuit- Option


be attached on the right

breaker
Panel type HF can only

Option with- Option 3)


either-or

drawable
3) 5) Option 3) Option
P2 P2
Option 2) 2) P1
P1
Option Option
6) 7) 6) 7) P1 and P2
are terminal
designations
Type LT31 Type HF Type LT22-W corresponds to type RK-U of the current
750 mm wide 375 mm wide 750 mm wide with type RK-U transformer

Siemens HA 41.21 · 2005 13


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range

Billing metering panels

Billing metering panels Billing metering panels Billing metering panels


630 A and 1250 A 630 A and 1250 A 630 A and 1250 A Capacitive
Standard for busbar connection for additional transformer voltage detection
Option system

HA41-2450a eps
2)
Option Option Option
2) 2)

HA41-2454 eps
HA41-2446 eps

Option

either-or
Block-type
current transformer
Option P2 Option P2 Option
either-or *

4MA,
2) P1 P2 2)
P1 P1 cast-resin insulated
Option 2)

Option *

either-or
2)
On request:
Option
Voltage transformer,
e.g. 4MR, 1-pole,
Scheme 1 Scheme 1 Scheme 1 cast-resin insulated
with HV HRC fuse
Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **:
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right

Option
Voltage transformer,
HA41-2451a eps

2) e.g. 4MR,
Option Option Option
1- or 2-pole,
HA41-2455 eps
HA41-2447 eps

cast-resin insulated

either-or
Option

Option Option Option


either-or *

P1 P2 Fixed
Option 2) earthing point
P2 P2

HA41-2390c eps
Option *

either-or
2) 2)
P1 2) P1
Fixed earthing
Option point for
busbar earthing
Scheme 2 *** Scheme 2 *** Scheme 2 ***
Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **:
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right

Option
HA41-2452a eps

2)
Option Option Option
HA41-2448 eps

HA41-2456 eps

Option
either-or

Option Option Option


either-or *

P2 P1
Option 2)
P1 P1
Option *
either-or

2) 2)
P2 2) P2
Option

Scheme 3 Scheme 3 Scheme 3

Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **:
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right

Option
HA41-2453a eps

2)
Option Option Option
HA41-2457 eps
HA41-2449 eps

either-or

Option P1 and P2
are terminal
Option P1 Option P1 Option designations
either-or *

2) P2 P1 2) of the current
P2 P2
Option 2) transformer

Option *
either-or

2) * On request
Option ** Option:
Transfer
to the left
Scheme 4 *** Scheme 4 *** Scheme 4 ***
*** Transformer
Type ME1 Standard **: Type ME1-S Standard **: Type ME1-H Standard **: terminals
750 mm wide Transfer to the right 750 mm wide Transfer to the right 750 mm wide Transfer to the right interchanged

14 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Product Range
Billing metering panels, busbar voltage metering panels,
busbar earthing panels and bus riser panels

Billing metering panels Billing metering panels Busbar voltage Bus riser panels
630 A and 1250 A ** 630 A and 1250 A ** metering panels 630 A and 1250 A
for cable connection for busbar connection Three-position
Option
switch-disconnector

HA41-2458 eps
Option HA41-2379a eps Option Option
HA41-2375a eps

HA41-2383a eps
Option *
Make-proof
Option P2 Option P2 earthing switch
2) 2)
P1 P1
Option
P2
Make-proof
P1 2)
earthing switch
Option

Scheme 1 Scheme 1 Scheme 1 Earthing switch


Type ME1-K Standard B): Type ME1-KS as right or left Type ME3 Type HF BB)
750 mm wide Transfer to the right 750 mm wide end panel 375 mm wide 375 mm wide 2)
Block-type
Option current transformer

HA41-2459 eps
4MA,
Option Option Option
cast-resin insulated
HA41-2384a eps
HA41-2380a eps
HA41-2376a eps

Option *

Option Option Voltage transformer,


e.g. 4MR,
Option Option 1- or 2-pole,
P2 P2 (on
request) cast-resin insulated
2) 2)
P1 P1

Transformer Transformer Option


terminals terminals P2
Voltage transformer,
interchanged Scheme 2 interchanged Scheme 2 P1 2) Scheme 2 e.g. 4MR, 1-pole
cast-resin insulated
Type ME1-K Standard B): Type ME1-KS as right or left Type ME31-F Type HF BB)
750 mm wide Transfer to the right 750 mm wide end panel 500 mm wide 375 mm wide

Busbar HV HRC fuse


earthing panels Option
HA41-2460 eps

Option Option
HA41-2385a eps

Capacitive
HA41-2381a eps
HA41-2377a eps

voltage detection
Option * system

Option Option HA41-2390c eps

Option Fixed
P1 P1 earthing point
2) 2)
P2 P2

Option
P1
P1 and P2
Scheme 3 Scheme 3 P2 2) Scheme 3 are terminal
designations
Type ME1-K Standard B): Type ME1-KS as right or left Type SE1 Type HF BB)
of the current
750 mm wide Transfer to the right 750 mm wide end panel 375 mm wide 375 mm wide
transformer
Option
HA41-2461 eps

Option Option Option * On request


HA41-2378a eps

HA41-2382a eps

HA41-2386a eps

up to 12 kV
Option * ** Connection
for 3 cables
Option P1 Option P1
possible
2) 2)
P2 P2 B Option:
Option Transfer
P1
to the left
P2 2)
BB For
Transformer Transformer Option attachment
terminals terminals to left or
interchanged Scheme 4 interchanged Scheme 4 Scheme 4 right
ring-main
Type ME1-K Standard B): Type ME1-KS as right or left Type SE2 Type HF BB) panels
750 mm wide Transfer to the right 750 mm wide end panel 500 mm wide 375 mm wide type RK-U

Siemens HA 41.21 · 2005 15


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Design

Panel design (examples)

Ring-main panel as feeder Transformer panel as feeder

HA41-2393d eps

HA41-2394d eps
1 60 1 60
2 2 2 2
3 23 23
4 24 24
5 11 19 5 11 19
6 12 58 6 12 58
7 13 7 13
26
8 14 25 8 14
15 15 27
9 9
10 16 18 10 16 18
17 17
27
18 18
59 57 59
20 20 57
21 21 34 34
61 28 35 35
61 31
29 31 33
22
22 32 29
33
61
56 22 22
23
30
30

Type RK Section Type TR Section

Billing metering panel Legend for pages 16 and 17


1 Option: Low-voltage compartment
HA41-2395e eps

2 Niche for optional low-voltage equipment,


cover can be unscrewed
3 Option: CAPDIS voltage detection system
1 60 4 Option: Short-circuit /earth-fault indicator
2 5 Option: Ready-for-service indicator
37
for switching device
23
2 24 6 Switch position indication for load-break
function “CLOSED – OPEN“
10 33 7 Switch position indication for earthing
function “OPEN – EARTHED“
38 8 Feeder designation label
38
9 Mimic diagram
8
16 10 Option: Sockets for capacitive voltage detection system
57 (depending on arrangement)
9 11 Option: Momentary-contact rotary control switch
33 33 “CLOSED – OPEN“ for motor operating mechanism
with local-remote switch
for three-position switch-disconnector

40 12 Option: Locking device for three-position


40
switch-disconnector
13 Pressure relief device for switching device
65 14 Manual operation for the mechanism of
the earthing function
15 Manual operation for the mechanism of
39 the load-break function
39
16 Rating and type plate
17 Gas-insulated vessel for switching device
30
18 Interlocking of the cable compartment cover

Type ME1 Section 19 Bushing-type insulator for busbar


20 Bushing-type insulator for feeder

16 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Design

Panel design (examples)

Circuit-breaker panel (with 3AH5 vacuum circuit-breaker) 21 Insulating sleeve (e.g. for Up > 95 kV)
22 Cable bracket with clamps (option) for fastening cables

HA41-2396e eps
23 Busbar
24 Insulating cap * on busbar
25 Spring-operated mechanism for
1 60 three-position switch-disconnector
2 2 26 Spring-operated/stored-energy mechanism for
51 23 three-position switch-disconnector
24 27 Three-position switch-disconnector
5
51
45 28 Cable connection
11 19
46
12 58 29 Cable compartment cover
44 13 30 Earthing connection (for location see dimension drawings)
8 14 25
47 6 31 Earthing switch for cable connection
43
10 7 32 Inspection window
48 15 64
16 33 Post insulator
41
17 34 Insulating sleeve
64 57 35 Option: HV HRC fuse link
59
50 36 Option only for panel types LS11 ... and LT11 ...:
49
20 Logical mechanical interlocking between circuit-breaker
9 20
“OPEN“ and three-position switch-disconnector and
21 21 locking device for three-position switch-disconnector
37 Option: ME1- fuse box for voltage transformer
28
61 38 Cover, screwed on
29
39 4MR voltage transformer
61 40 4MA7 block-type current transformer
22
22 Vacuum circuit-breaker:
41 3AH5 vacuum circuit-breaker, fixed-mounted

30 42 3AH6 vacuum circuit-breaker, withdrawable


43 Operating mechanism box
Type LS1 Section 44 Manual operation
– for closing with manual operating mechanism
– for emergency operation with motor operating
mechanism
Circuit-breaker panel (with 3AH6 vacuum circuit-breaker) 45 Mechanical “OFF“ pushbutton
46 Mechanical “ON“ pushbutton
HA41-2397d eps

(not supplied with spring-operated mechanism)


47 “Spring charged“ indicator
1 48 Operating cycle counter
60
55 49 Switch position indication
2
3 23 50 Option: Three-phase current transformer 4MC63 53
2 24 51 Option: Overcurrent-time protection relay
52 52 SIPROTEC easy 7SJ45
11 19
5 36 58 52 Option: Multifunction protection relay SIPROTEC 4 7SJ62
6 17 53 Cover * for screwed gland of cable connections
7 25
14
8 27 54 Insulating cap * on bushing-type insulator
15
9 55 Option: Wiring duct, removable,
10 16 64
for control cables and/or bus wires
54 13 50
20 56 Logical mechanical interlocking for three-position switch
64
56 57 57 Earthing busbar
59
50 54
36 58 Metal compartmentalization of busbar compartment
43
43 59 Metal compartmentalization of cable
44 connection compartment
29
45 60 Busbar compartment cover for panel extension
53
46 42
33 61 Cable sealing end (not included in scope of supply)
47
62 Option: Feeder earthing via make-proof earthing switch
48 62
33 63 or feeder earthing via vacuum circuit-breaker (= locking
49 63 device for feeder earthed when circuit-breaker “CLOSED“)
61
61 64 Interlocking of cable compartment cover in
22 circuit-breaker panels
56 30 65 Cover for transformer connection compartment

Type LS11 Section


* For example for Up W 95 kV, Ur W 15 kV

Siemens HA 41.21 · 2005 17


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

3AH5 and 3AH6 vacuum circuit-breakers


Common features 3AH5 vacuum circuit-
• Circuit-breakers with breaker
2
vacuum interrupters • Metal-enclosed
• Stored-energy spring- • Up to 630 A
operated mechanism for • Pole parts with vacuum
10,000 operating cycles interrupters fixed-mounted
• Maintenance-free for in- in hermetically welded, 3
1
door installation according gas-filled switchgear vessel
to IEC 60 694 / • System-conforming use
VDE 0670 -1000, sub- with three-position switch
sequently IEC 62 271-1* in gas-insulated switchgear 4

R-HA41-066 eps
• Individual secondary vessel
equipment • Operating mechanism
arranged outside the
Switching duties and switchgear vessel and
operating mechanisms behind the control board
5
The switching duties of the • Air-insulated primary 3AH5
vacuum circuit-breaker are terminals
vacuum circuit-breaker
dependent, among other (operating mechanism box open)
factors, on its type of oper- Installation in metal-clad 6
ating mechanism. Three panels
operating mechanism 1 Operating mechanism box 4 Spring-operated mechanism of
versions are available: • Feeder panels type LS1,
2 Bushing-type insulator for busbar three-position switch-disconnector
panel width 750 mm
• Motor operating stored- 3 Switchgear vessel, gas-filled, with 5 Bushing-type insulator for feeder
energy mechanism • Transfer panels type LS1-U, 3AH5 vacuum circuit-breaker and 6 Location for three-phase current
– For auto-reclosure (K), panel width 750 mm three-position switch-disconnector transformer (option)
– For synchronization and • Bus sectionalizer panels
rapid load transfer (U) type LT10 (for adjacent bus
• Manual operating stored- riser panel type HF),
energy mechanism panel width 750 mm 11
– For auto-reclosure (K)
3AH6 vacuum circuit-
• Manual spring-operated breaker
mechanism 8
(= spring CLOSED, • Withdrawable 1) lateral-
stored-energy OPEN) mechanism circuit-breaker, 7
– Not for auto-reclosure (K) air-insulated
– For normal closing and • Up to 1250 A
– For storage of one
• Circuit-breaker poles
opening
arranged one behind the
Trip-free mechanism other 10
• Operating mechanism in
• The vacuum circuit-
breakers are fitted with a separate box behind lower
trip-free mechanism panel cover
9
R-HA41-068 eps

according to • Logical mechanical inter-


IEC 62 271-100 / locking between 3AH6
VDE 0671-100 vacuum circuit-breaker and
three-position switch
• Installation in:
– Feeder panel type LS11,
* Standards see page 41 panel width 750 mm
– Transfer panel type LS11-U,
1) Withdrawable after loosening 3AH6
the respective contact panel width 750 mm
– Bus sectionalizer panels vacuum circuit-breaker
connections and fixing bolts
type LT11 and LT31 (for
adjacent bus riser panel 7 Operating mechanism box 11 Logical mechanical interlocking
with control elements between vacuum circuit-breaker
Abbreviations for switching type HF), panel width and three-position switch
duties and applications: 750 mm 8 Circuit-breaker poles with
vacuum interrupters (prevents switching of all three
U = Synchronization and – Feeder panel type LS31 switch positions).
rapid load transfer (for connection of 9 Truck Option for 630 A panel types with:
(make time w 90 ms) max. 2 cables), 10 Locking device (standard 3AH5: LS1, LS1-U, LT10
K = Auto-reclosure panel width 750 mm when earthing the feeder with 3AH6: LS11, LS11-U, LT11
closed 3AH6 vacuum circuit-breaker) Standard for 1250 A panel types with:
– Feeder panel type LS32 for the 3AH6 vacuum circuit-breaker 3AH6: LS31, LS31-U,
For further details, please refer (for connection of 3 cables; in switch position “CLOSED” LS32 and LT31.
also to Catalog HG 11.11 4 cables on request), with three-position switch
“3AH Vacuum Circuit-Breakers“ panel width 875 mm in switch position “EARTHED“

18 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

3AH5 and 3AH6 vacuum circuit-breakers


Operating mechanism
functions

Motor operating mechanism 1)


(M1 *)
In the case of the motor operat-
ing mechanism, the closing 1
spring is charged by means of 2 6
a motor and latched in the
charged position (the “spring 7
charged” indication is visible). 3
Closing is effected either by
means of an ON pushbutton or 4
a closing solenoid. The closing
spring is recharged automati- 5 8
cally (for auto-reclosure).
R-HA41-080 eps

Operating mechanism
elements of the
Manual operating stored-
3AH5 vacuum circuit-breaker
energy mechanism
The closing spring is charged
by means of the supplied hand Operating mechanism elements
crank until latching of the 1 Gear
closing latch is indicated 2 Coupling on gear for operation
(= “spring charged” indication). 1 with hand crank
– For closing with manual
Subsequently the vacuum 2 spring-operated mechanism
6
circuit-breaker can be closed – For charging the closing
either manually or electrically. 3 spring with stored-energy
The closing spring can be re- 7 mechanism
charged manually. The “possibil- 4 3 Closing spring
ity to close” is thus stored once 4 Motor (M1 *)
more (for auto-reclosure). 5 “Closing spring charged” indicator
5 8
6 Circuit-breaker “OPEN”
Manual spring-operated
mechanism 7 Circuit-breaker “CLOSED”
(= spring CLOSED, 8 Operating rod
stored-energy OPEN)
The closing spring of the vacuum
circuit-breaker is charged by
means of the supplied hand
R-HA41-069 eps

crank until the vacuum circuit-


breaker closes. Subsequently Operating mechanism
elements of the
either manual or electrical open- 3AH6 vacuum circuit-breaker
ing is possible.
Vacuum circuit-breakers with
spring-operated mechanism are Differences between the vacuum circuit-breakers depending on the operating mechanism version
not suitable for auto-reclosure. Operating Motor operating Manual operating Manual spring-operated
mechanism version stored-energy mechanism stored-energy mechanism mechanism
Typical uses Utility substations Classic transfer substations Simple utility substations
and industrial plants and substations without (circuit-breaker as
auxiliary voltage supply transformer switch)
1) Motor rating at
24 V to 220 V DC: 350 W Mechanism Stored-energy CLOSED, Stored-energy CLOSED, Spring CLOSED,
110 V and 220 V AC: 400 VA function stored-energy OPEN stored-energy OPEN stored-energy OPEN
2) With closing solenoid Mechanism With motor 1), manual With hand With hand
* Equipment code operation (emergency) operation crank crank
at the panel including
anti-pumping
Abbreviations:
Closing the Electrically 2) or Mechanically at the panel Mechanically at the panel
O = OPEN operation
vacuum mechanically at the panel with pushbutton, option: with hand crank
CO = CLOSE operation with subse- circuit-breaker with pushbutton electrically 2) (charging process)
quent OPEN operation at the
shortest internal close-open time Closing solenoid, Always provided, with Option Without
of the vacuum circuit-breaker e.g. for remote electrical signal
electrical closing “closing spring charged”
t = Dead time 0.3 s
Rated switching O-t-CO or O-t-CO O or CO
t ‘ = Dead time 3 min
sequence O-t-CO-t’-CO
Auto- Suitable (multiple Suitable (only with closing –
For further details, please refer also to
reclosure (K) auto-reclosure possible) solenoid)
Catalog HG 11.11 “3AH Vacuum
Circuit-Breakers“

Siemens HA 41.21 · 2005 19


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Secondary equipment of the 3AH5 and 3AH6 vacuum circuit-breakers


The scope of the secondary Anti-pumping (standard)
equipment of the 3AH vacu- (mechanical and electrical)
um circuit-breaker depends • Function: If CLOSE and

R-HA41-080 eps
on the type of application OPEN commands are ap-
and offers a wide range of plied simultaneously and
variations, thus allowing continuously to the vacuum 1
even the highest require- circuit-breaker, this reverts
ments to be satisfied. to its OPEN position after
closing. The circuit-breaker
Closening solenoid remains in this position until
• Type 3AY15 10 (Y9 *) the OPEN command is eli- 3

• For electrical closing minated and a new CLOSE


command is given. Thus
Shunt releases continuous closing and ope-
ning (= pumping) is avoided. 4
• Types: 2
– Standard: 3AY15 10 (Y1 *) Breaker tripping signal
– Option: 3AX11 01 (Y2 *), (standard)
with energy store
• For electrical signalling 5
• Tripping by protection re- (as pulse > 10 ms), e.g. to
lay or electrical operation remote control systems,
in the case of automatic
Current transformer- Secondary equipment of the 3AH5
tripping (e.g. protection) vacuum circuit-breaker (typical example)
operated release
• Via NO contact (S6 *)
• Type 3AX11 04 (Y6 *) for and cut-out switch (S7 *)
tripping pulse W 0.1 Ws in
conjunction with suitable Varistor module
protection systems, e.g.
7SJ4 protection relay, • As overvoltage protection 1
SEG relay (other designs for protection devices in
on request) conjunction with inductive
devices in the vacuum
• Used where no external circuit-breaker (limiting to 3
auxiliary voltage is avail- approx. 500 V)
able, tripping by protec-
tion relay • Recommended for auxil-
iary voltages W 60 V DC
4 6
Undervoltage release
Auxiliary switch
• Type 3AX11 03 (Y7 *) 2
• Type 3SV9 (S1 *)
• Comprising:
– Energy store and • Standard: 6NO+6NC, 5
unlatching mechanism of which 2NO+2NC
– Electromagnetic system, +2 changeover contacts
to which voltage is are free 1) 7

permanently applied in • Option: 12NO+12NC, of


the CLOSED position of which 7NO+4NC+2 change-
the vacuum circuit-breaker; over contacts are free 1)
tripping is initiated when
this voltage drops Mechanical interlocking
• Connection to voltage • Dependent on the type
R-HA41-046 eps

transformer possible of operating mechanism:


– Spring-operated
Position switch mechanism or
– Stored-energy mechanism Secondary equipment of the 3AH6
• Type 3SE4 (S4 *) vacuum circuit-breaker (typical example)
• For signalling “closing • Option:
spring charged“ Switchgear interlocking Basic equipment Additional equipment
with the three-position 1 Auxiliary switch 6NO+6NC (S1 *), 3 Position switch (S4 *)
• Only in conjunction with switch-disconnector option: 12NO+12NC
stored-energy mechanisms 4 Closing solenoid (Y9 *)
For further details concer- 2 1st release (Y1 *)
5 Operating cycle counter
ning interlocking functions,
refer to page 26. 6 2nd release
(e.g. Y2 *, Y6 * and Y7 *)
1) For utilization * Equipment Abbreviations: 7 Mechanical interlocking
by the code NO = normally-open contact with interrogation
customer NC = normally-closed contact of the three-position
switch-disconnector
For further details, please refer also to
Catalog HG 11.11 “3AH Vacuum Circuit-Breakers“

20 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Three-position switches as three-position switch-disconnectors or disconnectors


Common features Three-position
• Metal-enclosed switch-disconnector 630 A

• Located in a • Up to 630 A
1
gas-insulated • With gas-insulated,
switchgear vessel maintenance-free quench-
• Switch positions: ing principle
CLOSED-OPEN-
EARTHED Operating mechanism
2
• No cross insulation • Spring-operated mechanism
between phases with detachable lever

• Three-position switch • Manual operation with the


aid of a detachable lever 3 5
with air-insulated

R-HA41-057 eps
primary connections • Options:
for busbar and feeder – Mechanical ready-for-
• Operation via a service indication
gas-tight welded-in me- – Auxiliary switch
tal bellows in the front – Motor operating mechanism
of the switchgear for switch-disconnector 4
vessel – Locking device
6
• Spring-operated/stored-
Mode of operation energy mechanism for Three-position
transformer panel types TR, switch-disconnector
The switch shaft with the 630 A
moving contact pieces TR1 and ME31-F
rotates inside the cham-
ber containing the fixed Interlocks 1 Bushing-type insulator for busbar
contact pieces. • Opening of lower panel 2 Switchgear vessel for gas insulation

Compression vanes, cover or cable compartment 3 Three-position switch-disconnector


which rotate in conjunc- cover only in “EARTHED“ 4 Bushing-type insulator for feeder
tion with the switch position 5 Spring-operated mechanism with detachable lever
shaft, divide the arcing • Option: Logical mechanical 6 Mounting location for three-phase current transformer (option)
chamber into two sub- interlocking of three-position
chambers each of which switch-disconnector with
changes in conjunction vacuum circuit-breaker
Switch positions:
with the rotation.
Three-position 7
During the switching
HA41-2430b eps

disconnector 1250 A EARTHED


movement, the compres-
sion vanes generate a • Up to 1250 A, for panel
pressure difference be- types LS31, LS31-U, LS32
tween the subchambers. and LT31
OPEN
The SF6 gas flows • Metal-enclosed
through a nozzle, causes
a directional blow-out of Operating mechanism
the breaking arc and
• Spring-operated mechanism CLOSED
quenches it rapidly.
with detachable lever
Interlocking is not neces- Detachable lever mechanism
sary as the “CLOSED” • Manual operation by a with three-position switch-disconnector
and “EARTHED” func- detachable lever
7 Operating lever, inserted as as
tions cannot be imple- • Options: three-position three-position
mented simultaneously. – Mechanical ready-for- switch- disconnector
service indication disconnector 1250 A
– Auxiliary switch 630 A
– Motor operating mecha-
nism for disconnector Switching functions of the Switching functions of the
– Locking device three-position switch-disconnector three-position disconnector
630 A 1250 A
Interlocks • Switching and disconnecting under • Disconnecting
load • Switching functions according to
• Opening of lower panel
• Switching function as general purpose – IEC 62 271-102
cover or cable compartment switch-disconnector (class E3 and M1) – VDE 0671-102
cover only in “EARTHED” according to • Earthing function
position – IEC 60 265-1
– VDE 0670-301 • For panel types LS31, LS31-U,
• Logical mechanical – IEC 62 271-102 LS32 and LT31
interlocking with vacuum – VDE 0671-102
circuit-breaker • Make-proof earthing function
Note: Standards see page 41

Siemens HA 41.21 · 2005 21


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Busbars, HV HRC fuse assembly


Busbars HV HRC fuse assembly
Busbars
• Safe-to-touch due to • For transformer panel
metallic enclosure types TR and TR1

R-HA41-061 eps
1 Busbar
• Metal-clad busbar • For busbar voltage meter- 1 2 Insulating cap (e.g.
compartment ing panel type ME31-F for Ur > 17.5 kV) on
busbar
• Three-pole design, • HV HRC fuse links 2
3 Bushing-type
bolted from panel to acc. to DIN 43 625 (main insulator for busbar
panel dimensions) with striker 3

• Easy switchgear pin; version “medium”


extension acc. to IEC 60 282/
VDE 0670-4 *
• Made of copper: – As short-circuit protec-
– Fl E-Cu for w 630 A tion before transformers
– Rd E-Cu for > 630 A to – With selectivity (depend- Busbar compartment extending over 3 panels (example)
1250 A Side view
ing on correct selection)
• Versions: to upstream and down-
– 630 A, > 12 kV: stream connected equip-
With insulating shrink-on ment
sleeve • Requirements fulfilled as
– 1250 A, up to 24 kV: HV alternating current
Rd E-Cu bare switch fuse combination HV HRC fuse assembly
• Selection of HV HRC
R-HA41-071 eps

fuses for transformers “CLOSED“ indi-


cation, manual or
• Fuse replacement possi- motor operation
ble only when feeder is Indication “HV
earthed HRC fuse tripped”
or “shunt
• Option: Shunt release on release tripped”
operating mechanism of
“OPEN” indication
three-position switch-
disconnector
• Option: “Tripped indica-
tion” of three-position
switch-disconnector in
transformer feeder (trans-
former switch) for remote
electrical indication with
one normally-open con- Control board of a transformer feeder
tact (1NO)

“HV HRC fuse tripped”


Following the tripping of an
R-HA41-052 eps

HV HRC fuse link, the me- 4 Insulating sleeve


chanism for charging the 5 HV HRC fuse
spring must be set to the 4 (not included in the
“OPEN” position scope of supply)
6 Earthing switch (rated
Subsequently, earthing can short-circuit making
be implemented by means 5
current Ima = 4 kA)
of the three-position for cable connection
switch-disconnector and 7 Cover for bolted
e.g. the fuse can be cable lug connection
replaced. 6
(e.g. for rated voltage
Ur = 24 kV)
Replacement of HV HRC 8 Cable sealing end
fuse links 7 (not included in the
scope of supply)
• Isolating and earthing of
the transformer feeder
• Subsequent manual 8
replacement of the
HV HRC fuse link

HV HRC fuses in transformer panel type TR


Side view
* Standards see page 41

22 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Allocation of HV HRC fuses and transformers


The table opposite shows the Rated Transformer Rated normal current of the HV HRC fuse
recommended 3GD HV HRC system Rating SN Relative Rated Lowest Highest
fuse links (electrical data valid voltage impedance current I1 value value
for ambient temperatures of up voltage uk
to 40 oC) for the fuse pro- kV kVA % A A A
tection of transformers 6 to 7.2 50 4 4.8 16 16
75 4 7.2 16 16
100 4 9.6 20 25
Recommendation
125 4 12.0 25 25
The three-position switch- 160 4 15.4 32 32
disconnector in the trans- 200 4 19.2 40 40
former feeder (transformer 250 4 24.0 50 50
switch) was combined with 315 4 30.3 50 63
Siemens HV HRC fuse links 400 4 38.4 63 100
of type 3GD and tested *. 500 4 48.0 63 100
630 4 61.0 80 100
800 5 to 6 77.1 on request on request
Standards
10 to 12 50 4 2.9 10 10
HV HRC fuse links with 75 4 4.3 10 10
striker pin, “medium“ version 100 4 5.8 16 16
according to 125 4 7.2 16 16
160 4 9.3 20 20
• IEC 60 282-1 */ VDE 0670-4 * 200 4 11.5 25 25
• IEC 60 787 / VDE 0670-402 250 4 14.5 25 32
315 4 18.3 32 40
• DIN 43 625 main dimensions 400 4 23.1 40 50
500 4 29.0 50 63
630 4 36.4 63 80
800 5 to 6 46.2 63 80
1000 5 to 6 58.0 80 100
1250 5 to 6 72.3 100 100
1600 5 to 6 92.5 125 125
13.8 50 4 2.1 6 6
75 4 3.2 10 10
100 4 4.2 10 10
125 4 5.3 16 16
160 4 6.7 16 16
200 4 8.4 16 20
250 4 10.5 20 25
315 4 13.2 25 32
400 4 16.8 32 32
500 4 21.0 40 50
630 4 26.4 50 50
800 5 to 6 33.5 50 50
1000 5 to 6 41.9 63 63
1250 5 to 6 52.4 80 80
15 to 17.5 50 4 1.9 6 6
75 4 2.9 10 10
100 4 3.9 10 10
125 4 4.8 10 10
160 4 6.2 16 16
200 4 7.7 16 20
250 4 9.7 20 25
315 4 12.2 25 25
400 4 15.5 32 32
500 4 19.3 32 40
630 4 24.3 40 50
800 5 to 6 30.9 50 50
1000 5 to 6 38.5 63 63
1250 5 to 6 48.2 63 80
20 to 24 50 4 1.5 6 6
75 4 2.2 6 6
100 4 2.9 10 10
125 4 3.6 10 10
160 4 4.7 10 10
200 4 5.8 16 16
250 4 7.3 16 16
315 4 9.2 20 20
400 4 11.6 20 25
500 4 14.5 25 32
630 4 18.2 32 40
800 5 to 6 23.1 32 32
1000 5 to 6 29.0 40 40
1250 5 to 6 36.0 50 50
1600 5 to 6 46.5 63 80
* Standards see page 41
2000 5 to 6 57.8 80 80

Siemens HA 41.21 · 2005 23


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Operating mechanisms for three-position switches


Manual operating Shunt release (option)
mechanism Operating mechanisms (examples)
Spring-operated/stored-en-
• Standard: ergy mechanisms can be
As detachable lever equipped with a shunt re-
mechanism lease. Remote electrical
• Option: Different operating tripping of the three-position
handles1) for the operating switch-disconnector is possi-
ble via the magnetic coil

R-HA41-079 eps
mechanism of the three-
position switch of the shunt release, e.g.
transformer overtemperature
• Spring-operated mecha- tripping.
nism
– For ring-main panel To avoid thermal overloading
types RK and RK1 of the shunt release in the
event of a continuous signal Detachable lever mechanism
– For all three-position as spring-operated mechanism
switches (except in panel that may be applied, the for ring-main feeders
types TR and TR1) shunt release is switched off
via an auxiliary switch which
• Spring-operated /stored- is mechanically coupled with
energy mechanism the three-position switch-
For transformer panel disconnector.
R-HA41-070 eps

1 Terminal strip located


types TR and TR1 as well in the low-voltage
as for busbar voltage me- Auxiliary switch (option) niche (optionally in
tering panel type ME31-F 1
the low-voltage
Each operating mechanism compartment)
The three-position switch is of the three-position switch-
2 2 M.c.b. (option)
operated via a rocker with disconnector can be option- in the low-voltage
metal bellows which is ally equipped with an auxil- niche
3
gas-tight and welded at the iary switch for the switch 3 Local-remote switch
switchgear vessel. position indication: (option)
4
– Function switch-discon- 4 Actuation for the
Motor operating nector or disconnector: 5 motor operating
mechanism (option) CLOSED and OPEN: mechanism of the
2NO + 2NC three-position
The manual operating me- 6
switch-disconnector
chanisms can be equipped – Function earthing 5 Auxiliary contactors
with motor operating mecha- switch at the of the motor operating
nisms both for the three- three-position switch: mechanism for locking
position switch-disconnector CLOSED and OPEN: the motor
and for the three-position 2NO + 2NC 7 6 Auxiliary switch
disconnector. 7 Switch position
– Separate earthing switch
Operating voltages for motor 8 indicator for the
(at the feeder): three-position
operating mechanisms: CLOSED and OPEN: 9 switch-disconnector
– 24, 48, 60, 110, 220 V DC 2NO + 2NC 8 Locking device
– 50/60 Hz 110 and 230 V AC
(standard for motor
Electrical operation: 10
operating mechanism)

• Standard: Remote opera- 9 Operating mechanism


for the three-position
tion (applied to terminal) 11 switch-disconnector
• Option: Local operation coupled with the motor
by momentary-contact operating mechanism
rotary control switch Operating mechanism parts in 10 Shunt release (option)
transformer feeder 11 Motor operating
mechanism

Technical data of the auxiliary switch


Breaking capacity Rated switching capacity
AC operation at DC operation Rated insulation
40 Hz to 60 Hz voltage
250 V AC/DC
Operating Normal Operating Normal current Insulation group
1) According to
voltage current voltage resistive inductive: C to VDE 0110
VDN*/ VDEW**
T=20 ms
recommendation Continuous current
V A V A A
* Association of German 10 A
up to 230 10 24 10 10
network operators Making capacity
VDN e. V. in Germany 48 10 9
50 A
(as of 2003) 60 9 7
** Association of 110 5 4
German Power Stations – Abbreviations:
220 2.5 2
VDEW e. V. NO = normally-open contact
(until 2003) NC = normally-closed contact

24 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Indicating and measuring equipment


Short-circuit/earth-fault Voltage detection systems
indicator (option) Indicating and measuring equipment Symbols shown on
For voltage detection (examples)
The ring-main feeders can according to IEC 61 243-5 / CAPDIS-S1+ CAPDIS-S2+
be equipped with a 3-phase VDE 0682-415 L1 L2 L3 L1 L2 L3
short-circuit or earth-fault Plug-in voltage 1
indicator: A0
detection systems
• Optical signal when a pre- • Standard: HR system
2
A1
selected pickup value is
exceeded • Option: LRM system
A2
• With ring-type sensors Option: Integrated voltage
• Display panel, withdraw- detection systems 3 A3
able housing, depending • LRM system as
on the type CAPDIS-S1+ or A4
• Short-circuit pickup values: CAPDIS-S2+ (auxiliary
e.g. 400, 600, 800 or power required) A5

HA40-2052a eps
1000 A
Option: Remote electrical Features of the A6
indication via contact (1NO + HR/LRM system 4 ERROR

R-HA41-072c.eps
1NC contact, passing con- • Voltage indicator A0 CAPDIS-S2+: Operating voltage
tact), applied to terminal – HR system (standard) or not present
– LRM system (option) A1 Operating voltage present
Ready-for-service indicator • Verification of safe isolation
Control board of a ring-main panel A2 – Operating voltage not present
(option for three-position (example)
from supply phase by – For CAPDIS-S2+:
switch) phase through insertion in Mounting locations in the control
Auxiliary power not present
• Self-monitoring; easy to each socket pair board for A3 Earth fault or failure in phase L1,
read 1 Voltage detection system “CAPDIS- operating voltage at L2 and L3
• Voltage indicator flashes
S1+, -S2+” possible (option) A4 Voltage (not operating voltage)
• Independent of tempera- if high voltage is present
2 Short-circuit/earth-fault indicator present
ture and pressure varia- • For continuous operation (option) A5 Indication “device function test”
tions
• Safe-to-touch 3 Ready-for-service indicator passed
• Independent of site altitude (option) A6 Indication “ERROR“, e.g. in case
• Measuring system and
• Only responds to changes 4 Voltage indicator, HR system, of missing auxiliary voltage
voltage indicator can be plugged-in (standard) (see: “error indication M4“)
in gas density tested
• Option: Alarm switch • Fixed-mounted capacitive
“1NO contact”
R-HA40-088 eps

voltage divider in bushings


Mode of operation • Without auxiliary power Voltage indicator,
HR system (standard)
For the ready-for-service indi- Features of
cator, a gas-tight measuring CAPDIS-S1+, -S2+
box is installed on the inside • For phase indications
• Maintenance-free L1, L2 and L3
of the switchgear vessel.
A coupling magnet, which • Integrated display,
R-HA40-096 eps

R-HA40-098 eps

is fitted to the bottom end without auxiliary power


of the measuring box, trans- • Option: With remote
mits its position to an outside indication of the voltage
armature through the stain- state (auxiliary power
less steel switchgear vessel. required for CAPDIS-S2+)
This armature moves the
Short-circuit indicator ALPHA M Short-circuit/earth-fault indicator EKA-3
ready-for-service indicator of Mounting of voltage
the switchgear. detection systems
While changes in the gas See “Product range”
HA41-2462 eps

6 Measuring box
density during the loss of pages 10 to 15 7 Magnetic coupling
6
gas, which are decisive for
the insulating capacity, are 8 8 Red indication:
Verification of correct ter- 7 not ready for service
displayed, temperature- minal-phase connections 9 Green indication:
dependent changes in the ready for service
• Possible by means of a
gas pressure are not. The 9
gas in the measuring box has phase comparison test unit
the same temperature as (optional)
Stainless-steel vessel Ready-for-
that in the switchgear. • Safe-to-touch handling of filled with SF6 gas, service
The temperature effect is the phase comparison test gauge pressure indicator
compensated via the same unit by inserting it into the 500 hPa at 20 °C
pressure change in both gas capacitive taps (socket
volumes. pairs) of the switchgear Principle of operation of gas monitoring
with ready-for-service indicator

Siemens HA 41.21 · 2005 25


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Interlocking systems and locking devices


Interlocking of connection Interlocking in circuit-
compartment breaker panel types LS1, Interlocking systems
LS1-U and LT10 (with 3AH5

R-HA41-064c eps
Ring-main and fixed-mounted vacuum
circuit-breaker panel circuit-breaker)
• Access to the cable con- • Option: Logical mechanical
nection compartment interlocking with three-po-
(e.g. for cable testing) is sition switch-disconnector
only possible provided • Earthing of feeder via
that the feeder is isolated three-position switch-
and earthed (three-posi- disconnector in
tion switch-disconnector “EARTHED” position
in “EARTHED” position)
• Option: Closing lock-out Interlocking in circuit-
This prevents the three- breaker panels (with 3AH6
position switch-discon- removable vacuum circuit-
nector from being breaker)
switched from “OPEN” to • Option: For 630 A panel
“CLOSED” position, types LS11, LS11-U and
when the cable compart- LT11: Logical mechanical
ment cover is removed interlocking with three-po-
sition switch-disconnector
Transformer panel
• Standard: For 1250 A
• Access to the cable con- panel types LS31, LS31-U,
nection compartment and LS32 and LT31: Logical
to the HV HRC fuse com- mechanical interlocking
partment (e.g. for replace- with three-position
ment of HV HRC fuse disconnector Interlocking for cable compartment cover
links) is only possible pro- Removed cable compartment cover
vided that the feeder is • Logical mechan. interlock- with earthed bus sectionalizer panel
isolated and earthed ing of cable compartment
(three-position switch- cover: Opening of cable
disconnector in compartment cover only
“EARTHED” position) possible provided that the
feeder is earthed
• Option: De-earthing Locking device (option)
lock-out Feeder earthing
R-HA41-081 eps

This prevents the


three-position switch- • Standard: For panel types
disconnector from being LS11, LS11-U, LT11, LS31,
switched from position LS31-U and LS32:
“EARTHED” to “OPEN”. Earthing by switching of
vacuum circuit-breaker
Switchgear interlocking 3AH6 1) in position
“CLOSED” and of three-
• Dependent on the va- position switch 2) in
cuum circuit-breaker oper- position “EARTHED”
ating mechanism with
– Spring-operated or • Option: For circuit-breaker
– Stored-energy mechanism panel types LS11, LS31
and LS32: Earthing by
• Option: Switchgear-side means of an additional
mechanical interlocking make-proof earthing
with three-position switch at the feeder with
switch-disconnector inspection window in the
• Vacuum circuit-breaker cable compartment cover
cannot be closed when
three-position switch- Locking devices Locking device of the detachable lever mechanism
e.g. for padlock
disconnector is in the The three-position switch-
“OPEN” position: disconnector can be locked
– Spring-operated mecha- on the operating mechanism
nism: Hand crank opening side in any position (option).
is blocked
– Stored-energy mechanism
with closing solenoid 1) With additional locking device – 2) Three-position switch as
3AY15 10: Pushbutton optionally with signalling switch – for – Switch-disconnector in panel
(S12) operated by mecha- securing the “CLOSED” position of types LS11, LS11-U and LT11
nical interlock prevents the vacuum circuit-breaker for feeder – Disconnector in panel types
continuous command to “EARTHED” LS31, LS31-U, LS32 and LT31
closing solenoid

26 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

4MC63 three-phase current transformers for panel types LS ... and LT ...
Application
• For circuit-breaker panels

R-HA41-048 eps
type LS ...
• For bus sectionalizer panels
type LT ...
• Option: For ring-main panels
type RK ...

Features
• According to IEC 60 044-1/
VDE 0414-1
• Designed as a three-pole
ring-core current
transformer

R-HA41-044 eps
• Free of dielectrically
stressed cast-resin parts (due
to design)
• Insulation class E
• Inductive type
• Climate-independent 4MC63 53 three-phase
current transformer
• Secondary connection by 4MC63 53 three-phase current transformer
means of a terminal strip on the bushings of the three-position
inside the panel switch-disconnector

Installation 4MC63 53 three-phase current transformer


Technical data
• Arranged outside the switch- for IN < 150 A for IN < 400 A for IN < 1000 A
gear vessel on the bushings for ID = 630 A for ID = 630 A for ID = 1250 A

• Factory-assembled
Primary data

Other designs Max. equipment operating 0.72 kV 0.72 kV 0.72 kV


voltage Um
(option)
Rated current IN A 150 100 75 50 400 300 200 1000 750 600 500
Three-phase current transfor-
mers for protection equipment Rated short-duration 3 kV 3 kV 3 kV
based on c.t. operation: power-frequency
withstand voltage
• 7SJ4x protection relay as (winding test)
definite-time overcurrent Rated thermal short-time 25 kA 25 kA 25 kA
protection withstand current Ith
• Definite-time overcurrent Rated continuous thermal 630 A 630 A 1250 A
protection relay, current ID
make SEG, type WIP 1
Transient overload 1.5 x ID / 1 h 2 x ID / 0.5 h 1.5 x ID / 1 h
current
Rated peak withstand unlimited unlimited unlimited
current Idyn

Secondary data
Rated current A 1 0.67 0.5 0.33 1 0.75 0.5 1 0.75 0.6 0.5
Rating VA 5 3.33 2.5 1.67 5 3.75 2.5 5 3.75 3 2.5
Rated current (option) 5A 5A 5A
Current at ID 4.2 A 1.575 A 1.25 A
Protec- Class 10 P 10 P 10 P
tion
Overcurrent factor 10 10 10
core

Other values available on request

Siemens HA 41.21 · 2005 27


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

4MC70 33, 4MC70 31 cable-type current transformers and 4MC70 32 bus-type current transformers

Application
• For circuit-breaker panels

R-HA41-025 eps
R-HA41-049a eps
4MC70 31 cable-type
type LS ... current transformer

H
• For ring-main panels
type RK ...
• For transformer panels 4MC70 33 cable-type

R-HA41-024 eps
type TR ... current transformer,
4 different overall heights
Features

H
• According to IEC 60 044-1/
VDE 0414-1
• Designed as a single-pole
ring-core current transformer
• Only for shielded cables
• Climate-independent

R-HA41-027 eps
• Free of dielectrically
stressed cast-resin parts (due 4MC70 32
to design) bus-type
current transformer
• Insulation class E
• Inductive type 4MC70 33 cable-type current transformers
• Secondary connection by on the cable at the panel connection
means of a terminal strip
inside the panel
Technical data 4MC70 33 cable-type 4MC70 31 cable-type 4MC70 32 bus-type
Installation current transformer current transformer current transformer
• 4MC70 33 cable-type current
transformer and 4MC70 32 Primary data
bus-type current transformer
Max. equipment operating 0.72 kV 0.72 kV 0.72 kV
for panel type LS ... voltage Um
• 4MC70 31 cable-type current Rated current IN 30 A to 600 A 50 A to 600 A 200 A to 600 A
transformer: e.g. for panel
Rated short-duration 3 kV 3 kV 3 kV
types RK ..., K ... and TR ... power-frequency
• Arranged on the cable at withstand voltage
the panel connection (winding test)
Rated thermal short-time 25 kA 25 kA 25 kA
• Transformers mounted on a
withstand current Ith
supporting plate at our
factory; final assembly on Rated continuous thermal 1.0 x IN 1.0 x IN 1.0 x IN
current ID option: 1.2 x IN option: 1.2 x IN option: 1.2 x IN
the cables on site
Transient overload 1.5 x ID / 1 h or 1.5 x ID / 1 h or 1.5 x ID / 1 h or
current 2 x ID / 0.5 h 2 x ID / 0.5 h 2 x ID / 0.5 h
Rated peak withstand unlimited unlimited unlimited
current Idyn

Secondary data
Rated current 1 A (option: 5 A) 1 A (option: 5 A) 1 A (option: 5 A)
Meas- Class 0.2 0.5 1 1 0.2 0.5 1
uring
Overcurrent factor FS10 (option: FS5) FS5 (option: FS10) FS10 (option: FS5)
core
Rating 2.5 VA to 10 VA 2.5 VA to 10 VA 2.5 VA to 10 VA
Pro- Class 10 P 5P – 10 P 5 P (on request)
tection
Overcurrent factor 10 10 – 10 10
core
Rating 2.5 VA to 10 VA – 2.5 VA to 15 VA
Option: Secondary tap 1:2 1:2 1:2
(e.g. 150 A – 300 A) (e.g. 150 A – 300 A)

Dimensions
* Depending on the core data Overall height H ** mm 50* 100* 170* 285* 89 80 * 150 *
** Available installation height Outside diameter Ø 145 mm 85 mm x 114 mm Ø 125 mm
inside panel types RK or RK1:
Inside diameter Ø 55 mm Ø 40 mm Ø 55 mm
Approx. 285 mm, depending on
make, type and cross-section of For cable diameter Ø 50 mm Ø 36 mm Ø 50 mm
sealing end
Other values available on request

28 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

4MA7 block-type current transformers and 4MR voltage transformers


Application
• For billing metering panels

R-HA41-060a eps

R-HA41-030a eps
type ME1 ...
• For bus riser panel
type HF …
• For mounting at the
feeder
4MA7 block-
Features type current
transformer,
• 4MA7 current transformer single-pole
• According to IEC 60 044-1/
VDE 0414-1

R-HA41-029a eps
• Dimensions according to
DIN 42 600-8
• Designed as a single-pole
indoor block-type current
transformer
• Cast-resin insulated 4MR14 voltage
transformer,
• Insulation class E single-pole
• Secondary connection by
4MR voltage transformer and
means of screw-type 4MA7 block-type current transformer installed in
terminals billing metering panel type ME1

4MR voltage transformer


Technical data
• According to IEC 60 044-2/
VDE 0414-2 4MA7 single-pole block-type current transformer 4MR single-pole voltage transformer

• Dimensions according to Primary data Primary data


DIN 42 600-9 (small Max. equipment operating 12 kV 24 kV Max. equipment operating 12 kV
model) voltage Um voltage Um (= 1.2 x UN)
• Designed as an indoor Rated short-duration 38 kV 50 kV Rated voltage UN at max. 3.3/ 3 kV at 10 kV
voltage transformer: power-frequency rated short-duration 3.6/ 3 kV at 10 kV
– Type 4MR, single-pole withstand voltage power-frequency
4.8/ 3 kV at 20 kV
withstand voltage
– Option: Type 4MR, two-pole Rated lightning impulse 95 kV 125 kV 5.0/ 3 kV at 20 kV
withstand voltage 6.0/ 3 kV at 20 kV
• Cast-resin insulated 6.6/ 3 kV at 20 kV
Rated current IN 25 A to 1250 A
7.2/ 3 kV at 20 kV
• Insulation class E
Rated thermal short-time up to 25 kA 10.0/ 3 kV at 28 kV
• Secondary connection by withstand current Ith 11.0/ 3 kV at 28 kV
means of screw-type Rated continuous thermal up to 1.0 x IN Rated lightning impulse 75 kV
terminals current ID option: 1.2 x IN withstand voltage Up
Rated voltage factor 1.9 x UN
Rated peak withstand max. 2.5 x Ith (8 h)
current Idyn
Max. equipment operating 24 kV
voltage Um (= 1.2 x UN)
Rated voltage UN at max. 13.8/ 3 kV at 38 kV
rated short-duration 15.0/ 3 kV at 38 kV
power-frequency 17.5/ 3 kV at 50 kV
withstand voltage 20.0/ 3 kV at 50 kV
22.0/ 3 kV at 50 kV
Rated lightning impulse 125 kV
withstand voltage
Rated voltage factor 1.9 x UN
(8 h)

Secondary data Secondary data


Rated current 1 A or 5 A Rated voltage 100/ 3 V
Meas- Class 110/ 3 V (option)
0.2 0.5 1
uring 120/ 3 V (option)
Overcurrent factor FS5 or FS10
core Rated voltage for auxiliary 100/3 V
Rating 10 VA to 15 VA winding (option) 110/3 V (option)
Pro- Class 5 P or 10 P 120/3 V (option)
tection Overcurrent factor 10 Rating 20 VA 50 VA 100 VA
core
Rating 5 VA or 15 VA Class 0.2 0.5 1
Other values available on request Other values available on request

Siemens HA 41.21 · 2005 29


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Cable connection
General features
Cable connection (examples)
• Connecting lugs for sealing ends
arranged one behind the other L3 L2 L1 L3 L2 L1

• Uniform cable connection height

R-HA41-050 eps

R-HA41-051 eps
for the respective panel types
• With cable bracket, e.g. type C40
according to DIN EN 50 024 1
• Access to the cable connection 2
compartment only if feeder has 5
been isolated and earthed 4
3
Special features
– In ring-main panels
– In circuit-breaker panels
– In cable panels
• For thermoplastic-insulated cables
• For paper-insulated mass-
impregnated cables with
adapter systems Ring-main panel type RK Cable connection compartment with cable
• For connection cross- Cable connection compartment as delivered sealing ends (options: A, B, C 1) and D 1), see below)
sections up to 300 mm2 L1 L1
L2 L3 L2 L3
• Cable routing downwards
R-HA41-053 eps

R-HA41-052 eps
– In transformer panels:
• For thermoplastic-
insulated cables
• For connection cross-
sections up to 120 mm2:
Cable lug max. 32 mm wide
• For rated normal currents 6
of 200 A

For options see figures 7


8
Cable cross-sections
9
Panel type Connectable cables x
connection cross-section
No. x mm2
for rated voltage Transformer panel type TR Cable connection compartment with cable
Cable connection compartment as delivered sealing ends (option: A 2), see below)
12 kV 17.5 kV 24 kV
K Standard 1x 300 1x 300 1x 300
R-HA41-055 eps

On request 2x 300 – –
K1 2x 400 2x 400 2x 400 11
RK, Standard 1x 300 1x 300 1x 300 L1 L2 L3
K-E
On request 2x 300 – –
R-HA41-067 eps

RK1, K1-E 2x 300 2x 300 2x 300


LS1 2x 300 2x 300 2x 300
LS11, LS31 2x 400 2x 400 2x 300
LS32 Standard 3x 400 3x 400 3x 300
14
Option 4x 300 4x 300 –
10 13
On request – – 4x 300
ME1-K, ME1-KS 3x 400 3x 400 3x 300 12
1) Only with ring-main panel type RK1
2) Cable clamps with transformer
panels type TR ... partly mounted
underneath the panel in the cable
basement
3) Make Siemens, type 3EK7, Circuit-breaker panel type LS11 Cable connection compartment with cable
other makes on request Cable connection compartment as delivered sealing ends (options: A, B, C and D, see below)
Note
Cable sealing ends and cable clamps Options A Mounted cable clamps 2) C Double cable connection
are not included in the scope of supply B Short-circuit / earth-fault indicator D Suitable for connection of surge arresters 3)

30 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Selection data for various cable sealing ends


Cable sealing end, e.g. for panel types RK..., LS1..., LS11..., LS31..., LS32 Connection height **
Cable sealing ends and TR ...1) (for connection heights of cables see opposite dimension drawings) of cables above
(examples) Make Type Cross-section floor or above
mm2 lower edge of panel:
1 As-delivered condition,
e.g. for Up w 95 kV, prepared

HA41-2432b eps
for cable sealing end Single-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
2 As-delivered condition, Euromold AIN 10 25–300 (500*)
e.g. for Up > 95 kV, additionally with 35 MSC 16–300 (500*)
insulating sleeve, prepared 35 MSC (option 3)) 25–300 (500*)
for cable sealing end
ITK-212 50–300 (400*)
3 Phase L1:
Pirelli Elektrik Germany ELTI mb-1C-12 35–240
Make: Lovink (RXS)
ELTI-1C-12 25–300

785**
Type IAEM 20,
240 mm2 (20 kV) Tyco Electronics IXSU-F 16–300 (500*)
4 Phase L2: Raychem TFTI 25–300 (400*)
Make: Tyco Electronics Raychem EPKT 1) 16–300
Type EPKT 24 C / 1X, Panel type RK ...
185 mm2 (24 kV), Lovink (RXS) IAEM 10 25–300
as shrink-on sealing end, IAES 10 25–300 (500*)

HA41-2433b eps
for severe ambient conditions 3M Germany 92-EB 6xx-1 16–300 (400*)
5 Phase L3: Südkabel (ABB) SEHDI 10.2 35–300 (500*)
Make: Pirelli Elektrik Germany
SEI 12 70–300
Type ELTI mb-1C-2h-C-T3,

645**
240 mm2 (24 kV) nkt cables TI 12 25–240
AV 10 C 25–300 (500*)
AV 10 E 25–300 (500*)
6 As-delivered condition, prepared
for cable sealing end Panel type LS1 ...
Single-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/20 kV)
7 Phase L1:

HA41-2434a eps
Make: Lovink (RXS) Euromold AIN 20 25–300 (630*)
Type IAEM 20, 35 MSC 25–70
95 mm2 (20 kV) 35 MSC (option 3)) 25–185
8 Phase L2: 36 MSC 2) 95–300 (500*)
Make: Tyco Electronics Raychem 36 MSC (option 3)) 95–300 (500*)
Type TFTI/5131,

480
ITK-224 25–240
95 mm2 (24 kV),
Pirelli Elektrik Germany ELTI mb-1C-24 35–240
as push-on sealing end
ELTI-1C-24 25–300 Panel type LS11 ...
9 Phase L3:
Make: Euromold Tyco Electronics IXSU-F 25–300 (500*)
Type AIN, 95 mm2 (24 kV) Raychem 25–300 (400*)
HA41-2435b eps

TFTI
EPKT 16–300 (500*)
Lovink (RXS) IAEM 20 25–300
IAES 20 25–300 (500*)
3M Germany 93-EB 6xx-1 25–300 (400*)
35–300 (500*)
a
Südkabel (ABB) SEHDI 20.2
SEI 24 25–240
nkt cables TI 24 25–240 Panel type TR …
AV 20 E 25–300 (500*) Dimension a
10 As-delivered condition, AV 10 E 25–300 (500*) ~ 530 mm at 12 kV
e.g. for Up < 95 kV, prepared ~ 380 mm at 24 kV
for cable sealing end
Three-core thermoplastic-insulated cables for < 12 kV (6/10 kV)
11 As-delivered condition, Note
e.g. for Up W 95 kV, additionally with Euromold AIN 10 25–300 (500*)
insulating cap, prepared for SR-DI 12 35–300 (500*) Depending on make and
cable sealing end type, the termination of the
Pirelli Elektrik Germany ELTI-3C-12 25–300 cable sealing end (= shield
12 Phase L1: Tyco Electronics IXSU-F 16–300 (500*) earth) for the 3-core thermo-
Make: Lovink (RXS) Raychem plastic-insulated cable and
Type IAES 20, the fitted cable clamp (option)
Lovink (RXS) IAES 10 25–300
240 mm2 (20 kV) may be located underneath the
GHKI 16–300 (400*)
13 Phase L2: panel in the cable basement.
Make: Pirelli Elektrik Germany This must be taken into
Type ELTI 1C-24-D-T3, Three-core thermoplastic-insulated cables for > 12 kV to < 24 kV (12/10 kV) account in panels with
240 mm2 (24 kV), Euromold SR-DI 24 2) 35–300 (500*) floor cover (option).
as indoor sealing end,
Lovink (RXS) GHKI 25–300 (500*)
for severe ambient conditions
14 Phase L3: 1) Transformer panel types TR ...:
Make: Euromold 3) Cable sealing **Due to the installation of
– Lower edge of sealing end below panel end type with 4MA cast-resin insulated
Type AIN 20, – Cable lugs of sealing ends up to 32 mm width
240 mm2 (24 kV) insulation shields block-type current trans-
– Owing to the various sealing end lengths, some of formers in panels RK1
the mounted cable clamps are underneath the panel
* On request:
Max. connection and LS1, the connection
2) Circuit-breaker panel types LS11, LS31 and LS32: cross-section of height of the cables is
– Lower edge of sealing end below panel cable sealing end reduced to 380 mm
types

Siemens HA 41.21 · 2005 31


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Components

Low-voltage equipment
Low-voltage niche Electronic functions
(standard) Low-voltage niche (examples)
Multifunction protection
• Screwed-on cover as relay SIPROTEC 4 7SJ62 13
1 LED indications
– Cover (available mounting or 7SJ63 with the following 5
2 2 LCD
depth behind of features:
1 6 3 Navigation keys
approx. 184 mm) 1 User-programmable LEDs
– Frame cover, approx. with application- specific 3 7 4 Function keys
46 mm deeper version label, for display- ing any 5 Option:
4 8
(available mounting desired process and
Short-circuit/
depth behind of earth-fault
equipment data indicator
approx. 230 mm)
2 LCD for process and 6 Frame cover of
• For accommodation of equipment data, e.g. for: 9 low-voltage niche
terminals and standard – Measuring and metering (can be unscrewed)

R-HA41-062a eps
protection devices, e.g. values 7 Momentary-contact
in circuit-breaker panels – Binary information on the rotary control switch
combined with frame ON-OFF for motor
status of switching point operating mechanism
cover for panels and device In bus sectionalizer panel type LT11 of the three-position
– Type LS1: Protection – Protection data (low-voltage niche closed) switch-disconnector
relays (with max. 75 mm – General indications 8 Local-remote switch
wide mounting frame), e.g. – Alarms for three-position
– Type 7SJ45, 7SJ46 switch-disconnector
– Make SEG, type WIC 3 Keys for navigation in 10
14 9 Control board
On request: menus and for entering
values 10 Low-voltage niche
– 7SJ60 open
– Make SEG, WIP1 4 Four user-programmable 11
11 Option:
– Type LS11, LS31 and LS32: function keys for Installed equipment
Protection relays (with frequently performed 12 Panel front
max. 75 mm wide actions
mounting frame), e.g. 13 Option:
9 Multifunction
type 7SJ45, 7SJ46, Low-voltage cables protection relay
7SJ60 and 7SJ61.

R-HA41-083 eps
• Control cables of the SIPROTEC 4 7SJ61
On request: on swing-out frame
– 7SJ62 (150 mm wide) panel to the low-voltage
compartment are con- 14 Option:
– Make SEG, WIP1 Protection device
nected via multi-pole, In circuit-breaker panel type LS1 make SEG,
• For bus wires and/or con- coded module plug (low-voltage niche open) type WIC
trol cables; niche open at connectors
the side to the adjacent
• Option: Plug-in bus wires
panel
from panel to panel inside
• Safe-to-touch, separated the low-voltage niches, 10
from high-voltage part of optionally in separate
the panel cable duct on the panel
11
• Degree of protection
IP 3X (standard)

Low-voltage compartment 12
(option)
• Overall heights:
R-HA41-059a eps

350 mm, 550 mm


• Available mounting depth:
442 mm In billing metering panel type ME1
• Overall widths: (low-voltage niche open)
375 mm, 500 mm, 750 mm
• For mounting on the panel
Low-voltage compartment (option)
• Dependent on the panel-
specific scope of the SIPROTEC 4
secondary equipment 2 7SJ61:
• For accommodation of pro- 1 1 LED indications
tection, control, measuring 2 LCD
3
R-HA41-058 eps

and metering equipment, 3 Navigation keys


e.g. multifunction protec- 4 4 Function keys
tion relay SIPROTEC 4
7SJ62/ 7SJ63 or protec- On circuit-breaker panel type LS1
tion relay make SEG for additional low-voltage equipment
• Compartment 750 mm
wide for panel type LS32

32 Siemens HA 41.21 · 2005


Ring-main panels, transformer panels

 187.5

375
Type RK

1)

187.5

375
Type TR
375
*
1750

Type RK-U
1750

*
187.5

Type RK1

*
1750

187.5

Type TR1
500
HA41-2408b eps

500
 1750

150
*

*
1750

HA41-2407b eps
HA41-2409b eps

150

1050
1080

150
205

205
210

~184**

210
210
1050
1080
360
20

210
1050
1080
442**

~184**

~184**
350*
360
20

Ring-main panel
360
20
~380
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

785***
Ring-main
panels

for panel combinations

Transformer
panels
Dimensions

1) Location of voltage transformer


in left-hand panel,
e.g. in panel type
LT10 or LT11
* Option:
Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
*** For panel type RK1 the cable
connection height is reduced
to approx. 380 mm for panel
version with 4MA block-type
current transformer

Siemens HA 41.21 · 2005 33


Cable panels


34
187.5

375
Type K

187.5

375

Type K-E

* Option:
*
1750

*
1750

187.5

Type K1

187.5

Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment

Siemens HA 41.21 · 2005


500

500

Type K1-E
*

1750

*
1750

HA41-2411b eps
HA41-2412b eps


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Dimensions

150

150
205

205
210

210
210
1050
1080

210
1050
1080
442**

~184**

~184**
350*
360
20
360
20
785
785 Cable panels

Cable panels
(with additional make-proof
earthing switch)
Circuit-breaker panels

 562.5

Type LS1

390
750

110

750
Type LS11 (with make-
proof earthing switch)

390 110

750
1750
*
1750
1750

Type LS31 3) (for connection


of max. 2 cables)
*

*
HA41-2413c eps

 150

390
205

750

earthing switch)

390

of 3 cables)
210

110

Type LS11 (without

110 110

875
210
1050
1080

Type LS32 3) (for connection


1750

*
1750
442**

2)
~184**

~230**

HA41-2414d eps

2) 3)
150
HA41-2470b eps

350*
360
20
645***

205

150
210

205
210
1050
1080

210
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Circuit-breaker panel
630 A
with 3AH5 1)

210
1050
1080
~184**

~230**

~184**

~230**
20
360
480
20
360
480
Dimensions

Circuit-breaker panels
630 A
with 3AH6 1)

1) Type designation of the


vacuum circuit-breaker
2) Option: Inspection window
3) Option: With make-proof
earthing switch

* Option: Low-voltage compartment


available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
– Approx. 184 mm with cover
– Approx. 230 mm with extended
frame cover
*** The cable connection height is
reduced to approx. 380 mm for
panel version with 4MA block-type
current transformer

Circuit-breaker panels
1250 A
with 3AH6 1)

Siemens HA 41.21 · 2005 35


Dimensions

Bus sectionalizer panels with bus riser panel


36
1125

Type LT10 + type HF

1125
Type LT11 + type HF

1125

Type LT31 + type HF

Siemens HA 41.21 · 2005


*

*
1750
1750
1750

HA41-2416b eps
HA41-2417c eps


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

HA41-2471a eps

150

150

150
1050
1080

1050
1080

1050
1080
442**

~184**

~230**

~184**

~230**

~184**

~230**
350*
360
20
360
20360
20
Bus sectionalizer panel
630 A
with 3AH5 1)

Bus sectionalizer panel


630 A
with 3AH6 1)

Bus sectionalizer panel


1250 A
with 3AH6 1)
1) Type designation of the
vacuum circuit-breaker
* Option:
Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
– Approx. 184 mm
with cover
– Approx. 230 mm
with extended frame cover
Bus sectionalizer panels

 Type LT2
750
*
1750

(Ⳏ type RK-U with type HF)

750
Type LT2-W

* Option:
1750

Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
*
Type LT22
750

750
Type LT22-W
1750

(Ⳏ type RK-U with type


*

*
1750

HA41-2419b eps
HA41-2420b eps

 150

150
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

1050
1080

1050
1080
442**

~184**

~184**
350*
360
20
360
20
Dimensions

Bus sectionalizer panels


without transformers

Bus sectionalizer panels


with transformers

Siemens HA 41.21 · 2005 37


Dimensions

Billing metering panels


38
Type ME1
750

750
Type ME1-S
(for busbar connection)

750
Type ME1-H

Siemens HA 41.21 · 2005


*
1750

*
1750

*
1750

HA41-2421b eps
HA41-2422b eps
HA41-2423b eps


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

150

150

150
1050
1080

1050
1080

1050
1080
442**

~184**

~184**

~184**
350*
360
20
360
20
360
20

Billing metering panel


(standard)

375

Type ME1-K
750

(for cable connection)

Billing metering
panel for
2nd current transformer set
*
1750

HA41-2469 eps

150 250

* Option:
250
1050
1080

Low-voltage compartment
250

Billing metering panels


for busbar and cable
connection

available in two heights:


350 mm or 550 mm
** Available mounting depth
for low-voltage equipment
~184**

360
20
480
 375

Type SE1

375

Type HF
*
1750

HA41-2425b eps

without transformers

*
1750

HA41-2427b eps

without transformers

375
Type ME3
*
1750

Type ME31-F
with fuses


Busbar voltage metering panels, busbar earthing panels, bus riser panels

150

150

500
*
1750

1050
1080

1050
1080
HA41-2424b eps

150
~184**

~184**
360
20
360
20

1050
1080
Type SE2

1)

442**

~184**
500

375

Type HF
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

with voltage transformers

with transformers
350*
360
20
~ 415
*

1750

*
1750

Busbar
HA41-2426b eps
HA41-2428b eps

voltage metering
panels
150

150
1050
1080

1050
1080
Dimensions

~184**

~184**

360
20
360
20

transformer in
Busbar
earthing
panels

Bus
riser
panels

1) Location of voltage

left-hand panel
* Option:
Low-voltage compartment
available in two heights:
350 mm or 550 mm
** Available mounting depth
for low-voltage equipment

Siemens HA 41.21 · 2005 39


Dimensions

Floor openings (dimensions in red) and fixing points


For panel width 375 mm
For panel width 500 mm
For panel width 750 mm
For panel width 875 mm

40
1

1
1
150

5
HA41-2398 eps
150

5
HA41-2400 eps
150

5
HA41-2402 eps

1
150

5
HA41-2472a eps

20
80
385
385
110
20
80
385
385
110
20
80
385
385
110
20
80
385
385
110

Siemens HA 41.21 · 2005


58

18
60

58

18
60

58

18
60

18
60

Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

375

187.5

187.5

169.5
255

187.5

169.5

187.5

368
390

169.5
205
210
210

380
58
857

With cable connection

250

187.5

232
500
205
210
210

With cable connection

a
750

375

375
630

With cable connection

875

500

110 110

500
755

With cable connection


14 x 28
1000
850
205
210
210
60

28 x 14
58
857

14 x 28
1000
850
205
210
210
60

28 x 14
58857
For pa-
nel type
RK
K
K-E
TR

For pa-
nel type
RK1
K1+
K1-E
TR1

14 x 28
1000
850

28 x 14
58
857

58
60

14 x 28
1000
85060

28 x 14
150
6

HA41-2399 eps

For pa-
nel type
LS1
(Dim. a
= 562.5)
ME1-K
(Dim. a
= 375)
ME1-KS
(Dim. a
= 375)

For pa-
nel type
LS32
20
80
385
385
110
150

6
HA41-2401 eps
58

18
60
20
80
385
385
110
187.5

169.5

58

18
60

3
255
HA41-2403a eps
375

Without cable connection

250

232
500

380
58857
14 x 28

1000
850
28 x 14

Without cable connection

368

390 110

For dimensions not shown


60
58
857
205
210
210

see illustration on the left


With double cable connection
For pa-
nel type
RK-U
ME3
HF
SE1

14 x 28

60
1000
850

28 x 14
For pa-
nel type
RK1-U
ME31-F
SE2

For pa-
nel type
LS11

LS31
150

6
HA41-2404 eps
1 Wall distance
2 Fixing frame (base)

20
80
of an individual panel or panel block
3 Floor opening for high-voltage cables and,
where applicable, control cables; in panel
types LS11, LS31 and LS31-K: floor opening
also possible below floor cover
4 Position of the led-in cables for the feeder
5 Fixing points
6 Floor opening if required for panels
without cable connection

385
385
110

58

18
60
187.5

169.5
750

375

375
630
58
857

Without cable connection


14 x 28

60
1000
850

28 x 14
For pa-
nel type
LS1-U
LS11-U
LT10
LT11
LT2
LT2-W
LT22
LT22-W
ME1
ME1-S
ME1-H

LS31-U
LT31
Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Standards

Standards, specifications, guidelines

Standards Overview of standards (March 2005)


The SIMOSEC switch- IEC standard VDE standard EN standard
gear complies with the up to now current in future up to now current in future
relevant standards and
Switch- IEC 60 694 * IEC 60 694 * IEC 62 271-1 VDE 0670-1000 VDE 0670-1000 VDE 0671-001 EN 60 694
specifications applica- gear
ble at the time of IEC 60 298 IEC 60 298 IEC 62 271-200 VDE 0670-6 VDE 0670-6 *** VDE 0671-200 EN 62 271-200
IEC 62 271-200 VDE 0671-200
type tests.
Devices 1) IEC 60 056 ** IEC 62 271-100 – VDE 0670-101 to 106 VDE 0671-100 – EN 62 271-100
In accordance with the 2) IEC 60 129 ** IEC 62 271-102 – VDE 0670-2 VDE 0671-102 – EN 62 271-102
harmonization agree-
ment reached by the
3) IEC 60 265-1 * IEC 62 265-1 * IEC 62 271-103 VDE 0670-301 VDE 0670-301 VDE 0671-103 EN 60 265-1
countries of the Euro- 4) IEC 60 420 ** IEC 62 271-105 – VDE 0670-303 VDE 0671-105 – EN 62 271-105
pean Community, their 5) IEC 61 243-5 IEC 61 243-5 – VDE 0682-415 VDE 0682-415 – EN 61 243-5
national specifications 6) IEC 60 282 IEC 60 282 – VDE 0670-4 VDE 0670-4 – EN 60 282
conform to the IEC Degree of IEC 60 529 IEC 60 529 – VDE 0470-1 VDE 0470-1 – EN 60 529
standard. protection
Insulation IEC 60 071 IEC 60 071 – VDE 0111 VDE 0111 – EN 60 071
* In future, all standards Trans- 7) IEC 60 044-1 IEC 60 044-1 – VDE 0414-1 VDE 0414-1 – EN 60 044-1
for switching devices formers 8) IEC 60 044-2
and switchgear will be IEC 60 044-2 – VDE 0414-2 VDE 0414-2 – EN 60 044-2
summarized in Installation IEC 61 936-1 IEC 61 936-1 – VDE 0101 VDE 0101 – –
IEC 62 271
** Withdrawn standard 1) Circuit-breaker 4) Switch-disconnector / fuse 6) HV HRC fuses
2) Disconnector and earthing switch combination 7) Current transformer
*** Transition period until
Febr.1, 2007 3) Switch-disconnector 5) Voltage detection systems 8) Voltage transformer

Type of service location Table – Insulating capacity Insulating capacity


SIMOSEC switchgear can be Rated voltage (rms value) kV 7.2 12 15 17.5 24 • The insulating capacity is veri-
used as an indoor installation in fied by testing the switchgear
accordance with IEC 61 936 Rated short-duration power-frequency withstand voltage (rms value) with rated values of short-
(Power installations exceeding – Across isolating distances kV 23 32 39 45 60 duration power-frequency
1 kV AC) and VDE 0101 – Between phases and to earth kV 20 28 36 38 50 withstand voltage and light-
• Outside lockable electrical ning impulse withstand volt-
Rated lightning impulse withstand voltage (peak value) age according to IEC 60 694/
service locations at places
which are not accessible to – Across isolating distances kV 70 85 105 110 145 VDE 0670-1000 (see
the public. Enclosures of – Between phases and to earth kV 60 75 95 95 125 table “Insulating capacity”).
switchgear can only be • The rated values are referred
removed with tools. to sea level and to normal
Correction factor a for the site altitude atmospheric conditions
• Inside lockable electrical
service locations. A lockable (1013 hPa, 20 °C, 11 g/m3
1
humidity in accordance with
HA40-2037 eps

For site altitudes


electrical service location is
a place outdoors or indoors
above 1000 m, the IEC 60 071 and VDE 0111).
0,9
adjacent correction
Correction factor a

that is reserved exclusively for • The insulating capacity


factor a is recom-
housing electrical equipment 0,8 decreases with increasing
mended, depend-
and which is kept under lock altitude.
ing on the actual 0,7
and key. Access is restricted For site altitudes above
site altitude above
to authorized personnel and 1000 m (above sea level)
sea level. 0,6
persons who have been the standards do not provide
properly instructed in electri- any guidelines for the insula-
0,1
cal engineering. tion rating. Instead, special
Untrained or unskilled per- 0 regulations apply to these
sons may only enter under 0 1000 2000 3000 4000 5000 altitudes.
the supervision of authorized Site altitude in m above sea level
personnel or properly instruc- Site altitude
ted persons. As the altitude increases, the
Rated short-duration power-frequency withstand voltage to be selected
insulating capacity of insulation
Terms W
Rated short-dur. power-fre. withstand volt. (IEC 60 694 / VDE 0670-1000)
in air decreases due to the
“Make-proof earthing switches” 1.1 · a decreasing air density.
are earthing switches with For SIMOSEC switchgear the
Rated lightning impulse withstand voltage to be selected
short-circuit making capacity decreasing insulating capacity
Rated lightning impulse withstand volt. (IEC 60 694 / VDE 0670-1000)
according to W must be taken into account
– IEC 62 271-102 1.1 · a
for site altitudes above 1000 m
and (above sea level), see also
– VDE 0671-102 Example: Result:
IEC 60 694 / VDE 0670-1000.
3000 m site altitude above sea level According to the above
17.5 kV switchgear rated voltage table, a switchgear for a
95.0 kV rated lightning impulse withstand voltage rated voltage of 24 kV is
to be selected.
Rated lightning impulse 95 kV = 118 kV
withstand volt. to be selected 1.1 · 0.73

Siemens HA 41.21 · 2005 41


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Standards

Standards, specifications, guidelines

Cable testing Tests for resistance to • Definitions of criteria: Climate and ambient
• For circuit-breaker and internal arc faults – Criterion 1 conditions
switch-disconnector feeders • Safety of operating personnel Correctly secured doors, SIMOSEC switchgear may be
ensured by tests to verify re- shutters etc. must not open used, subject to possible addi-
• DC voltage test – Criterion 2
sistance to internal arc faults tional measures – e.g. panel
before the test: Parts of enclosed heaters or floor covers –
• Internal arc tests in accord- switchgear which may cause
Remove or disconnect any ance with IEC 60 298 / under the following ambient
a hazard must not fly off conditions and climate classes:
voltage transformers at the VDE 0670-6 * by agreement – Criterion 3
cable connection in between operator and manu- No holes in the freely • Ambient conditions
SIMOSEC switchgear. facturer accessible external parts of – Natural foreign materials
SIMOSEC switchgear for • Internal arc tests performed in the enclosure as the result of – Chemically active pollutants
rated voltages up to 24 kV accordance with IEC 60 298, burning in or tearing open – Small animals
can be subjected to cable Appendix AA / VDE 0670-6, – Criterion 4 • Climate classes
tests at a max. DC test Appendix AA * Vertically arranged The climate classes are
voltage of 72 kV. The voltage indicators must not ignite classified according to
at the busbar may be 24 kV • The possibility of arc faults
– Criterion 5 IEC 60 721-3-3
in this case. in SIMOSEC switchgear is Horizontally arranged
much less due to: indicators must not ignite SIMOSEC switchgear is largely
Test voltages: – Metal-enclosed and gas- insensitive to climate and
– Criterion 6
Rated Max. test insulated switching functions The effectiveness of the ambient conditions by virtue of
voltage voltage applied (e.g. of three-position the following features:
to cable earth connection must not
switch-disconnector and be detrimentally influenced • No cross insulation for
VLF 1) acc. Standard 3AH5 vacuum circuit-breaker)
0.1 Hz to in many In the event of an arc fault at isolating distances between
IEC com- – Logical arrangement of phases
(3 4U0) panies operating mechanism the cable connection, pressure
AC DC DC elements and mechanical relief is effected to the rear and • Metal enclosure of switching
kV kV kV kV interlocks upwards. devices (e.g. three-position
12 19 24 48 – Short-circuit-proof feeder For free-standing switchgear a switch) in gas-filled stainless-
earthing by means of the pressure-relief duct fitted at the steel switchgear vessel
24 38 48 70
three-position switch- rear is optionally available up to • Dry-type bearings in
• For cable testing disconnector 20 kA. operating mechanism
– the installation and
• Essential parts of the operat-
operating instructions of
ing mechanism made of
the switchgear
corrosion-proof materials
– the standards
IEC 60 298 / VDE 0670-6 / • Use of climate-independent
Section 5.107 * three-phase current trans-
– the information on manu- formers
facturer-dependent cable
sealing ends
– the cable version
(e.g. paper-insulated mass-
impregnated cables, PVC
cables or XLPE cables)
must be observed.

1) VLF = very low frequency


* Standards see page 41

42 Siemens HA 41.21 · 2005


Switchgear Type SIMOSEC up to 24 kV, Air-Insulated, Extendable

Standards

Standards, specifications, guidelines Notes

Protection against solid IEC 60 529 and EN 60 529: If not stated otherwise on
foreign bodies, electric shock the individual pages of this
Type of protection Degree of protection
and ingress of water catalog, we reserve the right
to include modifications, espe-
SIMOSEC switchgear fulfills
cially regarding the stated val-
acc. to the standards * I P 2X ues, dimensions and weights.
ss
IEC 60 694 VDE 0670-1000 Drawings are not binding.
EN 60 694 Protection against solid foreign bodies
Protected against the penetration All product designations used
IEC 60 298 VDE 0670-6 of solid foreign bodies, diameter W 12.5 mm are trademarks or product
IEC 60 529 VDE 0470-1 names of Siemens AG or
EN 60 529 Protection against electric shock other suppliers.
Protected against access to dangerous parts
by means of a finger (the distance between If not stated otherwise, all
the following degrees of
a test finger with a diameter of 12 mm dimensions in this catalog are
to dangerous parts must be sufficient) given in mm.
protection **:
Protection against the ingress of water The information in this document
Degree of Type of No definition
contains general descriptions of
protection protection the technical options available,
IP 2X Enclosure of live which do not always have to be
(standard) parts under I P 3X present in individual cases.
high-voltage ss The required features should
Compartments therefore be specified in each
Protection against solid foreign bodies
Protected against the penetration individual case at the time of
IP 3X Enclosure of live closing the contract.
of solid foreign bodies, diameter W 2.5 mm
(option) parts under high-
voltage in switchgear Protection against electric shock
with locking device Protected against access to dangerous parts
by means of a wire (the distance between a test
IP 3XD Enclosure of live
rod with a diameter of 2.5 mm and a length of
(on parts under high-
100 mm to dangerous parts must be sufficient)
request) voltage in switchgear
with locking device Protection against the ingress of water
No definition
IP 65 Metal enclosure
of gas-filled
switchgear vessels

I P 3 XD
Type of installation: sss
Wall-standing arrangement
Protection against solid foreign bodies
Protected against the penetration
of solid foreign bodies, diameter W 2.5 mm
Protection against the ingress of water
No definition
Protection against electric shock
Protected against access to dangerous parts
by means of a wire (the distance between a test
rod with a diameter of 1 mm and a length of
100 mm to dangerous parts must be sufficient)

IP 65
ss

Protection against solid foreign bodies


Dust-proof: no penetration of dust
Protection against electric shock
Protected against access to dangerous parts
by means of a wire (test probe with a diameter of 1 mm
may not penetrate)
Responsible for

Protection against the ingress of water Technical contents:


Protected against water jets, Christoph Maul
water which is directed towards Siemens AG, Dept. PTD M 2 PM
the enclosure from any direction Erlangen
may not have a damaging effect

General editing:
Gabriele Pollok
Siemens AG, Dept. PTD CC M
Erlangen
* Standards see page 41
KGK 04.05 0.0 VO/- 40 En 101354
** For explanations 6101/C6008
see adjacent table
Siemens HA 41.21 · 2005 43
If you have any questions about
Power Transmission and Distribution,
our Customer Support Center
is available around the clock
Tel: +49 180 / 524 70 00 (Subject to charges
Fax: +49 180 / 524 24 71 e.g.: 12 ct/min.)

E-mail: support@ptd.siemens.de
www.siemens.com/ptd-support

Published by
Siemens AG
Power Transmission and Distribution
Medium Voltage Division
Postfach 32 20
91050 Erlangen
Germany