Anda di halaman 1dari 58

TABLE 4E4A

Ref.Method 1 Ref.Method 11 TABLE 4E4B MEMDUCT 50 Hz, Copper Busbar Trunking System
2c, 1ø 3c/4c,3ø 2c, 1ø 3c/4c,3ø 1c,3ø 2c, 1ø 3c/4c, 3-ø Rated VL-L Drop in mV/m at rated current & at v
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 Current (A) 1.00 0.90
1.5 27 23 29 25 15.5 1.5 31 27 25 100 92.26
2.5 36 31 39 33 21 2.5 19 16 15 160 112.83
4 42 52 44 28 4 12 10 9.5 200 114.49
6 53 66 56 36 6 7.9 6.8 6.4 300 120.51
10 73 90 78 50 10 4.7 4.0 3.8 400 125.54
16 94 115 99 68 16 2.9 2.5 2.4 500 131.74
25 124 152 131 89 25 1.9 1.65 1.5 630 135.55
35 154 188 162 110 35 1.35 1.15 1.1 800 102.19
50 187 228 197 134 50 1 0.87 0.81 1000 93.74
70 238 291 251 171 70 0.69 0.60 0.57 1250 87.84
95 289 354 304 207 95 0.52 0.45 0.43 1400 81.93
120 335 410 353 239 120 0.42 0.37 0.35 1600 89.74
150 386 472 406 262 150 0.35 0.30 0.29 1800 83.90
185 441 539 463 296 185 0.29 0.26 0.25 2000 83.63
240 520 636 546 346 240 0.24 0.21 0.21 2500 86.57
300 599 732 628 394 300 0.21 0.185 0.185 3000 84.40
400 673 847 728 467 400 0.19 0.165 0.16 3200 80.35
630 892 892 3500 81.83
4000 80.97
4500 84.80
5000 78.30
6000 69.79

TABLE 4E2A
Multicore 900C Thermosetting insulated cables, non armoured (CU)
Ref. Method 4 Ref. Method 3 Ref. Method 1 Ref. Method 11 TABL
CSA 2c, 1ø 3c/4c,3ø 2c, 1ø 3c/4c,3ø 2c, 1ø 3c/4c,3ø 2c, 1ø 3c/4c,3ø Correction factors for groups of more than one circu
1 2 3 4 5 6 7 8 9
1 15 Reference method of
1.5 19.5 installation Num
Enclosed
(see table(Method
4A) 3 or
2.5 26 4) or bunched & 2 3 4 5
4 35 clipped direct to a non 0.8 0.7 0.65 0.6
Single
6 44 metallic surface
Touching 0.85 0.79 0.75 0.73
layer
(Method 1)
clipped to
a non-
metallic 0.94 0.9 0.9 0.9
10 60 surface Spaced*
(Method 1)
layer
16 80 Touching 0.86 0.81 0.77 0.75
clipped to
a non-
metallic 0.91 0.89 0.88 0.87
25 105 Spaced*#
surface
layer
35 128 clipped to Horizontal 0.9 0.85 - -
a non-
metallic 0.85 - - -
50 154 Vertical
surface
Single layer multicore
70 194 touching on ladder 0.86 0.82 0.8 0.79
supports (Method 13)
95 233
120 268
150 300
185 340
240 398
300 455
400 536

TABLE 4B2 TABLE 4B3


Correction factors for minerals insulated cables installed on perforated trays Correction factors for cables installed in enclosed trenches

Tray Arrangeme Number of multicore cables or circuits


Number Correction factor
orientatio nt of
of trays 1 2 3 4 6 9 Installation Method 18 Installation Method 19 Installation Method 20
n cables
Conductor 6 single- 6 single core 12 single
12 single
cross 2 single- 4 single- core cables, cables, 4 core cables,
3 single- 8 single core core cables,
sectional core cables, core cables, 4 two-core two-core 8 two-core
core cables, cables, or 4 three 8 two-core
area or 1 three- or 2 three- cables, or 3 cables or 3 cables, or 6
or 2 two- or four-core cables, or 6
or four-core or four core three-or three- or three- or
core cables cables three-or four
cable cables four-core four-core four core
core cables
Horizontal Multiconduc 1 1 0.9 0.8 0.8 0.75 0.75 cables cables cables
Horizontal Multiconduc 1 1 1 1 0.95 0.9 - 1 2 3 4 5 6 7 8 9
Vertical Multiconduc 1 1 0.9 0.8 0.75 0.75 0.7 mm²
Vertical Multiconduc 1 1 0.9 0.9 0.9 0.85 - 4 0.93 0.9 0.87 0.82 0.86 0.83 0.76 0.81
Horizontal Single condu 1 1 1 0.95 6 0.92 0.89 0.86 0.81 0.86 0.82 0.75 0.8
Vertical Single condu 1 1 0.9 0.9 10 0.91 0.88 0.85 0.8 0.85 0.8 0.74 0.78
16 0.91 0.87 0.84 0.78 0.83 0.78 0.71 0.76
+ space by a clearance between surfaces of at least one cable diameter (De) 25 0.9 0.86 0.82 0.76 0.81 0.76 0.69 0.74
++ separated by a clearance between adjacent surfaces of at least two cable diameters (2De) 35 0.89 0.85 0.81 0.75 0.8 0.74 0.68 0.72
- correction factor not tabulated 50 0.88 0.84 0.79 0.74 0.78 0.73 0.66 0.71
70 0.87 0.82 0.78 0.72 0.77 0.72 0.64 0.7
95 0.86 0.81 0.76 0.7 0.75 0.7 0.63 0.68
120 0.85 0.8 0.75 0.69 0.73 0.68 0.61 0.66
150 0.84 0.78 0.74 0.67 0.72 0.67 0.59 0.64
185 0.83 0.77 0.73 0.65 0.7 0.65 0.58 0.63
240 0.82 0.76 0.71 0.63 0.69 0.63 0.56 0.61
300 0.81 0.74 0.69 0.62 0.68 0.62 0.54 0.59
400 0.8 0.73 0.67 0.59 0.66 0.6 0.52 0.57
500 0.78 0.72 0.66 0.58 0.64 0.58 0.51 0.56
630 0.77 0.71 0.65 0.56 0.63 0.57 0.49 0.54

TABLE 4C1
Correction Factors for ambient temperature where protection is against short-circuit

Type of Operating Ambient temperature (°C)


Insulation temperature
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Rubber (flex60°C 1.04 1 0.91 0.82 0.71 0.58 0.41 - - - - - - - -
General
purpose
pvc 70°C 1.03 1 0.94 0.87 0.79 0.71 0.61 0.5 0.35 - - - - - -
Paper 80°C 1.02 1 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 0.32 - - - -
Rubber 85°C 1.02 1 0.95 0.9 0.85 0.8 0.74 0.67 0.6 0.52 0.43 0.3 - - -
Heat resisti 90°C 10.3 1 0.97 0.94 0.91 0.87 0.84 0.8 0.76 0.71 0.61 0.5 0.35 - -
Thermosett 90°C 1.02 1 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.5 0.41 0.29 - -
70°C sheath 1.03 1 0.93 0.85 0.77 0.67 0.57 0.45 0.31 - - - - - -
Mineral
105°C sheat 1.02 1 0.96 0.92 0.88 0.84 0.8 0.75 0.7 0.65 0.6 0.54 0.47 0.4 0.32

* this factor s are applicable only to ratings in column 2 to 5 of Table 4D1A


er Busbar Trunking System
op in mV/m at rated current & at various power factors
0.80 0.70 0.60 0.50 ECC
87.38 1.5 1.5
108.30 2.5 2.5
110.89 4 4
119.05 6 6
124.84 10 10
131.83 16 16
140.31 25 16
98.32 35 16
90.46 50 25
84.91 70 35
79.24 95 50
86.76 120 70
81.07 150 95
80.38 185 95
83.40 240 120
81.70 300 150
77.81 400 240
79.17
78.71
82.26
75.91
67.44

TABLE 4B1
s for groups of more than one circuit of single-cables, or more than one multicore cable

Correction factor (Cg)


Number of circuits or multi cables
6 7 8 9 10 12 14 16 18 20
0.57 0.54 0.52 0.5 0.48 0.45 0.43 0.41 0.39 0.38
0.72 0.72 0.71 0.7 - - - - - -

90 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9

0.74 0.73 0.73 0.73 0.71 0.7 - - - -

0.87 - - - - - - - - -

- - - - - - - - - -

- - - - - - - - - -

0.78 0.78 0.78 0.77 - - - - - -


Installation Method 20
18 single 24 single
core cables, core cables,
12 two-core 16 two-core
cables, or 9 cables, or 12
three or three- or
four-core four core
cables cables
10 11

0.74 0.69
0.73 0.68
0.72 0.66
0.7 0.64
0.67 0.62
0.66 0.6
0.64 0.59
0.62 0.57
0.6 0.55
0.58 0.53
0.57 0.51
0.55 0.49
0.53 0.48
0.52 0.46
0.5 0.44
0.48 0.43
0.47 0.41
UAE rating (A) 800 1000 1250 1350 1600 2000 2500 3200 4000 5000 6300
values at 50 Degrees based on UAE Size conductors.
Conductor CSA (mm2) 420 540 600 750 960 960 1380 1920 1920 2760 3600 1.5 1.5

2.5 2.5
Reactance (m ohm/m) 0.013 0.013 0.01 0.0088 0.0076 0.0076 0.0044 0.0038 0.03 0.0044 0.0025 4 4
6 6
Resistance (m ohm/m) 0.045 0.053 0.041 0.0355 0.03 0.03 0.016 0.015 0.011 0.016 0.009 10 10
16 16
Impedance (m ohm/m) 0.047 0.055 0.042 0.0365 0.031 0.031 0.017 0.015 0.11 0.017 0.0096 25 16
35 16
"Voltage drop, pf = 0.7 (V/m)" 0.0568 0.062 0.057 0.057 0.057 0.068 0.063 0.057 0.068 0.063 0.06 50 25
"Voltage drop, pf = 0.8 (V/m)" 0.0608 0.068 0.061 0.061 0.061 0.073 0.067 0.061 0.073 0.067 0.065 70 35

"Voltage drop, pf = 0.9 (V/m)" 0.0614 0.072 0.065 0.065 0.065 0.078 0.071 0.065 0.078 0.071 0.069 95 50

"Voltage drop, pf = 1.0 (V/m)" 0.0624 0.071 0.064 0.064 0.064 0.076 0.07 0.064 0.076 0.07 0.068 120 70

UAE rating (A) 800 1000 1250 1350 1600 2000 2500 3200 4000 5000 6300 150 95
values at 20 Degrees based on UAE Size conductors. 185 95
"Voltage drop, pf = 0.7 (V/m)" 0.0568 0.0568 0.0544 0.0544 0.0544 0.068 0.056 0.0544 0.068 0.07 0.059 240 120

"Voltage drop, pf = 0.8 (V/m)" 0.0608 0.0608 0.0584 0.0584 0.0584 0.073 0.0608 0.0584 0.073 0.076 0.064 300 150
"Voltage drop, pf = 0.9 (V/m)" 0.064 0.064 0.0616 0.0616 0.0624 0.078 0.064 0.0616 0.078 0.08 0.067 630 300
"Voltage drop, pf = 1.0 (V/m)" 0.0624 0.0624 0.06 0.06 0.0608 0.076 0.0632 0.06 0.076 0.079 0.066

10 2.5
16 4
20 4
A B 25 6

Calculation 32 6
40 10
VD @ PF Length M VOLTS VD % @400V 63 16
e.g. 0.068 100 6.8 1.7 80 25
100 35
125 50
160 70
200 95
225 120
Example 250 150
300 185
1000A busbar at full load over 100mtrs will have a volt drop at 0.8 p.f. of 350 240
400 300
500 150 4c x 2
100 x 0.068 = 6.8Volts or 1.7% 630 185 4c x 2
800 300 4c x 2
1000 240 4c x 3
1250 300 4c x 3
1600 630 1c x 8
2000 630 1c x 11
2500 630 1c x 11
HILTON GARDEN INN
AL BARSHA, DUBAI
UNITED ARAB EMIRATES

ELECTRICAL
VOLTAGE DROP CALCULATIONS REV 1

REVISED DETAIL DESIGN ISSUE 08-10-2014

Tameem House T : + 971 (0) 4 450 3999


P.O Box 500137 F : + 971 (0) 4 450 3998
Tecom, Dubai E : dubai@tjeg.com
United Arab Emirates W : www.tjeg.com
AKOYA
MDB-A1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

FIRE PUMP 150.00 0.90 135.00 30 350 733.70 0.77 0.87 0.67 1095.23 4/c- 240 1 636 636 0.240 5.28 2.30% 1/c- 120 1

MCC - AP2 82.00 0.90 73.80 15 200 401.09 0.77 0.87 0.67 598.73 4/c- 120 1 410 410 0.420 2.53 1.10% 1/c- 70 1

SMDB -LIFT -A 100.00 0.90 90.00 15 250 162.38 0.77 0.87 0.67 242.40 4/c- 185 1 463 463 0.250 0.61 0.15% 1/c- 95 1

BBR - B1 888.40 0.70 621.74 32 1600 1121.79 BBR - B1 1600A TPN + E Cu BUSBAR 0.061 #DIV/0! #DIV/0! 1/c- 95 1
MDB-A1

SURGE
63
PROTECTION
SPARE 100.00 0.90 90.00 200

SPARE 100.00 0.90 90.00 200 162.38

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

TOTALS 1420.40 0.77 1100.54 15 2500 1985.67 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 8 of 58
AKOYA
BBR - B1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-BL3 128.00 0.70 89.60 45 300 161.66 0.77 0.87 0.67 241.32 4/c- 185 1 463 463 0.250 1.82 0.45% 1/c- 95 1

SMDB-BL4 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-BL5 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-BL6 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1
BBR - B1

SMDB-BL7 108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-BL8 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-BL9 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-BL10 108.60 0.70 76.02 100 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.80 1.20% 1/c- 70 1

TOTALS 888.20 0.70 621.74 15 1600 1121.79 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 9 of 58
AKOYA
SMDB-BL3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-B301 6.10 0.80 4.88 69 32 8.80 0.77 0.87 0.67 13.14 4/c- 6 1 56 56 6.400 #DIV/0! #DIV/0! 1/c- 6 1

DB-B302 6.10 0.80 4.88 10 32 8.80 0.77 0.87 0.67 13.14 4/c- 6 1 56 56 6.400 #DIV/0! #DIV/0! 1/c- 6 1

DB-B303 6.10 0.80 4.88 25 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1

DB-B304 11.50 0.80 9.20 25 40 50.00 0.77 0.87 0.67 74.64 4/c- 10 1 90 90 4.700 #DIV/0! #DIV/0! 1/c- 10 1

DB-B305 9.00 0.80 7.20 22 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1

DB-B306 9.00 0.80 7.20 22 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1
SMDB-BL3

DB-B307 9.00 0.80 7.20 19 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1

DB-B308 9.00 0.80 7.20 19 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1

DB-B309 6.10 0.80 4.88 17 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1

DB-B310 6.10 0.80 4.88 17 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 #DIV/0! #DIV/0! 1/c- 6 1

DB-GYM 50.00 0.80 40.00 14 125 217.39 0.77 0.87 0.67 324.51 4/c- 50 1 228 228 1.000 #DIV/0! #DIV/0! 1/c- 25 1

TOTALS 128.00 0.80 102.40 1 300 184.76 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 10 of 58
AKOYA
MCC-AP2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

FAHU - 03 22.50 0.90 20.25 40 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1
MCC-AP2

FAHU - 03 18.50 0.90 16.65 20 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - 04 22.50 0.90 20.25 54 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - 04 18.50 0.90 16.65 31 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

TOTALS 82.00 0.90 73.80 1 200 4/c- 120 1/c- 70 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 11 of 58
AKOYA
SMDB-BL4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-B401 6.10 0.80 4.88 69 32 8.80 0.77 0.87 0.67 13.14 4/c- 6 1 56 56 6.400 3.89 1.69% 1/c- 6 1

DB-B402 6.10 0.80 4.88 10 32 8.80 0.77 0.87 0.67 13.14 4/c- 6 1 56 56 6.400 0.56 0.25% 1/c- 6 1

DB-B403 6.10 0.80 4.88 25 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 20.24 8.80% 1/c- 6 1

DB-B404 11.50 0.80 9.20 25 40 50.00 0.77 0.87 0.67 74.64 4/c- 10 1 90 90 4.700 #VALUE! #VALUE! 1/c- 10 1

DB-B405 11.50 0.80 9.20 22 40 50.00 0.77 0.87 0.67 74.64 4/c- 10 1 90 90 4.700 5.17 2.25% 1/c- 10 1

DB-B406 9.00 0.80 7.20 22 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 #VALUE! #VALUE! 1/c- 6 1
SMDB-BL4

DB-B407 9.00 0.80 7.20 19 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 5.87 2.55% 1/c- 6 1

DB-B408 9.00 0.80 7.20 19 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 11.16 4.85% 1/c- 6 1

DB-B409 6.10 0.80 4.88 17 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 6.09 2.65% 1/c- 6 1

DB-B410 9.00 0.80 7.20 17 32 39.13 0.77 0.87 0.67 58.41 4/c- 6 1 66 66 7.900 5.86 2.55% 1/c- 6 1

DB-B411 13.00 0.80 10.40 17 40 56.52 0.77 0.87 0.67 84.37 4/c- 10 1 90 90 4.700 #DIV/0! #DIV/0! 1/c- 10 1

DB-B412 6.10 0.80 4.88 17 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 3.56 1.55% 1/c- 6 1

DB-B413 6.10 0.80 4.88 17 32 26.52 0.77 0.87 0.67 39.59 4/c- 6 1 66 66 7.900 3.56 1.55% 1/c- 6 1

TOTALS 108.60 0.80 86.88 1 250 156.76 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 12 of 58
AKOYA
SMDB-LIFT-A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

LIFT - PL - 1 25.00 0.90 22.50 15 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 2.07 0.52% 1/c- 16 1

LIFT - PL - 2 25.00 0.90 22.50 48 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 5.29 1.32% 1/c- 16 1

LIFT - PL - 3 25.00 0.90 22.50 78 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 8.21 2.05% 1/c- 16 1
SMDB-LIFT-A

LIFT - SL 25.00 0.90 22.50 48 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 5.29 1.32% 1/c- 16 1

TOTALS 100.00 0.90 90.00 1 250 162.38 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 13 of 58
AKOYA
MDB-A2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB - R1 116.00 0.80 92.80 45 200 167.44 0.77 0.87 0.67 249.94 4/c- 95 1 304 304 0.430 3.24 0.81% 1/c- 50 1

SMDB - R2 116.00 0.80 92.80 48 200 167.44 0.77 0.87 0.67 249.94 4/c- 95 1 304 304 0.430 3.46 0.86% 1/c- 50 1

SMDB - R3 90.00 0.80 72.00 75 160 129.91 0.77 0.87 0.67 193.92 4/c- 70 1 251 251 0.570 5.55 1.39% 1/c- 35 1

SMDB - R4 81.00 0.80 64.80 84 200 116.92 0.77 0.87 0.67 174.53 4/c- 70 1 251 251 0.570 5.60 1.40% 1/c- 35 1
MDB-A2

SMDB - R5 64.50 0.80 51.60 88 160 93.10 0.77 0.87 0.67 138.98 4/c- 70 1 251 251 0.570 4.67 1.17% 1/c- 35 1

BBR - A1 1086.00 0.70 760.20 92 2500 1371.61 BBR - A1 2500A TPN + E Cu BUSBAR 0.067 #DIV/0! #DIV/0! 1/c- 95 1

SURGE PROTECTION 63

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

TOTALS 1553.50 0.73 1134.20 15 2500 2046.41 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 14 of 58
AKOYA
BBR - A1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-AL3 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-AL4 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-AL5 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-AL6 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1
BBR - A1

SMDB-AL7 108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-AL8 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-AL9 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-AL10 108.60 0.70 76.02 100 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.80 1.20% 1/c- 70 1

SMDB-AL11 108.60 0.70 76.02 225 0.77 0.87 0.67 0.00 4/c- 120 0 353 0 0.350 #DIV/0! #DIV/0! 1/c- 70 1

SMDB-AL12 108.60 0.70 76.02 225 0.77 0.87 0.67 0.00 4/c- 120 0 353 0 0.350 #DIV/0! #DIV/0! 1/c- 70 1

TOTALS 1086.00 0.70 760.20 15 2500 1371.61 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 15 of 58
AKOYA
MDB-A3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - A2 1086.00 0.70 760.20 45 2500 1371.61 BBR - A2 2500A TPN + E Cu BUSBAR #N/A #N/A #N/A 1/c- 50 1

SMDB - GR 149.50 0.80 119.60 48 300 215.79 0.77 0.87 0.67 322.12 4/c- 185 1 463 463 0.250 2.59 0.65% 1/c- 95 1

SMDB - R17 75.00 0.80 60.00 75 160 108.26 0.77 0.87 0.67 161.60 4/c- 70 1 251 251 0.570 4.63 1.16% 1/c- 35 1

SMDB - R6 62.00 0.80 49.60 84 160 89.49 0.77 0.87 0.67 133.59 4/c- 70 1 251 251 0.570 4.28 1.07% 1/c- 35 1
MDB-A3

DB - SS1 4.00 0.80 3.20 88 32 5.77 0.77 0.87 0.67 8.62 4/c- 6 1 56 56 6.400 3.25 0.81% 1/c- 6 1

SMDB - GA 82.90 0.80 66.30 160 119.62 0.77 0.87 0.67 178.57 4/c- 95 0 304 0 0.430 #DIV/0! 1/c- 50

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SPARE 100.00 200

SURGE PROTECTION 63

TOTALS 1559.40 0.68 1058.90 15 2500 1910.54 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 16 of 58
AKOYA
BBR - A2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-AL13 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-AL14 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-AL15 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-AL16 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1
BBR - A2

SMDB-AL17 108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-AL18 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-AL19 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-AL20 108.60 0.70 76.02 100 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.80 1.20% 1/c- 70 1

SMDB-AL21 108.60 0.70 76.02 225 0.77 0.87 0.67 0.00 4/c- 120 0 353 0 0.350 #DIV/0! #DIV/0! 1/c- 70 1

SMDB-AL22 108.60 0.70 76.02 225 0.77 0.87 0.67 0.00 4/c- 120 0 353 0 0.350 #DIV/0! #DIV/0! 1/c- 70 1

TOTALS 1086.00 0.70 760.20 15 2500 1371.61 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 17 of 58
AKOYA
MDB-A4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - A3 757.20 0.70 530.40 45 1250 956.99 BBR - A3 1250A TPN + E Cu BUSBAR 0.061 #DIV/0! #DIV/0! 1/c- 50 1

MCC - AG 126.00 0.90 113.40 48 300 204.60 0.77 0.87 0.67 305.43 4/c- 185 1 463 463 0.250 2.46 0.61% 1/c- 95 1
MDB-A4

MCC - ETS 1 200.00 0.90 180.00 75 630 324.77 0.77 0.87 0.67 484.80 4/c- 240 2 546 1092 0.210 2.56 0.64% 1/c- 240 1

MCC - ETS 2 200.00 0.90 180.00 84 630 324.77 0.77 0.87 0.67 484.80 4/c- 240 2 546 1092 0.210 2.86 0.72% 1/c- 240 1

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1283.20 0.78 1003.80 15 2500 1811.13 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 18 of 58
AKOYA
BBR - A3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-AL23 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-AL24 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-AL25 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-AL26
BBR - A3

108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1

SMDB-AL27 89.50 0.70 62.65 88 200 113.04 0.77 0.87 0.67 168.74 4/c- 95 1 304 304 0.430 4.28 1.07% 1/c- 50 1

SMDB-AL28 89.50 0.70 62.65 92 200 113.04 0.77 0.87 0.67 168.74 4/c- 95 1 304 304 0.430 4.47 1.12% 1/c- 50 1

SMDB-AL29 71.90 0.70 50.33 96 160 90.81 0.77 0.87 0.67 135.56 4/c- 70 1 251 251 0.570 4.97 1.24% 1/c- 35 1

SMDB-AL30 71.90 0.70 50.33 100 160 90.81 0.77 0.87 0.67 135.56 4/c- 70 1 251 251 0.570 5.18 1.29% 1/c- 35 1

TOTALS 757.20 0.70 530.04 15 2500 956.34 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 19 of 58
AKOYA
MDB-A5 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

MCC - AR 87.50 0.90 78.75 200 0.77 0.87 0.67 0.00 4/c- 150 1 406 406 0.290 1/c- 70 1

BBR - B2 1086.00 0.70 760.20 45 2500 1371.61 BBR - B2 2250A TPN + E Cu BUSBAR 0.067 #DIV/0! #DIV/0!

SMDB - P1B 155.12 0.80 124.10 48 300 223.91 0.77 0.87 0.67 334.24 4/c- 240 1 546 546 0.210 2.26 0.56% 1/c- 120 1
MDB-A5

SPARE 100.00 0.90 90.00 200 162.38

SPARE 50.00 0.80 40.00 100 72.17

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1391.12 0.73 1014.30 15 2500 1830.07 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 20 of 58
AKOYA
BBR - B2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-BL11 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-BL12 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-BL13 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-BL14 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1
BBR - B2

SMDB-BL15 108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-BL16 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-BL17 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-BL18 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 0.00 120 0 353 0 0.350 #DIV/0! #DIV/0! 1/c- 70 1

SMDB-BL19 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 0.00 120 0 353 0 0.350 #DIV/0! #DIV/0! 1/c- 70 1

SMDB-BL20 108.60 0.70 76.02 100 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.80 1.20% 1/c- 70 1

TOTALS 1086.00 0.70 760.20 15 2500 1371.61 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 21 of 58
AKOYA
MDB-A6 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - B3 865.80 0.73 631.75 45 1600 1139.85 BBR - B3 1600A TPN + E Cu BUSBAR 0.061 #DIV/0! #DIV/0!

SMDB - P1A 158.36 0.80 126.60 48 300 228.42 0.77 0.87 0.67 340.98 4/c- 185 1 463 463 0.250 2.74 0.69% 1/c- 95 1
MDB-A6

SPARE 100.00 0.90 90.00 75 200 162.38

EMDB - A 396.20 0.82 324.66 84 1000 585.78 0.77 0.87 0.67 874.42 4/c- 240 3 546 1638 0.210 3.44 0.86% 1/c- 120 3

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1520.36 0.77 1173.01 15 2500 2116.43 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 22 of 58
AKOYA
BBR - B3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-BL21 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-BL22 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-BL23 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-BL24 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1
BBR - B3

SMDB-BL25 108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-BL26 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-BL27 89.50 0.70 62.65 96 200 113.04 0.77 0.87 0.67 168.74 4/c- 95 1 304 304 0.430 4.67 1.17% 1/c- 50 1

SMDB-BL28 89.50 0.70 62.65 96 200 113.04 0.77 0.87 0.67 168.74 4/c- 95 1 304 304 0.430 4.67 1.17% 1/c- 50 1

SMDB-BL29 71.90 0.70 50.33 96 160 90.81 0.77 0.87 0.67 135.56 4/c- 70 1 251 251 0.570 4.97 1.24% 1/c- 35 1

TOTALS 902.50 0.70 631.75 15 2500 1139.85 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 23 of 58
AKOYA
EMDB - A - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

ESMDB - GA 45.00 0.80 36.00 95 100 64.95 0.77 0.87 0.67 96.96 4/c- 35 1 162 162 1.100 9.49 2.37% 1/c- 16 1

JOCKY PUMP 10.00 0.90 9.00 32 32 16.24 0.77 0.87 0.67 24.24 4/c- 10 1 78 78 3.800 4.67 1.17% 1/c- 10 1

ESMDB - PIA 90.80 0.80 72.64 15 200 131.06 0.77 0.87 0.67 195.64 4/c- 95 1 304 304 0.430 3.54 0.89% 1/c- 50 1
EMDB - A

ESMDB - PIB 93.40 0.80 74.72 15 200 134.82 0.77 0.87 0.67 201.25 4/c- 95 1 304 304 0.430 3.57 0.89% 1/c- 50 1

EMCC-AR 157.00 0.90 141.30 108 350 254.94 0.77 0.87 0.67 380.57 4/c- 70 1 251 251 0.570 18.39 4.60% 1/c- 35 1

TOTALS 396.20 0.84 333.66 1 2000 602.01 1/c- 630 9 1/c- 300 2

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 24 of 58
AKOYA
MDB-B1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - C2 1086.00 0.70 760.20 45 2500 1371.61 BBR - C2 2250A TPN + E Cu BUSBAR 0.067 #DIV/0! #DIV/0!

SMDB - R12 111.00 0.80 88.80 48 225 160.22 0.77 0.87 0.67 239.17 4/c- 120 1 353 353 0.350 2.69 0.67% 1/c- 70 1
MDB-B1

MCC - CR 87.50 0.90 78.75 75 800 142.09 0.77 0.87 0.67 212.10 4/c- 150 1 406 406 0.290 3.09 0.77% 1/c- 70 1

SPARE 150.00 0.80 120.00 84 300 216.51

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1434.50 0.73 1047.75 15 2500 1890.43 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 25 of 58
AKOYA
BBR -C2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-CL13 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-CL14 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-CL15 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-CL16 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1

SMDB-CL17
BBR -C2

108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-CL18 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-CL19 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-CL20 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-CL21 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-CL22 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

TOTALS 1086.00 0.70 760.20 15 2500 1371.61 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 26 of 58
AKOYA
MDB-B2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB - RMU 2 4.00 32 0.00 0.77 0.87 0.67 0.00 4/c- 10 1 78 78 3.800 0.00 0.00% 1/c- 10 1

SMDB - R14 105.00 0.80 84.00 48 200 151.56 0.77 0.87 0.67 226.24 4/c- 95 1 304 304 0.430 3.13 0.78% 1/c- 50 1

SMDB - R15 105.00 0.80 84.00 75 200 151.56 0.77 0.87 0.67 226.24 4/c- 95 1 304 304 0.430 4.89 1.22% 1/c- 50 1

SMDB - R16 66.00 0.79 52.00 160 93.82 0.77 0.87 0.67 140.05 4/c- 70 1 251 251 0.570 0.00 0.00% 1/c- 35 1

SMDB - R21 123.00 0.80 98.40 250 177.54 0.77 0.87 0.67 265.03 4/c- 150 1 406 406 0.290 0.00 0.00% 1/c- 70 1

FIRE PUMP CP 260.00 0.90 234.00 630 422.20 0.77 0.87 0.67 630.24 4/c- 240 2 546 1092 0.210 0.00 0.00% 1/c- 240 1
MDB-B2

MCC - BP2 82.00 0.90 73.80 200 133.16 0.77 0.87 0.67 198.77 4/c- 120 1 353 353 0.350 0.00 0.00% 1/c- 70 1

SMDB - LIFT - C 100.00 0.90 90.00 250 162.38 0.77 0.87 0.67 242.40 4/c- 185 1 463 463 0.250 0.00 0.00% 1/c- 95 1

SMDB - LIFT - B 100.00 0.90 90.00 250 162.38 0.77 0.87 0.67 242.40 4/c- 185 1 463 463 0.250 0.00 0.00% 1/c- 95 1

MCC - BR 87.50 0.90 78.75 200 142.09 0.77 0.87 0.67 212.10 4/c- 150 1 406 406 0.290 0.00 0.00% 1/c- 70 1

SPARE 150.00 0.80 120.00 300 216.51

SPARE 150.00 0.80 120.00 84 300 216.51

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1328.50 0.85 1124.95 15 2500 2029.72 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 27 of 58
AKOYA
MDB-B3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - C1 1086.00 0.70 760.20 45 2500 1371.61 BBR - C1 2250A TPN + E Cu BUSBAR 0.067 #DIV/0! #DIV/0!

SMDB - R11 94.00 0.90 84.60 48 200 152.64 0.77 0.87 0.67 227.86 4/c- 185 1 463 463 0.250 1.83 0.46% 1/c- 95 1

SMDB - R13 111.00 0.80 88.80 75 225 160.22 0.77 0.87 0.67 239.17 4/c- 120 1 353 353 0.350 4.21 1.05% 1/c- 70 1

SMDB - R18 51.00 0.80 40.80 160 73.61 0.77 0.87 0.67 109.89 4/c- 70 1 251 251 0.570 0.00 0.00% 1/c- 35 1
MDB-B3

SMDB - R20 56.00 0.80 44.80 160 80.83 0.77 0.87 0.67 120.66 4/c- 70 1 251 251 0.570 0.00 0.00% 1/c- 35 1

MCC - CP2 82.00 0.90 73.80 200 133.16 0.77 0.87 0.67 198.77 4/c- 95 1 304 304 0.430 0.00 0.00% 1/c- 50 1

SPARE 100.00 0.90 90.00 84 200 162.38

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1580.00 0.75 1183.00 15 2500 2134.45 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 28 of 58
AKOYA
BBR -C1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-CL3 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-CL4 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-CL5 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-CL6 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1

SMDB-CL7
BBR -C1

108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

SMDB-CL8 108.60 0.70 76.02 92 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.42 1.10% 1/c- 70 1

SMDB-CL9 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-CL10 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-CL11 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

SMDB-CL12 108.60 0.70 76.02 96 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.61 1.15% 1/c- 70 1

TOTALS 1086.00 0.70 760.20 15 2500 1371.61 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 29 of 58
AKOYA
MDB-B4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - C4 757.20 0.70 530.00 45 1600 956.26 BBR - C4 1600A TPN + E Cu BUSBAR 0.061 #DIV/0! #DIV/0!

SMDB - GC 112.45 0.80 89.96 48 225 162.31 0.77 0.87 0.67 242.29 4/c- 120 1 353 353 0.350 2.73 0.68% 1/c- 70 1
MDB-B4

SMDB - P1C 154.20 0.80 123.40 75 300 222.65 0.77 0.87 0.67 332.36 4/c- 185 1 463 463 0.250 4.17 1.04% 1/c- 95 1

EMDB - B 508.70 0.85 430.30 1000 776.38 0.77 0.87 0.67 1158.95 4/c- 240 3 546 1638 0.210 0.00 0.00% 1/c- 120 3

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 1532.55 0.77 1173.66 15 2500 2117.60 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 30 of 58
AKOYA
BBR - C4 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-CL23 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-CL24 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1

SMDB-CL25 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-CL26
BBR - C4

108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1

SMDB-CL27 89.50 0.70 62.65 88 200 113.04 0.77 0.87 0.67 168.74 4/c- 95 1 304 304 0.430 4.28 1.07% 1/c- 50 1

SMDB-CL28 89.50 0.70 62.65 92 200 113.04 0.77 0.87 0.67 168.74 4/c- 95 1 304 304 0.430 4.47 1.12% 1/c- 50 1

SMDB-CL29 71.90 0.70 50.33 96 160 90.81 0.77 0.87 0.67 135.56 4/c- 70 1 251 251 0.570 4.97 1.24% 1/c- 35 1

SMDB-CL30 71.90 0.70 50.33 96 160 90.81 0.77 0.87 0.67 135.56 4/c- 70 1 251 251 0.570 4.97 1.24% 1/c- 35 1

TOTALS 757.20 0.70 530.04 15 2500 956.34 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 31 of 58
AKOYA
EMDB - B - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

ESMDB - GC 34.00 0.80 27.20 95 80 49.08 0.77 0.87 0.67 73.26 4/c- 35 1 162 162 1.100 7.83 1.96% 1/c- 16 1

JOCKY PUMP 10.00 0.90 9.00 32 32 16.24 0.77 0.87 0.67 24.24 4/c- 10 1 78 78 3.800 4.67 1.17% 1/c- 10 1
EMDB - B

ESMDB - PIC 125.70 0.80 100.50 15 200 250.00 0.77 0.87 0.67 373.19 4/c- 150 1 406 406 0.290 3.79 0.95% 1/c- 70 1

EMCC-BR 157.00 0.90 141.30 141.3 350 254.94 0.77 0.87 0.67 380.57 4/c- 150 2 406 812 0.290 7.92 1.98% 1/c- 150 1

EMCC - CR 157.00 0.90 141.30 350 254.94 0.77 0.87 0.67 380.57 4/c- 185 2 463 926 0.250 4.08 1.02% 1/c- 185 1

SPARE 25.00 0.00 63

TOTALS 508.70 0.82 419.30 1 2000 756.53 1/c- 630 9 1/c- 300 2

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 32 of 58
AKOYA
MDB-B8 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

BBR - C3 543.00 0.70 380.10 45 2500 685.80 BBR - C3 2250A TPN + E Cu BUSBAR 0.067 #DIV/0! #DIV/0!
MDB-B8

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

SURGE PROTECTION 63

TOTALS 543.00 0.70 380.10 15 2500 685.80 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 33 of 58
AKOYA
BBR -C3 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SMDB-CL18 108.60 0.70 76.02 45 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.16 0.54% 1/c- 70 1

SMDB-CL19 108.60 0.70 76.02 48 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 2.30 0.58% 1/c- 70 1
BBR -C3

SMDB-CL20 108.60 0.70 76.02 75 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 3.60 0.90% 1/c- 70 1

SMDB-CL21 108.60 0.70 76.02 84 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.03 1.01% 1/c- 70 1

SMDB-CL22 108.60 0.70 76.02 88 225 137.16 0.77 0.87 0.67 204.75 4/c- 120 1 353 353 0.350 4.22 1.06% 1/c- 70 1

TOTALS 543.00 0.70 380.10 15 2500 685.80 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 34 of 58
AKOYA
MCC-BR - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

FAHU - RF - B1 22.50 0.90 20.25 40 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - RF - B1 18.50 0.90 16.65 20 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - RF - B2 22.50 0.90 20.25 54 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - RF - B2 18.50 0.90 16.65 31 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

PCHP - B1 22.50 0.90 20.25 33 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

PCHP - B2 22.50 0.90 20.25 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1
MCC-BR

PCHP - B3 22.50 0.90 20.25 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

PCHP - B4 22.50 0.90 20.25 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

SCHP - B1 55.00 0.90 49.50 125 89.31 0.77 0.87 0.67 133.32 3/c- 50 1 197 197 0.810 #REF! #REF! 1/c- 25 1

SCHP - B2 55.00 0.90 49.50 125 89.31 0.77 0.87 0.67 133.32 3/c- 50 1 197 197 0.810 #REF! #REF! 1/c- 25 1

SCHP - B3 55.00 0.90 49.50 125 89.31 0.77 0.87 0.67 133.32 3/c- 50 1 197 197 0.810 #REF! #REF! 1/c- 25 1

SCHP - B4 55.00 0.90 49.50 125 89.31 0.77 0.87 0.67 133.32 3/c- 50 1 197 197 0.810 #REF! #REF! 1/c- 25 1

GEF 1.50 0.90 1.35 16 2.44 0.77 0.87 0.67 3.64 4/c- 6 1 56 56 6.400 #REF! #REF! 1/c- 6 1

CW BOOSTER PUMP 4.00 0.90 3.60 16 6.50 0.77 0.87 0.67 9.70 4/c- 4 1 44 44 9.500 #REF! #REF! 1/c- 4 1

TOTALS 397.50 0.90 357.75 1 225 4/c- 120 1/c- 70 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 35 of 58
AKOYA
MCC-BP2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

FAHU - 03 22.50 0.90 20.25 40 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1
MCC-BP2

FAHU - 03 18.50 0.90 16.65 20 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - 04 22.50 0.90 20.25 54 63 36.54 0.77 0.87 0.67 54.54 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU - 04 18.50 0.90 16.65 31 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

TOTALS 82.00 0.90 73.80 1 225 4/c- 120 1/c- 70 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 36 of 58
AKOYA
SMDB-LIFT-B - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

LIFT - PL - 1 25.00 0.90 22.50 15 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 2.07 0.52% 1/c- 16 1

LIFT - PL - 2 25.00 0.90 22.50 48 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 5.29 1.32% 1/c- 16 1

LIFT - PL - 3 25.00 0.90 22.50 78 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 8.21 2.05% 1/c- 16 1
SMDB-LIFT-B

LIFT - SL 25.00 0.90 22.50 48 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 5.29 1.32% 1/c- 16 1

TOTALS 100.00 0.90 90.00 1 300 162.38 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 37 of 58
AKOYA
EMDB-01 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

ESMDB - GA 45.00 0.80 36.00 15 100 64.95 0.77 0.87 0.67 96.96 4/c- 70 1 251 251 0.570 1.16 0.29% 1/c- 35 1

LIFT - PL - 2 25.00 0.90 22.50 48 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 5.29 1.32% 1/c- 16 1

LIFT - PL - 3 25.00 0.90 22.50 78 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 8.21 2.05% 1/c- 16 1

LIFT - SL 25.00 0.90 22.50 48 63 40.60 0.77 0.87 0.67 60.60 4/c- 16 1 99 99 2.400 5.29 1.32% 1/c- 16 1
EMDB - 01

TOTALS 120.00 0.86 103.50 1 300 186.74 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 38 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
SMDB-L6-1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
(TYPICAL FOR SMDB-L2-1, SMDB-L3-1, SMDB-L4-1 & SMDB-L5-1)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
LOAD Length In Ib Table 4C1 Overall C.F. Ampacity It cables in
Cable Ampacity
Ampacity Ita Table 4E4B Voltage Drop required cables in
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-L6-1 6.25 0.90 5.63 10 32 10.15 0.77 0.87 0.67 15.15 4/c- 6 1 56 56 6.400 #REF! #REF! 1/c- 6 1

DB-601 6.35 0.78 4.96 25 40 26.93 0.77 0.87 0.67 40.20 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-602 6.35 0.78 4.96 25 40 26.93 0.77 0.87 0.67 40.20 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-603 3.65 0.80 2.93 22 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-604 3.65 0.80 2.93 22 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-605 4.05 0.79 3.21 19 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-606 4.05 0.79 3.21 19 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-607 3.65 0.80 2.93 17 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -
SMDB-L6-1 (TYPICAL FOR SMDB-L2-1, SMDB-L3-1, SMDB-L4-1 & SMDB-L5-1)

DB-608 3.65 0.80 2.93 17 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-609 4.05 0.79 3.21 14 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-611 4.05 0.79 3.21 10 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-613 4.05 0.79 3.21 10 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-615 3.65 0.80 2.93 10 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-617 4.05 0.79 3.21 12 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-619 3.65 0.80 2.93 15 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-620 4.05 0.79 3.21 18 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-621 4.05 0.79 3.21 18 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-622 4.05 0.79 3.21 21 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-623 3.65 0.80 2.93 21 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-624 3.65 0.80 2.93 25 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-625 4.05 0.79 3.21 25 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-626 3.65 0.80 2.93 30 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-627 3.65 0.80 2.93 30 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-628 4.05 0.79 3.21 32 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-629 4.05 0.79 3.21 32 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-631 3.65 0.80 2.93 35 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-633 4.05 0.79 3.21 36 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-672 4.05 0.79 3.21 61 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-673 4.05 0.79 3.21 61 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-674 3.65 0.80 2.93 65 32 15.90 0.77 0.87 0.67 23.73 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-675 4.05 0.79 3.21 65 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-676 4.05 0.79 3.21 71 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-677 4.05 0.79 3.21 71 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-678 6.35 0.78 4.96 75 40 26.93 0.77 0.87 0.67 40.20 3/c- 16 1 115 115 2.900 #REF! #REF! - -

DB-679 6.35 0.78 4.96 75 40 26.93 0.77 0.87 0.67 40.20 3/c- 16 1 115 115 2.900 #REF! #REF! - -

TOTALS 148.35 0.80 118.24 1 300 213.33 4/c- 240 1 1/c- 120 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (I n) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 39 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
SMDB-B1-2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-B1-2 18.00 0.90 16.20 52 40 29.23 0.77 0.87 0.67 43.63 4/c- 10 1 78 78 3.800 9.02 2.25% 1/c- 10 1

DB-B1-3 8.65 0.90 7.79 10 32 14.05 0.77 0.87 0.67 20.97 4/c- 6 1 56 56 6.400 4.14 1.03% 1/c- 6 1
SMDB-B1-2

DB-LAUN 42.05 0.90 37.88 60 100 68.34 0.77 0.87 0.67 102.01 4/c- 35 1 162 162 1.100 7.75 1.94% 1/c- 16 1

DB-SC 39.40 0.90 35.46 55 80 63.98 0.77 0.87 0.67 95.51 4/c- 25 1 131 131 1.500 8.52 2.13% 1/c- 16 1

TOTALS 108.10 0.90 97.32 1 225 175.59 4/c- 120 1 1/c- 70 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 40 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
SMDB-G2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-EXT2 15.00 0.90 13.50 41 40 24.36 0.77 0.87 0.67 36.36 4/c- 10 1 78 78 3.800 9.35 2.34% 1/c- 10 1

DB-GLP3 19.85 0.90 17.87 10 63 32.23 0.77 0.87 0.67 48.12 4/c- 16 1 99 99 2.400 6.33 1.58% 1/c- 16 1

SPARE 20.00 0.90 18.00 63 32.48


SMDB-G2

TOTALS 54.85 0.90 49.37 1 125 89.07 4/c- 50 1 1/c- 25 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 41 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
SMDB-L1-2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
LOAD Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-L1-2 8.25 0.90 7.43 10 40 13.40 0.77 0.87 0.67 20.00 4/c- 10 1 78 78 3.800 6.11 1.53% 1/c- 10 1

DB-135 4.05 0.79 3.21 55 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 10.10 4.39% - -

DB-137 3.65 0.80 2.93 53 32 15.90 0.77 0.87 0.67 23.73 3/c- 10 1 90 90 4.700 9.56 4.16% - -

DB-138 4.05 0.79 3.21 47 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 9.45 4.11% - -

DB-139 4.05 0.79 3.21 47 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 9.45 4.11% - -

DB-140 3.65 0.80 2.93 43 32 15.90 0.77 0.87 0.67 23.73 3/c- 10 1 90 90 4.700 8.81 3.83% - -

DB-141 3.65 0.80 2.93 43 32 15.90 0.77 0.87 0.67 23.73 3/c- 10 1 90 90 4.700 8.81 3.83% - -

DB-142 4.05 0.79 3.21 37 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 10.69 4.65% - -

DB-143 4.05 0.79 3.21 37 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 10.69 4.65% - -

DB-144 3.65 0.80 2.93 35 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 9.99 4.34% - -

DB-145 3.65 0.80 2.93 35 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 9.99 4.34% - -

DB-146 4.05 0.79 3.21 30 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 9.73 4.23% - -

DB-147 4.05 0.79 3.21 30 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 9.73 4.23% - -

DB-148 3.65 0.80 2.93 28 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 9.11 3.96% - -

DB-149 3.65 0.80 2.93 28 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 9.11 3.96% - -
SMDB-L1-2

DB-151 4.05 0.79 3.21 21 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 8.49 3.69% - -

DB-153 3.65 0.80 2.93 20 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 8.11 3.53% - -

DB-155 4.05 0.79 3.21 20 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 8.35 3.63% - -

DB-157 3.65 0.80 2.93 21 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 8.24 3.58% - -

DB-159 4.05 0.79 3.21 15 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 7.66 3.33% - -

DB-161 3.65 0.80 2.93 12 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 7.10 3.09% - -

DB-162 4.05 0.79 3.21 12 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 7.25 3.15% - -

DB-164 4.05 0.79 3.21 20 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 8.35 3.63% - -

DB-165 4.05 0.79 3.21 20 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 8.35 3.63% - -

DB-166 4.05 0.79 3.21 22 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 8.63 3.75% - -

DB-167 4.05 0.79 3.21 22 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 8.63 3.75% - -

DB-168 4.05 0.79 3.21 27 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 9.31 4.05% - -

DB-169 4.05 0.79 3.21 27 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 9.31 4.05% - -

DB-170 4.05 0.79 3.21 29 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 9.59 4.17% - -

DB-171 4.05 0.79 3.21 29 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 9.59 4.17% - -

TOTALS 121.70 0.80 97.57 1 300 176.04 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 42 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
SMDB-L6-2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)
(TYPICAL FOR SMDB-L2-2, SMDB-L3-2, SMDB-L4-2 & SMDB-L5-2)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
LOAD Length In Ib Table 4C1 Overall C.F. Ampacity It cables in
Cable Ampacity
Ampacity Ita Table 4E4B Voltage Drop required cables in
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-L6-2 5.45 0.90 4.91 10 40 8.85 0.77 0.87 0.67 13.21 4/c- 10 1 78 78 3.800 #REF! #REF! 1/c- 10 1

DB-635 4.05 0.79 3.21 55 32 17.42 0.77 0.87 0.67 26.00 3/c- 16 1 115 115 2.900 #REF! #REF! - -

DB-637 4.05 0.79 3.21 47 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-638 4.05 0.79 3.21 47 32 17.42 0.77 0.87 0.67 26.00 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-639 3.65 0.80 2.93 43 32 15.90 0.77 0.87 0.67 23.73 3/c- 10 1 90 90 4.700 #REF! #REF! - -
SMDB-L6-2 (TYPICAL FOR SMDB-L2-2, SMDB-L3-2, SMDB-L4-2 & SMDB-L5-2)

DB-640 3.65 0.80 2.93 43 32 15.90 0.77 0.87 0.67 23.73 3/c- 10 1 90 90 4.700 #REF! #REF! - -

DB-641 4.05 0.79 3.21 37 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-642 4.05 0.79 3.21 37 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-643 3.65 0.80 2.93 35 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-644 3.65 0.80 2.93 35 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-645 4.05 0.79 3.21 30 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-646 4.05 0.79 3.21 30 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-647 3.65 0.80 2.93 28 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-648 3.65 0.80 2.93 28 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-649 3.65 0.80 2.93 28 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-651 4.05 0.79 3.21 21 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-653 3.65 0.80 2.93 20 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-655 4.05 0.79 3.21 20 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-657 3.65 0.80 2.93 21 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-659 4.05 0.79 3.21 15 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-661 3.65 0.80 2.93 12 32 15.90 0.77 0.87 0.67 23.73 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-662 4.05 0.79 3.21 12 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-664 4.05 0.79 3.21 20 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-665 4.05 0.79 3.21 22 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-666 4.05 0.79 3.21 22 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-667 4.05 0.79 3.21 27 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-668 4.05 0.79 3.21 27 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-669 4.05 0.79 3.21 29 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-670 4.05 0.79 3.21 29 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

DB-671 4.05 0.79 3.21 29 32 17.42 0.77 0.87 0.67 26.00 3/c- 6 1 66 66 7.900 #REF! #REF! - -

TOTALS 118.90 0.80 95.05 1 300 171.50 4/c- 240 1 1/c- 120 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 43 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
MCC-R1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

MUWP1 (DUTY) 4.00 0.90 3.60 74 16 6.50 0.77 0.87 0.67 9.70 4/c- 4 1 44 44 9.500 #REF! #REF! 1/c- 4 1

MUWP2 (DUTY) 4.00 0.90 3.60 73 16 6.50 0.77 0.87 0.67 9.70 4/c- 4 1 44 44 9.500 #REF! #REF! 1/c- 4 1

MUWP3 (STDBY) 4.00 0.90 3.60 72 16 6.50 0.77 0.87 0.67 9.70 4/c- 4 1 44 44 9.500 #REF! #REF! 1/c- 4 1

FAHUZ1-S.FAN (DUTY) 15.00 0.90 13.50 24 63 24.36 0.77 0.87 0.67 36.36 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHUZ1-E.FAN (DUTY) 11.00 0.90 9.90 23 40 17.86 0.77 0.87 0.67 26.66 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

CT1 (DUTY) 15.00 0.90 13.50 23 63 24.36 0.77 0.87 0.67 36.36 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

CT2 (DUTY) 15.00 0.90 13.50 25 63 24.36 0.77 0.87 0.67 36.36 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

CT3 (DUTY) 15.00 0.90 13.50 27 63 24.36 0.77 0.87 0.67 36.36 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

PCHP1 (DUTY) 22.00 0.90 19.80 31 80 35.72 0.77 0.87 0.67 53.33 3/c- 25 2 131 262 1.500 #REF! #REF! 1/c- 16 1

PCHP2 (DUTY) 22.00 0.90 19.80 32 80 35.72 0.77 0.87 0.67 53.33 3/c- 25 2 131 262 1.500 #REF! #REF! 1/c- 16 1

PCHP3 (DUTY) 22.00 0.90 19.80 33 80 35.72 0.77 0.87 0.67 53.33 3/c- 25 2 131 262 1.500 #REF! #REF! 1/c- 16 1
MCC-R1

PCHP4 (STDBY) 22.00 0.90 19.80 34 80 35.72 0.77 0.87 0.67 53.33 3/c- 25 2 131 262 1.500 #REF! #REF! 1/c- 16 1

SCHP1 (DUTY) 30.00 0.90 27.00 26 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 131 131 1.500 #REF! #REF!

SCHP2 (DUTY) 30.00 0.90 27.00 27 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 131 131 1.500 #REF! #REF!

SCHP3 (DUTY) 30.00 0.90 27.00 28 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 131 131 1.500 #REF! #REF!

SCHP4 (STDBY) 30.00 0.90 27.00 29 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 131 131 1.500 #REF! #REF!

CWP1 (DUTY) 37.00 0.90 33.30 26 100 60.08 0.77 0.87 0.67 89.69 3/c- 35 2 162 324 1.100 #REF! #REF! 1/c- 16 1

CWP2 (DUTY) 37.00 0.90 33.30 27 100 60.08 0.77 0.87 0.67 89.69 3/c- 35 2 162 324 1.100 #REF! #REF! 1/c- 16 1

CWP3 (DUTY) 37.00 0.90 33.30 28 100 60.08 0.77 0.87 0.67 89.69 3/c- 35 2 162 324 1.100 #REF! #REF! 1/c- 16 1

CWP4 (STNDBY) 37.00 0.90 33.30 29 100 60.08 0.77 0.87 0.67 89.69 3/c- 35 2 162 324 1.100 #REF! #REF! 1/c- 16 1

FAHU-1 S.FAN 18.50 0.90 16.65 22 63 30.04 0.77 0.87 0.67 44.84 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

FAHU-1 E.FAN 15.00 0.90 13.50 24 63 24.36 0.77 0.87 0.67 36.36 3/c- 16 2 99 198 2.400 #REF! #REF! 1/c- 16 1

Presssurization unit 3.00 0.90 2.70 33 16 4.87 0.77 0.87 0.67 7.27 4/c- 4 1 44 44 9.500 #REF! #REF! 1/c- 4 1

TOTALS 382.50 0.90 344.25 1 1000 621.12 4/c- 240 3 1/c- 120 3

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 44 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
MDB-03 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

ATS-EMDB/EMDB 1017.92 0.92 934.86 30 2000 1686.75 0.77 0.87 0.67 2517.91 1/c- 630 3 892 2676 0.160 2.70 0.67% 1/c- 300 1

SMDB-KIT 230.97 0.90 207.87 75 500 375.06 0.77 0.87 0.67 559.87 4/c- 150 2 406 812 0.290 4.08 1.02% 1/c 150 1

SPARE 125.00 0.50 62.50 250 112.77 0.77


MDB-03

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

TOTALS 1373.89 0.88 1205.24 15 2500 2174.57 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 45 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
EMCC-B1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

GREY WATER
TRANSFER PUMPS 11.00 0.90 9.90 23 40 17.86 0.77 0.87 0.67 26.66 4/c- 10 1 78 78 3.800 6.23 1.56% 1/c- 10 1
1&2
GREY WATER
TRANSFER PUMPS 11.00 0.90 9.90 12 40 17.86 0.77 0.87 0.67 26.66 4/c- 10 1 78 78 3.800 5.49 1.37% 1/c- 10 1
EMCC-B1

3&4

CP-LS-2 15.00 0.90 13.50 43 40 24.36 0.77 0.87 0.67 36.36 4/c- 10 1 78 78 3.800 8.65 2.16% 1/c- 10 1

GWTP 22.00 0.90 19.80 15 63 35.72 0.77 0.87 0.67 53.33 4/c- 16 1 99 99 2.400 5.96 1.49% 1/c- 16 1

TOTALS 59.00 0.90 53.10 1 125 95.81 4/c- 50 1 1/c- 25 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 46 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
ESMDB-1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

EDB-B1-1 5.60 0.90 5.04 20 32 9.09 0.77 0.87 0.67 13.57 4/c- 6 1 56 56 6.400 4.71 1.18% 1/c- 6 1

FIRE JOCKEY PUM 10.00 0.90 9.00 92 40 16.24 0.77 0.87 0.67 24.24 4/c- 10 1 78 78 3.800 9.22 2.31% 1/c- 10 1

ESMDB-B1 161.00 0.90 144.90 85 350 261.44 0.77 0.87 0.67 390.27 4/c- 240 1 546 546 0.210 8.21 2.05% 1/c- 120 1

EMCC-CPSF 50.00 0.90 45.00 25 125 81.19 0.77 0.87 0.67 121.20 4/c- 50 1 197 197 0.810 5.19 1.30% 1/c- 25 1

USMDB-HGI 62.65 1.00 62.65 15 160 113.04 0.77 0.87 0.67 168.74 4/c- 70 1 251 251 0.570 4.51 1.13% 1/c- 35 1

EDR-G1 8.00 0.90 7.20 48 32 12.99 0.77 0.87 0.67 19.39 4/c- 6 1 56 56 6.400 7.53 1.88% 1/c- 6 1

EDB-MDF 10.00 0.90 9.00 30 63 16.24 0.77 0.87 0.67 24.24 4/c- 16 1 99 99 2.400 4.71 1.18% 1/c- 16 1

EDB-GLP1 13.70 0.90 12.33 15 40 22.25 0.77 0.87 0.67 33.21 4/c- 10 1 78 78 3.800 4.81 1.20% 1/c- 10 1
ESMDB-1

EDB-L1-1 5.30 0.90 4.77 30 32 8.61 0.77 0.87 0.67 12.85 4/c- 6 1 56 56 6.400 5.20 1.30% 1/c- 6 1

EDB-L2-1 5.30 0.90 4.77 35 32 8.61 0.77 0.87 0.67 12.85 4/c- 6 1 56 56 6.400 5.47 1.37% 1/c- 6 1

EDB-L3-1 5.30 0.90 4.77 40 32 8.61 0.77 0.87 0.67 12.85 4/c- 6 1 56 56 6.400 5.75 1.44% 1/c- 6 1

EDB-L4-1 5.30 0.90 4.77 45 32 8.61 0.77 0.87 0.67 12.85 4/c- 6 1 56 56 6.400 6.02 1.51% 1/c- 6 1

EDB-L5-1 5.30 0.90 4.77 50 32 8.61 0.77 0.87 0.67 12.85 4/c- 6 1 56 56 6.400 6.30 1.57% 1/c- 6 1

EDB-L6-1 5.30 0.90 4.77 55 32 8.61 0.77 0.87 0.67 12.85 4/c- 6 1 56 56 6.400 6.57 1.64% 1/c- 6 1

EMCC-R1 80.40 0.90 72.36 60 200 130.56 0.77 0.87 0.67 194.89 4/c- 95 1 304 304 0.430 6.91 1.73% 1/c- 50 1

EDB-GSM 10.00 0.90 9.00 108 63 16.24 0.77 0.87 0.67 24.24 4/c- 16 1 99 99 2.400 7.75 1.94% 1/c- 16 1

TOTALS 443.15 0.91 405.10 1 1000 730.91 4/c- 240 3 1/c- 120 3

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 47 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
ESMDB-B1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

CP-CWP 22.00 0.90 19.80 28 63 35.72 0.77 0.87 0.67 53.33 4/c- 16 1 99 99 2.400 10.61 2.65% 1/c- 16 1

CP-CWCP 2.00 0.90 1.80 28 16 3.25 0.77 0.87 0.67 4.85 4/c- 4 1 44 44 9.500 9.07 2.27% 1/c- 4 1

CP-CCWP 37.00 0.90 33.30 28 100 60.08 0.77 0.87 0.67 89.69 4/c- 35 1 162 162 1.100 10.06 2.52% 1/c- 16 1
ESMDB-B1

CP-LS-1 15.00 0.90 13.50 32 40 24.36 0.77 0.87 0.67 36.36 4/c- 10 1 78 78 3.800 11.17 2.79% 1/c- 10 1

CP-LS-3 15.00 0.90 13.50 57 40 24.36 0.77 0.87 0.67 36.36 4/c- 10 1 78 78 3.800 13.49 3.37% 1/c- 10 1

WATER SOFTENING
10.00 0.90 9.00 32 40 16.24 0.77 0.87 0.67 24.24 4/c- 10 1 78 78 3.800 10.19 2.55% 1/c- 10 1
PLANT

CPEF-1 (DUTY) 30.00 0.90 27.00 15 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 152 152 1.900 9.60 2.40% - -

CPEF-2 (DUTY) 30.00 0.90 27.00 15 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 152 152 1.900 9.60 2.40% - -

CPEF-3 (STDBY) 30.00 0.90 27.00 15 80 48.72 0.77 0.87 0.67 72.72 3/c- 25 1 152 152 1.900 9.60 2.40% - -

TOTALS 161.00 0.90 144.90 1 350 261.44 4/c- 240 1 1/c- 120 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 48 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
EMCC-CPSF - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

CPSF-1 (DUTY) 25.00 0.90 22.50 10 63 40.60 0.77 0.87 0.67 60.60 3/c- 16 1 115 115 2.900 6.37 1.59% - -

CPSF-2 (DUTY) 25.00 0.90 22.50 10 63 40.60 0.77 0.87 0.67 60.60 3/c- 16 1 115 115 2.900 6.37 1.59% - -
EMCC-CPSF

CPSF-3 (STDBY) 25.00 0.90 22.50 10 63 40.60 0.77 0.87 0.67 60.60 3/c- 16 1 115 115 2.900 6.37 1.59% - -

TOTALS 50.00 0.90 45.00 1 125 81.19 4/c- 50 1 1/c- 25 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 49 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
USMDB-HGI - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

UDB-G 7.00 1.00 7.00 45 32 12.63 0.77 0.87 0.67 18.85 4/c- 6 1 56 56 6.400 8.15 2.04% 1/c- 6 1

UDB-FCC 7.30 1.00 7.30 85 32 13.17 0.77 0.87 0.67 19.66 4/c- 6 1 56 56 6.400 11.68 2.92% 1/c- 6 1

UDB-SR 22.35 1.00 22.35 30 63 40.33 0.77 0.87 0.67 60.20 4/c- 16 1 99 99 2.400 7.41 1.85% 1/c- 16 1

UDB-B 2.00 1.00 2.00 86 32 3.61 0.77 0.87 0.67 5.39 4/c- 6 1 56 56 6.400 6.50 1.62% 1/c- 6 1

USMDB-L1-1 12.00 1.00 12.00 35 40 21.65 0.77 0.87 0.67 32.32 4/c- 16 1 99 99 2.400 6.33 1.58% 1/c- 16 1

USMDB-L1-2 12.00 1.00 12.00 85 40 21.65 0.77 0.87 0.67 32.32 4/c- 25 1 131 131 1.500 7.27 1.82% 1/c- 16 1
USMDB-HGI

TOTALS 62.65 1.00 62.65 1 160 113.04 4/c- 70 1 1/c- 35 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 50 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
USMDB-L1-1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

UDB-L1-1 2.00 1.00 2.00 8 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 7.02 3.05% - -

UDB-L2-1 2.00 1.00 2.00 14 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 7.53 3.27% - -

UDB-L3-1 2.00 1.00 2.00 20 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 8.05 3.50% - -

UDB-L4-1 2.00 1.00 2.00 26 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 8.56 3.72% - -

UDB-L5-1 2.00 1.00 2.00 32 32 10.87 0.77 0.87 0.67 16.23 3/c- 10 1 90 90 4.700 7.96 3.46% - -

UDB-L6-1 2.00 1.00 2.00 38 32 10.87 0.77 0.87 0.67 16.23 3/c- 10 1 90 90 4.700 8.27 3.60% - -
USMDB-L1-1

TOTALS 12.00 1.00 12.00 1 40 21.65 4/c- 16 1 1/c- 16 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 51 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
USMDB-L1-2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

UDB-L1-2 2.00 1.00 2.00 8 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 7.96 3.46% - -

UDB-L2-2 2.00 1.00 2.00 14 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 8.47 3.68% - -

UDB-L3-2 2.00 1.00 2.00 20 32 10.87 0.77 0.87 0.67 16.23 3/c- 6 1 66 66 7.900 8.99 3.91% - -

UDB-L4-2 2.00 1.00 2.00 26 32 10.87 0.77 0.87 0.67 16.23 3/c- 10 1 90 90 4.700 8.60 3.74% - -

UDB-L5-2 2.00 1.00 2.00 32 32 10.87 0.77 0.87 0.67 16.23 3/c- 10 1 90 90 4.700 8.91 3.87% - -

UDB-L6-2 2.00 1.00 2.00 38 32 10.87 0.77 0.87 0.67 16.23 3/c- 16 1 115 115 2.900 8.47 3.68% - -
USMDB-L1-2

TOTALS 12.00 1.00 12.00 1 40 21.65 4/c- 16 1 1/c- 16 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 52 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
EMCC-R1 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SPF-1 (DUTY) 50.00 0.90 45.00 15 125 81.19 0.77 0.87 0.67 121.20 3/c- 50 1 197 197 0.810 7.90 1.97%

SPF-2 (STDBY) 50.00 0.90 45.00 15 125 81.19 0.77 0.87 0.67 121.20 3/c- 50 1 197 197 0.810 7.90 1.97%

EDB-R1 8.45 0.90 7.61 10 32 13.72 0.77 0.87 0.67 20.48 4/c- 6 1 56 56 6.400 7.79 1.95% 1/c- 6 1

SEF-1 (DUTY) 2.20 0.90 1.98 15 16 3.57 0.77 0.87 0.67 5.33 4/c- 4 1 44 44 9.500 7.42 1.86% 1/c- 4 1

SEF-2 (STDBY) 2.20 0.90 1.98 15 16 3.57 0.77 0.87 0.67 5.33 4/c- 4 1 44 44 9.500 7.42 1.86% 1/c- 4 1

CP-SHCP-1 6.00 0.90 5.40 62 16 9.74 0.77 0.87 0.67 14.54 4/c- 4 1 44 44 9.500 12.65 3.16% 1/c- 4 1

CP-HWRP-1 4.40 0.90 3.96 64 16 7.14 0.77 0.87 0.67 10.67 4/c- 6 1 56 56 6.400 9.84 2.46% 1/c- 6 1
EMCC-R1

CP-HWP-1 4.00 0.90 3.60 60 16 6.50 0.77 0.87 0.67 9.70 4/c- 6 1 56 56 6.400 9.41 2.35% 1/c- 6 1

CP-HWP-2 2.00 0.90 1.80 58 16 3.25 0.77 0.87 0.67 4.85 4/c- 6 1 56 56 6.400 8.12 2.03% 1/c- 6 1

LPF-1 (DUTY) 10.00 0.90 9.00 55 32 16.24 0.77 0.87 0.67 24.24 3/c- 10 1 78 78 3.800 10.31 2.58%

LPF-2 (STDBY) 10.00 0.90 9.00 55 32 16.24 0.77 0.87 0.67 24.24 3/c- 10 1 78 78 3.800 10.31 2.58%

LPF-3 (DUTY) 10.00 0.90 9.00 45 32 16.24 0.77 0.87 0.67 24.24 3/c- 6 1 56 56 6.400 11.59 2.90%

LPF-4 (STDBY) 10.00 0.90 9.00 45 32 16.24 0.77 0.87 0.67 24.24 3/c- 6 1 56 56 6.400 11.59 2.90%

TOTALS 97.05 0.90 87.35 1 200 157.59 4/c- 95 1 1/c- 50 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 53 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
ESMDB-G - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

EDB-SC 4.80 0.90 4.32 52 32 7.79 0.77 0.87 0.67 11.64 4/c- 6 1 56 56 6.400 6.16 1.54% 1/c- 6 1
EDB-B1-2 8.90 0.90 8.01 49 32 14.45 0.77 0.87 0.67 21.57 4/c- 6 1 56 56 6.400 8.10 2.03% 1/c- 6 1

EDB-GLP3 12.70 0.90 11.43 35 40 20.62 0.77 0.87 0.67 30.78 4/c- 10 1 78 78 3.800 6.31 1.58% 1/c- 10 1

EDB-KIT 28.57 0.90 25.71 35 63 46.39 0.77 0.87 0.67 69.25 4/c- 16 1 99 99 2.400 7.47 1.87% 1/c- 16 1

EDR-G2 7.00 0.90 6.30 30 32 11.37 0.77 0.87 0.67 16.97 4/c- 6 1 56 56 6.400 5.75 1.44% 1/c- 6 1

EDB-L1-2
ESMDB-G

4.70 0.90 4.23 40 32 7.63 0.77 0.87 0.67 11.39 4/c- 6 1 56 56 6.400 5.52 1.38% 1/c- 6 1

EDB-L2-2 9.10 0.90 8.19 45 40 14.78 0.77 0.87 0.67 22.06 4/c- 10 1 78 78 3.800 6.10 1.52% 1/c- 10 1

EDB-L3-2 4.70 0.90 4.23 50 32 7.63 0.77 0.87 0.67 11.39 4/c- 6 1 56 56 6.400 6.01 1.50% 1/c- 6 1

EDB-L4-2 4.70 0.90 4.23 55 32 7.63 0.77 0.87 0.67 11.39 4/c- 6 1 56 56 6.400 6.25 1.56% 1/c- 6 1

EDB-L5-2 4.70 0.90 4.23 60 32 7.63 0.77 0.87 0.67 11.39 4/c- 6 1 56 56 6.400 6.50 1.62% 1/c- 6 1

EDB-L6-2 4.70 0.90 4.23 65 32 7.63 0.77 0.87 0.67 11.39 4/c- 6 1 56 56 6.400 6.74 1.69% 1/c- 6 1

EDB-R2 4.80 0.90 4.32 70 32 7.79 0.77 0.87 0.67 11.64 4/c- 6 1 56 56 6.400 7.06 1.77% 1/c- 6 1

TOTALS 99.37 0.90 89.43 1 225 161.36 4/c- 120 1 1/c- 70 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 54 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
ESMDB-LIFT - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

LIFT-S1 16.00 0.90 14.40 60 63 25.98 0.77 0.87 0.67 38.78 4/c- 16 1 99 99 2.400 #REF! #REF! 1/c- 16 1

LIFT-S2 16.00 0.90 14.40 60 63 25.98 0.77 0.87 0.67 38.78 4/c- 16 1 99 99 2.400 #DIV/0! #DIV/0! 1/c- 16 1
ESMDB-LIFT

LIFT-P1 13.00 0.90 11.70 60 40 21.11 0.77 0.87 0.67 31.51 4/c- 10 1 78 78 3.800 #DIV/0! #DIV/0! 1/c- 10 1

LIFT-P2 13.00 0.90 11.70 60 40 21.11 0.77 0.87 0.67 31.51 4/c- 10 1 78 78 3.800 #DIV/0! #DIV/0! 1/c- 10 1

LIFT-P3 13.00 0.90 11.70 60 40 21.11 0.77 0.87 0.67 31.51 4/c- 10 1 78 78 3.800 #DIV/0! #DIV/0! 1/c- 10 1

LIFT-P4 13.00 0.90 11.70 60 40 21.11 0.77 0.87 0.67 31.51 4/c- 10 1 78 78 3.800 4.81 1.20% 1/c- 10 1

TOTALS 84.00 0.90 75.60 1 200 136.40 4/c- 95 1 1/c- 50 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 55 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
EMCC-R2 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

SPF-3 (DUTY) 50.00 0.90 45.00 58 125 81.19 0.77 0.87 0.67 121.20 3/c- 50 1 197 197 0.810 22.21 5.55%

SPF-4 (STBY) 50.00 0.90 45.00 58 125 81.19 0.77 0.87 0.67 121.20 3/c- 50 1 197 197 0.810 22.21 5.55%

SPF-5 (DUTY) 50.00 0.90 45.00 30 125 81.19 0.77 0.87 0.67 121.20 3/c- 50 1 197 197 0.810 20.37 5.09%

SPF-6 (STBY) 50.00 0.90 45.00 30 125 81.19 0.77 0.87 0.67 121.20 3/c- 50 1 197 197 0.810 20.37 5.09%

CPF-1 (DUTY) 11.00 0.90 9.90 40 40 17.86 0.77 0.87 0.67 26.66 4/c- 10 1 78 78 3.800 21.11 5.28% 1/c- 10 1

CPF-2 (STBY) 11.00 0.90 9.90 40 40 17.86 0.77 0.87 0.67 26.66 4/c- 10 1 78 78 3.800 21.11 5.28% 1/c- 10 1

SEF-3 (DUTY) 2.20 0.90 1.98 58 16 3.57 0.77 0.87 0.67 5.33 4/c- 4 1 44 44 9.500 20.36 5.09% 1/c- 4 1
EMCC-R2

SEF-4 (STBY) 2.20 0.90 1.98 58 16 3.57 0.77 0.87 0.67 5.33 4/c- 4 1 44 44 9.500 20.36 5.09% 1/c- 4 1

LPF-5 (DUTY) 7.50 0.90 6.75 42 32 12.18 0.77 0.87 0.67 18.18 3/c- 6 1 56 56 6.400 21.67 5.42%

LPF-6 (STBY) 7.50 0.90 6.75 42 32 12.18 0.77 0.87 0.67 18.18 3/c- 6 1 56 56 6.400 21.67 5.42%

LPF-7 (DUTY) 7.50 0.90 6.75 25 32 12.18 0.77 0.87 0.67 18.18 3/c- 6 1 56 56 6.400 20.34 5.09%

LPF-8 (STBY) 7.50 0.90 6.75 25 32 12.18 0.77 0.87 0.67 18.18 3/c- 6 1 56 56 6.400 20.34 5.09%

SEF-5 (DUTY) 2.20 0.90 1.98 30 16 3.57 0.77 0.87 0.67 5.33 4/c- 4 1 44 44 9.500 19.41 4.85% 1/c- 4 1

SEF-6 (STBY) 2.20 0.90 1.98 30 16 3.57 0.77 0.87 0.67 5.33 4/c- 4 1 44 44 9.500 19.41 4.85% 1/c- 4 1

Solar Thermal Eqpt 7.00 0.90 6.30 40 32 11.37 0.77 0.87 0.67 16.97 4/c- 10 1 78 78 3.800 20.12 5.03% 1/c- 10 1

LPG VAPOURISER 5.00 0.90 4.50 30 20 8.12 0.77 0.87 0.67 12.12 4/c- 6 1 56 56 6.400 19.95 4.99% 1/c- 6 1

TOTALS 142.40 0.90 128.16 1 300 231.24 4/c- 185 1 1/c- 95 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 56 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
SMDB-KIT - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

DB-KIT1 29.42 0.90 26.48 10 80 47.77 0.77 0.87 0.67 71.31 4/c- 25 1 131 131 1.500 4.80 1.20% 1/c- 16 1

DB-KIT2 56.35 0.90 50.72 10 125 91.50 0.77 0.87 0.67 136.59 4/c- 50 1 197 197 0.810 4.82 1.20% 1/c- 25 1

KITCHEN-BD-Item 11 7.00 0.90 6.30 30 16 11.37 0.77 0.87 0.67 16.97 4/c- 6 1 56 56 6.400 6.26 1.57% 1/c- 6 1

KITCHEN-DW-Item 4 75.00 0.90 67.50 35 160 121.79 0.77 0.87 0.67 181.80 4/c- 70 1 251 251 0.570 6.51 1.63% 1/c- 35 1

KITCHEN-DW-Item 5 28.00 0.90 25.20 30 63 45.47 0.77 0.87 0.67 67.87 4/c- 16 1 99 99 2.400 7.35 1.84% 1/c- 16 1

KITCHEN-HK-Item 9 7.20 0.90 6.48 30 16 11.69 0.77 0.87 0.67 17.45 4/c- 6 1 56 56 6.400 6.32 1.58% 1/c- 6 1
SMBB-KIT

KITCHEN-HK-Item 12 6.00 0.90 5.40 30 16 9.74 0.77 0.87 0.67 14.54 4/c- 6 1 56 56 6.400 5.95 1.49% 1/c- 6 1

KITCHEN-HK-Item 17 7.00 0.90 6.30 30 16 11.37 0.77 0.87 0.67 16.97 4/c- 6 1 56 56 6.400 6.26 1.57% 1/c- 6 1

SPARE 15.00 0.90 13.50 40 24.36

TOTALS 230.97 0.90 207.87 1 500 375.06 4/c- 150 2 1/c- 150 1

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 57 of 58
HILTON - GARDEN INN, AL BARSHA, DUBAI
MDB-04 - CABLE SIZING & VOLTAGE DROP CALCULATION (BS)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Power (kW) Cable CPD Design Current Correction Factor (C.F.) Corrected Cable Cable size Equivalent Voltage Drop Percentage ECC Cable size
No. of Voltage Drop No. of ECC
required Table 4E4A
Length In Ib Table 4C1 Overall C.F. Ampacity It cables in Ampacity Ita Table 4E4B Voltage Drop required cables in
LOAD Cable Ampacity
TCL DF EMD Grouping (Cg) parallel parallel
(A)
(m) (A) (A) Amb. Temp. (Ca) (Ca x Cg) (A) ( mm2 ) required (A) (mV/A-m) (V) (%) ( mm2 ) required

CHILLER-1 235.00 0.90 211.50 80 500 381.60 0.77 0.87 0.67 569.64 4/c- 150 2 406 812 0.290 4.43 1.11% 1/c- 150 1

CHILLER-2 235.00 0.90 211.50 80 500 381.60 0.77 0.87 0.67 569.64 4/c- 150 2 406 812 0.290 4.43 1.11% 1/c- 150 1

CHILLER-3 235.00 0.90 211.50 80 500 381.60 0.77 0.87 0.67 569.64 4/c- 150 2 406 812 0.290 4.43 1.11% 1/c- 150 1

SPARE 140.00 0.90 126.00 227.34


MDB-04

SPARE 100.00 0.90 90.00 162.38

PFC 350 kVAr 8 STEP AUTO PFC 10 800 0.00 0.77 0.87 0.67 1194.21 4/c- 300 2 628 1256 0.185 0.00 0.00% 1/c- 300 1

TOTALS 945.00 0.90 850.50 1 2500 1534.53 1/c- 630 11

Legend:
CPD -Circuit Protective Device
VD -Voltage Drop

Notes:
1 Overcurrent device rating in column 4 (In) must be greater than or equal to design current (I b) in column 5. ( I n > I b )
2 Current values in column 13 ( Ita ) must always exceed Corrected Cable Current-carrying Capacity (Ampacity) rating in column 9 ( It ).
3 Column 9 = column 4 / column 8
4 Column 10 selected to suit column 9
5 Column 16 calculated according to columns 10 and 11.
6 Columns 10 and 11 adjusted if column 16 (Percentage Voltage Drop) exceeds 4%.
7 Nominal system voltage is 400/230V ±6%, 3 Phase, 4 Wire.

Page 58 of 58