Anda di halaman 1dari 2

DESIGN LOAD CALCULATION (35 derjat)

CONDUCTOR

A.1. VERTICAL LOAD


Normal Condition
Conductor weight = 1 x 476.61 x 0.00968 = 4.613 kN
Insulator weight = 2 2.969 = 5.939 kN
Total = 10.552 kN
Over Load Factor = 1.5 = 15.828 kN

Broken Condition
Conductor weight = 1 x 476.61 x 0.00968 = 4.613 kN
Insulator weight = 2 2.969 = 5.939 kN
Total = 10.552 kN
Over Load Factor = 1.1 = 11.607 kN

A.2. TRANSVERSE WIND LOAD


Normal Condition
Wind On Conductor = 1 x 369 x 0.392 x 0.0219 = 3.170 kN
Wind On Insulator = 2 x 0.286 x 1.68 x 0.588 = 0.565 kN
Line Angle = 2 x sin 17.5 degree x 24.00 = 14.434 kN
Total = 18.169 kN
Over Load Factor = 1.5 = 27.254 kN

Broken Condition
Wind On Conductor = 1 x 369 x 0.392 x 0.0219 = 3.170 kN
Wind On Insulator = 2 x 0.286 x 1.68 x 0.588 = 0.565 kN
Line Angle = 1 x sin 17.5 degree x 24.00 = 7.217 kN
Total = 10.952 kN
Over Load Factor = 1.1 = 12.048 kN

A.3. LONGITUDINAL WIND LOAD


Normal Condition
Wind On Conductor = sin 17.5 degree x 3.170 = 0.953 kN
Line Angle = 2 x sin 17.5 degree x 24.00 = 14.434 kN
Total = 15.387 kN
Over Load Factor = 1.5 = 23.081 kN

Broken Condition
Wind On Conductor = sin 17.5 degree x 3.170 = 0.953 kN
Line Angle = 1 x sin 17.5 degree x 24.00 = 7.217 kN
Total = 8.170 kN
Over Load Factor = 1.1 = 8.987 kN

A.4. LONGITUDINAL LOAD


Longitudinal Load = 100% x cos 17.5 degree x 24.00 = 22.889 kN
Over Load Factor = 1.1 Total = 25.178 kN
DESIGN LOAD CALCULATION (35 derjat)
EARTH WIRE

B.1. VERTICAL LOAD


Normal Condition
Earth wire weight = 1 x 476.61 x 0.00437 = 2.084 kN
Accesorries weight = 0.049 = 0.049 kN
Total = 2.133 kN
Over Load Factor = 1.5 = 3.200 kN

Broken Condition
Earth wire weight = 1 x 476.61 x 0.00437 = 2.084 kN
Insulator weight = 0.049 = 0.049 kN
Total = 2.133 kN
Over Load Factor = 1.1 = 2.347 kN

B.2. TRANSVERSE WIND LOAD


Normal Condition
Wind on earth wire = 1 x 369 x 0.392 x 0.0096 = 1.390 kN
Line Angle = 2 x sin 17.5 degree x 14.00 = 8.420 kN
Total = 9.809 kN
Over Load Factor = 1.5 = 14.714 kN

Broken Condition
Wind on earth wire = 1 x 369 x 0.392 x 0.0096 = 1.390 kN
Line Angle = 1 x sin 17.5 degree x 14.00 = 4.210 kN
Total = 5.599 kN
Over Load Factor = 1.1 = 6.159 kN

B.3. LONGITUDINAL WIND LOAD


Normal Condition
Wind On Conductor = sin 17.5 degree x 1.390 = 0.418 kN
Line Angle = 2 x sin 17.5 degree x 14.00 = 8.420 kN
Total = 8.838 kN
Over Load Factor = 1.5 = 13.256 kN

Broken Condition
Wind On Conductor = sin 17.5 degree x 1.390 = 0.418 kN
Line Angle = 1 x sin 17.5 degree x 14.00 = 4.210 kN
Total = 4.628 kN
Over Load Factor = 1.1 = 5.091 kN

B.4. LONGITUDINAL LOAD


Longitudinal Load = 100% x cos 17.5 degree x 14.00 = 13.352 kN
Over Load Factor = 1.1 Total = 14.687 kN