Technical Specifications – Surge Arresters


Section VII.VIII
Page VII.VIII-1

1 TECHNICAL DATA SCHEDULES


1.1 SURGE ARRESTER 288 kV, WITH DISCHARGE COUNTER

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 288 kV, WITH DISCHARGE COUNTER
CODE No: 4141

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer - -
1.1 Type - station metal
oxide gapless
1.2 Model - -
1.3 Country of origin - -
2.0 Nominal characteristics
2.1 Rated network maximum operating KV 362
voltage
2.2 Rated arrester voltage (Ur) KV 288
2.3 Rated continuous operating voltage (Uc) KV 230
2.4 Rated discharge current (peak) KA 20
2.5 Switching impulse current (peak) KA 2
2.6 Line discharge class (IEC 99-4) - 4
2.7 Rated frequency Hz 50

3.0 Protection characteristics


3.1 Max. residual voltages

- For a steep impulse current, 1 s front, kV 825


20 kA
- For a lightning impulse current, 8/20 kV 745
s, 20 kA
- For a switching impulse current, 30 s kV 625
30/60 s, 2 kA
3.2 Energy dissipation capacity kJ/kV -

Document TS 4140 Rev. 2 Implementation of Substation Projects-2010


TRANSMISSION COMPANY OF NIIGERIA (TCN).
Technical Specifications – Surge Arresters
Section VII.VIII
Page VII.VIII-2

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 288 kV, WITH DISCHARGE COUNTER
CODE No: 4141

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED


4.0 Operating performances
4.1 High current impulse withstand (4/10 s) kA 100
4.2 Temporary over voltage withstand (for kV 288
10 s)
4.3 Line discharge current withstand:
- peak duration s -
- line characteristic impedance ohms -
- charging voltage (peak value) kV -
5.0 Insulation levels
- lightning impulse withstand voltage kV 1050
- power frequency withstand voltage kV 510
(1min. wet)
- creepage distance mm/kV 31

-
- cantilever strength kN -
- torsion strength N-m
6.0 Pressure relief capacity
- current amplitude (rms) kA 31.5
- X/R, asymmetry factor - 17
- current duration s 0,2
7.0 External radio interference voltage
(RIV)
- RIV max. voltage level (IEC 694) at V 2500
0,5 MHz and 362 kV test voltage to
ground
8.0 Weights and dimensions:
- arrester height mm -
- arrester diameter mm -
– weight kg -
9.0 Accessories
9.1 Mounting hardware - Yes
9.2 Ground connector - Yes
9.3 Insulating bases - Yes
9.4 Discharge counter model - Yes

Document TS 4140 Rev. 2 Implementation of Substation Projects-2010


TRANSMISSION COMPANY OF NIIGERIA (TCN).
Technical Specifications – Surge Arresters
Section VII.VIII
Page VII.VIII-3

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 288 kV, WITH DISCHARGE COUNTER
CODE No: 4141

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED


10.0 Type test reports - To be included
with bid
11.0 Standards -
12.0 Quality control -
13.0 Installation - Outdoor,
desertic/tropical
environment

Document TS 4140 Rev. 2 Implementation of Substation Projects-2010


TRANSMISSION COMPANY OF NIIGERIA (TCN).
Technical Specifications – Surge Arresters
Section VII.VIII
Page VII.VIII-4

1.2 SURGE ARRESTER 120 kV, 145KV, WITH DISCHARGE COUNTER

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 120 kV, WITH DISCHARGE COUNTER
CODE No: 4143

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer - -
1.1 Type - station metal
oxide gapless
1.2 Model - -
1.3 Country of origin - -
2.0 Nominal characteristics
2.1 Rated max. network operating voltage kV 145
2.2 Rated operating voltage (Ur) kV 120
2.3 Rated continuous operating voltage (Uc) kV 92
2.4 Rated discharge current (peak) kA 10
2.5 Switching impulse current (peak) kA 0.5
2.6 Line discharge class (IEC 99-4) - 3
2.7 Rated frequency Hz 50
3.0 Protection characteristics
3.1 Max. residual voltages

- for a steep impulse current, 1 s front, Kv 350


10 kA
- for a lightning impulse current, 8/20 s, Kv 300
10 kA
- for a switching impulse current, kV 260
30/60 s, 0,5 kA
3.2 Energy dissipation capacity kJ/kV -

4.0 Operating performances


4.1 High current impulse withstand kA 100
(4/10 s)
4.2 Temporary over voltage withstand (for kV 120
10 s)
4.3 Line discharge current withstand:
- Peak duration s -
- Line characteristic impedance ohms -
- Charging voltage (peak value) kV -

Document TS 4140 Rev. 2 Implementation of Substation Projects-2010


TRANSMISSION COMPANY OF NIIGERIA (TCN).
Technical Specifications – Surge Arresters
Section VII.VIII
Page VII.VIII-5

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 120 kV, WITH DISCHARGE COUNTER
CODE No: 4143

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED


5.0 Insulation levels
- Lightning impulse withstand voltage kV 550
- Power frequency withstand voltage (1m kV 185
wet)
- Creepage distance mm/kV 31

- Cantilever strength kN -
- Torsion strength N-m -

6.0 Pressure relief capacity


- Current amplitude (rms) kA 31.5
- X/R, asymmetry factor - 17
- Current duration s 0.2
7.0 External radio interference voltage N/A
(RIV)
8.0 Weights and dimensions:
- arrester height mm -
- arrester diameter mm -
– weight kg -
9.0 Accessories
9.1 Mounting hardware - Yes
9.2 Ground connector - Yes
9.3 Insulating bases - Yes
9.4 Discharge counter model - -
10.0 Type test reports number - To be included
with bid
11.0 Installation - Outdoor, in
desertic/tropical
environment

Document TS 4140 Rev. 2 Implementation of Substation Projects-2010


TRANSMISSION COMPANY OF NIIGERIA (TCN).
Technical Specifications – Surge Arresters
Section VII.VIII
Page VII.VIII-6

1.3 SURGE ARRESTER 30 kV, WITH DISCHARGE COUNTER

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 30 kV, WITH DISCHARGE COUNTER
CODE No: 4144

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED

1.0 Manufacturer - -
1.1 Type - station metal
oxide gapless
1.2 Model - -
1.3 Country of origin - -
2.0 Nominal characteristics
2.1 Rated max. network operating voltage kV 36
2.2 Rated operating voltage (Ur) kV 30
2.3 Rated continuous operating voltage (Uc) kV 24
2.4 Rated discharge current (peak) kA 10
2.5 Switching impulse current (peak) kA 0.5
2.6 Line discharge class (IEC 99-4) - 3
2.7 Rated frequency Hz 50
3.0 Protection characteristics
3.1 Max. residual voltages

- for a steep impulse current, 1 s front, kV 90


10 kA
- for a lightning impulse current, 8/20 s, kV 80
10 kA
- for a switching impulse current, kV 65
30/60 s, 0,5 kA
3.2 Energy dissipation capacity kJ/kV -

4.0 Operating performances


4.1 High current impulse withstand kA 100
(4/10 s)
4.2 Temporary over voltage withstand (for kV 30
10 s)
4.3 Line discharge current withstand:
- Peak duration s -
- Line characteristic impedance ohms -
- Charging voltage (peak value) kV -

Document TS 4140 Rev. 2 Implementation of Substation Projects-2010


TRANSMISSION COMPANY OF NIIGERIA (TCN).
Technical Specifications – Surge Arresters
Section VII.VIII
Page VII.VIII-7

TECHNICAL DATA SCHEDULE


SURGE ARRESTER 30 kV, WITH DISCHARGE COUNTER
CODE No: 4144

ITEM DESCRIPTION UNITS REQUIRED GUARANTEED


5.0 Insulation levels
- Lightning impulse withstand voltage kV 170
- Power frequency withstand voltage (1m kV 70
wet)
- Creepage distance mm/kV 31
-
- Cantilever strength kN -
- Torsion strength N-m
6.0 Pressure relief capacity
- Current amplitude (rms) kA 17.5
- X/R, asymmetry factor - 17
- Current duration s 0.2
7.0 External radio interference voltage N/A
(RIV)
8.0 Weights and dimensions:
- arrester height mm -
- arrester diameter mm -
– weight kg -
9.0 Accessories
9.1 Mounting hardware - Yes
9.2 Ground connector - Yes
9.3 Insulating bases - Yes
9.4 Discharge counter model - -
10.0 Type test reports number - To be included
with bid
11.0 Installation - Outdoor, in
desertic/tropical
environment