Anda di halaman 1dari 10

Trihal - Up to 3150 kVA

Cast Resin Transformers

eco
design

Standard
Trihal at a glance These transformers comply with standards:

Cast resin, 50 Hz, three-phased • IEC 60076-11, PrEN 50588


distribution transformers with the following • Ecodesign Directive EU 548-2014
characteristics: Indoor use / Outdoor use Schneider Electric guarantees that its transformers are:
with properly designed enclosure.
• C3* Climatic class
• Thermal class F - Temperature rise 100 K • E3 Environment class according to IEC 60076-16
• Ambient ≤ 40°C, altitude ≤ 1000 m • F1 Fire behaviour class
• MV windings encapsulated in cast resin • Almost partial discharge free - Acceptance level:
• Pre-impregnated LV windings ≤ 10 pC Routine Test
• Natural air cooling system (AN type) ≤ 5 pC Special Test according to IEC 60076 standard
• Core and frame covered with protective
coating

* C2 Thermal shock test carried out at -50°C


MV Distribution // Cast Resin Transformers schneider-electric.com | 2

Trihal
Up to 3150 kVA

Ecodesign regulation EU 548-2014

eco
• Maximal Loss levels
• Statement on Loss tolerences:
-- No tolerance on transformer design

design -- 5% tolerance for end user checks


• Additional data requested on the name plates
-- Loss level and measured values
-- Type and weight of mail materials use
-- CE Marking is MANDATORY

A0 Dry Type Transformers maximum loss levels according to Ecodesign:

Ak • Insulation voltage: MV ≤ 24kV & LV ≤ 1.1kV


-- A0Bk up to 630kVA
Bk -- A0Ak over 630kVA
• Insulation voltage: MV ≤36kV & LV ≤ 1.1kV
Ck -- A0 + 15% Bk + 10% ≤ 630kVA
-- A0 + 15% Ak + 10% > 630kVA

Standard fittings

• Trihal without enclosure (IP00):



-- HV voltage variation by off circuit tapping links
-- 4 bi-directional flat rollers
-- 4 lifting holes
-- 4 haulage holes on the underbase
-- 2 earthing points
-- 1 rating plate (on HV side)

• Trihal with IP31 metal enclosure (except underframe IP21):


-- 2 lifting lugs for transformer and enclosure assembly
-- 1 earthing point on enclosure
-- access to HV tapping by removing a bolted panel
-- enclosure final colour RAL9002.
MV Distribution // Cast Resin Transformers schneider-electric.com | 3

Trihal
Up to 3150 kVA

Connections - Trihal transformers without enclosure housing (IP 00)


The winding resin coating and the plug-in connectors don’t ensure any protection against touch when the transformer
is energized. The contractor must ensure that cables and busbars are adequately supported to prevent mechanical
stresses from being imposed on the transformer terminals, busbars or bushings.

Minimum clearances required HV and LV standard connection

SM100019
SM100018

cable support

Insulation Dimension X (mm)


X LV n HV
LV (kV)
Full wall Grid wall

X X 7.5 90 300

12 120 300 120 120


mini mini

17.5-24 220 300


HV
X

Connections -Trihal transformers with IP 31 metal enclosure


Minimum clearances required HV and LV standard connection
SM100020

SM100021

200 mm

LV n HV
LV
200 mm

cable support

cable support
200 mm

HV

500 mm*

LV terminations HV terminations
SM100022

SM100023

70 80
23.5

23.5

40 33 33
15

Ø 14
33

33

33

4 x Ø 14 4 x Ø 14

50
160 to 400 kVA* 500 to 800 kVA* 1000 to 1250 kVA*
thickness 5 thickness 6 thickness 10

100 160
50 80 40
25

35
50

4 x Ø 14 4 x Ø 16
Ø 13
50

1600 kVA* 2000 kVA* thickness 10


thickness 12 2500 kVA* thickness 2u10
*Valid for aluminium terminations.

The contractor must ensure that cables and busbars are adequately supported to prevent mechanical stresses from
being imposed on the transformer terminals, busbars or bushings.
MV Distribution // Cast Resin Transformers schneider-electric.com | 4

Trihal
7.2 kV and 12 kV A0Ak

Electrical characteristics
Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150
Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50
Primary voltage (V) 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000
Isolation level (kV) 12 12 12 12 12 12 12 12 12 12 12 12
Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400
Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5
Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn
Losses (W) - no-load losses 520 620 750 900 1100 1300 1550 1800 2200 2600 3100 3800
Losses (W) - load losses at 120°C 3400 3900 4500 5630 7100 8000 9000 11000 13000 16000 19000 22000
Rated impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6 6
Max altitude (m) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40
Nature of HV/LV windings AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI
Nature of conductor ALU ALU ALU ALU ALU ALU ALU ALU ALU ALU ALU ALU
Core material GO GO GO GO GO GO GO GO GO GO GO GO
Conductor weight (kg) 210 250 315 275 330 395 520 510 680 910 975 1230

E/2
J J L I
Dimensions and weights without enclosure housing (IP00)
Dimensions and weights are for guidance only, and are provided for a
single-voltage transformer with the following HV insulation levels and low Ø 13

voltages. Only the definitive drawings following from the order will commit tapping
links
C
us contractually.
M
H
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
B

terminal
40 (50)
D
Ø 125 (160) D
A E

Insulation level: 7.2 kV and 12 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1290 1355 1370 1420 1500 1530 1620 1700 1830 1880 2050 2330

- Width B 680 800 800 800 800 800 950 950 950 1230 1230 1270

- Height C 1340 1430 1510 1550 1570 1720 1880 1940 2140 2220 2250 2680

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1180 1400 1600 1780 2080 2400 3020 3600 4180 5160 6240 10060

Dimensions and weights with IP31 metal enclosure


Dimensions and weights are for guidance only, and are provided for a
Ø 13
single-voltage transformer with the following HV insulation levels and low
voltages. Only the definitive drawings following from the order will commit tapping
links C

us contractually.
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
terminal 40 G
(50)
D
Ø 125 (160) D
A B

Insulation level: 7.2 kV and 12 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1650 1700 1800 1800 1800 1900 2150 2150 2130 2180 2350 2630

- Width B 950 1020 1020 1020 1020 1100 1170 1170 980 1230 1230 1270

- Height C 1750 1900 2050 2050 2050 2480 2480 2480 2440 2620 2650 3080

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight with enclosure (kg) 1340 1580 1790 1870 2270 2620 3320 3900 4470 5470 6565 10470
MV Distribution // Cast Resin Transformers schneider-electric.com | 5

Trihal
7.2 kV and 12 kV A0Bk

Electrical characteristics
Rated power (kVA) 250 315 400 500 630
Rated frequency (Hz) 50 50 50 50 50
Primary voltage (V) 10000 10000 10000 10000 10000
Isolation level (kV) 12 12 12 12 12
Secondary voltage at no-load (V) 400 400 400 400 400
Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5
Vector groups Dyn Dyn Dyn Dyn Dyn
Losses (W) - no-load losses 520 623 750 900 1100
Losses (W) - load losses at 120°C 3800 4550 5500 6425 7600
Rated impedance voltage (%) 6 6 6 6 6
Max altitude (m) 1000 1000 1000 1000 1000
Max ambiental temperature (C) 40 40 40 40 40
Nature of HV/LV windings AI/AI AI/AI AI/AI AI/AI AI/AI
Nature of conductor ALU ALU ALU ALU ALU
Core material GO GO GO GO GO
Conductor weight (kg) 195 200 220 250 310
E/2
J J L I
Dimensions and weights without enclosure housing (IP00)
Dimensions and weights are for guidance only, and are provided for a
single-voltage transformer with the following HV insulation levels and low Ø 13

voltages. Only the definitive drawings following from the order will commit tapping
links
C
us contractually.
M
H
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
B

terminal
40 (50)
D
Ø 125 (160) D
A E

Insulation level: 7.2 kV and 12 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1270 1290 1320 1370 1410

- Width B 680 800 800 800 800

- Height C 1340 1410 1510 1530 1660

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight without enclosure (kg) 1140 1260 1460 1640 1880

Dimensions and weights with IP31 metal enclosure


Dimensions and weights are for guidance only, and are provided for a
Ø 13
single-voltage transformer with the following HV insulation levels and low
voltages. Only the definitive drawings following from the order will commit tapping
links C

us contractually.
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
terminal 40 G
(50)
D
Ø 125 (160) D
A B

Insulation level: 7.2 kV and 12 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1650 1700 1800 1800 1900

- Width B 950 1020 1020 1020 1100

- Height C 1750 1900 2050 2050 2300

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight with enclosure (kg) 1300 1440 1650 1850 2100


MV Distribution // Cast Resin Transformers schneider-electric.com | 6

Trihal
17.5 kV and 24 kV A0Ak

Electrical characteristics for insulation level: 17.5 kV and 24 kV


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150
Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50
Primary voltage (V) 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
Isolation level (kV) 24 24 24 24 24 24 24 24 24 24 24 24
Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400
Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5
Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn
Losses (W) - no-load losses 520 620 750 900 1100 1300 1550 1800 2200 2600 3100 3800
Losses (W) - load losses at 120°C 3400 3900 4500 5630 7100 8000 9000 11000 13000 16000 19000 22000
Rated impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6 6
Max altitude (m) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40
Nature of conductor ALU ALU ALU ALU ALU ALU ALU ALU ALU ALU ALU ALU
Core material GO GO GO GO GO GO GO GO GO GO GO GO
Conductor weight (kg) 195 180 230 234 287 330 418 513 631 770 835 1100

E/2
J J L I
Dimensions and weights without enclosure housing (IP00)
Dimensions and weights are for guidance only, and are provided for a
single-voltage transformer with the following HV insulation levels and low Ø 13

voltages. Only the definitive drawings following from the order will commit tapping
links
C
us contractually.
M
H
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
B

terminal
40 (50)
D
Ø 125 (160) D
A E

Insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1320 1365 1410 1460 1480 1630 1660 1740 1850 1960 2050 2320

- Width B 730 810 820 830 830 850 950 950 970 1230 1230 1270

- Height C 1430 1520 1600 1640 1770 1810 1970 2140 2180 2280 2500 2660

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1180 1400 1600 1780 2000 2840 2840 3460 4180 5120 6160 8520

Dimensions and weights with IP31 metal enclosure


Dimensions and weights are for guidance only, and are provided for a
Ø 13
single-voltage transformer with the following HV insulation levels and low
voltages. Only the definitive drawings following from the order will commit tapping
links C

us contractually.
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
terminal 40 G
(50)
D
Ø 125 (160) D
A B

Insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1720 1800 1900 1900 1900 1900 2150 2140 2250 2360 2450 2720

- Width B 990 1020 1100 1100 1100 1100 1170 1130 1170 1230 1230 1270

- Height C 1730 2050 2300 2300 2300 2300 2480 2440 2480 2680 2900 3060

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight with enclosure (kg) 1360 1590 1820 2000 2220 3060 3140 3810 4530 5495 6560 8970
MV Distribution // Cast Resin Transformers schneider-electric.com | 7

Trihal
17.5 kV and 24 kV A0Bk

Electrical characteristics for insulation level: 17.5 kV and 24 kV


Rated power (kVA) 250 315 400 500 630
Rated frequency (Hz) 50 50 50 50 50
Primary voltage (V) 20000 20000 20000 20000 20000
Isolation level (kV) 24 24 24 24 24
Secondary voltage at no-load (V) 400 400 400 400 400
Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5
Vector groups Dyn Dyn Dyn Dyn Dyn
Losses (W) - no-load losses 520 620 750 900 1100
Losses (W) - load losses at 120°C 3800 4550 5500 6425 7600
Rated impedance voltage (%) 6 6 6 6 6
Max altitude (m) 1000 1000 1000 1000 1000
Max ambiental temperature (C) 40 40 40 40 40
Nature of conductor ALU ALU ALU ALU ALU
Core material GO GO GO GO GO
Conductor weight (kg) 175 170 200 200 287

E/2
J J L I
Dimensions and weights without enclosure housing (IP00)
Dimensions and weights are for guidance only, and are provided for a
single-voltage transformer with the following HV insulation levels and low Ø 13

voltages. Only the definitive drawings following from the order will commit tapping
links
C
us contractually.
M
H
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
B

terminal
40 (50)
D
Ø 125 (160) D
A E

Insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1300 1330 1360 1430 1480

- Width B 730 810 810 820 830

- Height C 1430 1520 1600 1640 1790

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight without enclosure (kg) 1140 1360 1520 1720 2040

Dimensions and weights with IP31 metal enclosure


Dimensions and weights are for guidance only, and are provided for a
Ø 13
single-voltage transformer with the following HV insulation levels and low
voltages. Only the definitive drawings following from the order will commit tapping
links C

us contractually.
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
terminal 40 G
(50)
D
Ø 125 (160) D
A B

Insulation level: 17.5 kV and 24 kV - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1650 1700 1800 1370 1900

- Width B 950 1020 1020 800 1100

- Height C 1730 1900 2050 1530 2300

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight with enclosure (kg) 1300 1440 1650 1830 2100


MV Distribution // Cast Resin Transformers schneider-electric.com | 8

Trihal
36 kV A0Ak

Electrical characteristics for insulation level: up to 36 kVA


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150
Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50
Primary voltage (V) 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000
Isolation level (kV) 36 36 36 36 36 36 36 36 36 36 36 36
Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400
Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5
Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn
Losses (W) - no-load losses 598 712 862 1037 1265 1495 1782 2070 2530 2990 3565 4370
Losses (W) - load losses at 120°C 3740 4264 4950 6193 7810 8800 9900 12100 14300 17600 20900 24200
Rated impedance voltage (%) 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5
Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40
Nature of conductor ALU ALU ALU ALU ALU ALU ALU ALU ALU CU CU CU
Core material GO GO GO GO GO GO GO GO GO GO GO GO
Conductor weight (kg) 225 218 288 283 295 426 495 505 643 1080 1143 1760

E/2
J J L I
Dimensions and weights without enclosure housing (IP00)
Dimensions and weights are for guidance only, and are provided for a
single-voltage transformer with the following HV insulation levels and low Ø 13

voltages. Only the definitive drawings following from the order will commit tapping
links
C
us contractually.
M
H
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
B

terminal
40 (50)
D
Ø 125 (160) D
A E

Insulation level: 36 kVA - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1490 1490 1530 1530 1580 1740 1810 1870 1950 2280 2500 2840

- Width B 800 870 880 880 890 920 1000 1010 1030 1230 1260 1340

- Height C 1790 1790 1950 1950 1990 2160 2230 2420 2460 2630 2710 2750

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1660 1660 1960 2000 2240 2960 3420 3980 4700 7220 9260 13180

Dimensions and weights with IP31 metal enclosure


Dimensions and weights are for guidance only, and are provided for a
Ø 13
single-voltage transformer with the following HV insulation levels and low
voltages. Only the definitive drawings following from the order will commit tapping
links C

us contractually.
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
terminal 40 G
(50)
D
Ø 125 (160) D
A B

Insulation level: 36 kVA - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

Dimensions (mm) - Lenght A 1990 1990 2030 2030 2080 2240 2310 2370 2450 2780 3000 3340

- Width B 1220 1220 1230 1240 1250 1310 1330 1350 1380 1490 1560 1670

- Height C 2090 2090 2250 2250 2290 2460 2530 2720 2760 3030 3110 3150

- Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

- Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

- Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

- Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

Weight without enclosure (kg) 1890 1895 2200 2245 2500 3260 3740 4320 5060 7650 9760 13760
MV Distribution // Cast Resin Transformers schneider-electric.com | 9

Trihal
36 kV A0Bk

Electrical characteristics for insulation level: up to 36 kVA


Rated power (kVA) 250 315 400 500 630
Rated frequency (Hz) 50 50 50 50 50
Primary voltage (V) 30000 30000 30000 30000 30000
Isolation level (kV) 36 36 36 36 36
Secondary voltage at no-load (V) 400 400 400 400 400
Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5
Vector groups Dyn Dyn Dyn Dyn Dyn
Losses (W) - no-load losses 598 712 862 1037 1265
Losses (W) - load losses at 120°C 4180 4990 6050 7054 8360
Rated impedance voltage (%) 6.5 6.5 6.5 6.5 6.5
Max ambiental temperature (C) 40 40 40 40 40
Nature of conductor ALU ALU ALU ALU ALU
Core material GO GO GO GO GO
Conductor weight (kg) 223 223 1005 331 280

E/2
J J L I
Dimensions and weights without enclosure housing (IP00)
Dimensions and weights are for guidance only, and are provided for a
single-voltage transformer with the following HV insulation levels and low Ø 13

voltages. Only the definitive drawings following from the order will commit tapping
links
C
us contractually.
M
H
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
B

terminal
40 (50)
D
Ø 125 (160) D
A E

Insulation level: 36 kVA - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1490 1470 1470 1500 1570

- Width B 800 870 870 880 890

- Height C 1790 1790 1810 1950 1990

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight without enclosure (kg) 1660 1640 1800 1920 2220

Dimensions and weights with IP31 metal enclosure


Dimensions and weights are for guidance only, and are provided for a
Ø 13
single-voltage transformer with the following HV insulation levels and low
voltages. Only the definitive drawings following from the order will commit tapping
links C

us contractually.
For other voltages, impedance voltages and dual-voltages, weights and
dimensions are different (consult us). earthing
terminal 40 G
(50)
D
Ø 125 (160) D
A B

Insulation level: 36 kVA - low voltage 400 V to 433 V


Rated power (kVA) 250 315 400 500 630

Dimensions (mm) - Lenght A 1990 1970 1970 2000 2070

- Width B 1220 1220 1220 1230 1250

- Height C 2090 2090 2110 2250 2290

- Roller pitch D 520 670 670 670 670

- Frame width E 645 795 795 795 795

- Roller diam. F 125 125 125 125 125

- Roller width G 40 40 40 40 40

Weight with enclosure (kg) 1885 1870 2040 2165 2480


Schneider Electric SAS
35 rue Joseph Monier - CS 30325
F92506 Rueil-Malmaison Cedex
Phone: + 33 (0) 1 41 29 70 00
www.schneider-electric.com

NRJED315631EN_291116 © 2016 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.