ENERGY STUDIES
Aquasmart EVOLUTION 2010
2
Aquasmart EVOLUTION 2010
SYSTEM ENERGY SIMULATION
Application
Office application
6145m² of surface
Location London, United Kingdom
HVAC system comprising
4 pipe ducted fan coil system
60Pa ESP
Cycled fan control
Air cooled chiller(s)
Heatingg system
y boiler
Fresh air handling unit
3
Aquasmart EVOLUTION 2010
System control energy optimisation
CASE ONE CASE TWO
Traditional
11% 1% 5% 10% 1% 3%
40%
46%
40%
43%
AHU System Fans Terminal unit fans (FCU's) Cooling Heating Pumps AHU System Fans Terminal unit fans (FCU's) Cooling Heating Pumps
SYSTEM ENERGY SIMULATION
Case study 1 –v- 2
CASE ONE CASE TWO
Site Energy
Component (kWh)
Air System Fans TOTAL) 10 474 6 002
TRADITIONAL AQUASMART
HVAC component consumption
y
Air System Fans TOTAL)) - 43%
AHU fans - 0%
Terminal unit fans (FCU's) - 52%
Cooling - 1%
Heating - 22%
Pumps - 21%
Traditional
7
SYSTEM ENERGY SIMULATION
Case study 3
HVAC COMPONENT ENERGY USAGE
STUDY THREE
(COMMUNICATING Controls and Variable flow)
5% 1% 3%
43%
48%
AHU System Fans Terminal unit fans (FCU's) Cooling Heating Pumps
8
SYSTEM ENERGY SIMULATION 9
Site Energy
Component (kWh)
Air System Fans TOTAL) 10 474 6 002 6 002
AHU fans - 0% 0%
Terminal unit fans (FCU's) - 52% 52%
Cooling - 1% 3%
Heating - 22% 22%
Pumps - 21% 64%
10
Agenda
Unit
mounted
controls
80 000
69 668
70 000
60 000
50 000
40 000
30 000
20 919
20 000
13 567
0
Air Handling unit Terminal fan coil Cooling Heating Pumps (Cooling) Pumps (Heating)
motors motors
Air Handling unit motors Terminal fan coil motors Cooling Heating Pumps (Cooling) Pumps (Heating)
17
ENERGY CONSUMPTION BY HVAC
COMPONENT
57%
17%
11%
6% 6%
3%
Example:
Office example of 1 380m² surface with occupancy hours: 07:00–19:00
Ducted fan coil system, air cooled chiller, boiler and fresh air handling
unit
BASELINE BUILDING MODEL
Simulated for eight european locations
Total Annual Cooling Plant Load… Total Annual Heating Plant Load… Total Annual Power Consumption …
250 000
200 000
150 000
kWh
100 000
50 000
0
Athens Rome Madrid Lyon London Brussels Munich Gothenburg
pumps)
network through the building Chiller system with integrated free-cooling system and/or integrated
heat
Conditions the air in the occupied space, heating, Communicating controllers (part of communicating system)
terminals
Room
cooling, filtering and introducing pre-treated Demand Control Ventilation (CO2 sensors) for certain areas (meeting
fresh/outdoor air quantities in some systems. and conference rooms)
High-efficiency/low-energy motors (EC/DC)
Basic functions include filtering, pre-cooling and/or Heat recovery technology (plate heat exchangers, heat wheels) to
h air
pre-heating
pre heating outdoor air to provide neutral impact on recover waste heat/cool air from exhaust air to pre-treat
pre treat entering air.
nt
plan
Fresh
the occupied space conditions. Communicating controls allow strategies such as night-time free cooling
to pre-cool buildings before occupied periods.
Means by which hot and/or cooled water is provided Variable speed pump motor(s)allowing variable water flow to the
diistribution
to the various system components, traditionally using distribution, offering pump motor energy savings at part load conditions.
Piping
a constant-volume design.
Unit-mounted controls allowing space occupants to Unit fitted with auto-fan mode control that adjusts fan speed to match
Terminal
controls
adjust the temperature set point and control the fan space load requirements to economise fan motor energy by steps or
Unit
Communicating controls offer connectivity with a • management of occupied and unoccupied temperature set points
central management system to adjust unit and • time scheduling of operating hours to match work days and holidays
system settings and performance to building • monitoring and adjusting equipment operating conditions such as
requirements. chilled water/hot water to match outdoor conditions and loads.
ENERGY CONSERVATION MEASURES
Selected studies
Study Description of energy-saving measure
Baseline Traditional stand-alone system
= Terminal fan coil units with non-communication, ‘stand-alone’ controls
= manual user fan speed control
= single temperature set- point
Study 1 Advanced Fan coil controls and management using communication controls
= Terminal fan coil units with Auto fan coil unit fan cycling to meet space load.
= Separate temperature set points for both cooling and heating modes
= Temperature set point reset according to the building occupancy schedule.
Study 2 Use of heat recovery exchanger (50% efficiency) on the fresh air handling unit
= Recovery energy from return air using a plate heat exchanger to reduce pre-heat need.
Study 3 Variable-speed pumps for chilled water distribution.
= Variation of chilled water flow according to building load
Study 4 Use of a chilled water free-cooling system
= Integration of free cooling to benefit from low outside air temperatures and reduce mechanical ccoling.
Study 5 Replace traditional boiler with thermodynamic heating unit
= Thermodynamic heating offering COPS <4.2 versus other fuel sources
Study 6 EC motors fitted to Fan coil units
= Higher efficiency motors and reduced unit consumption
= Variable air volume control to better match room or zone loads
Study 7 Simultaneous use of the first three energy saving measures described in studies 1, 2 and 3.
ENERGY CONSERVATION MEASURE
Study 1
by: Thermostat
Schedule
NO
24hr operation
YES
07:00 – 19:00
88
88,91
86
kWh/m²/yrr
⇒REDUCED COOLING (1%) & HEATING LOADS (2%) 84
78
76
140 000
Non-Eco Eco System
122 695 System
120 000
112 270
100 000
80 000
69 668 67 959
60 000
40 000
20 919 20 732
20 000 13 567
7 152 7 152 8 976 7 859 6 390
3 530
1 061
0
eline
eline
eline
eline
eline
eline
eline
0%
-1%
-2%
-8%
--70%
--34%
--19%
Base
Base
Base
Base
Base
Base
Base
Air Handling Unit Terminal Fans Cooling Cooling Heating Heating Pumps Pumps Non Eco Eco System
(NON-ECO (ECO (NON-ECO (ECO (Cooling) (Heating) System (FCU comfort
SYSTEM) SYSTEM) SYSTEM) SYSTEM) management)
kWh/m²/yr
140 000
50
122 695 40
120 000
30
20
100 000 10
0
80 129
Non-Eco Eco-System
80 000 System (Heat reclaim)
69 668
60 000
40 000
27 668
20 919 20 779
20 000 13 567 13 567
7 152 7 152 7 859 7 433
3 530 3 530
0
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
0,0%
0,0%
0,0%
-0,7%
-5,4%
-35%
-60,3%
B
B
Air Handling Unit Terminal Fans Cooling Heating Pumps Pumps Non Eco Eco
(Cooling) (Heating) System System
(Heat
kWh/m²/yr
84
82
80,6
140 000
80
122 695
120 000 111 160
78
100 000
76
Non-Eco System Eco-System
80 000 (VWF)
69 668 69 668
60 000
40 000
20 919 19 172
20 000 13 567
7 152 7 152 7 859 7 859
3 530 3 530 3 779
0
-8,4%
-9,4%
-72,1%
0,0%
0,0%
0,0%
0,0%
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Air Handling Terminal Fans Cooling Heating Pumps Pumps Non Eco
Unit (Cooling) (Heating) Eco System
System (VWF)
• Benefits
• Energy savings reducing compressor Average temperatures °C
run time City Oct Nov Dec Jan Feb Mar Ap
• Reduced equipment wear and noise Amsterdam 10 5.5 4.0 3.0 2.5 5.0 7.5
Berlin 93
9.3 42
4.2 1 1 -0.7
1.1 -0 7 07
0.7 37
3.7 85
8.5
London 10.9 6.8 4.9 4.1 4.3 6.3 8.2
• When Milano 13.1 6.9 2.3 1.4 4.2 8.3 12.3
• Free cooling not restricted to ‘cold’ Paris 10.8 6.4 3.7 2.9 4.1 6.6 9.9
countries, 5° outside air is sufficient Prague
g 9.1 3.5 0.1 -1.7 -0.3 3.4 8.5
for free-cooling
free cooling
Stockholm 6.8 1.9 -1.4 -3.2 -3.3 -1.0 3.8
Vienna 9.9 4.3 4.0 -1.2 0.6 4.5 9.8
Warsaw 8.2 2.5 -1.7 -3.8 -2.5 1.4 7.6
Zurich 9.1 4.0 0.5 -0.5 1.0 4.5 8.4
ENERGY CONSERVATION MEASURE
Traditional –v- Carrier DX free cooling
DX ffree cooling
li system
t
- Integrated with chiller
- Outstanding Energy Efficiency EER = <13
- No glycol
gy
- Reduced Maintenance costs
89
88,9
89
kWh/m²/yrr
88
=REDUCED COMPRESSOR OPERATION, FANS AND PUMPS
=ONLY REDUCING COMPRESSOR CONSUMPTION. 88
87,1
87
87
86
30,00%
Non-Eco… Eco-System…
25,00%
Free-cooling energy
savings (%)
CITY
over mechanical only
20,00% system
ATHENS
GREECE 0,18%
15,00% ROME
ITALY 0,74%
MADRID
10,00% SPAIN 2,00%
LYON
O
FRANCE 9,09%
LONDON
5,00% UK 7,12%
BRUSSELS
BELGIUM 11,72%
0,00% MUNICH
GERMANY 20,09%
ATHENS ROME MADRID LYON LONDON BRUSSELS MUNICH GOTEBURG GOTEBURG
GREECE ITALY SPAIN FRANCE UK BELGIUM GERMANY SWEDEN SWEDEN 26 39%
26,39%
Free‐cooling energy savings (%) over mechanical only system
Chiller
+
Heat P
Pump
mp
80
70
= Thanks to heating COP’s 1.9 at -20°C up to 4.6 at 20°C
60
kWh/m²/yr
53,1
= Supplying medium temperature temp for space heating (40°C) 50
30
20
10
0
75% Non-Eco Eco-System
System (Heat reclaim)
74%
HEAT PUMP
73% CITY
ECONOMYS
72% ATHENS
GREECE 74%
71% ROME
ITALY 73%
70%
MADRID
69% SPAIN 71%
LYON
68% FRANCE 71%
LONDON
67%
UK 72%
66% BRUSSELS
Savings % BELGIUM 71%
MUNICH
Athens, Greece Rome Italy Madrid Spain Lyon, France GERMANY 69%
London Heathrow Belgium, Brussels Munich, Germany Goteburg Sweden GOTEBURG
SWEDEN 69%
89 88,9
= Fan motor po
power er sa
savings
ings of 44%
= Corresponding savings in terminal cooling coil load of 1,3% 89
kWh/m²/yr
= with a small increase in heating of 0.2%. 88
87,6
140 000 88
122 695 120 919
120 000 87
100 000 87
NON-ECO ECO
SYSTEM SYSTEM
80 000 69 668 69 831
60 000
40 000
20 919 20 642
20 000 13 567 13 475
7 152 7 152 7 859 7 857
3 530 1 962
0
Baseline
Baseline
-44,4%
Baseline
Baseline
Baseline
Baseline
Baseline
0,0%
-1,3%
0,2%
-0,7%
0,0%
-1,4%
B
B
Air Handling Unit Terminal Fans Cooling Heating Pumps Pumps NON-ECO ECO
(Cooling) (Heating) SYSTEM SYSTEM
80
70
= Terminal fan savings of 70%
kWh/m²/yr
60
= Cooling savings of 33% 50 47,1
10
100 000 0
Non- Eco
Eco System System
80 000 69 668
64 995
60 000
40 000
28 698
20 919 19 425
20 000 13 567
7 152 7 152 7 859 6 087
3 530 1 061 2 572
0
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
0%
-70%
-59%
-81%
-23%
-47%
-7%
Air Handling Unit Terminal Fans Cooling Heating Pumps Pumps Non Eco Eco
(Cooling) (Heating) System System
Gothenburg
Brussels
London
Munich
Lyon
Madrid
Athens
Rome
-10,0%
-20,0%
-30,0%
-40,0%
40 0%
-50,0%
-60,0%
-70,0%
• Conclusion
– HAP performs both first and second stage calculations and
therefore offers results for non-24-hour operation that are
more accurate than programs such as Block Load.
ENERGY CASE STUDIES
U-values in Europe
Requirements and/or recommendations on component level
U-value [W/m²K]
Wall Roof Floor
ISO 3166-1 country
City Country code low high low high low High
Bruxelles Belgium BEL 0,6 0,6 0,4 0,4 0,9 1,2
Helsinki Finland FIN 0,25 0,25 0,16 0,16 0,25 0,25
Paris France FRA 0,36 0,36 0,2 0,2 0,27 0,27
München Germany DEU 0,3 0,3 0,2 0,2 0,4 0,4
Ah
Athens G
Greece GRC 07
0,7 07
0,7 05
0,5 05
0,5 19
1,9 19
1,9
Milano Italy ITA 0,46 0,46 0,43 0,43 0,43 0,43
Oslo Norway NOR 0,18 0,22 0,13 0,18 0,15 0,18
Warsaw Poland POL 0,3 0,5 0,3 0,3 0,6 0,6
Lisboa Portugal PRT 0,5 0,7 0,4 0,5 - -
Madrid Spain ESP 0,66 0,66 0,38 0,38 0,66 0,66
Zürich Suisse CHE 0,2 0,3 0,2 0,3 0,2 0,3
Goteborg Sweden SWE 0,18 0,18 0,13 0,13 0,15 0,15
Amsterdam The Netherlands NLD 0,37 0,37 0,37 0,37 0,37 0,37
London United Kingdom GBR 0 25
0,25 0 35
0,35 0 13
0,13 02
0,2 02
0,2 0 25
0,25
D t dS
Ducted Systems
t
0
500
1000
1500
2000
2500
3000
3500
09
9:12
09
9:25
09
9:37
09
9:49
10
0:01
10
0:13
10
0:25
10
0:37
10
0:49
11:01
11:13
11:25
11:37
11:50
12
2:23
12
2:35
12
2:47
12
2:59
Time 13
3:11
13
3:24
13
3:36
13
3:48
14
4:00
14
4:12
14
4:28
1300 ppm
14
4:40
14
4:52
Directive française
15
5:05
CO2 ppm
15
5:17
15
5:29
Demand Control Ventilation (DCV)
15
5:41
15
5:53
16
6:05
16
6:17
16
6:29
16
6:41
VARIATION OF CO² CONCENTRATION IN A MEETING ROOM
BEST PRACTICES: FAN COIL SOLUTIONS
BEST PRACTICES: TERMINAL SOLUTIONS
Chilled beam solution
• Selection of AHU:
– Optimization of different components:
– Energy class (Eurovent)
– Standards EN 13053 and EN 13779
• AHU velocity class
• Heat recovery y efficiencyy class
• Mixing temperature efficiency class
• Specific fan power kW/m3/s
• Motors with better efficiency (EC, EFF1)
• Si i (l
Sizing (larger size
i l
lower LCC)
• Include Energy features
– Free cooling
– Recirculation application with IAQ technology
– Use High efficient heat recovery systems
BEST PRACTICES: AIR HANDLING
UNITS
y
Consider life cycle cost of AHU for
selection Maintenance cost Capital
expenditure
8% 5%
Thermall energy
Th
humidification
17%
Thermal energy
cooling
4%
Power
consumption fans
Thermal energy 52%
heating
12% P
Power
consumption
pumps
2%
> 3.10
2.90 - 3.10
2.70 - 2.90
2.50 - 2.70
2.30 - 2.50
2.10 - 2.30
2.10
Innovation
L
Low operating
ti costs
t
Low sound
Economical installation
Reliability, low maintenance costs
E
Ease off operation
ti
Minimum environmental impact
And Options to satisfy customer needs
100% 35
90%
80% 30
% of Nominal
kW)
70% 25
Capacitty
EER (kW/k
60%
50% 20
40%
EER Energy Efficiency with 13 kW cooling for 1 kW power*
30% 15 Simple system with pure water no glycol
20% 10 Only the fans and a pump running, lower noise
10% Reduced Maintenance costs with less compressor run
0% 5 time
6 8 10 12 14 16 18 20 22 24 26 28 30
DT (LWT-OAT) - (°K)
Leaving chilled
water of 10°C