ATyS s / Sd

Motorised Changeover Switch


Instruction Manual

FR EN DE IT ES NL PT RU PL TR ZH
INDEX

1. GENERAL SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2. INTRODUCTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3. THE ATyS FAMILY PRODUCT RANGE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6


3.1. The ATyS back to back Range Key Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4. QUICK START. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

5. GENERAL OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.1. ATyS s & ATyS sd : RTSE « Product introduction » . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.2. ATyS : RTSE « Product identification ». . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.3. ATyS s and ATyS sd : RTSE « Environmental details» . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.1. IP Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2. Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2.1. Temperature / Current Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2.2. Temperature / Control Voltage Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2.3. Hygrometry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.2.4. Altitude. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3.3. Storage Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.3.1. Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.3.2. Storage duration period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.3.3. Storage position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.4. Volume and shipping weights : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.5. CE Marking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.6. Lead Free Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.3.7. WEEE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.8. EMC standard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

6. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.1. ATyS s and ATyS sd : RTSE « Product dimensions » . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.2. ATyS : RTSE « Mounting Orientation » . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.3. ATyS : RTSE «Assembly of Customer Mounted Accessories». . . . . . . . . . . . . . . . . . 16
6.3.1. Bridging bar installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.3.2. Terminal Shrouds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.3.2.1. Outgoing Terminal Shrouds (When using bridging bars). . . . . . . . . . . . . . . . . . . 17
6.3.2.2. Incoming Terminal Shrouds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.3.2.3. Sealing Facility for added security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.3.3. Direct handle and storage clip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

7. CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1. Power Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1.1. Cable Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1.2. Power Connection Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
7.1.3. Power Connection Sectional Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

ENGLISH
7.2. Control Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.2.1. Typical ATyS s and ATyS sd wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.2.1.1. ATyS sd : 230Vac x 2 (Dual Power Supply) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
7.2.1.2. ATyS s : 230Vac. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.2.1.3. ATyS s : 12Vdc. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
7.2.1.4. ATyS s : 24/48Vdc. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.2.1.5. External Power Supply (400Vac). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.2.2. ATyS s RTSE + ATS Controllers type ATyS C30 and ATyS C40. . . . . . . . . . . . . . . 23
7.2.3. ATyS s and ATyS sd Input and Output Contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2.4. Terminal denomination, description and characteristics. . . . . . . . . . . . . . . 24

8. ATyS OPERATING MODES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25


8.1. Auto Mode : Electrical Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.1.1. Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.1.2. Command Inputs - Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8.1.3. Command Inputs - Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.1.4. Command Inputs - Control Logic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
8.1.5. Dry Contact Outputs – Auxiliary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8.2. Emergency Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8.3. Padlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

9. ATyS s CHARACTERISTICS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

10. TROUBLE SHOOTING GUIDE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

11. SPARES AND ACCESSORIES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31


11.1. Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.2. ATyS s Spares. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.2.1. Motorisation Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
11.2.2. Spare Power Switches: ATyS S and ATyS Sd. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.2.3. Manual Emergency Direct handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.2.4. Mounting legs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11.2.5. Set of terminal connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

12. ATyS s and ATyS sd ORDERING INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33


12.1. ATyS s and ATyS sd Catalogue Reference numbers. . . . . . . . . . . . . . . . . . . . . . . . . . 33

ATyS S / Sd - Réf.: 541 892 A 3


1. GENERAL SAFETY INSTRUCTIONS
• T
 his manual provides instructions on safety, connections and operation of the ATyS s and ATyS sd motorised
changeover switches manufactured by SOCOMEC.
• W
 hether the ATyS s or ATyS sd are sold as a loose product, as a spare, as an enclosed solution or as any
other configuration, these devices must always be installed and commissioned by qualified and experienced
personnel, in line with the manufacturers recommendations, following good engineering practices and after
having read and understood the details in the latest release of the relative product instruction manual.
• M
 aintenance on the product and any other associated equipment including but not limited to servicing
operations must be performed by adequately trained and qualified personnel.
• E
 ach product is shipped with a label or other form of marking including rating and other important specific
product information. One must also refer to and respect markings on the product prior to installation and
commissioning for values and limits specific to that product.
• Using the product outside the intended scope, outside SOCOMEC recommendations or outside the
specified ratings and limits can cause personal injury and/or damage to equipment.
• T
 his instruction manual must be made accessible so as to be easily available to anyone who may need to
read it in relation with the ATyS s and ATyS sd.
• The ATyS s and ATyS sd meet the European Directives governing this type of product and includes CE
marking on each product.
• No covers on the ATyS should be opened (with or without voltage) as there may still be dangerous voltages
inside the product such as those from external circuits.
• D
 o not handle any control or power cables connected to the ATyS when voltage may be present on
the product directly through the mains or indirectly through external circuits.

• V
 oltages associated with this product may cause injury, electric shock, burns or death. Prior to carry out any
maintenance or other work on live parts or other parts in the vicinity of exposed live parts, ensure that the
switch including all control and associated circuits are de-energized.

DANGER
DANGER
DANGER
WARNING
WARNING
WARNING
CAUTION
CAUTION
CAUTION
Risk : RISK : RISK :
Electric shock, burns, death Possible personal injury Equipment damage

• As a minimum the ATyS s and ATyS sd comply with the following international standards:
- IEC 60947-6-1 - IEC 60947-3
- GB 14048-11 - IS 13947-3
- EN 60947-6-1 - EN 60947-3
- VDE 0660-107 - NBN EN 60947-3
- BS EN 60947-6-1 - BS EN 60947-3
- NBN EN 60947-6-1

The information provided in this instruction manual is subject to change without notice, remains for general
information only and is non-contractual.

4 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

2. INTRODUCTION
ATyS s family of “remotely operated transfer switching equipment” (RTSE) are designed for use in power systems
for the safe transfer of a load supply between a normal and an alternate source. The changeover is done in open
transition and with minimum supply interruption during transfer ensuring full compliance with IEC 60947-6-1, GB
14048-11 and other international TSE standards as listed.

The ATyS s and ATyS sd are full load break (switch type) derived transfer switching equipment where the main
components are proven technology devices also fulfilling requirements in IEC 60947-3 standards.

As Class PC RTSE, the ATyS s and ATyS sd products are capable of “making and withstanding short circuit currents”
assigned to IEC 60947-3 utilization categories of up to AC23B, GB 14048-11, IEC 60947-6-1 and equivalent

ENGLISH
standards with utilization categories of up to AC32B.

ATyS s and ATyS sd motorised source changeover switches ensure:


• Power Control and Safety between a normal and an alternate source.
• A complete product delivered as a fully assembled and tested solution.
• Intuitive HMI for emergency / local operation.
• Integrated and robust switch disconnection.
• Clear switch position indication.
• An inherent failsafe mechanical interlock.
• Stable positions (I – 0 – II) non affected by vibration and shocks.
• Constant pressure on the contacts non affected by network voltage.
• Energy Efficient with virtually no consumption whilst on the normal, alternate or off positions.
• Quick, easy and safe “on-load” dual emergency manual operation.
(Manual operation is functional with and without the motorization in place).
• Extremely rugged, error free and built in padlocking facility.
• Straight forward installation with effective ergonomics.
• Minimal downtime with the possibility to perform easy maintenance.
• Simple and secure motorization controls interface.
• Integrated and independent switch position auxiliary contacts.
• Ample accessories to suite specific requirements.
• Compatibility with virtually any make of ATS, AMF, Genset controller.
(Typically an ATyS C30 / C40 ATS Controller or similar and driven through volt free contacts)

• Power supply continuity for most applications…

Mains / Mains Mains / Genset Genset / Genset

ATyS C30 ATyS D10 ATyS C30 ATyS D20 ATyS C40
atys-s 027 B

atys-s 028 B
atys-s 026 C

ATyS S ATyS S
ATyS Sd

ATyS S / Sd - Réf.: 541 892 A 5


3. THE ATyS FAMILY PRODUCT RANGE
The ATyS family has been engineered together with the SOCOMEC centre of excellence in France who boasts it’s
very own in-house 100MVA instantaneous power test lab accredited by COFRAC and working in partnership with:
KEMA, CEBEC, UL, CSA, ASTA, Lloyd’s Register of Shipping, Bureau Véritas, BBJ-SEP, EZU, GOST-R,… and
others.

SOCOMEC has been manufacturing power control and safety products since 1922. The first generation SOCOMEC
“motorised changeover switches” were introduced in 1990 and today the ATyS brand has become trusted by major
players in the power industry worldwide.

The ATyS Family includes a complete range of remotely operated transfer switch equipment (RTSE) as well as
automatic fully integrated products and solutions (ATSE). Selecting the right ATyS will depend on the application as
well as the nature of installation in which the ATyS will be installed.

This instruction manual includes details and instructionS specific to the “ATyS s and ATyS sd” RTSE only. For all
other ATyS Family of products please refer to the specific instruction manual related to that product. (Available for
download on www.socomec.com).

An overview of the complete ATyS range is presented below:


(The ATyS s and ATyS sd are the transfer switch equipment detailed in this instruction manual).

Just the right ATyS for your application…


ATyS: ATyS M: Modular Profile
Small Footprint 125A - 3200A

40A - 160A
Back to Back
Configuration

ATyS p
Power / Genset ATyS M6e
Management Evolved Genset
Management
ATyS g
Simple Genset ATyS M6s
40A - 125A

Management Simple Genset


Management
ATyS t
Transformer ATyS M6b
Management Transformer (building)
Management
ATyS Sd ATyS d
Small Genset Dual Power ATyS M3s
with DPS Supply (DPS) RTSE

ATyS S (RTSE) ATyS


Small Genset RTSE Side by Side
Configuration

3.1. The ATyS back to back Range Key Features


Selecting the right ATyS will depend on the application, the functionality required as well as the nature of the installation
in which the ATyS will be installed. Below is an outline product selection chart listing the key features of each product
(back to back configuration) to help to quickly understand and select the right ATyS for your needs.

6 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

ATyS s ATyS sd ATyS ATyS d ATyS t ATyS g ATyS p

Motorised Changeover with control driven by dry contacts • • • • • • •


Manual Emergency Operation with external handle • • • • • • •
Wide band AC control voltage supply • • • • • • •
Wide band DC control voltage supply •
Watchdog relay to ensure product availability • • • • •
40 – 40 –
Ratings from 40 – 125A as indicated or 125A - 3200A for • 125A 125A • • • • •
Override controls and force switch to zero (off) position • • • • •
Integrated position auxiliary contacts (I - O - II) • • • • • • •

ENGLISH
Source availability LED display • • • •
Remote Display module RJ45 connection for ATyS D10 • • • ATyS D20
Integrated Dual Power Supply • • • • •
Network - Network Applications • • • • • •
Network - Genset Applications • • • • • •
Genset - Genset Applications • • • •
Pre-defined fixed I/O • 5/1 • 5/1 • 9/2 • 11/3 • 5/2
Programmable I/O • 6/1
Additional programmable I/O modules (Optional up to 4 modules) • 8/8
Remotely operated Transfer Switching Equipment
(RTSE Class PC) • • • •
Automatic Transfer Switching Equipment (ATSE Class PC) • • •
Remote + Manual Control • • • •
Auto + Remote + Manual Control • •
Auto + Remote + Local + Manual Control •
Auto-configuration of voltage and frequency levels • • •
Switch Position LED display • • •
Security Sealing Cover • •
Configuration through potentiometers and dip switches • •
Test on load functionality • •
Test off load functionality • •
Programmable configuration with keypad and LCD display •
Metering & Measurement: kW; kVar; kVA + kWh; kVarh; kVAh •
Communication RS485 + Ethernet + Ethernet gateway (Optional) •
Webserver Access through optional Ethernet module (Optional) •
Easy Configuration software (Through Ethernet/Modbus) •
Remote Terminal Unit RJ45 connection for ATyS D20 •
Data Logger for Event Recording with RTC
(Through Ethernet/Modbus) •
Programmable Engine Exerciser functionality
(Through Ethernet/Modbus) •
Multi level password access •
Load Shedding function •
Capacity Management functionality •
Peak shaving functionality •
4 - 20mA communication module (Optional) •
KWh Pulsed output module (Optional) •
Counters KWh, permutation… •
LCD display for programming, metering, timers and counters •
Possibility to add optional functionality •

ATyS S / Sd - Réf.: 541 892 A 7


4. QUICK START

Installation and Commissioning STEP 7A


Control by an external
QUICK START EN order (AUTO))

ATyS S / Sd
Motorised Source Changeover Switch
STEP 1
Cabinet / Back
Plate Installation
STEP 2
Connecting the
POWER Section
STEP 3
COMMAND /
CONTROL terminal
connections
STEP 4
Power Supply
terminal
connections
STEP 5
Emergency
Handle mounting
STEP 6
Check
STEP 7B
Emergency Manual
Operation

STEP 7C
Preliminary operations Padlocking
Check the following upon delivery and after removal of the
packaging:
n Packaging and contents are in good condition.
n The product reference corresponds to the order.
n Contents should include: STEP 3
Qty 1 x ATyS S / Sd product
Qty 1 x handle and storage clip
Quick Start instruction sheet
Qty 1 set of 3 terminal connectors
Qty 1 set of 16 screws, nuts and washers for connecting
the power section.

Warning
Risk of electrocution, burns or injury to persons and /
or damage to equipment.
This Quick Start is intended for personnel trained in the
installation and commissioning of this product. For further
details refer to the product instruction manual available on
the SOCOMEC website.
n This product should always be installed and commissioned
by qualified and approved personnel..
n Maintenance and service operations should be performed
by trained and authorised personnel.
n Do not handle any control or power cables connected to
the product when voltage may be, or may become present
on the product, directly through the mains or indirectly
through external circuits.
n Always use an appropriate voltage detection device to
confirm the absence of voltage.
n Ensure that no metal objects are allowed to fall in the
cabinet (risk of electrical arcing).
Failure to observe good enginering practises as well as to
follow these safety instructions may expose the user and
others to serious injury or death.
Aux 11
IEC IEC
60947-6-160947-3 STEP IEC
4 IEC GB
Risk of damage the device14 60947-6-160947-314048-11
Ue n In case
240V the product is dropped
240V 21 or damaged in any way it 240V 240V
Fn 50/60Hz 50/60Hz
Class is recommended
PC to replace the complete product. 50/60Hz 50/60Hz
PC
AC-33B AC-23A
24 Class
Ie 125A Ie 125A AC-33B AC-23A
Ie 125A AC-32A AC-32A
01 Motorised Changeover Switch Motorised Changeover Switch
Ie 125A
Icw / Icm 10/17kA
Accessories
Icw / Icm 10/17kA
Uimp power 6kV 125A 125A

code barres KIT


Uimp control 2,5kV
04 Ref : 95054012 Ref : 95054012 Uimp power 6kV
Uimp control 2,5kV
2A / 250V
n Bridging bars 4P 125A.
Icc prospect. 50kA Icc prospect. 50kA
(fuse 125AgG)
n Control
2A / 24V
voltage transformer 400V -> 230V.
GB 14048-11
STEP 7B Manual Operation STEP 6
(fuse 125AgG)
Check
n Terminal Shrouds Supply side / Load side. NOK OK NOK ATyS S
Ue 240V
314
code à barres

Ue 125A
Fn n Secure 50Hz Connector Bracket. I I I
Ref.: 88888888
Fn
Class PC
315 Whilst in manual mode, check the
n
Ie 125A Voltage
AC-33B taps. wiring and if ok power up the
Ie 125A AC-32A
n DIN-rail
Icw / Icm
4 modules.
316 ATyS S ATyS Sd product.
code à barres
Uimpn ATS6kVController type
power
317ATyS C30 + D10/D20.
Uimp control 2,5kV C
n ATS50kA
Icc prospect. Controller type ATyS C40.
(fuse 125AgG)
For further detailsCTRLrefer to the product instruction manual
under chapter "Spares and Accessories"
STEP 7A Automatic Operation
AUT
Ensure that the emergency handle
is not inserted in the product, and
de projet de KIT étiquettes ATyS S / Sd comprenant : turn the mode selector to the AUT
position.
un ensemble d’étiquettes concernant le Sircover avant montage de la motorisation
___________________________________________________________

Impulse logic Contactor logic


: un ensemble d’étiquettes à coller sur le produit fini
www.socomec.com order I
To download brochures, catalogues and technical manuals: order 0
STEP 7C Padlocking mode (in position O)
order II

position I
position 0
position II

AUT Imp. ≥60ms maintened

Printing informations: 1 color Black. White paper 90g/m .


ATyS s alim 1 source 230Vac Close the contact corresponding to
3x
2

Printing size: 420x297. Final size 210x148. This page visible first. the desired position.
Ø 4-8 m Order Priority:
m I and II are equal priority over 0. Should
I and II be closed simultaneously the
541 891 C - 05/13 - EN
Non contractual document.
Subject to change without notice. product will not change position.

8 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

STEP 1 Installation
All dimensions in mm.
Attention: Ensure that the product is installed on a flat rigid surface. 104.5 8 15
Orientation: 11 26.5 27.5 26.5

Recommended Ok Ok 37

72
40A -

50 50

143.5
125A

90.6
106

113
94

72

25

ENGLISH
Detailed fixing point: O° - 45° - 90° 115.2 74 44
198 100
181 42.5

14 Door cut-out for front panel mounting


(7 modules):
2 M6 125

AUT
3

45
16
Ø 6.4

STEP 2 Power Terminal Connections


To be connected using terminal lugs, rigid or flexable busbars.

40 A 63 A 80 A 10 0 A 125 A
Minimum cable sec-
tion Cu (mm2) at Ith 10 16 25 35 50
Maximum cable
section Cu (mm2) 70 70 70 70 70
Type of screw M6 M6 M6 M6 M6
2
Recommended tight-
ening torque (N.m) 4.5 4.5 4.5 4.5 4.5
Maximum tightening
torque (N.m) 5.4 5.4 5.4 5.4 5.4

All values are indicative. 1

CONTROL / Power Supply Terminals


STEP3 COMMAND Terminals
ATyS Sd: 2 x 230 VAC STEP4
1 2
Ensure that the product is in manual mode and connect the
product controls using the supplied connectors and suitable
cable of section 1.5 - 2.5 mm² . Fus.Changeover
Motorised 4 A Fus. 4 A
Switch Motorised Changeover Switch *Torque
gG type gG type
101102

201202

317 316 315 314 04 03 24 23 14 13

O I II

ATySCTRLS ATyS Sd
AUX. CONTACTS
ATyS S: 230 VAC

1 2

Fus. 4 A
gG type *Torque
Screw M3
301302

Exemple de projet de KIT étiquettes ATyS S / Sd:


Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm

Bande
STEP5 de 80mm de largeur et Marquages fixes
317 316 315 314 04 03 24 23 14 13
Handle Storage Assembly
O I II
CTRL AUX. CONTACTS
ATyS S DC version: 12 VDC / 24-48 VDC
1

1 2
Screw M3
*Tightening torque:
401402

min.: 0.5 Nm
ATyS
2 s alim 2 sources 230Vac
DC

Fus. 4 A max.: 0.6 Nm


317 316 315 314 04 03 24 23 14 13
gG type

O I II
CTRL AUX. CONTACTS

ATyS S / Sd - Réf.: 541 892 A 9


5. GENERAL OVERVIEW

5.1. ATyS s & ATyS sd : RTSE « Product introduction »

1
11 2

d 3
4
10
5

6
c 7

8
b
9

Included as standard: Available as an accessory:


1. Position Output Aux. Contacts x 3 a. Easy secure connector bracket
(Position indication I-O-II outputs: 6 pin connector) b. Supply side terminal shrouds
2. Control / Command Input contacts x 3 c. Reversible top/bottom bridging bars
(Position orders I-O-II : 4 pin connector)
d. Voltage tapping kit
3. Switch position indication window I – 0 – II
I (On) – O (Off) – II (On) e. Mounting holes for the ATyS s din rail accessory.
(Accepts up to 4 modules)
4. Motorisation module housing and control unit.
f. Load side terminal shrouds
5. Emergency manual operation handle and storage clip.
6. Emergency manual operation shaft location
(Accessible only in manual mode)
7. Auxiliary power supply : (Attn: Image shows ATyS sd)
ATyS sd : 230Vac x 2 (Dual Supply)
ATyS s : 230Vac, 12Vdc, 24/48Vdc
8. Auto / Manual / Padlocking mode selector switch
9. Facility for padlocking in “0” position. (3 x 4-8mm)
10. Power Section : 4P changeover switch assembly
Includes an inherent mechanical interlock.
Back Switch II, Front Switch I).
11. Back-plate mounting ATyS fixing lugs x 4

10 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

Exemple de projet de KIT étiquettes ATyS S / Sd:


Bande de 80mm de largeur et Marquages fixes
5.2. ATyS : RTSE « Product identification »

1 2 3

ATyS s alim 2 sources 230Vac

ENGLISH
4

ATyS Sd
5
AUT
Ø 4 ... 8mm

9
XXXXXXXX

12 11 10

1. Switch 1 (Front) and Switch 2 (back) identification labels (Top & Bottom)
2. Output contacts identification label.
3. Input contacts identification label.
4. Main changeover switch identification label including:
Electrical characteristics & Applicable standards
5. ATyS Product Type (ATyS s or ATyS sd)
6. ATyS s / ATyS sd current rating and product reference number
7. Product Type pictogram (RTSE – Motorised Changeover Switch)
8. Power Terminals incoming and outgoing wiring details.
9. Complete ATyS product serial number, barcode and CE marking.
10. Auxiliary power supply contacts and identification label
11. Switch position and mechanical interlock pictogram
12. Direction of rotation for emergency manual operation

ATyS S / Sd - Réf.: 541 892 A 11


5.3. ATyS s and ATyS sd : RTSE « Environmental details»
As a minimum, the ATyS s and ATyS sd products meet the following environmental requirements:

5.3.1. IP Rating
ø 1 mm

• IP2X against direct contact for the motorization control unit.


• IP2X against direct contact for the power section with the connections in place and when including suitable,
correctly installed incoming and outgoing terminal shields.
• IP 0 for the bare power section without terminal shields in place.

5.3.2. Operating Conditions

5.3.2.1. Temperature / Current Rating


• From -20 to +40°C without derating
• From -20 to +70°C when applying a Kt derating correction factor

Kt: Correction Factor Temperature


0.9 40 °C to 50 °C
0.8 50 °C to 60 °C
0.7 60 °C to 70 °C
* Simplified derating method: Ithu ≤ Ith x Kf
* A more precise calculation may be done for specific applications. Should this be required please contact SOCOMEC.

5.3.2.2. Temperature / Control Voltage Limits

Temperature Voltage (AC) DC 12V DC 24/48V


Ambient 154 - 310 V 8.4 - 15.6V 16.8V – 62.4V
-20 °C 165 - 310 V 9V - 15.6V 17.5V – 62.4V
-10 °C 165 - 310 V 9V - 15.6V 17.5V – 62.4V
55 °C 154 - 290V 8.4V - 15V 16.8V – 60V
70 °C 154 - 285V 8.4V - 15V 16.8V – 60V

5.3.2.3. Hygrometry
• 80% humidity without condensation at 55°C
• 95% humidity with condensation at 40°C

5.3.2.4. Altitude
• Up to 2000m in altitude without derating
• For higher altitude the Ka correction factors below apply

Ka: Correction Factor 2000 m < A ≤ 3000 m 3000 m < A ≤ 4000 m


Ue 0.95 0.8
Ie 0.85 0.85

12 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

5.3.3. Storage Conditions

5.3.3.1. Temperature
• From -40 to +70°C

5.3.3.2. Storage duration period


• Maximum storage up to a period of 12 months

ENGLISH
• (Recommendation: To be stored in dry, non corrosive and non saline atmospheric conditions)

5.3.3.3. Storage position

A maximum of 4 boxes may be stocked vertically

5.3.4. Volume and shipping weights :

ATyS s ATyS s ATyS s ATyS sd


Rating
12Vdc 24/48Vdc 230Vac 230Vac x2
40 A 9505 4004 9506 4004 9503 4004 9513 4004
63 A 9505 4006 9506 4006 9503 4006 9513 4006
80 A 9505 4008 9506 4008 9503 4008 9513 4008
100 A 9505 4010 9506 4010 9503 4010 9513 4010
125 A 9505 4012 9506 4012 9503 4012 9513 4012
Net Weight 3.1 kg 3.1 kg 3.15 kg 3.2 kg
Gross Weight 3.7 kg 3.7 kg 3.85 kg 3.9 kg

5.3.5. CE Marking
The ATyS s and ATyS sd comply with the European directive for :
• The Electromagnetic compatibility no. 2004/108/CE dated 15th of December 2004.
• Low voltage directive no. 2006/95/CE dated 12th of December 2006.

5.3.6. Lead Free Process


• The ATyS s and ATyS sd comply with the European directive for RoHS.

ATyS S / Sd - Réf.: 541 892 A 13


5.3.7. WEEE
The ATyS s and ATyS sd are built in accordance with 2002/96/CE directive:

5.3.8. EMC standard


The ATyS s and ATyS sd are designed and built in accordance with IEC 60947-1 standards

Class B products :
Products intended to be installed in an industrial, commercial or residential environment.

12DC Variant - 2kV, Criteria: B


Electrical Fast Transient/Burst 24/48DC Variant - 2kV Criteria: B
(EFT /Burst Test) 240Vac Variant - 2kV Criteria: B
applicable to command connector from earth, 1kV

12DC Variant - 2kV, Criteria: B


Surge Test 24/48DC Variant - 2kV Criteria : B
240Vac Variant - 2kV Criteria: B

Impulse Test 4.8 kV 1.2/50us - 0.5 J - IEC 60947-1 criteria A

DC Variant-4/8 kV, Criteria: B


Electrostatic Discharge (ESD) 240Vac Variant - 4/8kV Criteria: B

Contact Discharge 4kV, Air Discharge : 8kV

Frequency Range : 80-1000MHz


Radiated RF Electromagnetic 12DC Variant - 10V/m, Criteria: A
fields test 24/48DC Variant - 10V/m Criteria: A
240Vac Variant - 10V/m Criteria: A

Frequency Range : 0.15-80MHz


Conducted disturbances 12DC Variant - 10V, Criteria: A
induced by RF Fields 24/48DC Variant - 10V Criteria: A
240Vac Variant - 10V Criteria: A

Conducted Emission Test 150 kHz to 30 MHz, Class B

Radiated  Emission Test 30 MHz to 1000 MHz, Class B

14 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

6. INSTALLATION

6.1. ATyS s and ATyS sd : RTSE « Product dimensions »


Dimensions 40A to 125A

All dimensions in mm.


rface. 104.5 8 15
11 26.5 27.5 26.5

37

ENGLISH
72
50 50

143.5
90.6
106

113
94

angle de 58°

Tampo Disque indicateur

- Modification de la présentation des caractéristiques de performances commut.


- Marquage Tampo disque indicateur: on garde actuellement l’angle de 58°.

Modifications apportées entre les fichiers indicés k et L

Marquages P89 au 14/11/2012


72

Commutateur
IEC IEC GB
60947-6-160947-314048-11
240V 240V

25

Angl e
Angl
50/60Hz 50/60Hz

e 58°
Class PC

58°
Ie 125A AC-33B AC-23A
Ie 125A AC-32A
Icw / Icm 10/17kA
Uimp power 6kV
Uimp control 2,5kV
Icc prospect. 50kA
(fuse 125AgG)

Tampos Mode I<->0<->II


ATyS S
125A
Ref.: 88888888

code à barres

AUT

115.2 74 44
198 100

302 - N

301 - L
230V
Aux Supply
(160-310V )
181 42.5
code à barres

14 Door cut-out for front panel mounting

402
401

12V
Aux Supply
(9 - 15V
)
ATyS s 24Vdc
code à barres

(7 modules):
M6 125

402
401

24 - 48V
Aux Supply
(17 - 62V
)
Ø 4 ... 8mm
code à barres
2

AUT
AUT
3

45
16

à gauche : un ensemble d’étiquettes à coller sur le produit fini


à droite : un ensemble d’étiquettes concernant le Sircover avant montage de la motorisation
Exemple de projet de KIT étiquettes ATyS S / Sd comprenant :
Ø 6.4
code barres KIT

202 - N

201 - L

102 - N

101 - L
230V
Aux Supply
(160-310V )

Aux 2
Aux 1
Motorised Changeover Switch
125A Ref : 95054012

code à barres

XXXXXXXX
ATyS S

(fuse 125AgG)
Icc prospect. 50kA
Uimp control 2,5kV
Uimp power 6kV
Icw / Icm
Ie 125A
Ie 125A
Class
Fn
Fn
Ue
Ue

(fuse 125AgG)
Icc prospect. 50kA
Uimp control 2,5kV
Uimp power 6kV
Icw / Icm
Ie 125A
Ie 125A
Class
Fn
Ue

60947-6-160947-3
10/17kA
AC-32A
AC-33B AC-23A
PC
50/60Hz 50/60Hz
240V
AC-32A
AC-33B

50Hz
240V

GB 14048-11
PC

IEC
240V

IEC
2A / 24V
2A / 250V
CTRL

Aux
317
316
315
314
C

04
01
24
21
14
11
125A
Motorised Changeover Switch Motorised Changeover Switch
Ref : 95054012
ATyS s alim 1 source 230Vac

ATyS S
To consider the space required for mounting (storage) of the manual operation
ARNING CAUTION

125A
Ref : 95054012
handle as well as the wiring.

ATyS Sd
Ø 4 ... 8mm

STEP 2 Power Terminal Connections


AUT

Ref.: 88888888
125A
ATyS S
(fuse 125AgG)
Icc prospect. 50kA
Uimp control 2,5kV
Uimp power 6kV
Icw / Icm
Ie 125A
Ie 125A
Class
code à barres

60947-6-160947-314048-11
10/17kA
AC-32A
AC-33B AC-23A
PC
50/60Hz 50/60Hz
240V

IEC
Aux 11

To be connected using terminal lugs, rigid or flexable busbars.

240V
IEC IEC

IEC
60947-6-160947-3 IEC IEC GB
14 60947-6-160947-314048-11
Ue 240V 240V 21 240V 240V

GB
Fn 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Class PC PC
AC-33B AC-23A
24 Class
Ie 125A Ie 125A AC-33B AC-23A
Ie 125A AC-32A AC-32A
01 Motorised Changeover Switch Motorised Changeover Switch
Ie 125A
Motorised Changeover Switch Motorised Changeover Switch Motorised Changeover Switch
Icw / Icm 10/17kA Icw / Icm 10/17kA
Uimp power 6kV 125A 125A 125A Ref : 95054012
code barres KIT

Uimp control 2,5kV


04 Ref : 95054012 Ref : 95054012 Uimp power 6kV
Uimp control 2,5kV
2A / 250V

6.2. ATyS : RTSE « Mounting Orientation »


Icc prospect. 50kA Icc prospect. 50kA
(fuse 125AgG) 2A / 24V (fuse 125AgG)
GB 14048-11
ATyS S
XXXXXXXX

Ue 240V
314 125A
Ue
Fn 50Hz Ref.: 88888888
Fn
Class PC
Ie 125A AC-33B
315
Ie 125A
Icw / Icm
AC-32A
316 ATyS S ATyS Sd code à barres ATyS S ATyS Sd ATyS S code barres KIT

Uimp power 6kV


317
Uimp control 2,5kV C
Icc prospect. 50kA
(fuse 125AgG)
CTRL

jet de KIT étiquettes ATyS S / Sd comprenant : 40 A 63 A


Exemple de projet de KIT étiquettes ATyS S / Sd:
80 A 10 0 A 125 A
semble d’étiquettes concernant le Sircover avant montage de la motorisation
Bande de 80mm de largeur et Marquages fixes
Exemple de projet de KIT étiquettes ATyS S / Sd:
Bande de 80mm de largeur et Marquages fixes

Minimum cable sec-


nsemble d’étiquettes à coller sur le produit fini

tion Cu (mm2) at Ith 10 16 25 35 50 ATyS Sd


ATyS s alim 2 sources 230Vac
XXXXXXXX

ATyS s alim 1 source 230Vac ATyS s alim 2 sources 230Vac

Maximum cable
Motorised Changeover Switch Motorised Changeover Switch

70 70 70 70 70
XXXXXXXX XXXXXXXX XXXXXXXX

section Cu (mm2)
Exemple de projet de KIT étiquettes ATyS S / Sd:

ATyS S
Bande de 80mm de largeur et Marquages fixes
Motorised Changeover Switch Motorised Changeover Switch
Motorised Changeover Switch

ATyS Sd
ATyS S

ATyS S

ATyS Sd

125A
Motorised Changeover Switch

125A
Motorised Changeover Switch
AUT

AUT

Ø 4 ... 8mm
AUT
Ø 4 ... 8mm

Ø 4 ... 8mm

Type of screw M6 M6 M6 M6 M6
ATyS s alim 2 sources 230Vac

Ref : 95054012

Ref : 95054012
Ref : 95054012

Ø 4 ... 8mm

Ø 4 ... 8mm

Ø 4 ... 8mm
ATyS Sd

2
ATyS Sd
ATyS S

ATyS S

Ø 4 ... 8mm
AUT
125A

AUT

AUT

AUT

Recommended tight-
ATyS S

ening torque (N.m) 4.5 XXXXXXXX 4.5 4.5 XXXXXXXX 4.5 4.5
ATyS s alim 2 sources 230Vac ATyS s alim 1 source 230Vac ATyS s 24Vdc

Maximum tightening
XXXXXXXX

5.4 5.4 5.4 5.4 5.4


ATyS Sd

torque (N.m) Bande de 80mm de largeur et Marquages fixes


Exemple de projet de KIT étiquettes ATyS S / Sd:
à gauche : un ensemble d’étiquettes à coller sur le produit fini
à droite : un ensemble d’étiquettes concernant le Sircover avant montage de la motorisation

1
Exemple de projet de KIT étiquettes ATyS S / Sd comprenant :

All values are indicative.


40A to 125A Recommended OK OK Not OK
AUT

CTRL
(fuse 125AgG)
Icc prospect. 50kA
C Uimp control 2,5kV 402 402
317 Uimp power 6kV
(160-310V ) (160-310V )
code à barres

code à barres

code à barres

ATyS Sd ATyS S code à S


ATyS ATyS Sd ATyS S Icw / Icm 401 401 230V
code à barres

code barres KIT barres 316 Ie 125A


230V
AC-32A
Aux Supply Aux Supply Mode I<->0<->II
XXXXXXXX

Ie 125A AC-33B
315 Class PC
à droite : un ensemble d’étiquettes concernant le Sircover avant montage de la motorisation

Ref.: 88888888 Fn ) (17 - 62V ) (9 - 15V


Fn 50Hz
125A 314 Ue
Ue 240V 24 - 48V 12V
code barres KIT

code barres KIT

ATyS S 202 - N Aux Supply Aux Supply 302 - N


GB 14048-11
(fuse 125AgG) (fuse 125AgG) 2A / 24V
Icc prospect. 50kA Icc prospect. 50kA 2A / 250V
Uimp control 2,5kV Uimp control 2,5kV 201 - L 301 - L
Uimp power 6kV Ref : 95054012 125A Ref : 95054012 125A Ref : 95054012 125A 04 Uimp power 6kV
Icw / Icm
Motorised Changeover Switch Motorised Changeover Switch Motorised Changeover Switch10/17kA Motorised Changeover Switch Motorised Changeover Switch 01
Icw / Icm 10/17kA Aux 2
AC-32A Ie 125A Ie 125A AC-32A
AC-33B AC-23A Ie 125A Ie 125A AC-33B AC-23A Aux 1
PC Class 24 Class PC
60947-6-160947-314048-11

50/60Hz 50/60Hz Fn 50/60Hz 50/60Hz 102 - N


21
GB

240V 240V Ue 240V 240V


60947-6-160947-314048-11 ances commut.
50/60Hz 50/60Hz

14
AC-33B AC-23A

IEC IEC GB 60947-6-160947-3


240V

gle de 58°.
IEC

IEC IEC 101 - L

ARNING CAUTION
11 Aux
10/17kA
AC-32A
IEC

Uimp control 2,5kV

code à barres
240V

Icc prospect. 50kA


Uimp power 6kV

Ref.: 88888888
PC

Always install the product on a flat and rigid surface.


(fuse 125AgG)

ATyS S
Icw / Icm
Ie 125A
Ie 125A
Class

125A

AUT
ATyS s alim 1 source 230Vac

Ø 4 ... 8mm
Exemple de projet de KIT étiquettes ATyS S / Sd comprenant :

à gauche : un ensemble d’étiquettes à coller sur le produit fini


Motorised Changeover Switch Motorised Changeover Switch

ATyS Sd

Power Supply Terminals


STEP4
Ref : 95054012

ATyS Sd: 2 x 230 VAC


125A

s
ATyS S
125A Ref : 95054012
14
21
24
01
04
11

C
2A / 250V

CTRL
2A / 24V

314
315
316
317
Aux

50/60Hz 50/60Hz
60947-6-160947-3

AC-33B AC-23A
240V
IEC

GB 14048-11

1 2
10/17kA

AC-32A
AC-33B
AC-32A

Uimp control 2,5kV


IEC

240V
50Hz

Icc prospect. 50kA


Uimp control 2,5kV
240V

Icc prospect. 50kA

Uimp power 6kV


Uimp power 6kV

PC
PC

(fuse 125AgG)

(fuse 125AgG)
Icw / Icm

Icw / Icm
Ie 125A
Ie 125A

Ie 125A
Ie 125A

nnect the
Class

Class
Ue

Ue
Ue
Fn

Fn
Fn

ATyS S
XXXXXXXX

d suitable
code à barres
Aux Supply

Ref : 95054012 125A

Fus.Changeover
Motorised 4 A Fus. 4 A
Switch Motorised Changeover Switch
Aux 1
Aux 2

*Torque
(160-310V )

Motorised Changeover Switch


102 - N

202 - N
101 - L

201 - L

230V

code barres KIT

gG type gG type
101102

201202

AUT

ATyS S / Sd - Réf.: 541 892 A 15


code à barres
Ø 4 ... 8mm
Aux Supply

)
24 - 48V
(17 - 62V

401
402

yS s 24Vdc

code à barres
6.3. ATyS : RTSE «Assembly of Customer Mounted Accessories»
Never handle any customer mounted accessories while there may be the risk of
DANGER WARNING
voltage being or becoming present. CAUTION

6.3.1. Bridging bar installation


All Ratings : 40A to 125A

Bridging bars are delivered complete (4P copper bars rated at 125A Ith) together with associated bolts nuts and
washers. For ease of installation onto the ATyS s terminals, fixing of bridging bars is recommended to be carried out
prior to fixing the unit onto a backplate.

It is recommended to first install the bar closest to the motorization module followed by the adjacent bar until all 4
poles are installed. Pay attention to the tightening torque recommendations below.
Note:
Switch II screws and washers should be mounted from the rear towards the front using the nuts fixed to the bridging bars
for retaining. These replace 4 retaining nuts initially delivered loose with the switch therefore those 4 off extra nuts should be
discarded. Switch I screws and washers should be mounted from the front towards the rear using the loose nuts provided fit into
the back of the switch terminals.

Bridging bars may be fit as Top or Bottom in the same manner as described above.


‚

40A to 125A

Recommended tightening torque (N.m) 4.5

Maximum tightening torque (N.m.) 5.4

Type of screw M6

All values are indicative

16 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

6.3.2. Terminal Shrouds


Top and Bottom Terminal Shrouds are available for 40A to 125A products having the power connections wired with
suitable cable lugs of up to 50 mm². The terminal shrouds have a design that includes a facility for sealing without
the need of any specific accessory other than the seal itself.

6.3.2.1. Outgoing Terminal Shrouds (When using bridging bars)


The Outgoing terminal shrouds are designed specifically to accept the 4P bridging bar assembly and enclose all
around the terminals and outgoing live parts. One kit includes 2 parts each being specific for switch 1 and switch 2.
For ease of use please take note of the fitting instructions below.

Installing the Outgoing Terminal Shrouds:

ENGLISH


Removing the Outgoing Terminal Shrouds:



‚

ATyS S / Sd - Réf.: 541 892 A 17


6.3.2.2. Incoming Terminal Shrouds
The Incoming terminal shrouds may be fit to any side of the product (Incoming or Outgoing terminals) that are not fit
with bridging bars.
One kit ordered includes 2 identical parts, front mounted, one for each switch.
Included with a terminal shroud kit are sealing screws to limit the access to terminals.
The shrouds fit to front switch are designed in a way to allow for thermographic measurements without the need to
remove the shroud.

Installing the Incoming Terminal Shrouds


STEP 1 STEP 2 
‚


‚


Removing the Incoming Terminal Shrouds


STEP 1  STEP 2

 ‚ ‚




6.3.2.3. Sealing Facility for added security


The terminal shrouds include a sealing facility fully integrated in the design.
For ease of entry pay attention to the arrow that indicates the direction.

‚ 

18 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

6.3.3. Direct handle and storage clip


The ATyS s and ATyS sd include a handle and storage clip for emergency manual operation. The handle comes with
a standard 8mm hexagon extension shaft that fits into the front of the ATyS s for safe and easy manual operation.
Despite that the shaft includes a keyway the ATyS s will also accept a standard 8mm allen key.
For added safety, the handle may only be inserted into the shaft location in the front of the ATyS s when the mode
selector switch is in manual mode position.
In the unlikelyand
Installation event of a motorization module failure the module
Commissioning STEP 7A may be STEP removed
1 Installation as described below All(4dimensions screws).
in mm.
Control by an external
Emergency manual operation remains fully operational withorderthe (AUTO))motorization module
Attention: Ensure removed.
that the product is installed on a flatTo
rigid do
surface.this the hexagon 104.5 8
Orientation: 11 26.5 27.5 26.5

/ Sd
shaft must be removed from the handle by removing the central retaining screw on the handle. This will convert the
STEP 1 STEP 2 STEP 3 STEP 4 STEP 5 STEP 6 Recommended Ok Ok
male hexagon
Cabinet / Back shaft
Connecting the into
COMMANDa/ 10mm female
Power Supply direct handle
Emergency Check compatible
STEP 7B
Emergency Manual
with the
40A -
bare switch mechanism.
Plate Installation POWER Section CONTROL terminal terminal Handle mounting
connections connections Operation 125A
geover Switch

90.6
106
94

ENGLISH
The emergency direct handle storage clip has been designed to fit virtually anywhere:
STEP 7C
ns • Din rail mounting Padlocking
after removal of the

condition.  Detailed fixing point: O° - 45° - 90° 115.2


198
74

o the order.
STEP 3

2
3

16
Ø 6.4
hers for connecting

ry to persons and /
‚
nnel trained in the
product. For further
STEP 2 Power Terminal Connections
To be connected using terminal lugs, rigid or flex
manual available on
• Clipped directly into the side of the ATyS s • C
 lipped into the top or bottom secure connector 40 A 63 A 80 A 10 0 A 1
d and commissioned
.. bracket accessory. Minimum cable sec-
tion Cu (mm ) at Ith 10 2 16 25 35
should be performed
Maximum cable
section Cu (mm2) 70 70 70 70
cables connected to Type of screw M6 M6 M6 M6
may become present
mains or indirectly Recommended tight-
ening torque (N.m) 4.5 4.5 4.5 4.5
Maximum tightening
detection device to torque (N.m) 5.4 5.4 5.4 5.4

lowed to fall in the  All values are indicative.

ctises as well as to
xpose the user and ‚
CONTROL /
STEP IEC
4 IEC GB
60947-6-160947-314048-11
STEP3 COMMAND Terminals
ATyS Sd: 2 x 230 VAC
maged in any way it 240V 240V
plete product. Class
50/60Hz 50/60Hz
PC 1
Ie 125A AC-33B AC-23A Ensure that the product is in manual mode and connect the
Ie 125A AC-32A product controls using the supplied connectors and suitable
orised Changeover Switch Motorised Changeover Switch Icw / Icm 10/17kA
cable of section 1.5 - 2.5 mm² . Fus.
Motorised 4 A
Changeover Fu
Switch Motorised Changeover Switc
A 125A gG type gG
code barres KIT

Ref : 95054012 Ref : 95054012 Uimp power 6kV

101102

201202
Uimp control 2,5kV
Icc prospect. 50kA

230V. STEP 7B Manual Operation STEP 6


(fuse 125AgG)
Check
side. NOK OK NOK ATyS S
The same emergency handle may be used with and without the motorization in place.
317 316 315 314 04 03 24 23 14 13
I I I
125A
Ref.: 88888888
Whilst in manual mode, check the O I II
wiring and if ok power up the
ATyS S ATyS Sd product.
code à barres ATySCTRLS ATyS Sd
AUX. CONTACTS
/D20. STEP 2 ATyS S: 230 VAC
instruction manual
s" 1
STEP 7A Automatic Operation
AUT Fu
Ensure that the emergency handle gG
is not inserted in the product, and Screw M3 301302
s ATyS S / Sd comprenant : turn the mode selector to the AUT
position.
Exemple de projet de KIT étiquettes ATyS S
Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm

concernant le Sircover avant montage de la motorisation


___________________________________________________________
Bande
STEP5 de 80mm
Handle de largeur et Marquages fix
Storage Assembly
317 316 315 314 04 03 24 23 14 13

s à coller sur le produit fini


Impulse logic Contactor logic
order I ‚ CTRL AUX. CONTACTS
O I II

d technical manuals:
STEP
STEP 7C1 Padlocking mode (in position O)
order 0
order II 1
ATyS S DC version: 12 VDC / 24-48 VDC

position I 1


position 0
position II
STEP 3
401402

AUT Imp. ≥60ms maintened


ATyS s alim 1 source 230Vac ATyS
2 s alim 2 sources 230Vac
DC

Fus. 4
aper 90g/m2. Close the contact corresponding to gG ty
his page visible first. 3x the desired position. 317 316 315 314 04 03 24 23 14 13
Ø 4-8 m Order Priority:
m I and II are equal priority over 0. Should O I II
I and II be closed simultaneously the CTRL AUX. CONTACTS
ual document.
ange without notice. product will not change position.


Motorised Changeover Switch

ATyS S
AUT

AUT
Ø 4 ... 8mm

Ø 4 ... 8mm
125A Ref : 95054012

ATyS S / Sd - Réf.: 541 892 A 19


Motorised Changeover Switch

ATyS S
AUT
7. CONNECTIONS
Ø 4 ... 8mm

Ref : 95054012
7.1. Power Circuits

7.1.1. Cable Connections

125A
40A to 125A
Recommended tightening torque (N.m) 4.5

Maximum tightening torque (N.m.) 5.4

Type of screw M6
All values are indicative

7.1.2. Power Connection Terminals XXXXXXXX

40A to 125A

lation
All dimensions in mm.
uct is installed on a flat rigid surface. 104.5 8 15
11 26.5 27.5 26.5

Ok Ok 37 72
50 50

143.5
90.6
106

113
94

72

25
- 90° 115.2 74 44
198 100
181 42.5

14 Door cut-out for front panel mounting


(7 modules):
M6 125
2

AUT
3

or
45
16

Ø 6.4

Alternative connection facility for ease of outgoing cable.


The incoming: outgoing & bridging connections may be used as top or bottom depending on customer requirements.
STEP 2 Power Terminal Connections
7.1.3. Power Connection Sectional
To be connected Area
using terminal lugs, rigid or flexable busbars.

40 A 63 A 80 A 10 0 A 125 A
40A 63A 80A 100A 125A
Minimum cable sec-
(mm2) at Ith
tion Cu section 10 16 25 35 50
Minimum cable 10 16 25 35 50
Cu (mm Maximum
2
) at lth cable
section Cu (mm2) 70 70 70 70 70
Maximum cable Type section
of screw M6
70 M6
70 70M6 70M6 70 M6
Cu (mm2) at lth 2
Recommended tight-
ening torque (N.m) 4.5 4.5 4.5 4.5 4.5
All values are indicative
Maximum tightening
torque (N.m) 5.4 5.4 5.4 5.4 5.4

Note for all Allrating


values aredata:
indicative. 1
Take into account the connection cable lengths when defining the cable section.
The voltage tapping kit and terminal shrouds are designed to be used with lugs for cables of up to 50 mm² and 70 mm specific
lugs.

CONTROL / Power Supply Terminals


COMMAND Terminals
20 ATyS S / Sd - Réf.: 541 892 A
ATyS Sd: 2 x 230 VAC STEP4
Bande de 80mm de largeur et Marquages fixes
ATyS S / Sd

7.2. Control Circuits

7.2.1. Typical ATyS s and ATyS sd wiring diagrams


ATyS s alim 2 Verify
sources 230Vac
that the Auxiliary power supply feeding terminals the Auxiliary supply voltage
are within the limits. Refer to derating in the operating conditions section for
specific ambient temperatures.
ARNING CAUTION The maximum control cable length for terminals 314 – 317 is to be limited up to
100m /800Ω. In case of longer distances or a higher resistance include control
relays.

Do not handle any control or power cables connected to the ATyS when voltage

ENGLISH
DANGER WARNING
may be, or may become present. CAUTION
7.2.1.1. ATyS sd : 230Vac x 2 (Dual Power Supply)

ATyS Sd
AUT
Ø 4 ... 8mm
Example: Control wiring for a 415Vac application using an ATyS sd having a 3 phase and neutral power source and
a Dual Power Supply of 2x 230Vac. XXXXXXXX
XXXXXXXX

1 2
125A
Motorised Changeover Switch
125A
Motorised Changeover Switch

Fus. 4A
Ref : 95054012

Ref : 95054012

gG type
101102

201202

Ø 4 ... 8mm

Ø 4 ... 8mm
XXXXXXXX
ATyS S
ATyS S

AUT
AUT

317 316 315 314 04 03 24 23 14 13

O I II
CTRL AUX. CONTACTS

ATyS
TyS s alim
s alim 1 source
1 source 230Vac
230Vac

Control Inputs from :


• Local or remote pushbuttons
• Signals from a PLC Controller
oller
ler le le
sursur finifini
produit
produit
ATyS C30 • Virtually any ATS / AMF Controller
dede
Bande
Bande 8 rnant le le
cernant Sircover
Sircover avant
avant montage
montage la la
dede motorisation
motorisation • ATS controllers such as the ATyS C30 and
de
Exemple
Exemple comprenant
/ Sdcomprenant
S /SSd
yS : : ATyS C40 are available from SOCOMEC as an
accessory.
• T
 he ATS controllers allow to automate the
ATyS C40 transfer between main and alternative supply.
Also compatible with ATyS D10 and ATyS D20
remote display/control panels.

à barres
barres
code à code ATyS Sd Sd
ATyS S S
ATyS
TyS
Ref.: 88888888
Ref.: 88888888
125A 125A
code barres KIT

code barres KIT

ATyS ATyS
S S
(fuse 125AgG)
(fuse 125AgG)
Icc prospect.
Icc prospect. 50kA 50kA
ATyS S / Sd - Réf.: 541 892 A 21
control 2,5kV
Uimp2,5kV
Uimp control
Uimp6kV
Uimp power power 6kV 125A 125A Ref : 95054012
Ref : 95054012 54012
Icw / IcmIcw / 10/17kA
Icm 10/17kA
ller
r sursur
le le
produit
produit
finifini ATyS S / Sd - Réf.: 541 892 A 22
230V
301 - L

302 - N

(160-310V )
Aux Supply

code à barres
yS
TyS
s alim
s alim
1 source
1 source
230Vac
230Vac AT
IEC IEC IEC
GB GB
60947-6-1
60947-6-1
60947-314048-11
60947-314048-11
240V 240V 240V 240V
50/60Hz 50/60Hz
50/60Hz 50/60Hz
Class ClassPC PC
AUX. CONTACTS CTRL
Ie 125A Ie 125AAC-33B AC-33B
AC-23A AC-23A
Ie 125A Ie 125AAC-32A AC-32A
eover
Switch
Switch
Motorised
Motorised
Changeover
Changeover
Switch
Switch Icw / IcmIcw / 10/17kA
Icm 10/17kA
O I II
2 Ref : 95054012
125A 125A Ref : 95054012 Uimp power
Uimp6kVpower 6kV
Uimp control
Uimp2,5kV
control 2,5kV
Icc prospect. 50kA 50kA
Icc prospect.
(fuse 125AgG)
(fuse 125AgG)
402
401
12V

ATyS ATyS
S S
code barres KIT
code barres KIT

04 03 24 23 14 13 317 316 315 314


(9 - 15V

125A 125A
Ref.: 88888888
Ref.: 88888888
)
Aux Supply
AUT
AUT

STyS
S S ATyS
ATyS
Sd Sd code à code
barres
à barres
ATyS S
ATyS S

code à barres
gG type
DC

Ø 4 ... 8mm
Ø 4 ... 8mm

Fus. 4A
401402
Ref : 95054012
Ref : 95054012

Motorised Changeover Switch


125A
Motorised Changeover Switch
125A

S /SSd
/ Sdcomprenant
comprenant : : 2 Exemple
1Exemple
dede
p
rnant
ant le leSircover
Sircover
avant
avant montage
montagedede
la la
motorisation
motorisation Bande
Bande
dede
808
ller
r sursur
le le
produit
produit
finifini 402
401
a 12Vdc control power supply.
XXXXXXXX
XXXXXXXX
Example: Control wiring for a 415Vac application using an ATyS s having a 3 phase and neutral power source and
(17 - 62V
24 - 48V
)
Aux Supply

7.2.1.3. ATyS s : 12Vdc


code à barres
yS
TyS
s alim
s alim
1 source
1 source
230Vac
230Vac AT
AUX. CONTACTS CTRL
O I II
04 03 24 23 14 13 317 316 315 314
code barres KIT

AUT
AUT
XXXXXXXX
ATyS S
ATyS S

Ø 4 ... 8mm
Ø 4 ... 8mm

230V
201 - L
101 - L

202 - N
102 - N
gG type

Ref : 95054012
Ref : 95054012

(160-310V )
Aux 2
301302Aux 1
Fus. 4A

Aux Supply
Motorised Changeover Switch
125A
Motorised Changeover Switch
125A
code à barres
2

125A
1

Ref : 95054012
a 230Vac control power supply.
XXXXXXXX
XXXXXXXX

Ø 4 ... 8mm
Example: Control wiring for a 415Vac application using an ATyS s having a 3 phase and neutral power source and

Fn
Fn
Fn

Ue
Ue
Ue

Class
Class
AUT

ATyS S
Ie 125A
Ie 125A
Ie 125A
Ie 125A

Motorised Changeover Switch

Icw / Icm
Icw / Icm
7.2.1.2. ATyS s : 230Vac

(fuse 125AgG)
(fuse 125AgG)
PC

PC
Uimp power 6kV

Uimp power 6kV


240V

Icc prospect. 50kA


Uimp control 2,5kV

240V

Icc prospect. 50kA


50Hz
IEC

Uimp control 2,5kV


AC-32A

AC-33B
AC-32A
10/17kA

GB 14048-11
IEC

240V

AC-33B AC-23A

à droite : un ensemble d’ét


60947-6-160947-3

50/60Hz 50/60Hz

Exemple de projet de KIT é


ATyS S
Motorised Changeover Switc
AUT
ATyS S / Sd

Ø 4 ... 8mm

Ref : 95054012
7.2.1.4. ATyS s : 24/48Vdc
Example: Control wiring for a 415Vac application using an ATyS s having a 3 phase and neutral power source and
XXXXXXXX
XXXXXXXX
a 24/48Vdc control power supply.

125A
1 2

125A
Motorised Changeover Switch
125A
Motorised Changeover Switch
Ref : 95054012

Ref : 95054012

ENGLISH
401402
Fus. 4A

Ø 4 ... 8mm

Ø 4 ... 8mm
DC
gG type
ATyS S
ATyS S

XXXXXXXX

AUT
AUT
317 316 315 314 04 03 24 23 14 13

O I II
CTRL AUX. CONTACTS

ATyS
TyS s alim
s alim 1 source
1 source 230Vac
230Vac

7.2.1.5. External Power Supply (400Vac)


101 102
Power Transformer intended for 400 Vac, Phase to Phase
voltage applications that do not provide the availability of
230 Vac

oller
ler le le
sursur finifini
produit
produit
a neutral conductor. Transformer data: 400Vac – 230Vac:
dede
Bande
Bande 8
400 Vac

50VA. (Drawing for ATyS s 230Vac) For ATyS sd order 2


Source

rnant le le
cernant Sircover avant
avant
Sircover montage
montage dede motorisation
motorisation
la la
transformers connected to 101-102 and 201-202.
de
Exemple
Exemple comprenant
/ Sdcomprenant
S /SSd
yS : :

7.2.2. ATyS s RTSE + ATS Controllers type ATyS C30 and ATyS C40
Refer to the relevant ATS controller instruction manual for ATyS C30 and ATyS C40 details
à barres
barres
code à code ATyS Sd Sd
ATyS S S
ATyS
TyS
  Ref.: 88888888
Ref.: 88888888 
ATyS 125A 125A
ATyS
code barres KIT

code barres KIT

ATyS C30 D10/D20 ATyS C30 D10/D20


ATyS ATyS
S S
(fuse 125AgG)
(fuse 125AgG)

  
Icc prospect.
Icc prospect. 50kA 50kA
control 2,5kV
Uimp2,5kV
Uimp control  125A 125A Ref : 95054012
Ref : 95054012 54012
Uimp6kV
Uimp power power 6kV
Icw / IcmIcw / 10/17kA
Icm 10/17kA ngeover
ver Switch
Switch Changeover
Motorised
Motorised Switch
Switch
Changeover
Ie 125A Ie 125AAC-32A AC-32A
Ie 125A Ie 125A AC-23A AC-23A
AC-33B AC-33B

 
Class ClassPC PC

 ‚ ‚
50/60Hz 50/60Hz
50/60Hz 50/60Hz
240V 240V 240V 240V
60947-6-1
60947-6-1 60947-314048-11
60947-314048-11
IEC IEC GB
IEC GB

 Measurement and power


supply  U+F metering for each group
‚C ontrol and position ‚C  ontrol and position information
information feedback feedback
 Generating set «start/  Generating set «start/stop» control
stop»  External «start/stop» command for
 ATyS interface connection basic cycle
 DC power supply  DC power supply

ATyS S / Sd - Réf.: 541 892 A 23


emble d’étiquettes à coller sur le produit fini à droite : un ensemble d’étiquettes co

geover Switch
12
ATyS S

... 8mm

Exemple de projet
ATyS S / Sd comprenant : ATyS s alim 2 sources 230Vac Exemple
à gauche : un ensemble d’étiquettes à

AUT
concernant le Sircover avant montage de la motorisation
IEC IEC GB
60947-6-160947-314048-11
240V 240V
50/60Hz 50/60Hz
code à barres Bande d
à coller7.2.3.
surATyS s and ATyS sd Input and Output Contacts
Class PC

le produit
ATyS fini
Ie 125A AC-33B AC-23A
Ie 125A AC-32A
ch Icw / Icm 10/17kA Motorised Changeover Switch Motorised Changeover Switch

code barres KIT


Uimp power 6kV

s alim 1 source 230Vac

Aux Supply
Uimp control 2,5kV
Icc prospect. 50kA
(fuse 125AgG)

Aux 1
Aux 2

(160-310V )
ATyS S
125A

102 - N

202 - N
101 - L

201 - L
Ref.: 88888888

230V
d code à barres ATyS S ATyS Sd Position Commands
Independant Aux Contacts
ATyS s 24Vdc (non standard)
• Pos I: Aux Contact 13/14 • Sw to Pos IIcode
I/P: 314
barres KIT
nant : Exemple de projet de KIT étiquettes ATyS S / Sd:
• Pos II: Aux Contact
r avant montage de la motorisation 23/24 • Sw to Pos I I/P: 315
ATyS S

ATyS Sd
Bande de 80mm de largeur et Marquages fixes

AUT
t fini • Pos O: Aux Contact 03/04 • Sw to Pos O I/P: 316
ATyS s alim 1 source 230Vac

Ø 4 ... 8mm
• Common: 317
ATyS s alim 1 source 230Vac
ATyS Sd

urce 230Vac ATyS s alim 2 sources 230Vac

Motorised Changeover Switch

ATyS S
AUT
Ø 4 ... 8mm

Ref : 95054012
Motorised Changeover Switch

ATyS S
AUT
code à barres
Motorised Changeover Switch

ATyS S

ATyS Sd
AUT

AUT
Ø 4 ... 8mm
Ø 4 ... 8mm

Ø 4 ... 8mm
Power Supply Options

125A
coller sur le produit fini

Aux Supply
Ref : 95054012

)
Ref : 95054012

24 - 48V
Power Connections

(17 - 62V
ATyS Sd DPS AC Supply XXXXXXXX
125A

Bande d S1, S2, Load ncernant le Sircover avant montage de la motorisation

401
402
XXXXXXXX

Motorised Changeover Switch

ATyS S
Exempl
AUT

TyS S / Sd comprenant :

125A
Ø 4 ... 8mm

XXXXXXXX XXXXXXXX

ATyS S AC Supply

Ref : 95054012
XXXXXXXX

XXXXXXXX
1 code à barres

125A
2 ATyS SXXXXXXXX
DC Supply
ATyS Sd ATyS S

Aux Supply
code à barres

)
(9 - 15V
Ref.: 88888888

12V

401
402
401402

125A
DC
code barres KIT

ATyS S
(fuse 125AgG)
Icc prospect. 50kA
Uimp control 2,5kV
317 316 315 314 04 03 24 23 14 13
7.2.4. Terminal denomination, description and characteristics.
Uimp power 6kV Ref : 95054012 125A f : 95054012
Icw / Icm 10/17kA d Changeover Switch Motorised Changeover Switch
Ie 125A AC-32A XXXXXXXX
Ie 125A AC-33B AC-23A
O I II Class PC
50/60Hz 50/60Hz

Characteristics Recommended
240V 240V

Denomination Terminal Description


60947-6-160947-314048-11
IEC IEC GB
Cable Section
code à barres

Aux Supply

101 Power Supply : L (ATyS sd : 230V) (160-310V )


302 - N
301 - L

230V

102 Power Supply : N (ATyS sd : 230V)


230Vac
201 Power Supply : L (ATyS sd : 230V) +/- 30% 
202 Power Supply : N (ATyS sd : 230V) (160-310Vac)
50/60Hz
Tampos Mode I<->0<->II

Power Supply
301 Power Supply : L (ATyS s : 230V) 1,5 mm2
Input
302 Power Supply : N (ATyS s : 230V)
Power Supply : Positive + (ATyS s : 12/24/48Vdc) *12Vdc (9-15Vdc)
401 *12Vdc -25%/+30%, Others +/- 30% 24/48Vdc
402 Power Supply : Negative - (ATyS s : 12/24/48Vdc) (17-62Vdc)

314 Position II order if closed with 317


ATTN: Do not
ication de la présentation des caractéristiques de performances commut.

315 Position I order if closed with 317 AUT


connect to any
Control Inputs 1,5 mm2
age Tampo disque indicateur: on garde actuellement l’angle de 58°.

316 Position 0 order if closed with 317 Power Supply


Common control terminal for 314 - 316 Non isolated
317 (Specific Voltage Supply)
po Disque indicateur

03 Dry Contact : Aux Contact Position 0


ations apportées entre les fichiers indicés k et L

04 Normally Open Contact


uages P89 au 14/11/2012

23 Dry Contacts
Signalisation Dry Contact : Aux Contact Position I 2A AC1 / 250V 1,5 mm2
Outputs 24 Normally Open Contact 2A / 24Vdc
13 Dry Contact : Aux Contact Position II
14 Normally Open Contact
58°°
gle 58
Anngle
A

24 ATyS S / Sd - Réf.: 541 892 A


58°
ables connected to
ay become present IEC IEC GB
60947-6-160947-314048-11

mains or indirectly240V 240V


50/60Hz 50/60Hz
ATyS S / Sd
or injury
Class to persons
Ie 125A
PC
AC-33B AC-23A
and /
Ie 125A AC-32A
Motorised Changeover Switch Motorised Changeover Switch
etection trained
deviceintothe
Icw / Icm
personnel
10/17kA

code barres KIT


8. ATyS OPERATING MODES
Uimp power 6kV
Uimp control 2,5kV
this product. For further
Icc prospect. 50kA
(fuse 125AgG)
tionATyS
manual available on
owed to fall in the
125A
S

Ref.: 88888888
The ATyS includes 3 safe and distinct operating modes through a selector switch located on the front of the product.
stalled and commissioned
onnel..code à barresThe modes of operation are as follows : ATyS S ATyS Sd
tises as well
ions should as to
be performed
• Auto Mode: “Remotely operated transfer switching”
pose the user and
onnel.
wer cables connected • Manual
to Mode: “Local emergency manual operation”
e, or may become• present
Locked Mode: “Secure locked padlocking facility”
h the mains or indirectly STEP IEC
4 IEC GB
60947-6-160947-314048-11
ageddetection
tage in any way
deviceit to Exemple de projet de KIT étiquettes240V ATyS
240V S / Sd:

ENGLISH
.ete product. 50/60Hz 50/60Hz
age de tolafallmotorisation
are allowed in the Bande de 80mm de largeur et Marquages
Class PC
fixes
AUTO MODE:
Ie 125A AC-33B AC-23A
g). Ie 125A AC-32A
rised Changeover Switch Motorised Changeover Switch
g practises as well as to • Activates
Icw / control
Icm inputs.
10/17kA
mayRef : 95054012
expose the user and 125A Ref : 95054012 • Inhibits thepower
Uimp padlocking
6kV facility
Uimp control 2,5kV
• Inhibits the insertion of the
Icc prospect. 50kA

STEP 7B
manual operation handle
230V. MODE
Manual Operation STEP IEC STEP 6
(fuse 125AgG)
4whenIECin AUTGB
Mode Check
side. NOK OK NOK AUTO ATySposition
Mode S
60947-6-160947-314048-11
is inhibited
or damaged in any way it 240V 240V
complete product. I I ATyS s alim 2 sources 230Vac
I
Class
when
handle
PC
padlocked
125A
50/60Hz 50/60Hz
for
Ref.:manual
or when the
operation is
88888888
Ie 125A inserted Whilst
into theinATyS
AC-33B AC-23A manual
s. mode, check the
Motorised Changeover Switch Motorised Changeover Switch
Ie 125A AC-32A
wiring and if ok power up the
ATyS S ATyS Sd
Icw / Icm 10/17kA
125A 125A product.
code à barres

code barres KIT


Ref : 95054012 Ref : 95054012 Uimp power 6kV
Uimp control 2,5kV
D20. Icc prospect. 50kA

0V -> 230V. STEP 7B Manual Operation STEP 6


(fuse 125AgG)
Check
Load side. NOK OK NOK ATyS S
nstruction manual I I I
125A
Ref.: 88888888
Whilst in manual mode, check the
STEP 7A
MANUAL MODE:
wiring and if ok power up the Automatic
ATyS S ATyS Sd product.
code à barres
• Inhibits the control inputs.
Motorised Changeover Switch

AUT
ATyS S

D10/D20.
AUT

AUT
• Allows to insert the handle
for emergency manual

Ø 4 ... 8mm
Ensure that the emergency
operation. handle
oduct instruction manual is not inserted in the product, and
ATyS S / Sd comprenant :
Ref : 95054012

sories" Note: Pay attention to the keyway


MODE
STEPwhen
7A inserting
turnAutomatic
the mode selector to the AUT
Operation
the emergency
handle position.
into the product.
AUT
concernant le Sircover avant montage de la motor
125A

________________________________ Ensure that the emergency


Attention: Whenhandleoperating ma-
nuallyin the
is not inserted ensure
product,thatandthe position
tes ATyS S / Sd comprenant : Impulse logic indicator
turn the mode is centred
selector in the window
to the AUT
sesàconcernant
coller surlele produit
Sircover finimontage de la motorisation
avant
position. when inorderthe desired position.
I
_______________________________________________________
technical manuals: order 0
STEP
tes à coller sur 7C Padlocking
le produit fini
mode (in position O) XXXXXXXX
order I
Impulse logic
order II
Contactor logic

es and technical manuals: order 0


STEP 7C Padlocking mode (in position O)
order II
position
LOCKED MODE:I (Padlocked)
position
• Inhibits the0 control inputs.
position I
position 0 position
• Inhibits II
insertion of the
emergency handle.
AUT
position II Imp. ≥60ms
ATyS
ATyS ss alim
alim1 1source
source 230Vac
• Accepts up to 3 padlocks
AUT Imp. of
with a dia. ≥60ms
4-8mm. maintened
per 90g/m .
MODE
230Vac Close
• Allows the contact
padlocking when corresponding
the to
3xx
2
White papervisible
90g/m2first.
. Close the contact
ATyS corresponding
in O to
the desired position.
s is Position.
is page
148. This page visible first. 3 the desired position.
ØØ44--88mmm DANGER Order Priority: Order Priority:
WARNING I andCAUTION
m POS 0
I and II are equal priority IIover
are0.equal
Shouldpriority over 0. Shou
I and II be closed
I and II be closed simultaneously the simultaneously the
ontractual document.
al document.
t to change without notice. product will not change position.
product will not change position.
nge without notice.

ATyS S / Sd - Réf.: 541 892 A 25


h
Changeover Switch

ATyS S
AUT
Ø 4 ... 8mm
code à barres

Ref : 95054012
8.1. Auto Mode : Electrical Operation

Aux Supply
Motorised
Motorised Changeover Switch

ATyS S
AUT

24 - 48V
(17 - 62V
8.1.1. Power Supply

125A
Ø 4 ... 8mm

401
402
XXXXXXXX
The ATyS sd is to be powered between terminals 101 and 102 and
201 and 202 with a supply within the limits of:

Ref : 95054012
• 230Vac +/- 30% (160 – 310Vac)
• 50/60Hz +/- 10%

The ATyS s 230Vac version is to be powered between terminals 301 XXXXXXXX

125A
and 302 with a supply within the limits of :
• 230Vac +/- 30% (160 – 310Vac)
• 50/60Hz +/- 10%
IEC IEC GB code à barres
60947-6-160947-314048-11
240V 240V
The ATyS s 12Vdc version is to be powered between terminals
50/60Hz 50/60Hz 401

Aux Supply
Class PC
and 402 with a supply within the limits of :

)
Ie 125A AC-33B AC-23A
Ie 125A AC-32A
d Changeover Switch Motorised
• 12Vdc Changeover
– 25%Switch
/ + 30% (9 – 15Vdc)

(9 - 15V
Icw / Icm 10/17kA
125A Ref : 95054012

code barres KIT


: 95054012 Uimp power 6kV

12V

401
402
Uimp control 2,5kV
Icc prospect. 50kA
(fuse 125AgG)

ATyS S XXXXXXXX
The ATyS s 24/48Vdc version is to be powered125A between terminals
Ref.: 88888888
401 and 402 with a supply within the limits of :
ATyS S • 24/48Vdc
ATyS +/-Sd
30% (17 – 62Vdc) code à barres

Current Input: AC control versions Current Input: 24/48 Vdc control versions
• <20mA (Standby mode) • <20mA (Standby mode) code à barres

ATyS S / Sd comprenant :
• 0.2A – 0.4A (Switching mode) • 1.5A (Switching mode) Exemple
Aux Supply
• 0.7A – 1.25A for 100ms (Inrush) • 7 - 9A for 100ms (Inrush)
oncernant le Sircover avant montage de la motorisation Bande de
(160-310V )
302 - N
301 - L

Current Input: 12 Vdc control versions Terminal connector: (Control wiring)


à coller sur le produit fini
230V
• <20mA (Standby mode) • Minimum 1.5mm²
• 1.3A – 1.8A (Switching mode) • Maximum 2.5mm²
• 5 – 6.5A for 100ms (Inrush)
Mode I<->0<->II

8.1.2. Command Inputs - Description


ATySThes alim 1 source 230Vac
ATyS s includes for 3 off command inputs through a 4 pin
connector. No additional power supply should be used on these
contacts as the inputs MUST be used with the common supply off
terminal 317. These contacts are non isolated.

The ATyS s power supply must be available to activate inputs 314


to 317. Pulse duration for activation : ≤ 60ms.
ésentation des caractéristiques de performances commut.

AUT
que indicateur: on garde actuellement l’angle de 58°.

• Pin 314:- Position II order if closed with 317.


This contact is active with the ATyS s in AUT mode.
Impulse duration to activate and switch to position II is a minimum of 30 to 60ms.
Motorised Changeover Switch

ATyS S
Tampos
isque indicateur
AUT

• Pin 315:- Position I order if closed with 317.


Ø 4 ... 8mm

This contact is active with the ATyS in AUT mode.


ées entre les fichiers indicés k et L

Impulse duration to activate and switch to position I is a minimum of 30 to 60ms.


Ref : 95054012
89 au 14/11/2012

• Pin 316:- Position 0 order if closed with 317.


This contact is active with the ATyS in AUT mode.
Impulse duration to activate and switch to position O is a minimum of 30 to 60ms.
125A

For contactor logic maintain contacts on between terminal 316 and 317.
• Pin 317:- Common for inputs 314 to 316.
58°°
gle 58

26 ATyS S / Sd - Réf.: 541 892 A


Anngle
A
ATyS S / Sd

8.1.3. Command Inputs - Technical Data


• Command Input Qty: 3 x non isolated command inputs
• Direct Voltage : <5Vdc (On any input with respect to ground)
• Direct Current Iin : 0.35 to 0.5mA
• Line resistance : 800Ω
• Line length : 100m (Minimum wire 1.5mm² (#16AWG)
• Pulse duration : 30 - 60ms
• Terminal connector: 1.5mm² minimum / 2.5mm² maximum

8.1.4. Command Inputs - Control Logic

ENGLISH
Switching operation can be driven in AUT mode by external volt free contacts as described above.

Depending on the wiring configuration there are two types of logic that may be applied to the ATyS s.
• Impulse or
• Contactor logic.

The ATyS s input logic gives priority to orders I and II over O therefore contactor logic can be implemented by
bridging terminals 316 and 317.

Impulse logic:
ordre I
The ATyS s is driven to stable positions (I – O – II) after ordre 0
receiving an impulse order.
ordre II
• A switching command of at least 60 ms is
necessary to initiate the switching operation. position I
• Orders I and II have priority over order 0.
position 0
position II
XXXXXXXX
Imp. ≥60ms
maintened
(Note : Excludes position switching delays)
Contactor Logic:
ordre I
The ATyS s is driven to a specific position (I or II) for as ordre 0
125A
Motorised Changeover Switch

long as the order is maintained.


ordre II
• Order O is maintained. (Bridge 316 – 317)
Ref : 95054012

• Orders I and II have priority over order 0. position I


• Orders I and II have equal priority. position 0 Ø 4 ... 8mm
ATyS S

(1st order received is held until no longer


maintained). position II
AUT

• If order I or II disappears, the device returns to Imp. ≥60ms


zero position. (With the power supply available).
maintened
(Note : Excludes position switching delays)

8.1.5. Dry Contact Outputs – Auxiliary


The ATyS is equipped with integrated independent position
(I – O – II) auxiliary contact outputs through 3 off micro switches.

Dry contacts to be powered by the user.


ATyS s alim 2 sou
• Pins 13 – 14, 23 – 24, 03 – 04
rce 230Vac
(Normally Open and independent contacts)

fini
Bande de 80mm de largeur e avant montage de la motorisation ATyS S / Sd - Réf.: 541 892 A 27
Exemple de projet de KIT éti ant :
• Auxiliary Contact Quantity 3
• Configuration NO
• Mechanical Endurance 100k cycles
• Rated Voltage / Switching Voltage 250Vac / 24Vdc / 48Vdc
• Rated Current 2A
• Output Terminals 1.5mm² minimum / 2.5mm² maximum

8.2. Emergency Manual Operation


The ATyS s can be manually operated as a “Manual Transfer Switch Equipment – MTSE” whilst retaining the
electrical characteristics and performance of the power switching function. This function is usually used in case of
emergencies or during maintenance.

To operate the ATyS s manually ensure that no live parts are accessible, turn the front selector switch into the manual
position (figure 4.1 item 11) and insert the handle (figure 4.1 item 7) into the emergency handle shaft location hole
provided (figure 4.1 item 10). The shaft location includes a keyway to guide the handle into the right position.

Turn the handle 60° clockwise or anti-clockwise (depending on the position to be reached) for each consecutive
change in position.
IàO 60° Clockwise Attention: When operating manually
ensure that the position indicator is
I à O à II 60° + 60° Clockwise centred in the window when in the de-
sired position.
II à O 60° Anti Clockwise NOK OK NOK
II

I
60 °
II à O à I 60° + 60° Anti Clockwise
° 60 I I I
0

Ensure to verify the product position and direction of rotation before effecting
manual operation.
WARNING CAUTION Ensure to remove the handle from the product before changing the selector switch
to AUT or padlocking position.

8.3. Padlocking
The ATyS s can be padlocked in the 0 position using up to 3 padlocks.

To padlock the ATyS s first ensure that the manual operation handle is not inserted into the location hole, then turn
the front selector switch onto the padlock position.

Pull the padlocking mechanism outwards to reveal the slot for inserting the padlocks.

Padlock the device with approved quality padlocks of minimum diameter 4mm and maximum diameter of 8mm. A
maximum of 3x 8mm padlocks may be padlocked onto the ATyS padlocking mechanism.

Padlocking is allowed in the “O position”, when in padlock mode and with the
WARNING CAUTION emergency handle not inserted into the shaft location.

28 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

9. ATyS s CHARACTERISTICS
Characteristics according to IEC 60947-3 and IEC 60947-6-1
40 to 125 A

Thermal current Ith at 40°C 40 A 63 A 80 A 100 A 125 A


Rated insulation voltage Ui (V) (power circuit) 800 800 800 800 800
Rated impulse withstand voltage Uimp (kV) (power circuit) 6 6 6 6 6
Rated insulation voltage Ui (V) (operation circuit) 300 300 300 300 300
Rated impulse withstand voltage Uimp (kV) (operation circuit) 4 4 4 4 4

Rated operational currents Ie (A) according to IEC 60947-3

ENGLISH
Rated voltage Utilisation category A/B A/B A/B A/B A/B
415 VAC AC-20 A / AC-20 B 40/40 63/63 80/80 100/100 125/125
415 VAC AC-21 A / AC-21 B 40/40 63/63 80/80 100/100 100/125
415 VAC AC-22 A / AC-22 B 40/40 63/63 80/80 100/100 100/100
415 VAC AC-23 A / AC-23 B -/40 -/63 -/63 -/63 -/63

Rated operational currents Ie (A) according to IEC 60947-6-1


Rated voltage Utilisation category A/B A/B A/B A/B A/B
415 VAC AC-31 B 40 63 80 100 125
415 VAC AC-32 B 40 63 80 80 80

Fuse protected short-circuit withstand (kA rms prospective)


Prospective short-circuit current (kA rms) 50 50 50 25 15
Associated fuse rating (A) 40 63 80 100 125

Circuit breaker protected short-circuit withstand with any circuit breaker that ensures tripping in less than 0.3s(1)
Rated short-time withstand current 0.3s. Icw (kA rms) 3.5 3.5 3.5 3.5 3.5

Short-circuit capacity (without protection)


Rated short-time withstand current 1 s. ICW (kA rms) 2.5 2.5 2.5 2.5 2.5
Rated short-circuit making capacity 4.5 4.5 4.5 4.5 4.5

Connection
Maximum Cu cable cross-section (mm2) 50 50 50 50 50
Tightening torque mini / maxi (Nm) 1.2/3 1.2/3 1.2/3 1.2/3 1.2/3

Switching time (Standard setting)


I - 0 or II - 0 (ms) 500 500 500 500 500
I - II or II - I (ms) 1000 1000 1000 1000 1000
Duration of "electrical blackout" I - II (ms) minimum 500 500 500 500 500

Power supply
Power supply 12 VDC min / max (VDC) 9/15 9/15 9/15 9/15 9/15
Power supply 24/48 VDC min / max (VDC) 17/62 17/62 17/62 17/62 17/62
Power supply 230 VAC min / max (VAC) 160/310 160/310 160/310 160/310 160/310

Control supply power demand


Power supply 12 VDC inrush / nominal (VA) 200/40 200/40 200/40 200/40 200/40
Power supply 24/48 VDC inrush / nominal (VA) 200/40 200/40 200/40 200/40 200/40
Power supply 230 VAC inrush / nominal (VA) 200/40 200/40 200/40 200/40 200/40

Mechanical characteristics
Durability (number of operating cycles) 10 000 10 000 10 000 10 000 10 000
Weight ATyS S and ATyS Sd 4 P (kg) 3 3 3 3 3

(1) Value for coordination with any circuit breaker that ensures tripping in less than 0.3s. For coordination with specific circuit-breaker references, higher short-circuit current values are available.
Please consult us.

ATyS S / Sd - Réf.: 541 892 A 29


10. TROUBLE SHOOTING GUIDE

The ATyS s does not operate electrically • V erify the power supply on terminals 101 to 402 is within
the acceptable voltage limits relative to the specific
device and it’s intended nominal voltage.
12Vdc: 9 – 15Vdc
24/48Vdc: 17 – 62Vdc
230Vac: 160 – 310Vac
• Verify that the front selector switch is in position (AUT)
• Verify the contact terminal and contact signals between
314 and 317. Normally open contacts with priority to
signals I & II.

It is not possible to manually operate the switch • V erify that the front selector switch position is on the
Manual position.
• Make sure that the product is not padlocked.
• Verify the rotation direction of the handle.
• Apply a sufficient progressive action in the direction as
indicated on the ATyS s.

Electrical operation does not correspond to • V


 erify the selected control logic wiring (impulse or
external order I, O, II contactor)
Impulse >60ms
314 – 317 : Switch to position II
315 – 317 : Switch to position I
316 – 317 : Switch to position 0
Maintained - Bridge between:
316 – 317 : Contactor Logic (Return to zero)

Impossible to padlock • V erify that the front selector switch is in padlocking


position.
• Verify that the emergency handle for manual operation is
not inserted into the ATyS s manual slot.
• Verify that the ATyS s is in 0 position.
• (Padlocking is only possible in 0 position with the
emergency manual operation handle removed).

Product does not respond to remote orders • Put the product into manual mode and switch to the
zero position using the emergency handle.
• Reset by switching from manual to auto in the zero
position.
• Verify that AUX Supply voltage is within limits.
• Verify that the remote signals are being received.

Maintenance • It is recommended to operate the switch in auto or


manual through a complete cycle at least once per year.

30 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

11. SPARES AND ACCESSORIES

11.1. Accessories
Terminal Shrouds Terminal Shrouds
Source Side Load Side

Ref.: 9594 4012 Ref.: 9594 9012

ENGLISH
Voltage Tapping Kit: top or bottom Bridging Bars: top or bottom
mounting possibility

Ref.: 9599 4001 Ref.: 9509 4012

Easy Secure-Connector Bracket Din Rail 4 Module


The easy connector secure bracket consists of one part
(base part) that clips directly into the ATyS s motorization
module and another part that clips around, retains and
protects the control, aux
contact and aux power
supply connectors. Besides Ref.: 9599 4002
being easy to install and
secure for the connectors
the retainer is very easy to
remove without the need to
use a special tool.

Ref.: 9599 4003

11.2. ATyS s Spares

11.2.1. Motorisation Module


Online replacement of motorization and controls is easy and may
be carried out by following these simple steps:
• Unplug the green connectors (wiring for control, aux supply
and aux contacts)
• Remove the 4 screws in the front of the ATyS S.
• Gently pull away the motorization module.

To install a new motorisation module:


• Mount the motorisation module onto the switch by using
the manual operation shaft on the switch as a locating key.
(Ensure that the switch and motorisation module are in the
same position (I – 0 or II) when mounting the motorisation)
• Insert the 4 originally included screws in their location and Only 4 screws
tighten to the recommended torque.
• Plug the green connectors

Never handle any customer mounted accessories while there may be the risk of
DANGER WARNING CAUTION
voltage being or becoming present.

ATyS S / Sd - Réf.: 541 892 A 31


Spare Motorisation Module References
9513 5004 40A
9513 5006 63A
ATyS sd
9513 5008 80A
230Vac x2 9513 5010 100A
9513 5012 125A
9503 5004 40A
9503 5006 63A
ATyS s
9503 5008 80A
230Vac 9503 5010 100A
9503 5012 125A
9505 5004 40A
9505 5006 63A
ATyS s
9505 5008 80A
24/48Vdc 9505 5010 100A
9505 5012 125A
9506 5004 40A
9506 5006 63A
ATyS s
9506 5008 80A
12Vdc 9506 5010 100A
9506 5012 125A

11.2.2. Spare Power Switches: ATyS S and ATyS Sd

40A 9509 1004


63A 9509 1006
80A 9509 1008
100A 9509 1010
125A 9509 1012

11.2.3. Manual Emergency Direct handle

9599 5012

11.2.4. Mounting legs

x2

x2
9599 0001

32 ATyS S / Sd - Réf.: 541 892 A


ATyS S / Sd

11.2.5. Set of terminal connectors

For all ATyS S / Sd models

x5

ENGLISH
xxxx XXXX

12. ATyS s and ATyS sd ORDERING INFORMATION


The following is an ordering guide for ATyS s and ATyS sd Motorised Changeover Switches delivered inclusive of
the emergency handle and storage clip. This guide is intended so as to explain the logic behind SOCOMEC ATyS s
reference numbers.

When ordering please consult the latest SOCOMEC catalogue.

95 0 5 4 063
Product Type Ctrl Voltage N° of poles Rating
95 - TSE: I - O - II 0 - Single Aux Supply 3 - 230Vac 4-4 Pole 004 - 40A
1 - Dual Aux Supply 5 - 12Vdc 006 - 63A
(DPS) 6 - 24/48Vdc 008 - 80A
010 - 100A
012 - 125A
Ratings lth@40° C

12.1. ATyS s and ATyS sd Catalogue Reference numbers


ATyS s kVA at ATyS s ATyS s ATyS s ATyS sd
N° of Poles
Rating 415 Vac 12Vdc 24/48Vdc 230Vac 230Vac x2
40A ≤28 kVA 4 9505 4004 9506 4004 9503 4004 9513 4004
63A ≤45 kVA 4 9505 4006 9506 4006 9503 4006 9513 4006
80A ≤57 kVA 4 9505 4008 9506 4008 9503 4008 9513 4008
100A ≤70 kVA 4 9505 4010 9506 4010 9503 4010 9513 4010
125A <90 kVA 4 9505 4012 9506 4012 9503 4012 9513 4012

ATyS S / Sd - Réf.: 541 892 A 33


Socomec worldwide
In EUROpE In ASIA In MIDDLE EAST In nORTh AMERICA
BELGIUM NORTh EAST ASIA UNITED ARAB EMIRATES USA, CANADA & MEXICO
B - 1070 Bruxelles P.R.C 200052 Shanghai - China Dubai, U.A.E. Cambridge, MA 02142 USA
Tel. +32 (0)2 340 02 30 Tel. +86 (0)21 5298 9555 Tel. +971 (0)4 29 98 441 Tel. +1 617 245 0447
info.be@socomec.com info.scp.cn@socomec.com info.scp.ae@socomec.com info.scp.us@socomec.com
FRANCE SOUTh EAST ASIA & PACIFIC
F - 94132 Fontenay-sous-Bois Cedex Singapore 408723
Tel. +33 (0)1 45 14 63 30 Tel. +65 6506 7600
info.scp.fr@socomec.com info.scp.sg@socomec.com
GERMANY SOUTh ASIA
D - 76275 Ettlingen 122001 Gurgaon, Haryana - India
Tel. +49 (0)7243 65 29 2 0 Tel. +91 124 4027210
info.scp.de@socomec.com info.scp.in@socomec.com
ITALY
I - 20098 San Giuliano Milanese (MI)
Tel. +39 02 9849821
info.scp.it@socomec.com
NEThERLANDS
NL - 3991 CD Houten
Tel. +31 (0)30 760 0901

Non contractual document. © 2013, Socomec SA. All rights reserved. - To help protect the environment, this document has been printed on PEFC paper (Programme for the Endorsement of Forest Certification)
info.scp.nl@socomec.com
POLAND
01-625 Warszawa
Tel. +48 91 442 64 11
info.scp.pl@socomec.com
SLOVENIA
SI - 1000 Ljubljana
Tel. +386 1 5807 860
info.scp.si@socomec.com
SPAIN
E - 08329 Teià (Barcelona)
Tel. +34 93 540 75 75
info.scp.es@socomec.com
UNITED KINGDOM
Hitchin Hertfordshire SG4 0TY
Tel. +44 (0)1462 440033
info.scp.uk@socomec.com
TURKEY
34775 Istanbul
Tel. +90 (0)216 540 71 20
info.scp.tr@socomec.com

hEAD OffICE InTERnATIOnAL SALES YOUR DISTRIBUTOR


DEpARTMEnT
SOCOMEC GROUP SOCOMEC
S.A. SOCOMEC capital 10 951 300 € 1, rue de Westhouse - B.P. 60010
R.C.S. Strasbourg B 548 500 149 F - 67235 Benfeld Cedex - FRANCE
B.P. 60010 - 1, rue de Westhouse Tel. +33 (0)3 88 57 41 41
F-67235 Benfeld Cedex - FRANCE Fax +33 (0)3 88 74 08 00
info.scp.isd@socomec.com

VALID FOR FRANCE

www.socomec.com
Réf. 541 892 A - 05/13