CLIENT DATA

TECHENOMICS MONGOLIA LLC


TRANSFORMER DATA OIL SAMPLE DATA
K
Report Number 18575 Equipment ID :T-1 BOTTOM Date sampling :11/4/2018
Customer : MCS International Design Op ( Kv ) : 121/35 Date Analysis : 17/4/2018
Address :Tsogttsetsii, Umnugobi Serial number : Z2426 Sample Quantity : 1 Ltr 100 ml
Attention : Location : Tsetsii sample container : Bottle Syringe
Contact no : Brand : ABB Sample Point : VALVE
Email : Power ( Kva ) : Oil Colour : WHITE
Fax : Oil Capacity : Oil Brand /Grade : NYTRO GEMINI
DISSOLVED GAS ANALYSIS ( DGA )
SAMPLE PERIOD ( dd/mm/yy ) 20/04/2018 Recommended limit
ELEMENT Method Unit 18575 Normal watch Problem
Hydrogen ( H2 ) ppm 192.93 <150 BW >1000
Oxygen ( O2 ) ppm <3000 BW >5000
Carbon Monoxide ( CO ) ppm 106.66 <500 BW >1000
Carbon Dioxide ( CO2 ) ASTM ppm 913.8 <10.000 BW >15.000
Methane ( CH4 ) D-3612 ppm 4.37 < 25 BW >80
Ethylene ( C2H4 ) ppm 1.05 <20 BW >100
Ethane ( C2H6) ppm 1 <10 BW >35
Acetylene ( C2H2 ) ppm 0.75 <15 BW >70
Total Dissolved Combustable Gas ppm 500 BW > 2500

INTERPRETATION COMMENT
* High content of Hydrogen ( H2 ) indicated Arching and corona Dissolved gas contain ( Hydrogen ) being slightly above
* High Methane ( CH4 ) indicated sparking acceptance limit . Keep monitoring at next sampling.
* High Ethane ( C2H6 ) indicated local over heating
* High Acetylene ( C2 H2 ) indicated Arching
* High CO and CO2 indicated overloading

TECHENOMIC MONGOLIA LLC


Khan-Uul District, 3 - R Khoroo - Building 120 Chinggis Avenue. Ulanbaatar - Mongolia.
mail to : lab_mongolia@techenomics.com
Phone : 77107459 Fax : 77107459