John Hall
Choate Rosemary Hall
August
July12,
31, 2013
SECTION 22 08 00
SECTION 220800 - COMMISSIONING
- COMMISSIONING OF PLUMBING
OF PLUMBING SYSTEMS
SYSTEMS
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and other Division 01 Specification Sections, apply to this Section.
B. OPR and BoD documentation are included by reference for information only.
1.2 SUMMARY
A. This Section includes general requirements that apply to implementation of the commissioning
process without regard to specific systems, assemblies, and components.
B. Related Sections include the following:
1. Division 01 Section 01 91 13 Commissioning General Requirements for general
commissioning process activities.
2. Division 22 – Plumbing
1.3 DEFINITIONS
A. Commissioning Plan: A document, prepared by CxA, that outlines the organization, schedule,
allocation of resources, and documentation requirements of the commissioning process. This
Plan is included in Volume 4 of these specifications. These Checklists are included in the
Commissioning Plan which is in Section 4 of these specifications.
B. CxA: Commissioning Authority.
C. Quality Assurance: A program for the systematic monitoring and evaluation of the various
aspects of a system, assembly, or component to ensure that standards of quality are being met.
This is the responsibility of the CxA.
D. Quality Control: A system for ensuring the maintenance of proper standards in systems,
assemblies, and components. This is the responsibility of the Contractor.
E. Official: State or Local official having jurisdiction over the conveying systems
F. Systems, Assemblies, Equipment, and Components: Where these terms are used together or
separately, they shall mean “as-built” systems, assemblies, equipment, and components.
PART 2 - PRODUCTS (NOT USED)
PART 3 - EXECUTION
A. The CxA shall provide Construction Checklists to the Contractors for execution that will
indicate expected Quality Control features required for a highest-quality installation. The
contractor shall complete the checklists as construction progresses and return them to the CxA
as indicated in Section 01 91 13 Commissioning General Requirements.
B. Checklists for this section will include:
A. Prior to the testing of these systems or assemblies, the Contractor shall certify that:
1. The system or assembly is completely installed, functional, and documented.
2. Work performed by other trades, but essential for this system or assembly’s operation, is
complete (e.g., electrical components are wired and power is provided)
3. All contractor-performed start-up procedures and tests are complete and documented.
4. The system or assembly is ready for the Owner to take beneficial use.
3.3 SYSTEM OR ASSEMBLY TEST REQUIREMENTS
A. The CxA will provide Functional Performance Test procedures to the Contractor for execution
for the following specific systems, assemblies, and components:
B. Acceptance criteria and test details will be in accordance with the related sections including the
following:
1. Division 01 Section 019113 Commissioning General Requirements for general
commissioning process activities.
1. Division 22 – Plumbing
C. A sample functional performance test is included to show the typical scope and rigor of the
process.
3.4 TEST REPORTS
A. Provide copies of all reports required in the listed reference sections (see Section 1.02
SUMMARY above for the sections) for review.
3.5 SAMPLE FORMS
Model Verification
Specified Submitted Installed
Construction
Standards
Installation Checks
ID Description Pass/fail Comments
Water piping :
1. Below ground water service piping 4” and larger shall be cement lined ductile
1 iron pipe and fittings.
2. Above ground potable and non-potable water systems: ½”-4” Type L copper
tubing with soldered joints.
Gas Piping:
2 1. Aboveground exterior and interior gas and vents shall be schedule 40 steel pipe
2. Fittings 2-1/2” and less shall be screwed type for 3” and larger shall be welded.
Verify sleeves are installed for pipes passing through concrete walls or floors, ½” air
3
space around pipe to sleeve and sealed to make smoke/fire proof.
Verify that proper provisions for expansion and contraction of the hot water piping
4 systems piping is provided by means of pipe bends, pipe offsets, swing connections or
changes in direction of piping.
5 Verify that hose and drain valves are provided for complete draining of the system.
Verify that all high point in closed water piping systems have either equipment venting or
6
manual vents installed.
Natural Gas piping:
1. Verify piping pitches to drains at drip legs at least 6” long.
2. Verify shut off valve is installed at each equipment connection on the
7
downstream side of any regulators and installed in accessible location.
3. Piping is securely fastened, separately hung and not strapped or supporting other
devices.
Identification:
1. Verify color coded piping identification makers on piping systems are installed
8
including flow direction markings: Identify equipment such as pumps,
compressors, water heaters, and tanks with names and equipment numbers.
Verify Plumbing piping, fittings, and valves Insulation:
9
All interior water piping.
1. Participants
Name/Representing Participation (Testing, Witness, etc)
Owners Representative
2. Prerequisite Checklist
END OF TEST
END OF SECTION 22 08 00
SECTION 22 10 00
PLUMBING SYSTEMS
TABLE OF CONTENTS
1.1 SUMMARY...................................................................................................................................... 1
1.2 REFERENCES ................................................................................................................................. 3
1.3 QUALITY ASSURANCE ................................................................................................................ 3
1.4 SUBMITTALS ................................................................................................................................. 5
1.5 MANUALS AND INSTRUCTIONS ............................................................................................... 6
3.1 EXAMINATION/PREPARATION................................................................................................ 19
3.2 HANGERS, SUPPORTS, AND ATTACHMENTS....................................................................... 19
3.3 SOIL, WASTE, VENT, AND RAIN WATER PIPING ................................................................. 20
3.4 CLEANOUTS................................................................................................................................. 21
3.5 INSTALLATION OF WATER PIPING ........................................................................................ 21
3.6 FIXTURE ROUGHINGS ............................................................................................................... 22
3.7 INSTALLATION OF SPECIALTY ITEMS .................................................................................. 23
3.8 EQUIPMENT ROUGHINGS AND CONNECTIONS .................................................................. 24
3.9 CROSS CONNECTION PROTECTION AND APPROVALS ..................................................... 24
3.10 INSTALLATION OF FIXTURES ................................................................................................. 25
3.11 DISINFECTION OF WATER SYSTEMS..................................................................................... 25
3.12 FUEL GAS PIPING........................................................................................................................ 26
3.13 ANCHORS, EXPANSION JOINTS AND OFFSETS ................................................................... 27
3.14 BUILDING AUTOMATION SYSTEM ........................................................................................ 27
3.15 CORE DRILLING .......................................................................................................................... 28
3.16 TESTING........................................................................................................................................ 28
PLUMBING SYSTEMS 22 10 00 - i
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
PLUMBING SYSTEMS 22 10 00 - ii
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
SECTION 22 10 00
PLUMBING SYSTEMS
PART 1 - GENERAL
1.1 SUMMARY
A. Related Documents: The work of this Section is governed by the General and
Supplementary Conditions of the Contract, Sections in Division 1, and Section 20 05 00
of this Project Manual.
B. Perform work and provide material and equipment as shown on Drawings and as
specified or indicated in this Section of the Specifications. Completely coordinate work
of this Section with work of other trades and provide a complete and fully functional
installation.
C. Give notices, file plans, obtain permits and licenses, pay fees and backcharges, and obtain
necessary approvals from authorities that have jurisdiction as required to perform work in
accordance with all legal requirements and with the Contract Documents.
D. Commissioning
E. In general, the work of this Section shall include, but not be limited to:
1. Soil, waste, and vent piping systems to 10 feet outside the building.
2. Cold water system to 10 feet outside the building.
3. Hot water supply and circulation piping systems.
4. Rainwater piping system to 10 feet outside the Building foundation wall.
5. Non-potable HVAC make up water piping systems to the point of connection to
the Division 23/Section 23 06 00 system.
6. Fuel gas piping system.
7. Water meters and backflow preventers.
8. Valves, unions, and flanges.
9. Floor drains.
10. Piping insulation.
11. Hangers, supports, and attachments.
12. Plumbing demolition.
13. Core drilling.
14. Sleeves and escutcheons.
15. Underslab drainage systems.
PLUMBING SYSTEMS 22 10 00 - 1
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. Starters.
2. Access Panels.
G. Related work specified in other Sections includes, but is not necessarily limited to:
1. Excavation, Filling, and Rough Grading: Trench excavation, pipe bedding, and
backfilling.
2. Water Distribution
5. Cutting and Patching: Openings in masonry, concrete, tile, and other parts of
structure, except drilling for hangers, providing holes and openings in metal
decks, and core drilling.
6. Flashing and Sheet Metal: Flashing of roof penetrations and roof drains.
8. Painting.
9. Firestops and Smokeseals: Caulking of pipe penetrations through floor slabs and
fire-rated partitions.
12. Temporary Facilities and Controls: Sanitary facilities for use during
construction.
PLUMBING SYSTEMS 22 10 00 - 2
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
H. Allowances: Refer to Division 1 for description of work under this Section requiring
Allowances.
I. Alternates: Refer to Division 1 for description of work under this Section affected by
Alternates.
1.2 REFERENCES
A. Qualifications: Use adequate numbers of skilled, licensed plumbers who are thoroughly
trained and experienced in the installation and testing of the specified systems and who
are completely familiar with the requirements and the methods needed for proper
performance of the work of this Section.
a. The testing, adjusting and balancing agency shall meet the qualifications
specified below to be the single source of responsibility to test, adjust
and balance the domestic hot water systems. Services shall include
checking installations for conformity to design, measurement and
establishment of the temperatures of the domestic hot water systems as
required to meet design specifications and recording and reporting the
results.
PLUMBING SYSTEMS 22 10 00 - 3
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
C. Materials and equipment shall be manufactured, installed, and tested as specified in latest
editions of applicable publications, standards, and ruling of:
1. Local and State building, plumbing, mechanical, electrical, fire, and health
department codes.
E. Specific reference is made to the following Standards of the National Fire Protection
Association (NFPA) which shall govern provision of work as specified and as required
by codes and authorities:
PLUMBING SYSTEMS 22 10 00 - 4
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1.4 SUBMITTALS
B. Shop Drawings: Submit product data submittals for materials and equipment specified in
Part 2 of this Section including, but not limited to:
1. Floor drains.
5. Piping insulation.
9. Backflow preventers.
13. Data sheets for products containing VOCs shall include the VOC limit as part of
the submittal.
D. Record Drawings: Submit record drawings in accordance with the provisions of Division
1 and Section 20 05 00 - Basic Mechanical and Electrical Requirements.
E. Operation and Maintenance Manuals: Submit copies of the Operation and Maintenance
Manual in compliance with Division 1 and Section 20 05 00 - Basic Mechanical and
Electrical Requirements, and the additional requirements of this Section.
F. Prepare and submit shop drawings, O&M manuals and perform training as indicated on
the following matrix.
PLUMBING SYSTEMS 22 10 00 - 5
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. Product data cut sheets and approved shop drawings for equipment and materials
as specified in this Section.
PLUMBING SYSTEMS 22 10 00 - 6
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
PART 2 - PRODUCTS
A. Materials and equipment provided under this Section shall be in conformance with the
Code referenced Standards and be in compliance with all State and Local codes and
regulations.
1. Buried piping:
b. Type 301 stainless steel heavy duty hubless couplings may be used for
connections to existing buried systems.
c. Schedule 40 PVC Drainage Waste and Vent Piping and fittings with
solvent welded joints.
2. Above-ground piping:
b. Waste and vent piping 3 inches and smaller: Standard weight galvanized
steel pipe with galvanized cast-iron drainage fittings or Hub-less cast-
iron pipe and fittings or Type “L” copper with cast brass drainage fittings
and solder joints.
d. Schedule 40 PVC Drainage Waste and Vent Piping and fittings with
solvent welded joints.
a. Service weight cast iron pipe and fittings with lead and oakum caulk
joints.
PLUMBING SYSTEMS 22 10 00 - 7
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
a. Service weight cast iron pipe and fittings with lead and oakum caulked
joints.
B. Water System:
a. Hard drawn Type L copper with wrought copper or cast brass fittings
with 95-5 lead-free solder joints or Viega ProPress mechanical joints.
a. Hard drawn Type L copper pipe with wrought copper or cast bronze
fittings with soldered joints or roll grooved joints with ductile iron
mechanical couplings with offsetting angle-pattern bolt pads.
a. Type "K" annealed (soft) copper with wrought copper fittings and brazed
connections installed with no buried joints.
a. Buried: Type K, soft copper with wrought copper fittings and soldered
joints with no buried joints. Provide Armaflex 2000 or equal elastomeric
expanded closed cell insulation on buried piping.
b. Above Grade: Type L, soft copper with wrought copper fittings and
soldered joints.
5. Buried piping, sizes 4 inches and larger: Provide Class 56 cement-lined ductile
iron pipe and fittings with restrained mechanical joints.
1. 2 inches and smaller: Schedule 40 black steel pipe with malleable iron screwed
fittings.
PLUMBING SYSTEMS 22 10 00 - 8
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
2. 2½ inches and larger: Schedule 40 black steel pipe with welded joints.
3. Exterior exposed above grade: Polymer coated, schedule 40 black pipe and
fittings with welded joints.
4. Exterior buried: Polyethylene gas pipe and fittings in conformance with ASTM
D 2513 identified as “Gas” and “ASTM D 2513”. Provide electronically
detectable yellow warning tape equal to Terra Tape identified as “Gas Piping
Below” buried 12 inches to 15 inches above piping.
1. Galvanized Schedule 40 ASTM A53 steel pipe with galvanized malleable iron
fittings.
3. Exposed 1½ inches and smaller: chrome plated brass, threaded connections and
fittings.
1. Above Ground: Hubless cast-iron pipe and fittings with heavy-duty stainless
steel hubless couplings or galvanized steel pipe with galvanized cast-iron
drainage fittings and threaded joints.
a. Service weight cast iron pipe and fittings with lead and oakum caulked
joints.
PLUMBING SYSTEMS 22 10 00 - 9
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
A. Cast-Iron Soil Pipe and Fittings: Pipe and fittings shall be marked with the Collective
Trademark of the Cast Iron Soil Pipe Institute or be manufactured by an ISO 9001
Certified foundry in compliance with ASTM A 888-98.
E. Resilient Gaskets:
G. Unions:
2. For connections in iron pipe lines 2-½ inches and smaller, provide ground joint
brass-to-iron unions.
H. Solder:
2.4 VALVES
PLUMBING SYSTEMS 22 10 00 - 10
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. Provide 3 inch and larger, rubber encapsulated cast iron wedge disc, MSS-SP70
outside screw and yoke gate valves rated for 175 psig and 140 degrees F.
2. Watts Series 408-OSY-RW flanged epoxy coated cast iron outside screw and
yoke gate valve.
3. Non-rising stem valves: Watts Series 406-NRS-RW flanged epoxy coated cast
iron gate valve with handwheel. Non-rising stem valves may be used only where
there is insufficient clearance for outside screw and yoke gate valves.
1. Provide: two- piece bronze body, full-port TFE seats with solid brass chrome-
plated ball and stem extension.
4. Drain Valves: Watts B-6000CC, Apollo 78-203 ¾-inch hose connection with
Watts 8A vacuum breaker, and cap and chain
C. Balancing Valves:
1. 2½ inches and smaller: Apollo 77.100 full port bronze body with tee handle or
Watts B-6000 UL-Mass.
E. Check Valves:
1. 3 inches and smaller: Provide Crane No. 37, bronze, screwed, Y-pattern, 200#
WOG.
2. 4 inches and larger: Provide Watts 411, Crane No. 373, IBBM, flanged 200 lbs.
WOG.
1. Eclipse series 1000, 150 lb. Class bronze body swing check, aluminum disk,
screwed cap and threaded ends.
PLUMBING SYSTEMS 22 10 00 - 11
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
G. Strainers:
1. 2-½ inches and smaller: Bronze body, stainless steel screens, 300 psi working
pressure, threaded end with blow-off valved and piped to drain, by Watts 777
series, Mueller No. 751, Braukman FY-32 or Strong SYB.
2. 3 inches and larger: Epoxy coated, iron body, stainless steel screens, 175 psi
working pressure, flanged end with blow-off valved and piped to drain, by Watts
77FD1-FDA Mueller No. 751, Braukman FH33 or Strong F1.
2. Local thermostatic mixing valves: Provide ASSE 1070 Listed safety valves for
multiple fixture use equal to Watts MMV-M1, Symmons 5-225-CK or Powers
HydroGuard Series LM495.
A. Vacuum Relief Valves: Watts 36A, bronze body, silicon, disc, 200 PSI working pressure,
and 250 degrees F temperature rating. ANSI Z21.22, A.G.A. Certified.
B. Pressure and Temperature Relief Valves: Watts or approved equal in compliance with
ANSI Z21.22, A.G.A. Certified.
1. TP-1 for use on ½-inch supply lines: Watts A200S, J.R. Smith Fig. 2699-1 cast
bronze body with 1/2-inch sweat connections.
2. TP-2 for use on Lavatory P-Trap: J.R. Smith water saver Fig 2698, 17-gauge,
chrome-plated P-trap with trap primer tap and supply with escutcheons.
PLUMBING SYSTEMS 22 10 00 - 12
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
E. Dielectric Fittings:
F. Vent terminal Caps: Jay R. Smith 1748, Wade 3690, Zurn Z193 or Watts RD-680-VC.
A. Provide hangers, rods, and attachments to support the Work of this Section from the
building structure with UL-listed or FM-approved attachments. Provide oversized
hangers on insulated piping.
B. Water Piping:
1. 3 inches and smaller: Provide B-Line Systems Inc. Fig. B3104 light duty clevis
hangers or Fig. B3174C and B3174CT band hangers.
2. 4 inches and larger: Provide B-Line Systems Inc. Fig. B3100 clevis hangers over
insulation with 12-inch long galvanized insulation shields with supporting rods.
4. 2 inches and smaller within toilet chase: Carpenter & Patterson Fig. 81 CT
copper- plated malleable iron with Fig. 94CT copper-plated steel rod.
5. Gang Hangers: Carpenter & Patterson Fig. 342 adjustable gang hanger with
clips.
C. Drainage Piping:
1. Horizontal Supports: Provide B-Line Systems Inc. Fig. B3100 clevis hangers
with supporting rods and adjustable turnbuckles.
PLUMBING SYSTEMS 22 10 00 - 13
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
2. Riser Clamps: Provide B-Line Systems Inc. Fig. B3373 riser clamps at each
floor and as required.
4. Buried Piping Hangers: All pipe hanger components for buried piping shall be
304/316 stainless steel equal to FM Stainless Fasteners LLC.
D. Gas Piping:
1. Provide Fee and Mason No. 212 split ring hangers with supporting rods.
E. Structure Attachments:
4. Ceiling Bolts: For installation in metal decks, Carpenter & Patterson Fig. 143.
F. Provide hanger rods for horizontal piping sized according to the following schedule:
H. Trapeze Hangers: Provide metal strut trapeze hangers by B-Line, Unistrut, or Grinnell
with Clip-It nylon, B-Line Systems Inc. BVT series, or Grinnell PS-1400 insulated pipe
clamps attached to the strut.
PLUMBING SYSTEMS 22 10 00 - 14
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
J. Buried Piping:
1. Prepare trench base with bell holes and uniform slope with compacted bedding to
support the full length of the pipe between the bell holes.
2.7 CLEANOUTS
A. Exterior:
1. Provide Smith No. 4235 or Josam No. 8860 with XH cast-iron top in concrete
areas.
B. Floors:
1. Finished Tile Floors: Provide Smith No. 4160 square nickel-bronze top with tile
recess.
2. Carpeted floors: Provide J.R. Smith No. 4021-Y cast iron body with nickel
bronze top and carpet marker.
3. Unfinished Floors: Provide Smith No. 4021 with round cast-iron top.
A. Acceptable Manufacturers:
1. 2 inches and smaller: Watts 009QTS, bronze body, for hot water Watts 909HW-
QTS stainless steel check seats.
2. 2-½ inches and larger: Watts 909-0SY, epoxy coat cast-iron body, bronze seats,
and stainless steel trim.
PLUMBING SYSTEMS 22 10 00 - 15
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. ¾ inch and smaller: Watts 9D, bronze body and rubber check valve assembly
with stainless steel internal parts.
E. Provide inlet and outlet pressure gauges and strainers on inlets except in fire protection
systems.
F. Provide spare parts kit for each backflow preventer installed and a test kit for each type
installed.
B. Hose Bibb HB-1: Hose Bibb shall be ½ -inch with vacuum breaker and removable tee
handle.
2. Drinking water filter: Cuno Aqua-Pure Model No. BEV 160 or approved equal
to provide 3.34 GPM service flow rate and 0.2 micron filtration.
C. Provide inlet and outlet pressure gauges and required reducers and adapters.
2.11 DRAINS
A. Manufacturers:
PLUMBING SYSTEMS 22 10 00 - 16
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. All area drains shall be the product of one manufacturer such as Zurn Industries,
Watts, J. R. Smith, Wade or pre-approved substitution.
A. Traps:
1. Provide separate traps with integral cleanouts on fixtures and equipment that
require connections to sanitary system, except on fixtures with integral traps.
A. Adhesives and Insulation Materials: ASTM E-84 composite fire and smoke hazard rating
maximum 25 for Flame Spread and 50 for Smoke Developed. Adhesives shall be
waterproof.
C. Fire Rated Penetrations: Provide minimum density 3.5 pcf fiberglass insulation through
fire rated partitions or heavier as required by the UL through penetration system number.
D. Plenum Pipe Wrap: 3M Fire Master ceramic fiber plenum wrap to cover plastic piping to
meet UL910 and ASTM E84.
E. Hot water and hot water recirculation piping: 1-inch minimum thickness with all service
jacket (ASJ) and self-sealing lap (SSL).
F. Cold water piping: ½-inch minimum thickness with all service jacket (ASJ), self-sealing
lap (SSL), with tape and continuous vapor seal. Do not use staples.
1. Fittings and Valves: Single layer of pre-cut fiberglass blanket insulation with
PVC covers.
PLUMBING SYSTEMS 22 10 00 - 17
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
G. Horizontal Rain Water Piping (including emergency rainwater piping): ½-inch minimum
thickness with all service jacket self-sealing lap (SSL), with tape and continuous vapor
seal from 12 inches down vertical stack and all horizontal off-sets, up to and including
drain body.
1. Fittings: Provide single layer of pre-cut fiberglass blanket insulation with PVC
covers taped for continuous vapor barrier.
H. Indirect Waste Piping and Trap Primer Piping: 1/2-inch Armaflex 2000 or approved
equal 25/50 rated elastomeric expanded closed-cell insulation. Color: white.
J. Piping Guards: Provide Handi Lav-Guard insulation by Truebro on water supplies and
waste piping below Handicapped Use Lavatories.
2.14 THERMOMETERS
A. Thermometers shall be adjustable angle design of the separable well type and shall have a
9” cast aluminum case. The scale shall be white with black figures and graduations
embossed on the scale. Thermometers shall be mercury-free manufactured by Trerice
Co. or Dwyer Instrument.
B. Thermometers shall be furnished complete with all necessary sockets, wells, connectors
and accessories required for installation suitable for the service in which installed.
Extension necks shall be furnished for insulation piping.
A. Pressure gauges shall have brass movement, aluminum case, double strength clear glass
window with black embossed figures and graduations on a white dial face, with 1%
accuracy of scale range. Gauges shall be manufactured by Trerice Co., Taylor
Instrument, or Marshalltown Mfg. Gauges shall be furnished with snubbers and needle
valve shutoff valves. Provide bleed valves on pressure gauges installed at pumps.
B. Gauges shall be 4½-inch diameter furnished with ranges that will locate the intended
pressure at the point of application approximately midpoint on the range scale. Gauges
for natural gas, vacuum and similar low pressure systems shall be gauges specifically
designed for low pressure applications.
PLUMBING SYSTEMS 22 10 00 - 18
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
C. Pressure gauges shall be furnished with pressure ranges of 0 to 200 psi. Equal to Dwyer
or Trerice.
A. Provide all electrical components including, but not limited to starters, disconnects,
contactors, and controllers as required for all equipment included under this Section.
Controllers shall be wired to require a single power supply provided under Division 26.
B. All electrical equipment and components shall be listed in compliance with NFPA 70 –
National Electrical Code.
A. Equipment provided under this Section shall be furnished with manufacturer applied
lead-free primer and covered with hard gloss enamel finish.
PART 3 - EXECUTION
3.1 EXAMINATION/PREPARATION
A. Inspect existing site conditions in areas where piping and equipment will be installed and
verify existing systems and the impact of the proposed modifications before fabricating
systems to be installed.
B. Notify the Architect immediately regarding any substantially different conditions than
those shown in the Contract Documents.
A. Support all piping included in the work of this section with hangers and rods attached to
the building structure with UL-Listed attachments.
B. Space hangers and support for horizontal steel pipes according to the following schedule:
C. Space hangers and supports for horizontal copper tubing according to the following
schedule:
PLUMBING SYSTEMS 22 10 00 - 19
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
E. Support vertical piping with riser clamps secured to the piping and resting on steel
support sleeve. Provide riser clamp at each floor. Do not set riser clamp on floor
penetration sleeve.
F. Provide insulation continuous through hangers and install hanger outside of insulation.
Protect insulation with galvanized steel shields.
G. Arrange pipe supports to prevent excessive deflection and to avoid excessive bending
stress.
I. Provide stainless attachments, rods and hangers to support buried piping below structural
slabs on grade. Provide rigid installation mounted vertically and over piping attached to
hanger rods to eliminate backfill on supported piping.
J. Hubless piping: Provide adequate hangers to maintain alignment and proper pitch and to
prevent sagging of the pipe in compliance with CISPI 310.
1. Provide hangers on the piping within 6 inches of hubless piping couplings at each
change of direction.
2. Provide a minimum of one hanger every 3 feet when supporting three or more
fittings.
3. Provide hangers every 5 feet on horizontal piping except where 10-foot sections
are used. Provide hangers within 12 inches of the coupling.
4. Base of Stacks: Provide concrete or brick and mortar piers or metal brackets
attached to the structure to support the bases of cast-iron stacks.
A. Furnish and install piping plumb and parallel to building walls, beams, and columns.
Pitch horizontal lines evenly and properly secured with iron or steel hangers. Maintain a
pitch of ¼-inch per lineal foot on all drainage piping 3 inches unless otherwise indicated.
Piping 4 inches and larger shall be pitched at 1/8 inch per foot.
1. Torque hubless piping clamps to the manufacturers specified torque using the
coupling manufacturers appropriate torque wrench.
2. Extend soil and waste stacks, full size through the roof or connect to a common
vent 6 inches above the fixture flood rim.
PLUMBING SYSTEMS 22 10 00 - 20
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
3. Run vent stacks parallel to the drainage stacks and connect to the stack vent at
least 6 inches above the rim of the highest fixtures on the stack. Drip vent stacks
into the bottom of the drainage stack through a Y and 1/8 bend on an upright Y
fitting below the lowest fixture drain branch. Pitch horizontal vent lines to drain
to fixture or stack.
B. Buried Piping
1. Install buried piping only after the trench has been properly prepared with bell
holes and uniform slope with compacted bedding to support the full length of the
pipe between the bell holes. Piping shall be installed with uniform slope to
maintain a minimum slope of 1/8th inch per foot for sizes 4 inches and larger.
C. Vent Terminals:
1. Extend vents through roof and terminate at least 24 inches above the roof at least
25 feet from fresh air intakes and operable windows.
2. Terminate vents through roof and parking decks 8 feet above the roof with a
vandal proof vent cap. Secure vents to the building structure to be rigid and free
of movement.
3.4 CLEANOUTS
A. Provide cleanouts with brass caps and screws same size as pipe up to 4 inches and not
less than 4 inches for larger piping at the ends of all branches on soil and waste piping
and in such other portions of the piping where run is over 50 feet. Locate floor cleanouts
generally as indicated on drawings. Locate flush floor cleanouts in finished lobby floors
as coordinated with the architect on site. Provide extensions from changes in direction to
adjacent rooms or spaces where cleanout locations are approved by the architect.
A. Provide at least 5 feet of exterior cover over service entrance including 5-foot horizontal
distance from areaways.
B. Provide water piping pitched at least 1 inch in 40 feet to allow for complete system
draining. Slope piping to drain through fixtures, equipment or through accessible hose
end drain valves located at low points to allow systems to be drained completely by
gravity flow.
C. Provide riser shut-off valve and hose end drain valves at the base of system risers.
Provide hose end drain valves at system low points where piping cannot be drained to a
fixture.
PLUMBING SYSTEMS 22 10 00 - 21
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
E. Provide swing check valves on the downstream side of shut-off branch piping to
individual fixtures or fixture banks with faucets or mixing valves not equipped with
integral check stops.
G. Provide automatic air relief valves at high points where distribution piping cannot be
vented through fixture connections. Provide isolation shut-off valves on air relief valves
and pipe discharge to floor drain or mop service basin.
H. Piping Assembly: Cut piping square with tube cutter or hacksaw. Ream pipe and
remove burrs and slivers from both inside and outside of cut end. Ensure that burrs and
particles do not enter piping. Clean end of pipe and fitting socket with fine sand cloth to
remove dirt and surface film. Do not remove metal.
2. Assemble joint with a quarter turn to ensure distribution of flux over surfaces to
be joined. Remove excess flux with clean rag. Exercise care to ensure excess
flux is not left inside pipe joint.
I. Provide insulating shield on copper piping installed through metal stud perforations.
Maintain isolation between copper piping and ferrous metals.
A. Provide plumbing rough-in installation including fixture carriers and supports, valves and
water hammer arrestors within chase tolerances. Supply roughing through finish walls
and at hose bibbs and shower heads shall be secure and free of movement. Locate valves
and water hammer arrestors within 12 inches of approved access panel location.
B. Align exposed waste and supply pipe roughings with fixture connections within 1 inch
tolerance. Provide roughing to install flush valves in alignment with the fixture, without
vertical or horizontal offsets. Obtain fixture manufacturer roughing data sheets for
recommended roughing dimensions.
C. Rough handicapped use water closets to locate the flush valve handle on the wide side of
the toilet stall. Rough public toilet room hose bibbs 18 inches above finish floor located
below lavatories.
PLUMBING SYSTEMS 22 10 00 - 22
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
D. Secure fixture supports to floor slab construction with lag bolts and metal expansion
shields to support at least 250 pounds on the front rim of the fixture for 5 minutes.
F. Provide fixture rough-in piping connections sizes in accordance with the following
schedule:
HW CW S or W
Water Closets - 1 inch 4 inches
Lavatories 1/2 inch 1/2 inch 1-1/2 inches
Urinals - 1 inch 2 inches
Service Sinks 3/4 inch 3/4 inch 3 inches
Sinks 1/2 inch 1/2 inch 1-1/2 inches
Drinking Fountains - 1/2 inch 1-1/2 inches
G. Provide floor drains with trap primers and related piping through floor with connections
to primer connections on floor drains located in toilet rooms.
A. Provide vacuum relief valves located above the top of the heater on cold water supply
lines to water heaters between the isolation valve and the tank. Provide quantity of
vacuum relief valves in accordance with the following schedule:
1 inch 3 1
1-1/4 inches 5 2
1-1/2 inches 7 3
2 inches 10 5
2-1/2 inches - 8
3 inches - 12
PLUMBING SYSTEMS 22 10 00 - 23
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
B. Gauges: Provide gauges where indicated on the drawings and as specified. Provide
pressure gauges at water service entrance on inlet and outlet sides of strainers, filters,
backflow preventers, thermostatic mixing valves and pumps. Provide temperature gauges
on inlet and outlet side of water heaters, thermostatic mixing valves and on hot water
circulation line at least 10 feet upstream of circulation pumps. Gauges shall be legible
from 4 feet to 6 feet above the floor.
C. Trap Primers: Provide trap primer and related piping through floor and connection to
primer connection on all floor drains installed in finished areas.
D. Water Hammer Arrestors: Provide water hammer protection at all fixtures and
equipment. Equip quick-closing valves such as flush valves and solenoids, including
make-up water connections to HVAC equipment with water hammer arrestors. Banks of
plumbing fixtures may be protected with a single properly sized and located PDI-
Certified arrestor. Obtain approval for access panel location prior to installation.
A. Provide roughing and final connections for water, waste, air and gas systems including
indirect wastes, traps, tailpieces, stops and supplies, valves, reducers, shock absorbers,
adapters and unions for all equipment and fixtures including those supplied under other
sections including ice machines.
B. Provide piping and isolation shut-off valves with unions or flanges at all equipment
connections arranged to allow removal of the equipment without dismantling piping.
C. Provide complete plumbing roughings with capped and valved services with union or
flange to suit Owner furnished equipment, including, but not limited to ice machine.
D. Pipe multiple pieces of parallel equipment such as water heaters, storage tanks, or air
compressors as reverse return to maintain balance of flow through the units.
E. Refer to architectural floor plans and equipment schedules for all equipment provided
under other sections or by Owner. Roughing for all equipment including floor drain
locations shall be based on approved shop drawings. Spill indirect waste discharge into
floor drain funnel. Floor drain grate and sediment bucket shall be removable.
F. Coordinate locations of access panels for valves and slip joints with the Architect prior to
piping rough in.
G. Coordinate floor drain locations with the low point of the floor area being served. Refer
to architectural and structural drawings for location and installation requirements.
A. Protect potable water piping outlets and connections to equipment or machinery against
backflow with an air-gap or approved backflow preventer.
PLUMBING SYSTEMS 22 10 00 - 24
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. Mount reduced pressure backflow preventers between 3 to 4 feet above the floor
to the bottom of the device with a minimum of 12 inches clear space all around.
2. Mount double check valve assemblies between 1 to 4 feet above the floor to the
top of the device with 12 inches clear space all around.
C. Submit plans to DEP and obtain permits for each reduced pressure or double check valve
backflow preventer installation and submit copies of permit to Architect for record.
D. Provide indirect waste piping with funnel to receive discharge from reduced pressure
backflow preventer atmospheric vents and spill through air gap into floor drain.
A. Mount fixtures level at elevations shown on architectural drawings. Refer to toilet room
elevations and casework details.
B. Mount handicapped use fixtures in accordance with the requirements to the Architectural
Access Board Code and ANSI A117.1. Insulate hot water supply and waste piping under
lavatories.
1. Where urinals are provided, mount one urinal with the rim 17 inches above the
finish floor in compliance with the handicapped code.
C. Grout wall and floor mounted fixtures watertight where the fixtures are in contact with
walls and floors.
D. Caulk deck-mounted trim at the time of assembly, including fixture and casework
mounted. Caulk self-rimming sinks installed in casework.
A. Flush the pipe system with clean, potable water until dirty water does not appear at all
outlet points.
B. After installing faucets and trim, disinfect the domestic water piping system in
accordance with the following procedure. Open and close all valves and faucets several
times during the specified disinfection standing time.
C. After installing faucets and trim, disinfect the domestic water piping system in
accordance with the following procedure. Open and close all valves and faucets several
times during the specified disinfection standing time.
1. Fill the system with a water/chlorine solution containing at least 50 parts per
million (50 mg/1) of chlorine and valve-off the system and allow to stand for 24
hours.
PLUMBING SYSTEMS 22 10 00 - 25
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
2. Fill the system with a water/chlorine solution containing at least 200 parts per
million (200 mg/1) of chlorine and allowed to stand for three hours.
D. Following the allowed standing time, flush the system with clean potable water until
added chlorine does not remain in the water coming from the system.
A. Installation and testing shall comply with NFPA 54, State and Local codes, the
requirements of the approving authorities, and the additional requirements of this Section.
Provide piping pitched not less than 1/4-inch in 15-foot slope upward to risers and down
to meter and equipment. Provide branch tees off the side or top of mains and provide 6-
inch minimum size drip legs at low points.
B. Pipe sizes shown on the drawings are based on schedule 40 black steel. If CSST is used,
pipe sizes shall be adjusted by the contractor and be submitted for approval with
complete plans and calculations, stamped by a Professional Engineer.
C. Provide shut-off valve, reducers, adapters and union or flange at each equipment
connection. Locate valve within 6 feet of equipment served with union downstream of
valve. Provide control valves and shut-off valves in accessible locations. Do not locate
valves above ceilings. Drip leg traps shall be readily accessible.
1. Gas piping and isolation valves serving equipment shall be full sized as indicated
on the drawings up to the inlet of the gas train or connection to equipment.
D. Work of this Section shall start with the emergency shut-off valve at the discharge side of
the meter/regulator assembly installed by the gas supplier.
E. Provide independent gas vent piping from each vent on gas trains and regulators to the
building exterior. Gas vent terminal locations shall be field approved by the Architect.
F. Seismic Earthquake Valves: Provide automatic seismic gas shut-off fire valves on main
gas service immediately after the emergency shut-off valve on the discharge of the gas
meter.
PLUMBING SYSTEMS 22 10 00 - 26
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
A. Make proper provisions for expansion and contraction in all parts of the hot water and hot
water recirculation piping systems wherever possible by means of pipe bends, pipe
offsets, swing connections or changes in direction of piping. Where piping deflection
cannot be employed to absorb expansion and contraction, furnish expansion joints.
Expansion joints in copper piping shall be two-ply stainless steel bellows protected from
torsion and misalignment by an outer steel or brass casing. Stroke shall provide for a
minimum total expansion of 1¾ inch per hundred feet in copper piping between anchors.
Ratings shall be 150 psig w.p. and 300 degrees F temperature, designed for use with
copper pipe. Expansion joints shall be as manufactured by U.S. Flexible Metallic Tubing
Company, Robertshaw-Fulton or approved equal.
B. Provide pipe guides where necessary or required to confine lateral movement and on each
side of expansion loops or expansion joints. Guides for piping 2 inches and under shall
be Teflon lined copper, as manufactured by Keflex-Mave Type “BC” or approved equal.
Guides for piping 2½ inch and up shall be fabricated steel, covered inside and outside
with protective coating, top half removable.
C. All mains and risers having expansion offsets or joins shall be securely anchored to the
building construction in such a manner as to throw all expansion towards the offsets of
joints. All anchors shall be constructed from heavy galvanized iron, secured to the pipe
and securely fastened to the construction. Anchors shall be furnished with turnbuckles or
other suitable means for adjustment. The Plumbing Contractor shall be responsible for
any additional structural items that may be required for proper installation of hangers.
Anchors, guides and supports shall be approved by the Architect.
A. The building automation system shall be furnished and installed under another Section of
the specifications. Provide the tees, pipe wells, valves, and caps to allow the connection
from the BAS system to the plumbing points required. The pH probes, moisture content
meter and resistivity probe shall be provided for BAS tie-in. The following table
itemizes the equipment and location of the type of device necessary to connect to the
BAS system.
PLUMBING SYSTEMS 22 10 00 - 27
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
A. Perform all core drilling required for the installation of the plumbing system under the
work of this section. Carry all costs for core drilling. Locate all required openings prior
to coring, coordinate the opening with all other trades. Do not disturb the existing
systems. Thoroughly investigate the existing conditions in the vicinity of the required
opening prior to coring. The contractor performing the core drilling work shall be
responsible for damages to the building and its systems from the coring operations.
Disturbances from coring shall be kept to a minimum.
3.16 TESTING
A. Test the piping installation work of this Section in accordance with the direction of the
reviewing inspectors and the requirements of this Section.
1. All piping systems shall be tested, inspected and accepted before any part of the
system is covered or concealed.
2. Notify the inspecting authority at least 48 hours before tests are scheduled to be
performed.
B. Drainage Systems: Test systems in their entirety or in sections so that every pipe and
joint is subject to a minimum pressure of ten foot head of water for at least 30 minutes.
Air may be used by providing 5 PSIG for at least 30 minutes.
C. Water Piping: Test water piping at 150 percent of the working pressure but not less than
125 PSIG for 30 minutes.
D. Fuel Gas: Maintain a minimum of 150 percent of the working pressure but not less than
3 PSIG for 30 minutes.
A. Provide piping insulation on all piping as specified in Part 2 of this Section including but
not limited to water distribution and circulation piping; horizontal storm drainage piping,
storm drain bodies; secondary storm water piping; cooling tower waste piping, indirect
waste and trap primer piping; and sanitary discharge, garage drain traps, force mains,
pump discharge piping and water piping subject to freezing.
1. Insulate all piping located in unheated spaces including but not limited to attics
and parking garages as specified in Part 2 of this Section. Provide insulation over
heat tracing provided under other sections of the specifications.
B. Start installation of piping insulation only after the piping system has been pressure tested
and accepted by the plumbing inspector. Provide insulation continuous through walls,
floors and partitions through sleeves as specified in Section 20 05 00. Provide insulation
continuous through hangers and provide insulation shields. Butt insulation sections
tightly together and secure with water proof tape. Maintain the integrity of the vapor
barrier during installation and replace or repair damaged sections in compliance with the
manufacturer’s recommendations.
PLUMBING SYSTEMS 22 10 00 - 28
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. Provide two layers of cut blanket insulation with PVC covers over fittings and
valves installed and secured in compliance with the manufacturer’s requirements.
C. Provide insulation through fire rated walls and assemblies in compliance with the listing
requirements of the Listed Through-Penetration Assembly.
D. Cover insulation exposed to the elements with aluminum jacket with 2” transverse and
longitudinal lapped seams oriented to shed water. Seal seams with weatherproof
adhesive and secure jacket with 1” wide aluminum draw-bands on 12” centers.
E. Cover plastic piping in plenum spaces with ceramic fiber plenum wrap.
F. Provide insulation over heat tracing at least 12 inches beyond the end of the heat trace
cable.
A. After completing installation work and equipment start-ups, perform the necessary
adjustments to systems installed under this Section. Submit verification that systems are
operating at the specified temperatures and pressures.
B. Adjust pressure relief valves, pressure regulating valves, and thermostatic control valves,
and verify that normally open or closed valves are set in accordance with the Contract
Drawings.
2. Perform hot water system balancing as necessary to provide circulated hot water
to all remote fixtures. Schedule a minimum period of several days for the
balancing procedure.
a. Provide several days within the construction schedule to allow for system
balancing after water heater start up. System balancing shall be complete
prior to request for final punchlist. The balancing report and certification
shall be approved by the engineer
3. Balancing Procedure
a. Confirm that the water heaters are properly set and producing 140 deg. F
hot water.
PLUMBING SYSTEMS 22 10 00 - 29
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
c. Partially close hot water return system balancing valves closest to the
water heaters to force hot water through longer circulated branches.
After several hours when temperatures have adjusted to the balancing
valve adjustments, measure hot water temperatures at fixtures throughout
the system.
i. Set local thermostatic mixing valves at hand wash sinks and lavatories.
D. Adjust flush valves, open fixture stops, flush piping and clean all outlets including faucet
aerators.
E. Set aqua-stats on water heaters and circulation pumps to comply with the contract
documents.
F. Adjust metering faucets to deliver a maximum of 1/4 gallon of hot water per cycle and
operate for at least 10 seconds upon activation.
PLUMBING SYSTEMS 22 10 00 - 30
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
1. Adjust master thermostatic mixing valve assembly at the water heaters as defined
in the approved manufacturer’s literature to provide a maximum discharge
temperature of 130 degrees F.
A. The contractor shall ensure that original equipment manufacturers (OEM), providing
equipment with integral controllers (DDC, electric, electronic or pneumatic), shall
coordinate with the Building Controls System (BCS) contractor to ensure complete
integration of the OEM controls with the BCS. Provision of any gateways, wiring, etc.,
shall be by the BCS contractor.
B. The contractor shall refer to the Building Controls Systems drawings to ensure the
sequences required by OEM equipment are followed.
C. The OEM controllers shall coordinate with the BCS contractor to provide for the
following, as applicable to the device, for connection by the BCS contractor.
a. Remote start/stop.
b. Remote set-point adjust.
c. Remote alarming.
d. Remote status.
e. Remote monitoring of all process variables measured by the OEM controller. In
short, all information that is available on the local OEM control panel shall be
communicated to the BCS.
END OF SECTION
PLUMBING SYSTEMS 22 10 00 - 31
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\221000 plumbing systems-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
SECTION 22 30 00
PLUMBING EQUIPMENT
TABLE OF CONTENTS
PLUMBING EQUIPMENT 22 30 00 - i
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
SECTION 22 30 00
PLUMBING EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. Related Documents: The work of this Section is governed by the General Conditions,
Supplementary Conditions, Sections in Division 1, and Section 20 05 00 of this Project
Manual.
B. Perform work and provide material and equipment as shown on Drawings and as
specified or indicated in this Section of the Specifications. Completely coordinate work
of this Section with work of other trades and provide a complete and fully functional
installation.
C. Give notices, file plans, obtain permits and licenses, pay fees and backcharges, and obtain
necessary approvals from authorities that have jurisdiction as required to perform work in
accordance with all legal requirements and with the Contract Documents.
D. Commissioning
E. In general, the work of this Section shall include, but not be limited to:
1. Starters.
2. Access Panels.
G. Related work specified in other Sections includes, but is not necessarily limited to:
PLUMBING EQUIPMENT 22 30 00 - 1
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
H. Allowances: Refer to Division 1 for description of work under this Section requiring
Allowances.
I. Alternates: Refer to Division 1 for description of work under this Section affected by
Alternates.
1.2 REFERENCES
A. Qualifications: Use adequate numbers of skilled, licensed plumbers who are thoroughly
trained and experienced in the installation and testing of the specified plumbing systems
and who are completely familiar with the specified requirements and the methods needed
for proper performance of the work of this Section.
C. Materials and equipment shall be manufactured, installed, and tested as specified in latest
editions of applicable publications, standards, and ruling of:
1. Local and State building, plumbing, mechanical, electrical, fire, and health
department codes.
PLUMBING EQUIPMENT 22 30 00 - 2
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
E. Specific reference is made to the following Standards of the National Fire Protection
Association (NFPA) which shall govern provision of work as specified and as required
by codes and authorities:
1.4 SUBMITTALS
B. Shop Drawings: Submit product data submittals for materials and equipment specified in
Part 2 of this Section including, but not limited to:
2. Water Meters.
3. Circulators.
4. Sewage Ejectors.
5. Pressure reducing station.
PLUMBING EQUIPMENT 22 30 00 - 3
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
6. Data sheets for products containing VOCs shall include the VOC limit as part of
the submittal.
C. Record Drawings: Submit record drawings in accordance with the provisions of Division
1 and Section 20 05 00 - Basic Mechanical Requirements.
D. Operation and Maintenance Manuals: Submit copies of the Operation and Maintenance
Manual in compliance with Division 1, Section 20 05 00 - Basic Mechanical
Requirements, and the additional requirements of Article 1.7 of this Section.
E. Prepare and submit shop drawings, O&M manuals and perform training as indicated on
the following matrix.
A. Operation and Maintenance Manuals: Prepare manuals in compliance with Division 1, Section
20 05 00 - Basic Mechanical Requirements, and the additional requirements of this Section. In
addition to the requirements of other Sections, each manual shall include:
1. Product data cut sheets and approved shop drawings for equipment and materials
as specified in Article 1.5 of this Section.
B. Instruction Seminar: Perform systems instruction seminar and walk-through with the
Owner's representatives after preparation and review of the Operation and Maintenance
Manuals.
PLUMBING EQUIPMENT 22 30 00 - 4
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
PART 2 - PRODUCTS
A. Provide NRTL approved equipment, devices, materials and systems. Where a UL listing
is not available, submit the test reports of an NRTL testing engineer hired under the work
of this section to perform field testing to confirm that electrical equipment, devices,
materials and systems are in conformance with local and state codes as enforced by the
local inspector. Tests and inspections required for approval shall be performed under the
work of this Section at no additional cost to the Owner.
B. Reference Standards: Electrical equipment shall comply with the following standards:
A. Submit manufacturers not listed below for review and approval as specified for
substitutions in the General Conditions and Section 20 05 00.
B. Furnish and install 1 Weil Series Model No. 1422 submersible screenless sewage
ejectors. Each pump rated at 70 gallons per minute against a total head of 20 feet.
1. Motors will be not less than 3/4 horsepower, 208 dual voltage, 1 phase, 60 hertz,
air filled, NEMA 6 submersible design, speed not over 1750 RPM. Motors to be
furnished with neoprene jacketed power cable.
2. The motors shall be housed in an air foil water tight cast iron motor shell with the
windings having Class "F" insulation and prefabricated double seal bearings.
The motor shaft shall be 300 stainless steel with key way for positive positioning
and securing of the impeller. Motor end bell to be designed as a terminal box.
3. The impeller shall be two vane type and shall be made of close grained cast iron
accurately machined to the proper diameter and to be statically and dynamically
balanced.
4. The mechanical seal shall be fitted with two rotating carbon faces and two
ceramic stationary seats with a single spring between the rotating faces. Lower
seal faces are to be "silicone carbide coated". The entire double mechanical seal
PLUMBING EQUIPMENT 22 30 00 - 5
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
shall be housed in an oil filled chamber with no portion of the seal faces coming
in contact with the pumping media.
5. Controls shall include four Weil Series 8230 mercury float switches mounted on
a galvanized rod. One NEMA I duplex factory wired control cabinet controls
including; two magnetic starters with three coil overload protection, two fusible
disconnect switches, one automatic alternator, two momentary pump test buttons,
two pump running lights, one control circuit transformer, _____/120 volts, one 4
inch alarm bell with silencer 120 volts separate circuit.
6. Furnish and install one 52 inch by 52 inch square duplex cover with all necessary
openings including through cover discharge pipe arrangements and a 2 inch vent
connection, rectangular access door, hinged, with drop handles and locking hasp
and matching angle iron curb frame for a 48 inch by 48 inch pit. Concrete pit
shall be by the General Contractor.
7. Each pump shall include a Figure No. C-9030 lever and weighted type check
valve and OS&Y gate valve located outside of the pit. Each valve shall be the
same size as the discharge pipe.
A. Pumps shall be all bronze or stainless steel, centrifugal type, close coupled, with side
suction as manufactured by Bell and Gossett Company, Taco Inc., Armstrong Pump Co.
or approved equal.
B. Pump shall be in line type piped with full size bypass, inlet and outlet pressure gauges
and thermometer.
D. Pump operation shall be controlled by an immersion type aquastat installed at least 5 feet
upstream of the pump and set to start pump when temperature drops below ( F) and stop
pump at ( F.)
PLUMBING EQUIPMENT 22 30 00 - 6
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
A. Water meters shall be Rockwell (turbo type) (compound type) with remote reader. Meter
shall register in (cubic feet) (gallons). Provide concrete base or pipe supports as required.
A. Provide all electrical components including, but not limited to starters, disconnects,
contactors, and controllers as required for all equipment included under this Section.
Controllers shall be wired to require a single power supply provided under Division 26.
B. All electrical equipment and components shall be listed in compliance with NFPA 70 –
National Electrical Code.
A. Equipment provided under this Section shall be furnished with manufacturer applied
lead-free primer and covered with hard gloss enamel finish.
PART 3 - EXECUTION
A. Circulation pump, aquastat, piping and accessories shall be installed in accordance with
manufacturers’ recommendations.
B. Installation shall include unions and full size by-pass with shutoff valves.
A. Sewage ejector pumps, controllers, piping and accessories shall be installed in accordance
with manufacturers’ recommendations.
C. Float Settings: Float switches shall be set by the factory representative during the initial
equipment start-up. General float switch settings shall be as follows:
B. Pipe multiple water heaters as a reverse return to maintain flow balance through the units.
PLUMBING EQUIPMENT 22 30 00 - 7
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
A. All plumbing fixtures, except as otherwise noted, shall be furnished and installed by this
Contractor; he shall be responsible for correctly setting these fixtures as shown on
Architect's Plans and interior elevations.
A. After completing installation work and equipment start-ups, perform the necessary adjustments to
systems installed under this Section. Submit verification that systems are operating at the
specified temperatures and pressures.
B. Adjust pressure relief valves, pressure regulating valves, and thermostatic control valves,
and verify that normally open or closed valves are set in accordance with the Contract
Drawings.
A. The contractor shall ensure that original equipment manufacturer’s (OEM), providing
equipment with integral controllers (DDC, electric, electronic or pneumatic), shall
coordinate with the Building Controls System (BCS) contractor to ensure complete
integration of the OEM controls with the BCS. Provision of any gateways, wiring, etc.,
shall be by the BCS contractor.
B. The contractor shall refer to the Building Controls Systems drawings to ensure the
sequences required by OEM equipment are followed.
C. The OEM controllers shall coordinate with the BCS contractor to provide for the
following, as applicable to the device, for connection by the BCS contractor.
a. Remote start/stop.
b. Remote set-point adjust.
c. Remote alarming.
d. Remote status.
e. Remote monitoring of all process variables measured by the OEM controller. In
short, all information that is available on the local OEM control panel shall be
communicated to the BCS.
END OF SECTION
PLUMBING EQUIPMENT 22 30 00 - 8
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\223000 plumbing equipment-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
SECTION 22 40 00
PLUMBING FIXTURES
TABLE OF CONTENTS
PLUMBING FIXTURES 22 40 00 - i
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
SECTION 22 40 00
PLUMBING FIXTURES
PART 1 - GENERAL
1.1 SUMMARY
A. Related Documents: The Work of this Section is governed by the General Conditions,
Supplementary Conditions, Sections in Division 1, and Section 20 05 00 of this Project
Manual.
B. Perform work and provide material and equipment as shown on Drawings and as
specified or indicated in this Section of the Specifications. Completely coordinate work
of this Section with work of other trades and provide a complete and fully functional
installation.
C. Give notices, file plans, obtain permits and licenses, pay fees and backcharges, and obtain
necessary approvals from authorities that have jurisdiction as required to perform work in
accordance with all legal requirements and with the Contract Documents.
D. Commissioning
E. In general, the work of this Section shall include, but not be limited to:
1. Access Panels.
G. Install the following items furnished under other Sections or by the Owner:
1. .................................................................................
PLUMBING FIXTURES 22 40 00 - 1
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
A. Related work specified in other Sections includes, but is not necessarily limited to:
B. Allowances: Refer to Division 1 for description of work under this Section requiring
Allowances.
C. Unit Prices: Refer to Measurement and Payment - Division 1 for description of work
under this Section requiring Unit Prices.
D. Alternates: Refer to Division 1 for description of work under this Section affected by
Alternates.
1.3 REFERENCES
A. Qualifications: Use adequate numbers of skilled, licensed plumbers who are thoroughly
trained and experienced and who are completely familiar with the specified requirements
and the methods needed for proper performance of the work of this Section.
PLUMBING FIXTURES 22 40 00 - 2
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
D. Materials and equipment shall be manufactured, installed, and tested as specified in latest
editions of applicable publications, standards, and ruling of:
1. Local and State building, plumbing, mechanical, electrical, fire, and health
department codes.
E. Listing and Labeling: Provide electrically operated fixtures specified in this Section that
are listed and labeled.
1. The terms "listed" and "labeled" shall be as defined in the National Electrical
Code, Article 100.
1.5 SUBMITTALS
B. Shop Drawings: Submit product data submittals for materials and equipment specified in
Part 2 of this Section including, but not limited to:
C. Record Drawings: Submit record drawings in accordance with the provisions of Division
1 - Project Record Documents, and Section 20 05 00 - Basic Mechanical and Electrical
Requirements.
PLUMBING FIXTURES 22 40 00 - 3
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
D. Operation and Maintenance Manuals: Submit copies of the Operation and Maintenance
Manual in compliance with Division 1, Section 20 05 00 - Basic Mechanical and
Electrical Requirements, and the additional requirements of this Section.
E. Prepare and submit shop drawings, O&M manuals and perform training as indicated on
the following matrix.
B. Instruction Seminar: Perform systems instruction seminar and walk-through with the
Owner's representatives after preparation and review of the Operation and Maintenance
Manuals.
1. Sensor faucets.
1.7 WARRANTY
A. Upon completion of the Work of this Section and as a condition of its acceptance, deliver
to the Architect two copies of a written Warranty agreeing to replace the work of this
Section which fails due to defective materials or workmanship within one year after Date
of Substantial Completion as that date is determined in accordance with the General
Conditions.
PLUMBING FIXTURES 22 40 00 - 4
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
PART 2 - PRODUCTS
A. Acceptable Manufacturers: Submit manufacturers not listed below for review and
approval as specified for substitutions in Article 1.04 - Quality Assurance in this Section.
B. Fixture Trim and Accessories: Provide fixtures complete with floor mounted fixture
carrier supports; faucets, flushometers; drain outlets, tailpieces, P-traps and stops and
supplies with in-line checks.
1. Color and Finish: All trim exposed to view shall be polished chrome plated, and
all fixtures and toilet seats shall be white unless specified otherwise.
2. P-Traps: Cast brass adjustable P-trap with cleanout plug, ground joint and 17
gage minimum weight extension with escutcheon. Provide McGuire No. 8090 1-
1/4 inch by 1-1/2 inch on lavatories and No. 8098 1-1/2 inch by 1-1/2 inch on
sinks.
3. Drain Outlets: Provide drain outlet of the same manufacturer as the fixture or
faucet trim with chrome plated cast brass plug with 17 gauge minimum weight
tailpiece. Provide 1-1/4 inch tailpiece on lavatories and 1-1/2 inch on sinks.
Provide off-set drain outlets on handicapped use lavatories.
4. Stops and Supplies: Provide stops and supplies of the same manufacturer as the
fixture or faucet trim, or provide McGuire Model 170 angle stop with 5 inch long
1/2 inch nominal copper sweat extension, bell escutcheon, and 3/8 inch O.D. by
12 inch flexible riser. Provide in-line checks on both hot and cold water supplies.
Provide loose key stops on supplies in public spaces.
C. Sinks: Seamlessly drawn, self-rimming 18 gauge, type 302 (18-8) nickel bearing
stainless steel with 1-3/4 inch minimum rounded corners, satin finish, and fully
undercoated.
PLUMBING FIXTURES 22 40 00 - 5
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
D. Faucets: Chrome plated cast brass with stainless steel seats and monel stems. Gooseneck
spouts shall be interchangeable and convertible rigid/swing type. Handles shall be
interchangeable with square handle broachings.
E. Flushometers: Diaphragm operated, cast-brass body, brass or copper pipe or tubing inlet
with wall flange and tailpiece with spud, screwdriver check stop, vacuum breaker, and
brass lever handle actuation except where other variations are specified.
F. Water Conservation: Provide water conserving fixtures and trim in compliance with the
following maximum water use requirements. Provide variable pressure flow controls on
showers, sinks, and lavatory faucets.
G. Fixture Supports:
2. Provide floor mounted fixture support carriers for wall mounted fixtures
including, but not limited to, water closets, lavatories, scrub sinks and clinical
sinks. Fixture support shall support at least 250 lbs. for (5) minutes. Furnish
complete with foot piece, all necessary bolts, nuts, washers and gaskets. The
adjustable nipple for the water closets between the cast iron fitting and closet
bowl shall be threaded cast iron. Secure all foot pieces to floor slab using four
bolts per foot.
H. Toilet Seats: Provide extra heavy-duty, commercial/industrial type, elongated, open front,
solid white injection molded plastic with integral bumpers; and self sustaining stainless
steel check hinges.
PLUMBING FIXTURES 22 40 00 - 6
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
2.3 URINALS
2.4 LAVATORIES
2.5 SINKS
A. Provide all electrical components including, but not limited to starters, disconnects,
contactors, and controllers as required for all equipment included under this Section.
Controllers shall be wired to require a single power supply provided under Division 26.
B. All electrical equipment and components shall be listed in compliance with NFPA 70 –
National Electrical Code.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine roughing-in for potable cold water and hot water supplies and soil, waste, and
vent piping systems to verify actual locations of piping connections prior to installing
fixtures.
B. Examine walls, floors, and cabinets for suitable conditions where fixtures are to be
installed.
A. Provide flush valves in alignment with the fixture, without vertical or horizontal offsets.
B. Furnish fixture templates for casework contractor for counter mounted sinks and
lavatories.
PLUMBING FIXTURES 22 40 00 - 7
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
D. Provide local under-counter thermostatic mixing valve for all lavatory sensor faucets.
E. Stops and Supplies: Provide in-line checks on all hot and cold water fixture supplies
unless the faucet has integral checks.
F. Piping below accessible fixtures shall be located as close to the wall as possible and shall
be recessed, insulated or guarded without sharp or abrasive surfaces.
A. Install handicapped use fixtures in accordance with the requirements to the Architectural
Access Board Code and ANSI A117.1. Insulate hot water supply and waste piping under
lavatories.
1. Where urinals are provided: Install one urinal with the rim mounted 17 inches
above the finish floor in compliance with the handicapped code.
B. Provide thermostatic mixing valves at all public use toilet room lavatories to limit water
temperature to 110 degrees F.
C. Grout wall and floor mounted fixtures watertight where the fixtures are in contact with
walls and floors.
D. Caulk deck-mounted trim at the time of assembly, including fixture and casework
mounted. Caulk self-rimming sinks installed in casework.
A. After completion of the installation work and equipment start-ups, perform the necessary
adjustments to systems installed under this Section. Submit verification that systems are
operating at the specified temperatures and pressures.
B. Operate and adjust faucets and controls. Replace damaged and malfunctioning fixtures,
fittings, and controls.
C. Operate and adjust disposers, hot water dispensers, and controls. Replace damaged and
malfunctioning units and controls.
D. Adjust water pressure at drinking fountains, electric water coolers, and faucets, and
flushometers having controls, to provide proper flow and stream.
F. Adjust flush valves, open fixture stops, and clean faucet aerators.
PLUMBING FIXTURES 22 40 00 - 8
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
H. Adjust metering faucets to deliver a maximum of 1/4 gallon of hot water per cycle and
operate for at least 10 seconds upon activation.
J. Clean fixtures, fittings, and spout and drain strainers with manufacturers' recommended
cleaning methods and materials.
3.5 PROTECTION
B. Do not allow use of fixtures for temporary facilities, except when approved in writing by
the Owner.
A. The contractor shall ensure that original equipment manufacturers (OEM), providing
equipment with integral controllers (DDC, electric, electronic or pneumatic), shall
coordinate with the Building Controls System (BCS) contractor to ensure complete
integration of the OEM controls with the BCS. Provision of any gateways, wiring, etc.,
shall be by the BCS contractor.
B. The contractor shall refer to the Building Controls Systems drawings to ensure the
sequences required by OEM equipment are followed.
C. The OEM controllers shall coordinate with the BCS contractor to provide for the
following, as applicable to the device, for connection by the BCS contractor.
a. Remote start/stop.
b. Remote set-point adjust.
c. Remote alarming.
d. Remote status.
e. Remote monitoring of all process variables measured by the OEM controller. In
short, all information that is available on the local OEM control panel shall be
communicated to the BCS.
END OF SECTION
PLUMBING FIXTURES 22 40 00 - 9
d:\ddriveold_folders\a1202-choate\a1202-specifications\a1202-cd specifications\a1202-100% cd specifications\224000 plumbing fixtures-8-12-13.doc
100% Construction Documents – Specifications St John Hall
Choate Rosemary Hall
August 12, 2013
SECTION 23 05 93
TESTING, ADJUSTING AND BALANCING
TABLE OF CONTENTS
SECTION 23 05 93
TESTING, ADJUSTING AND BALANCING
PART 1 - GENERAL
B. Commissioning
A. This Section specifies the requirements and procedures for total mechanical systems testing,
adjusting, and balancing. Requirements include measurement and establishment of the fluid
quantities of the mechanical systems as required to meet design documents and recording
and reporting the results. Coordinate readings with Section 23 09 00 Vendors to help
calibrate BCS system. Testing, adjusting and balancing of systems shall not begin until the
BCS System is complete and functional. All work required in this section shall be performed
in conjunction with the work required of the BCS Contractor, not independently.
1. Testing boilers and pressure vessels for compliance with safety codes;
4. Requirements and procedures for piping and ductwork systems leakage tests.
1.3 DEFINITIONS
A. Systems testing, adjusting, and balancing is the process of checking and adjusting all the
building environmental systems to produce the design objectives. It includes:
C. Adjust: To regulate the specified fluid flow rate and air patterns at the terminal equipment
(e.g., reduce fan speed, throttling, change pulleys).
D. Balance: To proportion flows within the distribution system (submains, branches, and
terminals) according to specified design quantities.
F. Report forms: Test data sheets arranged for collecting test data in logical order for
submission and review. These data should also form the permanent record to be used as the
basis for required future testing, adjusting, and balancing.
G. Terminal: The point where the controlled fluid enters or leaves the distribution system.
There are supply inlets on water terminals, supply outlets on air terminals, return outlets on
water terminals, and exhaust or return inlets on air terminals such as registers, grilles,
diffusers, louvers, and hoods.
1.4 SUBMITTALS
A. Agency Data:
1. Submit proof that the proposed testing, adjusting, and balancing agency meet the
qualifications specified below.
1. Submit proof that the Test and Balance Engineer assigned to supervise the
procedures, and the technicians proposed to perform the procedures meet the
qualifications specified below.
C. Procedures and Agenda: Submit a synopsis of the testing, adjusting, and balancing
procedures and agenda proposed to be used for this project.
D. Maintenance Data: Submit maintenance and operating data that include how to test, adjust,
and balance the building systems. Include this information in maintenance data specified in
Division 1 and Section 20 05 00.
E. Sample Forms: Submit sample forms, if other than those standard forms prepared by the
AABC or NEBB are proposed.
F. Certified Reports: Submit testing, adjusting, and balancing reports bearing the seal and
signature of the Test and Balance Engineer. The reports shall be certified proof that the
systems have been tested, adjusted, and balanced in accordance with the referenced
standards; are an accurate representation of how the systems have been installed; are a true
representation of how the systems are operating at the completion of the testing, adjusting,
and balancing procedures; and are an accurate record of all final quantities measured, to
establish normal operating values of the systems.
2. Final Report: Upon verification and approval of draft reports, prepare final reports,
type written, and organized and formatted as specified below. Submit 3 complete
sets of final reports.
3. Report Format: Report forms shall be those standard forms prepared by the
referenced standard for each respective item and system to be tested, adjusted, and
balanced. Bind report forms complete with schematic systems diagrams and other
data in reinforced, vinyl, three-ring binders. Provide binding edge labels with the
project identification and a title descriptive of the contents. Divide the contents of
the binder into the below listed divisions, separated by divider tabs:
4. Report Contents: Provide the following minimum information, forms and data:
b. The remainder of the report shall contain the appropriate forms containing
as a minimum, the information indicated on the standard report forms
prepared by the AABC and NEBB, for each respective item and system.
Prepare a schematic diagram for each item of equipment and system to
accompany each respective report form.
G. Calibration Reports: Submit proof that all required instrumentation has been calibrated to
tolerances specified in the referenced standards, within a period of one month prior to
starting the project.
H. Balancing report shall include as a minimum, the following information (other parts of the
specifications may require additional information).
1. Fan Data:
3. Motor Data:
4. Starter Data:
5. VFD Data:
a. Reproducible floor plan drawings showing all air outlet locations and
numbers assigned to outlets for purpose of test.
b. Air outlet manufacturer and model number.
c. Size.
d. Actual free area.
e. Manufacturer's test factor.
f. Measured velocity.
g. Airflow design.
h. Airflow actual.
i. Airflow percentage above or below design.
j. Airflow pattern.
a. Size of inlet.
b. Actual free area.
c. Manufacturer's test factor.
d. Measured velocity.
e. Outdoor air temperature.
f. Return air temperature.
g. Mixed air temperature with averaged traverse readings (when at least a 20ºF
temperature difference exists).
9. Heat exchangers:
A. Agency Qualifications:
1. The testing, adjusting, and balancing agency shall meet the qualifications specified
below, to be the single source of responsibility to test, adjust, and balance the
building mechanical systems identified above, to produce the design objectives.
Services shall include checking installations for conformity to design, measurement
and establishment of the fluid quantities of the mechanical systems as required to
meet design specifications, and recording and reporting the results.
2. The testing, adjusting, and balancing agency certified by Associated Air Balance
Council (AABC) or by National Environmental Balancing Bureau (NEBB) in those
testing and balancing disciplines required for this project, and having at least one
Professional Engineer registered in the State in which the services are to be
performed, certified by AABC or NEBB as a Test and Balance Engineer.
B. Codes and Standards: Where the referenced codes and standards conflict, the more stringent
requirement shall apply.
D. Testing, adjusting and balancing shall not commence until all systems are complete and
functional.
A. Test, adjust, and balance the air systems before hydronic, steam, and refrigerant systems.
B. Test, adjust and balance air conditioning systems during summer season and heating systems
during winter season, including at least a period of operation at outside conditions within 5
deg. F wet bulb temperature of maximum summer design condition, and within 10 deg. F dry
bulb temperature of minimum winter design condition. Take final temperature readings
during seasonal operation.
C. Notify Owner’s Representative 14 days before scheduled testing, adjusting, and balancing is
to commence.
PART 2 - PRODUCTS
A. Not Used.
PART 3 - EXECUTION
3.1 GENERAL
A. Ensure that all contractors and trades whose work and installed systems are under testing and
balancing, are present on site during the entire time that these procedures take place. Note
that some procedures listed below have a distinct order of precedence, e.g., the testing of
Building Control System shall not occur until major pieces of mechanical equipment have
been started up and testing is complete. Prepare schedule, order and procedure for testing and
balancing, submit to the Owner’s Representative (OR) for review and approval.
C. Before the procedure begins a meeting shall be held at the site, between the balancing
contractor, the BCS contractor, the mechanical contractor and prime contractor. The prime
contractor shall present the Owner’s Representative (OR) with the completed checklists
certifying that equipment startup and testing has been completed. The contractor shall then
present his procedures for testing the overall system to OR for review and approval.
D. When the BCS testing has been completed a second meeting will be held at the site offices
between the parties mentioned above. At this time the BCS contractor shall present OR with
the completed control startup checklist. The balancing contractor shall present OR with
certificates of calibration for balancing instruments, proposed balancing forms and proposed
balancing procedures to OR, for review and approval.
E. Do not cover or conceal work before testing and inspection and obtaining approval.
F. Instruments for testing and balancing shall have been calibrated within one month prior to
testing and calibration. Calibration shall be traceable to NIST Standards. Provide photostat
of certificate of calibration to OR at meeting demonstrating balancing procedures mentioned
in this section.
G. Leaks, damage and defects discovered or resulting from testing, adjusting and balancing
shall be repaired or replaced to like-new condition with acceptable materials. Tests shall be
continued until system operates without further requirements for adjustments or repairs.
I. For each piece of equipment, copy nameplate data and include in report.
K. Provide capacity and performance of equipment by field testing. Install equipment and
instruments required for testing, thermo-wells and gauge connections at no additional costs.
M. Testing, adjusting and balancing procedures outlined below are the minimum effort required
for the project. Contractor shall use any additional procedures he feels will be necessary to
properly startup, test and balancing the job.
1. Obtain design drawings and specifications and become thoroughly acquainted with
the design intent.
2. Obtain copies of approved shop drawings of all air handling equipment, outlets
(supply, return, and exhaust) and temperature control diagrams.
4. Walk the system from the system air handling equipment to terminal units to
determine variations of installation from design. Ensure discrepancies are shown on
the record drawings.
6. Check dampers (control, smoke, volume and fire) for correct and locked position,
and temperature control for completeness of installation before starting fans.
7. Prepare report test sheets for both fans and outlets. Obtain manufacturer's outlet
factors and recommended procedures for testing. Prepare a summation of required
outlet volumes to permit a crosscheck with required fan volumes.
8. Determine best locations in main and branch ductwork for most accurate duct
traverses.
9. Place all volume dampers in the full open position. Open appropriate quantity of
VAV boxes (if applicable) to simulate air flow diversity.
10. Prepare schematic diagrams of system "as-built" ductwork and piping layouts to
facilitate reporting.
1. Open all valves to full open position. Close all bypass valves.
3. Examine hydronic systems and determine if water has been treated and cleaned.
Notify or if it is determined treatment has not occurred.
5. Clean and set automatic fill valves for required system pressure.
6. Check expansion tanks to determine that they are not air bound and that the system
is completely full of water. Adjust as necessary.
7. Check air vents at high points of systems and determine if all are installed and
operating freely (automatic type) or to bleed air completely (manual type). Adjust
as necessary.
8. Request BCS Contractor to set temperature controls so all coils are calling for full
flow.
10. Request BCS Contractor to set operating temperatures of chillers and boilers to
design requirements.
3.4 MEASUREMENTS
C. Use only those instruments, which have the maximum field measuring accuracy and are best
suited to the function being measured.
E. Use instruments with minimum scale and maximum subdivisions and with scale ranges
proper for the value being measured.
F. When averaging values, take a sufficient quantity of readings so that the average results in a
repeatability error of less than 5 percent. When measuring a single point, repeat readings
until 2 consecutive identical values are obtained.
G. Take all reading with the eye at the level of the indicated value to prevent parallax.
H. Use pulsation dampeners where necessary to eliminate error involved in estimating average
of rapidly fluctuation readings.
A. Perform procedures on each system installed under this contract, in accordance with the
detailed procedures outlined in the referenced standards and in these specifications.
B. Cut insulation, ductwork, and piping for installation of test probes to the minimum extent
necessary to allow adequate performance of procedures.
C. Patch insulation, ductwork, and housings, using materials identical to those removed.
D. Seal ducts and piping, and test for and repair leaks.
F. Mark equipment settings, including damper control positions, valve indicators, fan speed
control levers, and similar controls and devices, to show final settings. Mark with paint or
other suitable, permanent identification materials.
G. Retest, adjust, and balance systems subsequent to system modifications, and resubmit test
results.
B. Water Systems
A. Visually inspect all fire, smoke, control and volume dampers on branch take offs to each
floor to ensure that they are fully open. Open as necessary (coordinate with the BCS
Contractor).
B. Verify with straight edge that fan and motor shafts are parallel and that sheaves are in proper
alignment. Use belt tensioner to confirm belts are at proper tension. Refer to deflection
tables appropriate for installed belts. Adjust alignment and tension as necessary.
C. Start fans and verify that fan rotation is correct. If not, coordinate with electrical contractor
to switch power leads such that the fan rotates correctly.
D. Verify that fan belts are tight on one side and have slight bow on other side when fan is
operating with no squeal at startup. If not correct, adjust sheaves or motor base accordingly.
2. Divide this total by the maximum cfm scheduled for the unit to get diversity factor.
For example, if total box cfm is 50,000 and AHU is scheduled for 40,000 cfm
diversity is 40,000/50,000 = 80%.
3. Open the volume boxes necessary to approximate diversity, i.e., in the above
example, open the variable boxes to 80% of their design maximum.
G. Check motor nameplates full load amps, measure and record amperage across all power
leads. If there are marked discrepancies in amperage draws between legs, notify OR
immediately.
H. Measure and record fan and motor RPM. Check that motor rpm agrees with nameplate and
scheduled rpm.
I. Perform static pressure profile as follows: Record all results and submit to OR.
3. Determine the correct causes of any excessively high readings, i.e. open/throttled
dampers, clean/dirty coils, etc. and make necessary adjustments or coordinate
necessary repairs. Seal all holes when measurements are complete. Label locations
of measurements and cross reference labeling in report.
J. For all supply and exhaust systems with filters and volume controls (terminal boxes, or
VFD) add static pressure to the system to simulate the effect of dirty filters and wet cooling
coils. For all supply and exhaust systems with filters and no volume controls, add static
pressure to the system to simulate the effect of 1/2 dirty filters and wet cooling coils. Static
(see drawings for exact P.D. of dirty filters and wet coils) shall be added by covering filter
section with cheesecloth or other suitable material. Confirm appropriate static pressure has
been added with new static pressure reading across filters and fan. Remove cheesecloth, etc.
after traverses are complete.
K. Perform pitot tube traverse of supply, exhaust and return main ducts. Summing CFM totals
from diffusers is not an acceptable method of determining total airflow from AHU's or
fans. Balancing Contractor shall provide and install hardware for test locations and shall
properly seal them after tests. Label location of traverses and cross-reference on the report.
Perform traverses in accordance with procedures outlined in latest edition of the SMACNA
HVAC Testing, Adjusting and Balancing Manual, except that if recommended lengths of
straight duct before and after traverse points are not available, increase number of measuring
points by 50%. If a 24 point traverse would be called for given the duct cross section
area-measure 36 points, for example.
L. Adjust sheave pulley diameters or replace fixed pitch sheaves as necessary to meet the
balancing tolerance of the fan at full speed. Replace belts as necessary.
M. Measure amperage at each power leg after traverse is complete. If an overload condition
exists with measured CFM equal to scheduled CFM, notify OR immediately.
N. For economizer systems with Section 23 09 00 BCS contractors presence and assistance,
adjust minimum and maximum outdoor air CFM to quantities shown on schedules. Place
outdoor air dampers in minimum position as adjusted by controls contractor. Measure
temperature in mixed air plenum, temperature of outdoor air and by proportioning determine
% of outdoor air being supplied. Place outdoor air damper in maximum open position or
fully open variable outside air damper and repeat above measurements.
O. For systems with terminal volume boxes do the following, with BCS Contractor present for
necessary coordination:
1. At static pressure probe location in field, with number of space temperature sensors
necessary to approximate installed diversity calling for full cooling, measure static
pressure with manometer and compare with reading registering at DDC system field
panel or CRT. The "most critical" volume box shall be determined by the OR from
approved sheet metal shop drawings submittals. Typically the pressure drop from
the supply fan outlet to this box inlet is greater than for any other box. Observe
damper linkage, at this box, instruct controls contractor to vary static pressure
setpoint as required so that with stats calling for full cooling, most critical box
damper is 75% open. (Score line on damper linkage and mark full open and closed
positions of box damper. Using protractor mark 75% position open position on
volume box.)
2. At each supply terminal volume box, confirm that temperature sensor and box
controller are compatible. At each terminal volume box disconnect the actuator's
control line and confirm that box damper fails to position called for on control
drawings. Confirm second position for two position boxes, confirm room
pressurization. Adjust volumes to meet required pressurization in accordance with
the control drawings.
3. At each supply variable volume terminal box, set temperature sensor serving box for
no cooling. At box test ports take differential pressure reading with a manometer.
Adjust box minimum position at controller so that differential pressure reading
corresponds to box minimum primary air CFM shown on schedules. Place
temperature sensor controlling box to full cooling position. Using manometer gauge
adjust box controller maximum position setting to produce differential pressure
corresponding to box maximum primary air as shown on schedules. Measure CFM's
from all diffusers served by box. Confirm total agrees with scheduled box cfm.
4. Supply boxes with reheat coils, set temperature sensor to call for full heating and
confirm that hot water control valve modulates open.
5. At each constant volume terminal box, use manometer to adjust setpoint of box
controller to differential pressure corresponding to velocity(s) (airflow) scheduled
for box.
6. At each exhaust and return box, use manometer to adjust calibration of controller.
P. Balance each diffuser, register and grille to within specified tolerances. Follow procedures
in SMACNA manual referenced above. For branch ductwork and runouts, one runout in
each branch shall have its damper at least 90% open. Ensure proper pressure relationships
between adjoining spaces and include in submittal.
Q. For constant volume systems, perform pilot tube traverses for branch ducts on each floor.
Adjust volume dampers to produce design CFM for each branch.
S. Fire Dampers:
1. Random test 10% of the fire dampers, selected by the OR, for proper operation by
applying heat to release fusible links.
A. Balancing shall not begin until systems have been installed complete, including pumps,
piping, valves and coils.
D. For systems with backup equipment ensure that terminal balancing is adjusted for both
conditions - flow from control system and flow from back-up system.
3. Set all automatic control valves for full flow through the terminals.
5. For chilled and hot water system, operate building at design differential pressure.
Adjust main supply valve to maintain this differential.
a. Actual flow divided by design flow shall equal actual pump delivery
divided by design pump delivery.
a. Actual flow divided by design flow shall equal actual pump delivery
divided by design pump delivery.
b. Balance all coils in terminal so that at least one coil's throttling valve is
fully open at the completion of balance with proper flow through that coil.
9. Set pump flow to design requirements by adjusting the throttling valve at the pump
discharge.
10. Check and adjust flows through equipment to design requirements after pump flow
adjustment.
11. Check leaving and return water temperatures through heat exchangers, and at
building entrances. Reset to correct design temperatures.
12. Check water temperatures at inlet side of equipment. Note rise or drop of
temperature from source.
13. Measure pressure at control points of the system bypass control valve.
1. Manufacturer, size, type, location including room number, and zone of each coil and
piece of equipment.
3. Complete nameplate data for each piece of equipment reported along with actual
pressure readings.
A. Test and adjust mechanical systems for sound and vibration in accordance with the detailed
instructions of the referenced standards.
A. Record all data obtained during testing, adjusting, and balancing in accordance with, and on
the forms recommended by the referenced standards, and as approved on the sample report
forms.
3.11 DEMONSTRATION
A. Training:
END OF SECTION
SECTION 23 06 00
HEATING, VENTILATING AND AIR CONDITIONING
TABLE OF CONTENTS
SECTION 23 06 00
HEATING, VENTILATING AND AIR CONDITIONING
PART 1 - GENERAL
1.1 SUMMARY
B. Perform work and provide materials and equipment as shown on Drawings and as
specified or indicated in this Section of the Specifications. Completely coordinate work
of this Section with work of other trades and provide complete and fully functional
systems installation.
C. Give notices, file plans, obtain permits and licenses, pay fees and backcharges, and obtain
necessary approvals from authorities that have jurisdiction as required to perform work in
accordance with all legal requirements and with the Contract Documents.
D. Commissioning
E. In general, the work of this section shall include, but not be limited to:
1. Access panels.
2. Air and water system balancing.
3. Air conditioning unit and air cooled condenser.
4. Air distribution system including all pressure classes of ductwork, diffusers,
registers, grilles, splitters, dampers, etc.
5. Air flow control valves.
6. Air flow measuring stations.
7. Air handling units.
8. Air separators.
9. Air volume terminal boxes.
10. Automatic temperature controls, variable air volume controls and other controls.
11. Boiler flue pipe and breeching.
12. Cabinet unit heaters.
13. Centrifugal water chiller.
14. Chemical water treatment.
15. Cleaning.
16. Complete hot water system including pumps, expansion tanks, piping, valves,
fittings and other hardware.
17. Complete chilled water system including pumps, expansion tanks, piping, valves,
fittings and other hardware.
18. Condensate piping.
19. Condensate pumps
20. Constant volume and variable air volume air handling units, including fans, coils,
filters, motors and mixing boxes.
21. Coordination drawings.
22. Ductwork, piping, tanks and equipment insulation.
23. Electric cabinet heaters.
24. Equipment bases and supports.
25. Expansion joints.
26. Expansion tanks.
27. Fans : supply, exhaust, return, ventilation, miscellaneous, etc.
28. Fin-tube radiation.
29. Flexible connections for pumps and other vibrating and rotating equipment.
30. Flexible ductwork.
31. Grilles, registers, and diffusers.
32. Heat exchangers.
33. Hoisting and rigging required to complete the work of this Section.
34. Hot water boilers, trim and controls.
35. Hot water heating packaged pumping system.
36. Hot water radiant heating panels: floor, wall or ceiling.
37. Hot water unit heaters.
38. Instruction manuals and startup instructions.
39. Insulation materials.
40. Motors.
41. Motor starters.
42. Piping materials.
43. Pressure gauges.
44. Prime painting.
45. Record drawings.
46. Self-operating temperature regulator.
47. Sheet metal work.
48. Sleeves, inserts and hangers.
49. Sound attenuators.
50. Strainers.
51. Testing and balancing.
52. Thermometers.
53. Unit heaters.
54. Valves.
55. Variable frequency drives. (Furnished by this section, specified under section 26
10 00).
56. Vibration isolators and inertia blocks.
57. Water flow metering stations.
58. Water prefilters and water softener.
59. Water system accessories.
60. Water treatment equipment and chemicals and testing.
G. Install the following items furnished under other Sections or by the Owner:
H. Related work specified in other Sections includes, but is not necessarily limited to:
1. Cutting and Patching: Openings in masonry, concrete, tile, and other parts of
structure, except drilling for hangers, providing holes and openings in metal
decks, and core drilling.
2. Temporary Facilities and Controls: Temporary heat for use during construction.
7. Firestops and Smokeseals: Caulking of pipe penetrations through floor slabs and
fire-rated partitions.
9. Access Panels: Access to all equipment requiring access including but not limited
to VAVs, circuit setters, concealed valves, cleanouts, and water hammer
arrestors.
11. Acoustical Ceilings: Removal of existing ceilings for new work under this
Section.
I. Allowances: Refer to pertinent Sections of Division 1 for description of work under this
Section requiring Allowances.
J. Unit Prices: Refer to pertinent Sections of Division 1 for description of work under this
Section requiring Unit Prices.
K. Alternates: Refer to pertinent Sections of Division 1 for description of work under this
Section affected by Alternates. Air cooled chiller and associated hydronic components in
lieu of air cooled condensing unit.
1.2 REFERENCES
1. Standard 52: Gravimetric and Dust Spot Procedures for Testing and Cleaning
Devices Used in General Ventilation for Remaining Particulate
Matter
2. Standard 15: Safety Code for Mechanical Refrigeration
1. Standard 112: Standard Test Procedures for Polyphase Induction Motors and
Generators
2. RS 232:Set of Standards Specifying Three Types of Interfaces
Electrical, Functional and Mechanical
3. RS 485:Recommended Practice for Sizing Lead-Acid Batteries for
Stationary Applications.
4. RJ11: A Six Conductor Modular Jack that is Typically Wired to Four
Conductors
A. Qualifications: Use adequate numbers of skilled, licensed workers who are thoroughly
trained and experienced in the necessary crafts and who are completely familiar with the
specified requirements and the methods needed for proper performance of the Work of
this Section.
C. All materials and work provided shall be in accordance with most recent editions of
applicable standards and publications of the organizations referenced above.
1.4 SUBMITTALS
A. Comply with the pertinent provision of Sections in Division 1 and Section 20 05 00 Basic
Mechanical and Electrical Requirements.
B. Organization of Shop Drawings: Submit shop drawings and product data submittals in
bound packages organized and titled to match the Articles of Part 2 as specified in this
Section.
C. Submit shop drawings and/or product data submittals for all materials and equipment
specified in Part 2 of this Section.
G. Submit record drawings in accordance with the pertinent provisions of Division 1 for
Project Record Documents and Section 20 05 00 - Basic Mechanical and Electrical
Requirements.
H. Submit copies of the Operation and Maintenance Manuals in compliance with the
requirements of Division 1 as specified for Contract Close-Out requirements, Section 20
05 00 - Basic Mechanical and Electrical Requirements, and the additional requirements
of this Section.
I. Prepare and submit shop drawings, O&M manuals and perform training as indicated on
the following matrix.
A. Definition: Sheet Metal fabrication drawings are the installation shop drawings normally
prepared by the installing sheet metal sub-contractor.
B. Coordination Drawings: Prepare sheet metal fabrication drawings in accordance with the
requirements for coordination drawings as specified in Section 20 05 00 - Basic
Mechanical and Electrical Requirements.
C. Submit sheet metal fabrication drawings for review after all coordination with specialty
trades is completed. Drawings shall show the following:
3. Equipment including terminal boxes, coils, diffusers, grilles, fans, air handling
units, air flow stations, and sound attenuators.
A. Operation and Maintenance Manuals: Prepare manuals in compliance with the pertinent
requirements of Division 1 Section regarding Contract Close-Out Issues, Section 20 05
00 - Basic Mechanical and Electrical Requirements and the additional requirements of
this Section. In addition to the requirements of other Sections, each manual shall include:
1. Product data cut sheets and approved shop drawings for equipment and materials
as specified in this Section.
2. Lubrication instructions.
B. Instruction Seminar: Perform systems instruction seminar and walk-through with the
Owners Representatives after preparation and review of the Operations and Maintenance
Manuals.
PART 2 - PRODUCTS
A. Reference Standards
Standard As Applicable to
SMACNA HVAC Duct Sheet Metal Ductwork; Duct Liners;
Construction Standards (Metal and Adhesives; Fasteners; Flexible Ductwork.
Flexible)
Standard As Applicable to
SMACNA HVAC Air Duct Duct Leakage Testing
Leakage Test Manual
Industrial Ventilation and Dust Collection System; Canopy Hoods;
SMACNA Industrial Duct 4" and higher negative pressure ductwork
Construction and 3" neg. pressure round ductwork
B. General
2. Provide supporting and hanging devices necessary to attach entire HVAC system
including ductwork and equipment, and to prevent vibration.
a. Transverse Joints
b. Longitudinal Seams
9. Support
b. Supports, bar/angle reinforcements and other products that are not part of
the duct that are manufactured of uncoated mild steel shall either be
painted with two coats of primer or shall be manufactured of a
galvanized equivalent material.
10. Connections
a. Connect inlets and outlets of air handling units and fans to ductwork with
flexible connections unless fan has vibration isolator mounts inside unit
with flexible connections and no external vibration isolators. Exception:
Do not use flex on life safety smoke exhaust fans.
11. Construction
b. Install drive slips on air-leaving side of duct with sheet metal screws on
6" centers.
12. Joints
c. Round Joints
a. Elbows and bends for rectangular ducts shall have radiused heels and
(where possible) throats and shall have centerline radius of 1.5 times duct
width wherever possible. Elbows for grease exhaust and fume hood
exhaust shall be full radius. Square heeled elbows, turning vanes, or
mitered elbows are not allowed.
b. Where centerline radius is less than 1.5 times duct width (on supply,
return and exhaust ductwork), elbows shall be radius throat with radius
heel and full length splitter vanes when required. Minimum inside radius
(not centerline) shall be 2". Install vanes in accordance with SMACNA.
When centerline radius (r) divided by the duct width (w) is less than 1.5,
provide the following number of splitter vanes:
c. For round ductwork provide stamped elbows, with centerline radii equal
to 1-1/2 times duct diameter, or gored elbows as follows:
Angle Gores
0 36 2
37 -72 3
73 -90 5
d. Elbows for flat oval ducts shall have centerline radii equal to 1-1/2 times
duct diameter in plane of bend, or gored elbows with gores as specified
for round ducts.
10) Provide access door for all supply air ductwork upstream and
downstream of each elbow and tee and at intervals of
approximately 40 ft. to allow maximum reach of 20 ft. in straight
horizontal runs for cleaning - 24" x 24" unless duct size is
smaller in which case largest size possible shall be used (min. 6"
x 6").
b. Access doors are not shown on the drawings, but shall be provided in
accordance with the above.
16. Extractors shall have adjusting rod and locknut on outside of duct.
b. Shall have bottom and corner seams soldered watertight at least 12" up
from bottom.
18. Materials
d. Provide sealing compound and draw bands for installation. See further
paragraphs in this specification, and details for other installation
requirements.
f. Hanger and saddle in contact with flexible duct shall be wide enough to
prevent restriction of internal duct diameter when weight of supported
section rests on hanger or saddle material.
h. Collars to which flexible ducts are attached shall be at least 2" long.
Sleeves for joining sections of flexible duct shall be at least 4" long.
i. Runouts from ducts to inlet connections of air terminal boxes, except fan
boxes, shall not be flexible duct.
20. Provide factory fabricated round or oval ductwork and fittings as manufactured
by United Sheet Metal Company, Semco or Lindab.
1. Ducts wider than 19" with more than 10 square feet of unbraced panel shall be
beaded or cross-broken.
2. Internal stiffening struts shall only be used upon prior written approval of the
Architect.
4. Transverse joints shall be TDF/TDC or slip joints; use flat or standing seam
according to SMACNA. Where duct size requires standing seam, but space
restrictions dictate flat seam, notify Architect prior to fabrication.
1. Joints
a. Longitudinal joints shall be spiral seam, butt welded, lap and seam
welded, or ACME lock-grooved seam. Snap lock seams shall be used on
1/2" w.g. pressure class duct only.
1. Joints
6. Takeoffs shall be 45 leading edge type except that Bellmouths (Buckley or equal)
may be used for takeoffs to terminal boxes if the distance between the box and
point of takeoff is less than 8 ft.
7. Ducts with an aspect ratio greater than 3:1 shall be minimum of 18 gauge unless
a thicker gauge is required by SMACNA.
F. 3" and 4" Pressure Class Metal Ductwork - Flat Oval - Single Wall
1. Joints
a. Ducts shall have spiral lock seams or longitudinal seams. Seams and
joints in fittings shall be continuously welded. If coating is damaged
during welding, repair joints to prevent corrosion.
G. 3" and 4" Pressure Class Metal Ductwork - Round - Single Wall
1. Joints
b. Transverse joints shall be slip joints. Draw band joints shall be used on
longitudinal seam duct only. Loose flange Ductmate Spiralmate or
Vanstone joints may be used on ducts over 36" in diameter.
H. 6" and 10" Pressure Class Metal Ductwork - Round - Single Wall
1. Joints
1. Combination fire smoke dampers with air-foil shaped blades meeting the
requirements of the latest edition of UL Standard 555 and UL Standard 555S.
2. Due to the layout, some dampers may be out of the wall or floor through
penetration combination fire and smoke dampers. Coordinate with space
available in field.
3. References
4. Submittals
5. Quality Assurance
b. Dampers shall be tested, rated and labeled in accordance with the latest
UL requirements.
b. Storage: Store materials in a dry area indoor, protected from damage and
in accordance with manufacturer's instructions.
7. Acceptable Manufacturers
8. Ratings:
a. Fire Resistance:
b. Smoke Rating:
1)
1) 2000 fpm.
9. Construction:
10. Blades:
a. Style: True airfoil-shaped, single piece, double skin. Box or Square type
blades will not be accepted.
b. Action: Opposed.
c. Material: Minimum 14 gage (2.0 mm) equivalent thickness, galvanized
steel.
d. Width: Maximum 6 inches (152 mm).
12. Seals:
14. Axles: Minimum ½ inch (13) diameter plated steel, hex-shaped, mechanically
attached to blade.
a. Close (in a controlled manner) and lock damper during test, smoke
detection, power failure, or fire conditions through actuator closure
spring. At no time shall actuator disengage from damper blades.
18. Actuator:
a. Type:
1) Electric 24V, 60 Hz, two-position, fail close.
b. Mounting:
1) External.
19. Accessories
a. Drivemate.
b. Ductmate.
c. TDF.
23. Examination
24. Installation
b. Install dampers square and free from racking with blades running
horizontally.
d. Handle damper using sleeve or frame. Do not lift damper using blades,
actuator, or jackshaft.
1. Provide fire dampers throughout air supply system as shown on Drawings and as
required by applicable codes, standards and authorities. Provide access door for
each fire damper of sufficient size to repair internal link (see access panel/door
section).
2. Ratings
a. Fire Resistance
1) 165°F
d. Blades: Galvanized curtain style. Damper blades shall be out of the air
stream.
f. Where duct passes through fire walls or partitions, the spaces around the
fire damper sleeves shall have the necessary clearance for expansion in
conformance with the UL approval. Installation shall conform to all UL-
555 requirements.
l. The installing contractor shall provide and install bracing for multiple
section assemblies to support assembly weight and to hold against
system pressure. Attach multiple damper section assemblies together in
accordance with manufacturers instructions. Install support mullions as
reinforcement between assemblies as required.
m. Do not compress or stretch the damper frame into the duct or opening.
K. Volume Dampers
1. Provide manual adjustable volume dampers, with extended mount indicating and
locking quadrants:
2. For Seal Class A, penetrations shall be provided with sealed assemblies, Ventlok
HIVEL 641 and HIVEL 609 end bearing or approved equal. For insulated ducts
provide proper assembly.
3. Dampers shall be 1/2" smaller in both dimensions or 1" smaller diameter than
size of duct in which they are installed; e.g., use 23-1/2" by 23-1/2" damper for
24" square duct.
5. Damper blades shall be two gauges heavier than adjoining ductwork, and shall be
riveted to supporting rods. Hem over edges parallel to rods.
6. Brackets shall be galvanized metal, secured to ductwork with sheet metal screw
with locking quadrant arms (see seal class section for additional requirements).
Provide 2" handle extension for all dampers on externally insulated ductwork.
7. Volume dampers are not necessarily shown on the plans, but dampers shall be
provided as necessary for system balancing.
1. Provide steel diffusers, registers and grilles for supply, return and exhaust outlets,
of size, type and design shown on Drawings. Acceptable manufacturers shall be
Trox, Anemostat, Krueger, Metalaire, Nailor, Price or Titus.
4. Supply, return and exhaust outlets shall have opposed blade volume dampers
operable from front, where scheduled.
6. Diffusers within same room or area shall be of same type and style to provide
Architectural uniformity.
7. Surface mount diffusers, registers and grilles shall be furnished with gaskets and
installed with faces set level and plumb, tightly against mounting surface.
8. Finish shall be as directed by Architect.
9. Coordinate diffusers, registers and grilles with ceiling and wall construction.
Refer to Architectural Drawings for exact lengths and for framing and mitering
arrangements that may differ from those shown on HVAC Drawings.
A. Provide 1" thick acoustical lining by Certainteed, Knauf, Owens Corning or Manville for
following ductwork:
1. Supply and return air ductwork, including plenums, for minimum of 20 feet from
air handling units (or to sound attenuator if attenuator is located further than 20'
from fan). Exception: 3 feet before and 20 feet after humidifiers (use external
wrap); and dedicated life safety smoke exhaust systems.
3. Low pressure duct downstream from variable and constant volume boxes.
6. 10 linear feet off each VAV box unless an integral sound attenuator is scheduled.
1. For all lined ductwork at the inlets and outlets of fans, and for all lined medium
and high pressure ductwork (including plenums) within 20 feet from AHU's
provide a perforated 24 gauge aluminum or 28 gauge galvanized steel liner, with
28% minimum free area on the side of the liner exposed to the moving airstream.
Metal liner shall be held in place by weld pins spaced no more than 12" O.C.
E. Duct liner shall be installed without interruptions or gaps, using 100% coverage of
adhesive and mechanical fasteners. Mechanical fasteners shall be welded or secured
mechanically to duct on 12" maximum centers.
F. Cut liner to ensure overlapped and compressed longitudinal joints at corners. Transverse
joints in liner shall abut precisely. Seal joints against fiber entrainment with approved
adhesive, as recommended by manufacturer. Use sheet metal nosing at beginning of
lining (in direction of flow) to minimize erosion.
G. The contractor shall ensure the integrity of acoustical lining when slip in duct heaters are
installed; loose lining shall not flap about in the airstream. Secure edges of lining with
sheet metal nosing, where liner is interrupted to make room for the slip in heaters.
H. Submit samples and catalog data for duct liner, mechanical fasteners, and adhesive to
Architect for approval.
I. Friction coefficient correction factor at 1000 FPM shall be no greater than 1.1. Liner
shall be Certain-teed Ultra Liner, Knauf Duct Liner M or Manville Linacoustic. Other
liners from these manufacturers with friction coefficient correction factors greater than
listed above, are not acceptable.
J. Mylar used for vapor barrier shall meet ASTM E-84 classification.
K. Any cut liner due to duct takeoffs and branches shall be totally sealed at edges (with sheet
metal nose pieces) to prevent entrainment of loose fibers.
C. Filler material shall be inorganic mineral or glass fiber packed under not less than 5%
compression. Material shall be inert and vermin- and moisture-proof. Filler shall have
ASTM E-84 (NFPA Standard 255, UL No. 723) combustion rating of no greater than 25
flame spread, 15 smoke developed and 20 fuel contributed.
D. Silencers shall not leak air or fail structurally when subjected to differential pressure of
8" w.g. inside to outside of casing.
1. Acoustic testing shall meet ASTM E-477 standard method of testing duct liner
materials and manufactured silencers for acoustical and airflow performance.
2. Tests shall be run both with and without air flowing through silencer, and at not
less than three different flow rates.
3. Ratings shall be based on test data from nationally known, qualified independent
laboratory.
4. Test methods shall eliminate effects due to end reflection, vibration, flanking
transmission, and standing waves in reverberant room.
5. Air flow and pressure loss measurements shall be made in accordance with
applicable portions of ASME, AMCS, and ADC airflow tests.
E. Air flow shall be in same direction as attenuation for tests on dynamic insertion loss.
Sound power levels shall be measured at downstream end of silencer. Dynamic insertion
loss in dB shall not be less than that scheduled at scheduled face velocity.
F. Silencers shall not produce self-noise levels that would create sufficient noise to cause
the occupied space noise to be above its target noise level.
3. Multiple silencer units grouped together in parallel within duct system shall be
sealed airtight with sealant by Ductmate, United Sheet Metal, 3M or Hardcast.
A. General
2. Apply insulation after systems have been tested, proved tight and approved by
Architect. Remove dirt, scale, oil, rust and other foreign matter prior to
installation of insulation.
4. ASTM E-84 minimum fire hazard ratings shall be 25 flame spread, 50 fuel
contributed and 50 smoke developed.
9. Insulation shall be continuous through wall and ceiling openings and in sleeves.
10. Transmission rates of vapor barriers shall not exceed 0.02 perms.
1. Insulate supply and fresh air ducts and plena in concealed spaces and return duct
not in ceiling plenum with at least 1-1/2" thick fibrous glass duct wrap, with
foil-kraft flame resistant vapor barrier.
2. Insulation density shall be 3/4 lb/cf and maximum K-factor shall be 0.30 at 75
deg. F mean temperature.
3. If insulation does not have precut lap make lapped, butt joints by cutting 2" strip
of insulation away from vapor barrier. Apply 6" strips of approved adhesive on
16" centers and wrap duct with insulation. Staple lapped joint with
outward-clinching staples. Seal stapled joints airtight with approved vapor
barrier mastic or pressure-sensitive tape.
4. For rectangular duct 24" or larger in any dimension, augment application method
specified in item 3 with approved mechanical fasteners, such as weld pins with
speed washers, on 18" centers on bottom of duct.
5. Cover breaks in vapor material with patches of same material, secured with
adhesive and staples. Seal staples with approved vapor barrier coating.
6. Fill voids in insulation at jacket penetrations and seal with vapor barrier coating.
7. Seal and flash terminations and punctures with fibrous glass cloth between two
coats of vapor barrier coating.
1. Insulate exposed supply, return and fresh air ducts and exposed plena with 1"
thick, semi-rigid fibrous glass boards with factory-applied fire retardant
foil-reinforced kraft vapor barrier facing.
4. Extend insulation to standing seams, reinforcing, and other vertical projections 1"
and less; do not carry over. Vapor barrier jacket shall be continuous across
seams, reinforcing and projections. Insulation and jacket shall be carried over
projections that exceed insulation thickness.
6. Cover breaks, ribs and standing seam penetrations with patch of jacket material
no less than 2" beyond break; secure with adhesive and staple. Seal staples and
joints with brush-coat of vapor barrier coating.
7. Fill voids in insulation at jacket penetrations and seal with vapor barrier coating.
8. Seal and flash-terminations and punctures with fibrous glass cloth between two
coats of vapor barrier coating.
1. Exposed supply, return and fresh air ducts and exposed plena shall be insulated
with at least 1-1/2" fibrous glass ductwrap with foil-kraft flame resistant vapor
barrier.
2. Insulation density shall be 3/4 lb/cf and maximum K-factor shall be 0.30 at 75
deg. F mean temperature.
3. If insulation does not have precut lap make lapped, butt joints by cutting 2" strip
of insulation away from vapor barrier. Apply 6" strips of approved adhesive on
16" centers and wrap duct with insulation. Staple lapped joint with
outward-clinching staples. Seal stapled joints airtight with approved vapor
barrier mastic or pressure-sensitive tape.
4. Cover breaks in vapor material with patches of same material, secured with
adhesive and staples. Seal staples with approved vapor barrier coating.
5. Fill voids in insulation at jacket penetrations and seal with vapor barrier coating.
6. Seal and flash terminations and punctures with fibrous glass cloth between two
coats of vapor barrier coating.
8. Cover insulation with 6 oz./sq. yd. canvas coat adhered with approved
fire-retardant lagging adhesive.
A. General
1. Pipe materials and fitting materials shall be as indicated in Schedule of Pipe and
Fitting Materials. Provide dielectric fittings to connect different piping materials.
2. Steel piping 2-1/2" and larger shall be welded; 2" and smaller shall be screwed.
Steel piping shall be seamless or electric-resistance welded ASTM A53, Grade
B.
3. All steam condensate piping and all direct-buried piping regardless of pipe size
shall be welded. Piping shall be seamless or electric-resistance welded ASTM
A53, grade B.
5. Solder for copper pipe shall be 95/5 tin/antimony. Lead solder shall not be used.
1. Provide air vent at each high point and drain valve at each low point for complete
system drainage.
a. To each supply and return riser or branch serving two or more devices.
b. To each supply and return riser or branch from a main serving two or
more devices.
c. To each supply and return main take-off serving two or more devices.
e. Not all valves are not shown on the floor plans or flow diagrams but are
necessary as described.
1. Refrigerant piping shall be cleaned, dehydrated and capped for refrigerant service
conforming to ASTM B280. All fittings shall conform to ANSI B16.22. All
joints shall be made using a brazing alloy containing silver or using a
copper-phosphorous alloy. Brazing alloys shall have a minimum of 1,100
degrees F melting temperature and shall conform to ASTM B260.
2. Hangers for refrigerant piping shall be 1A band type of copper plated steel.
4. All refrigerant piping shall be installed to ensure that all oil returns to the
compressor. Suction line piping shall be sized on a pressure drop between the
evaporator and the compressor equal to an equivalent temperature of not greater
than 2 degrees F, with a velocity in the vertical rise of not less than 1,000 FPM.
Hot gas line piping shall be sized for 3 psig drop between the compressor and the
evaporator. Liquid line piping shall be sized on a pressure drop not to exceed 5
psig.
5. Test refrigerant system for leaks with halide torch. After leaks have been made
tight, thoroughly dehydrate system and charge with Refrigerant. Be responsible
for any leakage of refrigerant during first year of operation and replace any
refrigerant lost.
6. Adjust the refrigeration system (head pressure control valve and the condenser
pressure differential valve to maintain a constant pressure at the refrigerant
receiver. Adjust the) liquid expansion valve and hot gas regulator to maintain a
relatively constant suction temperature at all entering air conditions of operation
and therefore, a constant discharge air temperature leaving the cooling coil.
7. Provide all pilot operated expansion valves, liquid (and hot gas) solenoid valves,
(hot gas regulators), (side connectors for each coil distributor for hot gas bypass),
(adjustable head pressure control valve, condenser differential pressure valve,
refrigerant receiver), strainers, sight glasses with moisture indicators, silica gel
dryers, purge valves, relief valves, service valves, shut off valves and all other
accessories and appurtenances to provide a complete and properly functioning
refrigerant system under all conditions of operation. Provide sufficient valves to
enable system to be pumped down.
8. Side connector at each coil distributor shall be a Sporlan Type ASC. Hot gas
bypass valve shall be a Sporlan Type ADRPE.
9. Refrigerant service valves shall be designed for use with refrigerant used and
shall have pressure ratings compatible with system working pressure
encountered. Valves shall be packed, wing cap, non-rotating swivel seat disk
valves as manufactured by either Henry or Mueller.
10. Check valves shall be brass body suitable for refrigerant liquid or gas service as
required by the system design operation. Valves shall be as manufactured by
either Henry or Mueller.
11. Filter dryer in the liquid line shall consist of a steel cylinder filled with a suitable
desiccant that will not plug, cake, rust, channel or break down and shall remove
both water and acid from the refrigerant. The dryer shall be constructed so that
none of the desiccant will pass into the refrigerant lines. The filter dryer shall be
replaceable core type "Catch-All" as manufactured by either Sporlan or Alco.
12. Sight glasses shall be see through type with cover cap on each side. Sight glasses
shall be provided in liquid line before each expansion valve. Sight glasses shall
be "See All" combination moisture and liquid indicator as manufactured by either
Sporlan or Alco.
E. Connections
2. Provide eccentric reducing couplings to bring pipes flush on top for water service
and flush on bottom for steam service.
3. Branch lines in welded piping shall be made with welding tees except that branch
lines less than one-half diameter of main may be made with Weld-O-Lets.
4. Nipples shall be same material, make and thickness as pipe with which they are
used. Close nipples shall not be used.
5. Make piping connections 2-1/2" diameter and larger to valves and equipment
with flat face welding neck flanges for pressures 125 psig and less raised face for
pressures above 125 psig.
6. Make piping connections 2" dia. and smaller to valves and equipment with 300
psi brass seat unions on steel piping and with heavy semi-flushed brass unions on
copper tubing.
7. Fit flanged joints with Johns-Manville or approved equal ring gaskets. Flanges
shall be faced and drilled to ASA standards and fitted with semi-finished
hexagon machine bolts and nuts of proper number and size.
8. Make screw joints tight with Teflon (polytetrafluoroethylene) tape for water or
litharge-glycerin mixture for steam applied to male threads. Use tapered threads.
1. System
b. When liquid is detected, an audible alarm shall sound and LCD readout
of the probe activation shall be visible on the front display. The DPMS
shall alarm within one (1) minute or less after contact with liquid.
c. The system supplier shall have at least ten (10) years experience in the
manufacturing of leak detection systems.
2. Components
a. The standard sensors shall be probes. The probes shall be less than ¾ in
diameter and less than 2 long for use with organic or conductive (water
based) liquids. The probe shall be of solid state construction and in a
corrosion resistant housing with no moving parts. The probes shall reset
after liquids are removed from the probe. Lead wires shall consist of 24
AWG shielded conductor with color-coded insulation.
b. The use of other probes such as float switches, ground water monitoring
or other devises shall use a dry contact to indicate an alarm condition.
Float switch probes shall be resettable after fluids are removed and shall
use material of construction suitable for liquids to be sensed for
corrosion resistance.
d. The LCD shall provide indication of the systems status. When a probe
alarms, the type of alarm (active, short or break) and the probe number
shall be indicated. Using the membrane keypad the operator shall be
able to program the system and review the history archive. An RS-232
interface port shall be available for use in remote monitoring of the unit
using ASCII commands. The enclosure shall be NEMA 4X.
3. Safety
a. The unit must be UL Listed and provide connections for intrinsically safe
sensor circuits for use in Class 1, Division 1, Groups C & D hazardous
locations where required.
B. Installation and testing of all components of underground piping system shall be in strict
accordance with manufacturers best recommended practice. Give the Owners
Representative 48 hr. notice prior to commencing installation of piping. A field engineer,
employed by the piping system manufacturer, shall be on site during the entire time that
the installation takes place. At the completion of the installation, the manufacturer of the
system shall deliver a letter to the Owners Representative, stating that the piping system
has been installed in accordance with manufacturer's directions, and that a factory
employed engineer was on site during the entire time that the installation and testing took
place, and that the installation and testing conforms to manufacturers recommended
practice. The general contractor shall also deliver a letter to the Owners Representative
stating that the installation of the piping system was made in accordance with the
instructions of the manufacturer. Both letters shall be signed by an officer of the
respective company.
C. Provide structural insulating cement support guides on 10-ft. centers. Guides shall be 1"
wide and same diameter as pipe. Install as recommended by manufacturer.
D. Provide oval, prefabricated expansion ells with oval support guides incorporated in ells.
E. Provide steel plate anchors welded to carrier pipe and bonded to FRP casing. Plate shall
be 3/8" for pipe sizes through 6", 1/2" for 8 through 16" pipe and 3/4" for 18 through 30"
pipe. Provide holes in anchors between carrier and casing, for drain and vent. Pour
concrete thrust blocks at anchors as recommended by manufacturer.
F. Provide compressible silicon rubber, adjustable gland seals between carrier and casing,
suitable for 450 deg. F.
G. Provide 1/2" NPS vent and drain connections on vertical center lines of casing where
pipe terminates inside building or manhole wall, at least 3" inside wall.
H. Provide FRP leak plate fusion welded to casing, protruding 3" beyond outside casing
diameter, where pipe penetrates building wall, as close as possible to center of wall.
I. Provide polyester resin end seals welded to outside casing and bonded to carrier to seal
insulation terminations.
J. Provide steel head plates welded to carrier pipe and to steel sleeve of same size as casing,
at anchors within 5 ft. of piping terminal ends. Casing shall be wound on and bonded to
steel sleeve. Weld drain and vent connections to sleeve.
A. General Requirements
1. The contractor at his option may propose for the owners consideration, the use
of a grooved piping system as an alternate for chilled water, condenser, hot water
(below 230°F), dual-temperature and glycol as specified below. System shall be
manufactured by Victaulic (Basis of Design), Grinnell, Anvil Intl. or an
approved equal provided comparable performance requirements to the basis are
met.
2. The Contractor shall include all work, material, connections, installation, related
work, accessories, testing, adjusting and balancing, freight, rigging, labor, profits,
overhead and taxes, and all other items necessary to provide complete and
functional installation as required by Contract Documents.
4. Grooved piping shall not be used on steam systems, or on any hot water piping
loop above 230°F, or any piping installed in inaccessible areas such as hard
ceilings or in shafts or any hot water piping connected to a steam heat exchanger
in the immediate area of the heat exchanger.
5. Pipe, used with grooved fittings, shall be Schedule 40 steel, or as specified in the
"Piping" paragraph of these specifications.
B. Products
1. Grooved Piping
2. Branch Connections
a. For piping 2 1/2" and larger, full size branch connections shall be made
with manufactured grooved end tees. Branch connections for less than
full size shall be made with hole cut products. Similar to Victaulic, Style
920 or Style 920N branch connections with locating collar engaging into
hole or Style 72 outlet coupling used to join grooved pipe and to create a
branch connection.
3. Gaskets
a. All gaskets for water services 8 and smaller shall be Grade EHP
EPDM synthetic rubber compound with working temperature of -30F to
250F. For 10 and larger, Grade "E" EPDM synthetic rubber compound
with working temperature of -30°F to 230°F and manufactured in
accordance with ASTM D-2000.
4. Flange Adapters
a. Flange Adapters shall be similar to Vic-Flange Style 741 (2" - 12") for
connection to ANSI class 125 and 150 flanged components, or
Vic-Flange Style 743 (2" - 12") for connection to class 300 flanged
components. AGS Vic-Flange Style W741 (14-24) for connection to
class 125 and 150 flanged components
b. Flange Adapters for grooved Copper Tubing (26) for copper tubing
for connection to ANSI Class 125 Cast Iron and Class 150 Steel flanged
components. Victaulic Style 641.
2) Sizes 14" - 24": Victaulic Style AGS Vic®-300 (300 psi rated)
grooved valves. Valve body shall be ductile iron with AGS
grooved ends. Valves shall have PPS coated ductile iron disc
with stainless steel stem.
b. Ball Valves shall be similar to Victaulic style 726 Ball Valves, designed
for 800 psi (CWP) bubble tight working pressure.
c. Check valves (2" - 24") for pump discharge shall be spring loaded non-
slam design similar to Victaulic Style 716, 779 or W715. Rates as
shown:
e. Eccentric Balancing Plug Valves shall be Victaulic Style 377 for sizes
3"-12" sizes, with memory stop for throttling, metering or balancing
service. Unidirectional bubble-tight shut-off, bi-directional sealing
optional. Ductile iron body, bonnet, and plug, ASTM A-536, Grade 65-
45-12. Plug encapsulated with synthetic rubber suitable for intended
service. Welded-in nickel seat, stainless steel self-lubricating bearings.
175 PSI. AWWA rigid groove dimensions may be adapted to IPS sized
system through the use of Victaulic Style 307 transition couplings.
f. Strainer shall be similar to Victaulic Style 730 Tee Pattern Strainer for
easy access and cleaning with grooved ends for installation in vertical
downflow or horizontal flow position. Victaulic Style 732/W732 "Y"
pattern may be used for sizes 2" - 18".
2) Strapless Outlet: 1/2" or 3/4" NPT outlet on 4" and larger header
sizes rated for 300 PSI. Victaulic Style 923.
c. Pipe Hanging:
e. Grooved joints shall be clean and free from indentations, projections, and
roll marks in the area from pipe end to groove.
g. AGS series products shall be installed with the latest in accordance with
the latest Victaulic Installation Instructions. Do not install AGS products
with standard grooved-end components. Grooved pipe using an
approved grooving tool equipped with an AGS roll set.
A. Valves on steam, steam condensate, condenser water, chilled water, hot water, glycol and
fuel oil services shall be as shown on tables.
B. Valves shall have name of manufacturer and guaranteed working pressure cast or
stamped on bodies. Valves of similar type shall be by single manufacturer. Provide
chain operators for valves 3" and larger and that are 7 feet and higher above floor.
Gaskets and packings shall not contain asbestos.
C. Ratings shall include ANSI Class Rating and hole pattern for flanges.
D. Butterfly Valves: Provide lug style butterfly valves shown in tables. Provide balancing
stop on at least one valve per equipment connection and as necessary for balancing
services. When manufacturer requires, valves must be installed in proper direction for
shutoff and dead end service.
2. General Service valves shall be Ductile iron body, threaded-lug with resilient
EPDM seats, bronze disc and 416 stainless stem, by Centerline, DeZurik,
Keystone, or Grinnell.
5. If valves are used for fuel oil, provide reinforced Teflon seats and 316 stainless
disks.
E. Ball Valves: Provide full port ball valves with reinforced Teflon seats, seals, bearings
and packing. Provide balancing stop on at least one valve per equipment connection and
as necessary for balancing service. Valves on insulated piping shall have 2" extended
stems. All ball valves shall have locking handles to allow servicing and removal of
equipment. Valves shall be by Apollo, Cannon, Kitz, Milwaukee, Rockwell, Stockham,
Grinnell or Watts.
F. Globe Valves: Provide globe valves as shown in table by Crane, Jenkins, Milwaukee,
Stockham, Grinnell or Walworth. All packing shall be non-asbestos type.
G. Plug Valves: Provide plug valves with 70% port opening shown in tables for balancing.
Valves shall be by DeZurik, Mueller, Rockwell, Stockham or Walworth. Provide gear
operator with memory indicator.
H. Check Valves: Provide check valves shown in tables by APCO, Milwaukee, Mueller,
Stockham, Grinnell or Metraflex.
I. Spring Loaded Relief Valves: Reliefs shall be brass with external lever,
ASME-approved. For water reliefs pipe discharge to indirect drain. Pipe chiller
refrigerant and steam relief devices through building envelope.
J. Gate Valves: Provide gate valves shown in tables by Crane, Milwaukee or Stockham.
All packing shall be non-asbestos type.
1. In general, valves shall have OS&Y rising stems to indicate position. For
restricted clearances valves shall have non-rising stems. Contractor shall submit
where each type is used.
L. Provide unions for threaded end valves to facilitate removal from pipe.
M. Suction Diffusers
1. Suction diffuser/strainers shall have 200 psi cast iron body and stainless steel
sleeve with 5/32" perforations. Units shall include flanged connections,
removable gasketed cover and straightening vanes units shall be Mueller type
1011, Taco or B&G.
3. Valves shall be bronze body/brass ball construction with glass and carbon filled
TFE seat rings. Valves shall have dual temperature and differential pressure
readout ports across valve seat area. Valves shall be equipped with readout ports
fitted with internal EPT inserts and check valves. Valves shall have memory stop
to allow valve to be closed for service, then reopened to setpoint without
disturbing balancing position.
4. Each valve shall be equipped with a Venturi flow measuring section and ball
valve.
5. Provide preformed insulation, which permits access for balance and readout.
6. Provide one direct reading flow meter complete with calibration charts for the
project. The meter shall be used for balancing and turned over to the Owner at
the close of the job.
B. Insulation shall be fibrous glass insulation with factory-applied fire retardant vapor
barrier jacket with K factor of at least 0.23 at 75 deg. F mean temperature.
C. ASTM E-84 fire hazard ratings shall be 25 flame spread, 50 smoke developed and 50 fuel
contributed.
D. Apply insulation after systems have been tested, proved tight and approved by Architect.
Remove dirt, scale, oil, rust and foreign matter prior to installation of insulation.
F. Insulation and vapor barrier on piping which passes through walls or partitions shall pass
continuously through sleeve, except that piping between floors and through fire walls or
smoke partitions shall have space allowed for application of approved packing between
sleeves and piping, to provide firestop as required by NFPA. Seal ends to provide
continuous vapor barrier where insulation is interrupted.
G. Insulate flexible connections to same thickness and with same material as adjoining pipe
insulation.
H. Provide fibrous dual temperature insulation with factory applied vapor barrier jacket on
condensate, chilled water, drain, hot and cold water piping, unless noted otherwise.
I. Provide PVC jacket covers over all pipe insulation located in mechanical rooms within 5
feet of the floor.
J. Cooling coil condensate drain piping shall have 3/4" thick insulation. Insulation
thickness for indoor, chilled water, hot water and cold water piping shall be as follows:
Chilled Water 40-55 1.5 1.5 1.5 1.5 1.5 1.5 0.23 @ 75
Refrigerant or Below 40 1.0 1.5 1.5 1.5 1.5 1.5 0.23 @ 75
brine
K. Provide longitudinal lap and 6" wide vapor barrier joint seal strips secured with approved
adhesive.
L. Seal ends of pipe insulation and seal insulation to pipe with approved fire retardant vapor
barrier, at flanges, valves and fittings and at intervals of no more than 21 feet on
continuous runs of piping.
M. Secure covers on concealed pipe with metal bands at least 3/4" wide and no more than
18" apart, spaced to hold ends and centers of each section.
N. Insulate all refrigerant suction piping with 1-1/2 inch thick and all refrigerant hot gas
piping with ¾ inch thick and all condensation drainage piping with ¾ inch thick flexible
elastomeric thermal piping insulation similar and equal to Armaflex AP Pipe Insulation
that meets 25 Flamespread and 50 Smoke-Developed ratings as tested by ASTM E84-89.
All joints, slits and seams shall be sealed with Armstrong 520 contact adhesive to provide
a continuous vapor seal. Coat all insulation that is exposed or that is outdoors with two
coats of Armstrong Armaflex Coating to provide a protective finish.
1. Provide 1" thick flexible unicellular elastomeric foam rubber tubing insulation by
Armstrong (Armaflex), Manville, Owens Corning or Halstead/Nomaco
(Insultube), with maximum K-factor of 0.27. Install as recommended by
manufacturer.
2. Insulate valves and fittings with same thickness insulation as pipe using
manufacturer's preformed fitting and valve insulation or field-fabricated covers
made with manufacturer's templates.
3. Adhere insulation to pipe and seal butt joints with full coverage of insulation
manufacturers approved adhesive.
5. Apply two coats of approved vinyl lacquer coating over woven glass yarn mesh
adhered to insulation surface with Insulcolor or approved equal lagging adhesive.
6. Provide cork or dowel supports and metal shields at pipe hangers and supports as
recommended by manufacturer.
P. Piping outdoors or underground shall be waterproofed with 45 lb. glazed roofing felt, as
follows:
3. Provide 4" butt joint strips and secure with two wire ties.
a. Wrap insulation around fitting and tuck ends into fitting throat.
c. If two layers of insulation are used on fittings, wrap and secure first layer
with twine before applying second layer.
4. Top layer of insulation shall be covered with one piece, PVC, molded jacket
cover. Secure cover with stainless steel tack fasteners inserted into jacket throat
overlap seam.
5. Tape joints with pressure-sensitive vapor barrier tape; tape shall extend 2" on
either side of joint.
6. Prior to taping of joints on chilled water and condenser water lines, apply vapor
barrier mastic (brushed on) to fitting cover, throat overlap and edges. Also apply
vapor barrier mastic to pipe insulation jacket ends.
7. For strainers and other valves or fittings which need maintenance, provide
preformed removable insulation section.
1. Suction lines, hot gas bypass lines, and outdoor liquid lines shall be insulated
with 3/4" thick rigid closed cell foam insulation, Armstrong Rigid Armaflex,
Manville, Owens Corning or Halstead/Nomaco (Insultube), except in computer
room plena.
3. Outside above ground insulation shall be protected with two coats of approved
vinyl lacquer coating over woven glass mesh adhered to insulation with
Insulcolor or approved equal lagging adhesive, as recommended by
manufacturer.
4. Refrigerant piping in hung ceiling and underfloor supply and return plena shall
be insulated with 1" thick fibrous glass insulation that meets applicable
requirements of this Paragraph.
A. Provide pipe stands, supports, hangers and other supporting appliances as necessary to
support work required by Contract Documents.
Nom. Pipe Size Max. Span Min. Rod Size Hanger Type
(inches) (feet) (inches)
1-1/4 and Smaller 7 3/8 Clevis Hanger
1-1/2 9 3/8 Clevis Hanger
2 10 3/8 Clevis Hanger
2-1/2 10 1/2 Clevis Hanger
3 12 1/2 Clevis Hanger
4 14 5/8 1 Rod Roll Hanger
5 14 5/8 1 Rod Roll Hanger
6 14 3/4 1 Rod Roll Hanger
8 - 12 15 7/8 (two) 2 Rod Roll Hangers
D. Horizontal copper tubing shall have maximum hanger spacing of 5 ft. for tubing 1-1/4"
dia. and smaller and 10' for tubing 1-1/2" and larger. Maximum spacing for PVC pipe
hangers shall be 4'.
E. Reduce spacing, regardless of pipe size, as necessary for fittings, valves and other
concentrated loads.
F. Support piping 4" dia. and larger from structure with pipe roll hangers with adjustable
steel rod hangers, sized to accommodate insulation.
G. Support piping 3" dia. and under from structure with Carpenter and Patterson Fig. 100
clevis hangers or approved equal.
H. Hangers shall be by Carpenter and Patterson, F & S, or Grinnell Co. Figure numbers of
Carpenter and Patterson are specified to establish standards of quality for performance
and materials.
I. Provide spring hangers with travel stops as specified in Vibration Isolation Paragraph of
Section 20 05 48 and where shown on Drawings.
J. Pipe supports for 4" and larger pipe and insulated high-temperature piping shall have
welded inserts of equal thickness to insulation to prevent compression of insulation.
Other insulated pipe shall have 12", 14 GA shields at hangers, composed of 180 coverage
of galvanized sheet metal and high density, preformed, rigid insulation. Where rollers are
required, shield shall be steel pipe.
K. Hangers for horizontal lines shall be vertically adjustable to obtain pitch requirements of
Piping Paragraph.
3. Automatic air vent valves with manual shut-off for each high point on supply and
return mains with 1/4" copper overflow run to nearest plumbing fixture for
drainage.
5. Drain valve at each low point with 3/4" brass heads with hose connections.
B. Provide a Spirotherm (Spirovent Air / Dirt Eliminator), Bell & Gossett, Amtrol or Taco
air eliminator on hot water heating, chilled water and other closed water system. All
units shall be fabricated steel, rated for 150 psig design pressure and be selected for
specified flow rate with pressure drop not to exceed one foot of head and velocity not to
exceed 4 feet per second. Units to include copper coalescing medium to facilitate
maximum air and dirt elimination. Alternate units shall be furnished with galvanized
steel strainer and stainless steel collector tube for a similar purpose. Provide integral high
capacity float actuated air vent at top fitting of tank. Alternates must include cast iron
float vent rated at 150 psig located at top of vessel. All units will include bottom blow
down connection.
C. Provide at high points Spirotherm (Spirotop), Bell & Gossett, Spirax Sarco or approved
equal air release valves on hot and/or chilled water systems and other closed water loops.
All valves shall be cast brass, rated for 150 psig design pressure and 270 degree F
operating temperature. Units to include non-ferrous floats, stainless steel linkage and
Viton seal, which closes against a brass spring operated seat. Alternate units shall be
high capacity cast iron type with brass or Viton shut-off valve. Alternates must be rated
for 150 psig working pressure and 250 degrees F operating temperature.
A. General
1. Apply insulation after systems have been tested, proved tight and approved by
Architect. Remove dirt, scale, oil, rust and foreign matter prior to installation of
insulation.
a. Chiller
b. Hot and chilled water storage tanks
c. Heat exchangers
d. Expansion tanks
e. Air separators
f. Drain pans
g. Duct-mounted coils
h. Pumps
i. Surge and flash tanks
j. Valve heads
5. Insulation shall be 1" thick fibrous glass rigid block or semi rigid board rated for
temperature intended. Insulation shall be formed or fabricated to fit equipment.
Ensure tight fit. Bevel edges and butt and stagger joints.
B. Secure with bands or wires at intervals recommended by manufacturer, no more than 12"
centers. Provide corner angles.
C. Set cellular glass insulation and seal joints with bedding compound. Fill mineral fiber
joints with insulating cement.
D. Apply two coats of adhesive with fibrous glass cloth embedded in first coat before
application of second. Dry film thickness of finish shall be 1/8". Apply insulating
cement over coated insulation; do not coat removable sections.
E. Equipment, which needs servicing, such as pumps and plate heat exchangers shall be
provided with removable insulation sections. Coordinate method of insulating plate heat
exchanger with exchanger manufacturer.
A. Provide motors and controls. Furnish starters for HVAC equipment. Provide control and
other related wiring including interlocks. Power wiring (to panelboards, disconnect
switches, starters and motors) will be provided under Section 26 10 00, ELECTRICAL.
Starters that are not integral to equipment will be furnished under this Section 23 06 00
and installed and wired under Section 26 10 00, ELECTRICAL.
1. Motors under 1/2 HP, shall be designed for 120 V, 60 Hz, single phase, unless
otherwise specified.
C. Motors for use with variable frequency drives (VFD's) shall be "inverter-duty" or "drive
duty" motors, compatible with the drive to which it is connected. Use of the motor with a
VFD shall not adversely affect the operation, useful life, or warranty of the motor.
Motors listed in the schedules to be powered by VFD shall conform to the following:
3. Motors used with VFD shall have a minimum three (3) year warranty.
4. If the motor is located more than 50 feet away from the VFD it serves, the
contractor shall provide an output filter on the VFD.
D. All motors shall be premium efficiency type. They shall conform to NEMA Standard
MG-1-12.53a and shall have their efficiencies determined in accordance with IEEE
Standard 112 Method B. The NEMA nominal efficiency shall be listed on the motor
nameplate. Minimum nominal efficiencies shall be according to the tables below:
TABLE I
PERFORMANCE DATA for ENERGY EFFICIENT MOTORS
DRIP-PROOF TYPE
Minimum Efficiency at Full Load
(percent)
HP 1200 RPM 1800 RPM 3600 RPM
Eff. Eff. Eff.
1 82.5 85.5 80.0
TABLE I
PERFORMANCE DATA for ENERGY EFFICIENT MOTORS
DRIP-PROOF TYPE
Minimum Efficiency at Full Load
(percent)
HP 1200 RPM 1800 RPM 3600 RPM
Eff. Eff. Eff.
1.5 86.5 86.5 85.5
2 87.5 86.5 86.5
3 89.5 89.5 86.5
5 89.5 89.5 89.5
7.5 91.7 91.0 89.5
10 91.7 91.7 90.2
15 92.4 93.0 91.0
20 92.4 93.0 92.4
25 93.0 93.6 93.0
30 93.6 94.1 93.0
40 94.1 94.1 93.6
50 94.1 94.5 93.6
TABLE II
PERFORMANCE DATA for ENERGY EFFICIENT MOTORS
TOTALLY ENCLOSED FAN COOLED TYPE
Minimum Efficiency at Full Load
(percent)
HP 1200 RPM 1800 RPM 3600 RPM
Eff. Eff. Eff.
1 82.5 85.5 78.5
1.5 87.5 86.5 85.5
2 88.5 86.5 86.5
3 89.5 89.5 88.5
5 89.5 89.5 89.5
7.5 91.7 91.7 91.0
10 91.7 91.7 91.7
15 92.4 92.4 91.7
20 92.4 93.0 92.4
TABLE II
PERFORMANCE DATA for ENERGY EFFICIENT MOTORS
TOTALLY ENCLOSED FAN COOLED TYPE
Minimum Efficiency at Full Load
(percent)
HP 1200 RPM 1800 RPM 3600 RPM
25 93.0 93.6 93.0
30 93.6 93.6 93.0
40 94.1 94.1 93.6
50 94.1 94.5 94.1
200 95.8 96.2 95.8
E. Starters that require interlocks or remote control shall be magnetic with HAND-OFF-
AUTOMATIC switch (fast-slow-off-auto for two speed motors) in cover. Provide
magnetic starters as necessary, with auxiliary contacts, buttons and switches in required
configurations. Refer to specification section AUTOMATIC TEMPERATURE
CONTROLS and to Control Drawings for interlock requirements. Starters shall be by
single manufacturer: Cutler-Hammer, Clark, Arrow Hart or Square D.
2. Other motors shall be provided with a manual starter with ON-OFF switch.
3. Control relay for each starter shall be for operation on 120 V, single phase, and
transformer of sufficient capacity within starter case shall be furnished for this
purpose.
4. Provide inverse time limit overload and under voltage protection in each leg and
with pilot lights. Provide red and green On-Off pilot lights.
8. Furnish for all single speed motors, 10 HP and above, 95% power factor
correction capacitors. Capacitors shall be in NEMA enclosure of the same rating
as the motor's starter.
9. Furnish reduce voltage starters for all 3 phase motors, 20hp and above.
10. Starters shall be furnished as combination magnetic and circuit breaker type, non-
reversing (unless otherwise noted). Each combination starter shall be rated
65,000 symmetrical amperes at 480V.
2.14 DRIVES
A. Drives for belted motors shall be flame retardant and by Allis-Chalmers, Browning or
Woods V-belt drives with adjustable motor sheave. Drives shall be as short as practical
and shall have number of belts necessary to transmit required horsepower without undue
slip or strain.
A. General Requirements
*Armstrong
*Bell and Gossett
*Taco
5. Provide cyclone type abrasive separators to provide clean water flush to seals for
all pumps on open systems (open cell cooling towers), and all pumps over 3 HP
on closed systems requiring flush. Separator materials and pressure ratings shall
be suitable for intended class of service and maximum working pressure of the
pump. Provide sheet metal guard to protect separator tubing from damage - do
not use plastic tubing for separator. Provide shut off cocks with three valve
bypass line to allow separator to be removed for cleaning while seals continue to
be flushed.
6. Provide, under the work of the mechanical section, flexible connections (if
shown on details) and vibration isolation components for all pumps. See the
vibration isolation section.
7. Provide steel channel base for each pump with drip rim and drain connection.
9. Provide an allowance for all necessary work in the field and shop to trim each
pump impeller, if needed, for water balancing purposes.
1. General:
a. For all types of pumps listed below, bearing frame and pump internals
shall be serviceable without disturbing motor or connected piping.
b. For all types of pumps listed below, provide mechanical seals with
carbon rings and ceramic faces, stainless or brass metal parts, stainless
springs and synthetic rubber bellows. Seals shall operate satisfactorily to
225.
c. Unless otherwise stated in the schedules, all pumps shall be single stage.
d. Provide tappings for pressure gauges at inlet and discharge of all pumps.
2. In-Line Pumps
a. In Line pumps shall have bronze fitted construction, including cast iron
casings, bronze or copper shaft sleeves, alloy steel shafts and bronze
impellers. Bearings shall be either be sleeve type or regreasable ball
bearings. Provide casing wear rings, drain and vent connections and
flexible coupling or direct drive connection between pump and motor. If
the scheduled pump includes ball bearings and a direct drive motor to
impeller connection, the submitted pump shall not have sleeve bearings
or a flexible coupling between pump and motor.
A. Provide round double wall air or fill insulated to limit skin temperature to 140 deg. F,
prefabricated double-wall duct breeching for water heaters furnished under plumbing
section and for boilers and other mechanical equipment that burn gas or oil, by Ampco,
Van Packer, Metal Fab, Schebler or Metalbestos. UL 1738 approved and suitable for
positive pressure ANSI Class III and IV equipment.
B. The inner diameter of the breeching and stack shall be verified by the manufacturers
computations. The computation shall be technically sound, shall follow ASHRAE
calculation methods and incorporate the specific flow characteristics of the inner pipe.
The contractor shall furnish the exact boiler, generator or water heater and their
respective operating characteristics to the factory representative. Operating
characteristics shall include exhaust flow rate, BTU input, outlet temperature, local
altitude, stack layout and available external pressure at the devices outlet, etc. necessary
to determine system operation at the maximum and minimum levels of burner turndown
range. The calculations shall be submitted to the engineer with the breaching and stack
submittal.
C. This contractor shall coordinate with the plumbing subcontractor, to ensure that if a water
heater using forced draft venting is submitted, a stack designed for positive pressure will
also be submitted. Do not submit Type B gas vents for water heaters.
D. Breeching shall be 304 stainless steel outer jacket where exposed to the weather,
galvanized where not exposed. Internal pipe shall be 304 stainless steel. Provide stack
with integral spacers or insulation. For condensing boilers and condensing water heaters,
use AL 294C stainless steel internal pipe or material recommended by the boiler
manufacturer.
F. Joints shall be vapor-tight with locking groove slip joints with locking tabs and bands.
G. Provide high temperature expansion fittings between flue and structural penetrations.
H. Provide aluminized water-tight insulated thimble, exit cone, rain collar and supporting
hardware, including guys and bands.
I. Provide vapor, gas and liquid tight connection between boiler or water heater and flue.
J. Vent connectors shall be fitted directly to the exhaust connection of the gas fired
appliances with a gas tight flanged connection. Combustion test holes shall be factory
built into the appliance adapter. The vent pipe shall be supplied with a slip ring/tab
connection to positively join the pipe inner liner, and draw band connections to join the
outer jacket airtight. All inner liner joints shall be field sealed with RTV high
temperature RTV sealant to prevent leakage of condensate from the inner liner surfaces.
Fittings shall be of the same materials and be constructed to facilitate the flow of flue
gases and allow drainage of any condensate inside the vent.
K. Breeching shall be pitched a minimum of 1/4 per foot back towards the appliance for
elimination of any condensate. Wherever breeching passes through combustible material,
a suitable wall thimble or fire stop fitting shall be employed. The breeching shall be
fitted with an inspection end cap on the end opposite the chimney.
L. The chimney system shall be at least the size of the largest breeching diameter, and the
required diameter as shown on the plans. The chimney shall be supported at the base
without any of the chimney weight being supported by the breeching connector or the
vented appliances. A drip tee connection shall be fitted at the base of the chimney for
elimination of any condensate within. The drip connection shall be piped with a trap to a
suitable disposal point. The chimney shall have roof braces of stainless steel as provided
by the manufacturer at least every 12 feet of linear pipe. The chimney shall be supplied
with an insulated roofjack and flashing collar. The chimney shall have a rain cap of the
same materials on top to prevent entering rain. The chimneys shall be guyed at the roof
as required. The chimney manufacturer shall provide all necessary components for a
complete operating system.
M. Engineered System - The venting system shall be an engineered system. The system
design shall be consistent with current national and local venting codes, and in
accordance with the installation instructions of the installed appliance. Combustion air
requirements shall also be considered. ASHRAE or other approved venting calculations
shall be supplied including the specific heating appliance and final flue/combustion
system routing.
N. Test ports, baffles, Test port, and accessories shall be supplied by the vent manufacturer.
O. Depictions on drawings are for bidding purposes only. Offset and accessories may be
required. Inner diameter size may change based on the submitted appliance, coordinate
with appliance and draft equipment manufacturer for system diameter size.
Q. The chimney or gas vent system shall be designed to prevent recirculation of exhaust gas
through idle boilers.
T. Follow all pertinent national, state, and/or local codes where applicable.
U. All barometric dampers and draft hoods equipment shall have safety interlocks devices
such as thermal spill switches or carbon monoxide detector.
a. CFM
b. Velocity
c. CO2
d. BTU Max/Min inputs
e. Outlet Temperature
f. Additional pressure losses including muffler and economizer
g. Vent layout
h. Available draft
i. Other parameters that could affect system operation at maximum and
minimum levels of burner turndown range.
4. Product Data: Submit data indicating the system layout details, including
dimensional details of components, dimensions and weights.
7. Manufacturers Warranty
X. PRODUCTS
1. Acceptable Manufacturer:
Security Chimney International
5. The entire stack system from each appliance to the termination; including
adapters, supports, drains, test ports, pressure probe port, and baffles shall be
supplied by the vent manufacturer.
Y. Accessories
2. Provide pertinent operating and service instructions in illustrated and bound form
which shall be furnished by the manufacturer, minimum three (3) copies, within
30 days of Substantial Completion with close-out documents
1. Contractor shall examine areas and conditions at the site for compliance with
requirements for installation tolerances and other conditions affecting
performance of work.
2. Proceed with installation only after unsatisfactory conditions have been fully
corrected.
5. Chimney and engine exhaust support system from building structure using rigid
structural shapes for attachment of fixed point supports (vertical and horizontal).
Anchor supports to structure by welding to inserts, bolting, steel expansion
anchors or concrete inserts. Size of structural shapes shall be in accordance with
manufacturers recommendations.
7. Connect base section of foundation using anchor lugs of size and number
recommended by manufacturer.
BB. Cleaning
2. Clean breeching internally, during and after installation, to remove dust and
debris. Clean external surfaces to remove welding slag and mill film.
3. Provide temporary closures at ends of breechings, chimneys and stacks that are to
be completed or connected to equipment.
CC. Warranty
1. Transfer the full Warranty to Owner to include all parts and labor for a full one
(1) year period after the venting systems is put into sustained operation.
2. Transfer any and all other special warranties, as applicable, over to the Owner.
A. General
1. Provide treatment systems and service for primary water systems. Water
treatment shall include feeding devices necessary to feed chemical solution into
piping system and bring chemical properties of water to within manufacturer's
recommended operating limits, in order to minimize corrosion and reduce
build-up of slime or other contaminants. Provide all equipment, chemicals and
service necessary for a complete water treatment program.
4. Acceptable Manufacturers
6. Mechanical contractor shall provide the steel support shelf for the chemical feed
pumps and other equipment.
9. Shot Feeder
a. Closed loop systems shall have water treatment to feed chemical solution
into each piping system.
b. Provide five gallon bypass feeder for systems equal to or less than 1,000
gpm of system flow.
c. Provide ten gallon bypass feeder for systems over 1,000 gpm of system
flow.
11. Chemicals
1) Rough 50 micron. Used first until the system can be operated for
an appropriate period of time without noticeable build up.
2) Fine 5 micron. Used second. Circulate water and replace as need
until the system can be operated for an appropriate period of
time without noticeable build up.
B. Ongoing Service
C. Service Binder
A. Provide bronze Bourdon tube pressure gauges where shown on Drawings and where
specified, by U.S. Gauge, Trerice, or Weksler, accurate to +1%.
1. Gauges shall have white faces with black-filled engraved lettering. Gauge bodies
shall be set in phenolic cases. Provide syphons and shut-off cocks.
2. Gauges shall be easily accessible and easily read. Gauges readable from floor at
less than five feet shall have 4-1/2" dials. Other gauges shall have 6" dials.
Gauges graduations shall meet limit requirements of normal operation. Gauge
shall indicate at mid-scale.
B. Provide separable well V-case thermometers by U.S. Gauge, Trerice, or Weksler where
shown on Drawings and where specified. Thermometers shall have 9" scale and white
face with black-filled engraved letters. Thermometers shall be angular or straight
stemmed, as conditions necessitate. Thermometer wells shall be bronze and shall be
installed so as to ensure minimum restriction of water flow in pipe.
1. Provide thermometer ahead of and beyond cooling coils, chillers and where
shown on Drawings. Thermometers shall have scale range of 0 -120 deg. F with
2 scale division.
3. Provide thermometer in hot water system ahead of and beyond each boiler, coil
and where shown on the drawings. Scale range shall be 30 300 deg. F with 2
scale division.
2. Plug shall be 1/4" or 1/2" NPT, constructed of solid brass with a Nordel valve
core suitable for temperatures up to 350 deg. F. Plug shall be rated zero leakage
from vacuum to 1000 psig.
3. Provide extension fitting for each plug suitable for use with 2" maximum pipe
insulation.
a. (2) 3-1/2" dial face gauges 0-100 psi and 0-231 feet.
A. Do not operate systems without design filters. Provide a new set of filters before the
balancing is performed.
C. Filter media shall be bonded to an enclosed beverage board frame. The media shall be of
non-woven cotton, which is laminated to a welded wire grid, and have an average
efficiency of 25-30% by ASHRAE test standard 52-76. Filter area shall be not less than
11 pleats per lineal foot for 4" thick or 15 pleats per lineal foot for 2" thick filter.
A. Filters shall be AAF or Farr Riga Flo of the sizes and quantities shown on the drawings.
B. Each filter shall consist of high loft micro fine glass fiber media, which has a non-woven
backing and is laminated to a welded wire grid. The entire pack shall be sealed into a
galvanized frame with metal contour stabilizers, and galvanized steel diagonal support
braces on air entering and air leaving side (cardboard is not permitted). Each filter shall
have a minimum efficiency reporting value (MERV) of 13 by ASHRAE test standard
52-99.
A. The Contractor shall furnish a dry air filter gauge by Dwyer Magnehelic across each filter
bank. Gauge shall have static pressure tips, vent valves, and tubing and shall have an
adjustable flag to indicate need to change filter. The scale shall be 1.0" greater than the
final pressure drop.
B. A decal containing filter service information (quantity, size, type, final resistance) shall
be placed at each gauge.
A. Filter housing shall be AAF or Farr 4P Glide Pack side service filter housing, as noted on
the drawings. Unit shall be constructed of not less than 16 gauge galvanized steel with
gasketed access doors on each side and extruded aluminum tracks (for filter insertion).
B. Unit shall have an integral static pressure tap to measure pressure drop across the filters.
A. General
1. Provide fan array indoor air handling units as shown and scheduled on Drawings.
3. The unit manufacturer shall be responsible for provision and warranty of fans,
dampers and all other unit and plenum components as specified in this Section or
other Sections of this division and performance characteristics as shown in
schedules or on drawings.
4. Shop drawings shall be subject to approval of the Owner and the Engineer.
a. The air handling unit shop drawing shall be submitted in a binder with
the following features:
e) Sound analysis
5. The unit may require field erection to get into the project area and into the new
mechanical rooms. The mechanical contractor shall coordinate the required
shipping splits with the required dimensions for shipping and in the field.
9. Seal casing penetrations made in field for piping, conduit, tubing and equipment
installed under Sections 15600 and 16100. Advise manufacturer in advance of
required field penetrations of casing. Make and seal penetrations under
supervision of manufacturers field engineer.
10. Acceptable manufacturers will be Johnson Controls, McQuay, York, Trane and
Carrier. Providing they meet the requirements of this Section and the
performance requirements listed and scheduled.
11. All units shall be ETL listed. All manufactured products shall be ETL listed and
shall be labeled with an ETL certification label at the plant. Field approvals are
not acceptable.
12. Appurtenances
b. Base rails suitable for rigging and lifting will be provided as needed.
13. Finishes
B. Testing
a. Pressure test water coils if coil manufacturer has not already performed
pressure test and piping. The test shall be per the latest edition of
ARI 410. 150 psig for heating coil and 300 psig for cooling coils.
b. Unit operation and vibration analysis. All fans have a dynamic balance
performed after assembly at the fan manufacturers facility. An IRD or
PMC analyzer shall be used to measure velocity. The final reading shall
not exceed 0.1 inch per second vertically or horizontally at the bearing
caps nor exceed 0.09 inch per second in the axial direction. The exact
level of vibration shall be recorded on the operation and maintenance
manual as proof of the dynamic balance at the factory.
C. Unit Construction
1. Unit Casing
c. Unit casing will consist of a structural frame and insulated roof, wall, and
floor panels.
e. Unit will have double wall, 2 insulated panels for walls, roof, and floor.
Exterior skin will be galvanized sheet steel. Individual segments will
have galvanized sheet steel.
2. Double wall access doors will be provided on the fan, filter, mixing box and
before and after the coil sections.
a. Drain pans will be double sloped at least 1/8 per foot, and have no
horizontal surfaces.
e. Drain pans will have at least 1 clearance between pan and coil supports.
4. Electrical
a. Fan motors will be built in accordance with the latest NEMA and IEEE
standards.
3. VFDs will be UL or ETL listed and comply with applicable provisions of the
National Electric Code.
a. Shipped loose VFDs and VFDs provided on units without single point
power will be housed in a NEMA 3R enclosure.
b. Weatherproof compartments will be provided on units with single point
power.
1) over current
2) ground fault
3) over voltage
4) under voltage
5) over temperature
6) input power loss of phase
7) loss of reference/feedback
8) adjustable current limit regulator
9. VFD will include high input transient protection and surge suppression:
a. Premagnetization on start
b. DC braking/hold at stop
c. Ramp or coast to stop
d. Seven preset speeds
e. Three critical frequency lockout bands
f. Start function will include ramp, flying start, automatic torque boost, and
automatic torque boost with flying start
E. Water Coils
1. Coils have 5/8 O.D., 0.035 thick copper tubes with continuous aluminum plate
fins. U Bends shall have a minimum of 0.035 wall thickness, rated for 400 psi
working pressure.
c. After coils are piped through casing, seal pipe penetrations and cap with
grommets or escutcheon plates on both the inside and outside of the
casing.
5. Filter access will be provided via access doors on filter segments or adjacent
segments as required by filter loading scheme. See product drawings for details.
G. Fans
2. Fans will be Class I, II, or III, as required to meet selected RPM and horsepower
shown in performance specifications.
3. Airfoil fans will bear the AMCA Seal. Airfoil fan performance will be based on
tests in accordance with AMCA standard 210 and will comply with the
requirements of AMCA certified ratings programs for air and sound. Airfoil
wheels will comply with AMCA standards 99-2408-69 and 99-2401-82.
4. Fans shafts will be polished steel and sized such that the first critical speed will
be at least 125% of the maximum operating speed for the fan pressure class.
Shaft will be coated with an anti-corrosion coating.
5. Fan and motor assembly will be internally mounted on a common base. Fan and
motor base will be spring isolated on a full width isolator support channel.
a. Fan motor will be on an adjustable base.
b. Fan discharge will be connected to cabinet via a flexible connection.
c. Access doors will be provided as shown on product drawing.
1. Fan bearings will have average life (L50) of at least 200,000 hours. Bearing
fatigue life ratings will comply with ANSI/AFBMA 9.
2. Re-greaseable fan bearings will be factory lubricated and equipped with standard
hydraulic grease fittings.
3. Fan drives will be selected for a 1.5 service factor and will be furnished with
anti-static belts.
b. Sheaves will be machined from close grain cast iron and statically
balanced.
c. Drive belts will be V type, precision molded, raw edge construction, anti-
static, oil and heat resistant.
1. Dwyer Magnehelic Type 2003 AF dry air filter gauge, with an appropriate scale
across each filter with appropriate static pressure tips, vent valves and tubing
with flag suitably marked to indicate need to change filter.
J. Dampers
2. Dampers will have airfoil blades with extruded vinyl edge seals and flexible
metal compressible jamb seals.
3. Dampers will have a maximum leakage rate of 4 CFM/square foot at 1" w.g. and
comply with ASHRAE 90.1.
K. Appurtenances
1. Safety grates capable of supporting a 300 lb. center load will be provided over
bottom openings, as shown in performance specifications.
2. Formed steel base rails suitable for rigging and lifting will be provided, as shown
on product drawings.
L. Finishes
2. Unit wiring with voltage greater than 30VAC will be hipot tested prior to
shipping.
A. Provide single duct variable volume air control assemblies of sizes and capacities shown
on Drawings. Acceptable manufacturers shall be: Titus, Envirotec, Trane, Metalaire, or
Krueger. Units shall be 24 gauge galvanized steel, lined with 1-1/2 pound insulation as
required by UL-181 and NFPA-90A.
1. Responsibility for the provision of damper actuator, DDC VAV box controller
including velocity pressure transducer and control transformer shall be by
Automated Logic as campus standard and under the Automatic Temperature
Controls paragraph of this specification. Terminal box manufacturer shall
include with his bid, costs of mounting the Automated Logic controller on his
box at his factory and piping the controller's transducer to his flow sensor (in
accordance with control manufacturers instructions).
B. Provide 3' long sound attenuators where scheduled and shown on Drawings. If sound
attenuator is not scheduled, provide 10 linear feet of lined duct at discharge of the VAV.
C. Boxes shall have multipoint averaging type airflow sensors. Boxes with single point
sensors are unacceptable.
D. Assemblies shall be pressure independent between supply unit's external static pressure
and minimum static pressure schedule on Drawings. Valves shall be normally open or
normally closed as shown on Schedules. Differential static of complete assembly shall
not exceed 0.45" wg for units with sound attenuators or 0.20" wg for units without.
Damper leak rate shall not exceed 2% of full volume at 3" static pressure rated by ADC.
Units shall not deviate from set minimum or maximum flow settings by more than 10%
regardless of inlet angle. Inlet velocities shall not exceed 2250 fpm.
E. Sound ratings shall not exceed noise criteria (NC) levels scheduled on the Drawings. All
NC data must be in accordance with ADC 1062 R4. Discharge NC data shall include
10db room attenuation only. Radiated NC data is to assume a ceiling with sound
transmission class 35-39.
F. Terminal units shall be capable of the heating and cooling operation sequences and
quantities shown on the schedule, plan and control drawings. Units' control apparatus
shall be compatible with the control system.
G. The mechanical division contractor shall have complete responsibility for ensuring that
the submitted terminal box and VAV DDC controller are compatible with each other, and
that they can perform all sequences of operation shown on the control drawings.
Contractor shall submit the following items with his shop drawing submittal:
3. A statement that the mechanical division contractor has contacted both vendors
and verified that the terminal box and DDC controller are compatible with each
other.
A. Provide electric cabinet heaters where shown on Drawings and on schedules. Cabinet
heaters shall be factory assembled for field installation. Cabinets shall be 16 gauge steel
with corrosion-resistant finish. Color selection shall be by Architect.
B. Heating coils shall be single terminal end long life electric fin tube with brazed helical
coiled fins.
A. Provide steel panel radiator elements of lengths and in locations as indicated and of
capabilities, style and having accessories as scheduled. Heating panel radiation shall be
one-piece all welded steel construction, consisting of flattened water tubes welded to
headers at each end. FTR to have steel corrugated fins welded to the rear side of the
water tubes to increase the convective output of the unit. There shall be no less than 32
fins per foot. Fins shall start within 1 of the headers and shall be spot-welded three
times per tube.
B. The radiators headers shall include all necessary inlet, outlet and vent connections as
required. Standard connection sizes are ½ NPT tapered thread for supply and return
piping and 1/8 for the vent connection. Internal baffling is provided where required for
proper water flow. Optional ¾ connections shall be available at an additional cost.
C. The radiant heating panels shall be available in lengths from 2-0 to 29-6 in two inch
even increments without the need for splicing. The panel radiation shall be capable of
being mounted to typical stud wall construction without additional blocking strapping.
Appropriate wall mounting brackets or optional floor post mounting shall be provided
with the radiation. Panel radiation expansion shall not exceed 1/64 per foot of radiation
at 215°F. The installer shall provide adequate expansion compensation for each radiator.
D. Provide hot water fin-tube heating elements and enclosures, where, and of capacities
shown on Drawings, by Runtal, Slant Fin, Vulcan, Sterling, Trane or Sigma.
E. Heating elements shall consist of 0.012" thick aluminum plate fins permanently bonded
to seamless copper tube and guaranteed for working pressure at 300 deg. F of 128 psi for
1" tube. Fins shall be bonded to copper tube by mechanical expansion.
F. Enclosures shall be galvanized steel with 18 gauge front panel, baked enamel finish.
Color selected by Architect from factory-provided color chart.
G. Provide end trims with roll-flanged edges between ends of enclosures and walls on
wall-to- wall applications, attached without visible fasteners and flush with enclosures.
H. Enclosure brackets and element hangers shall be no farther than 4 ft. apart. Brackets
shall be die-formed from 16 gauge stock, 1-1/2" wide.
3. Support heating element with sliding saddles and provide positive positioning of
element in enclosure. Fins shall not impinge on brackets or enclosure joints
during expansion or contraction.
4. Element supports shall be 16 gauge galvanized steel. Saddle shall slide freely on
saddle support arm bolted to support bracket.
L. Flex connectors shall be used where appropriate to provide expansion compensation for
the radiators.
A. Provide hot water coils suitable for duct installation with capacities, pressure drops and
leaving air temperatures as scheduled on Drawings. Acceptable manufacturers shall be
Aerofin, Carrier, McQuay, York, Trane or Precision.
B. Coil shall be 1/2" or 5/8" copper tube expanded mechanically into continuous aluminum
fin collars, with copper or bronze headers and galvanized steel casings.
C. Proof test at 300 psi and leak test at 250 psi air pressure under water. Certify suitability
for 200 psi working pressure.
A. Provide plate-and-frame heat exchanger for the purpose of fluid heating of capacity and
pressure rating scheduled and shown on Drawings by Taco, Alfa-Laval, Tranter,
American Vicarb or Mueller.
B. Construction shall meet requirements of ASME Boiler and Pressure Vessel Code
(Section VIII), American Water Works Association, and TEMA Standards.
C. Construction
2. The plates shall be vacuum brazed together with material compatible with
application, brazed material shall be:
a. Copper (standard).
D. Installation
1. Contractor must install fluid strainers on the inlet of each circuit to ensure proper
protection of the heat exchanger. Strainer shall be 16 mesh or better.
E. Warranty
1. The supplier shall provide its standard product warranty and shall warrant the
unit for 18 months from the date of manufacture, or one year from date of
installation, whichever is longer.
A. General
* Carrier
* McQuay
* Trane
* York
2. The chiller shown on the drawings has been coordinated with architectural and
structural elements, and with electrical service requirements. If a different unit is
submitted, ALL mechanical, electrical, architectural and structural modifications
which are required shall be performed under the work of the mechanical section,
by the mechanical contractor, under the original contract price.
B. Quality Assurance
1. Chiller shall be rated in accordance with the latest edition of ARI Standard 590.
2. Unit construction shall comply with ANSI B9.1 Safety Code, National Electrical
Code and applicable ASME Codes.
3. Unit Cabinet shall be capable of withstanding Federal Test Method Standard No.
141 (method 6061) 500 hour salt spray test.
4. Cooler shall be tested and stamped in accordance with ASME Code for a
minimum refrigerant working side pressure of 225 PSIG and a minimum water
side pressure of 150 PSIG.
5. Air cooled condenser coils shall be leak tested at minimum 150 PSIG and
pressure tested at 425 PSIG.
6. Each chiller shall be factory tested at full and part load conditions-the current
draw shall be noted. Results of the test shall be provided to Owner. The chiller
shall be tested for refrigerant leaks and shipped with a full charge of refrigerant.
C. Equipment
1. Casing
2. Evaporator
a. Evaporator shall be shell and tube type with copper tubes expanded into
tube sheets. Provide drain connection and wells for temperature and
safety controls as required. Provide 3/4" insulation over entire surface of
the evaporator; maximum insulation k factor shall be 0.28. Provide
heater tapes, and thermostatic controls, to protect evaporator and water
piping (to field provided piping). Heat tapes shall protect evaporator to
-20 degrees. The mechanical contractor shall coordinate with the
electrical section to ensure that heat trace is supplied for all outdoor field
supplied water piping. If such trace, and all required controls, have not
been provided under the work of the electrical section, they shall be
provided by the mechanical contractor under the work of the mechanical
section. Field supplied trace will protect piping to -20 degrees.
3. Condenser
a. Air cooled condenser coils shall have aluminum fins bonded to copper
tubing with integral subcooling circuits.
b. Condenser fans shall have three phase motors with three phase overload
protection, permanently lubricated ball bearings, and shall be statically
and dynamically balanced. Fans shall discharge vertically.
4. Refrigerant Circuits
c. Provide all controls necessary to start and operate the chiller at 0 deg. F.
Controls may be modulating damper or fan speed control and shall be
activated by sensing refrigerant head pressure. Control systems which
are activated exclusively by ambient temperature are unacceptable.
d. Provide all valves, piping and other controls necessary for hot gas bypass
operation. All components shall be factory installed.
6. Compressors
D. General
1. General Requirements
2. Scope
3. Quality Assurance
E. Products
1. Manufacturers
2. General
e. Shipping: Unit shall ship in one piece and shall require installer to
provide only a single evaporator inlet and outlet pipe connection. If
providing chiller model that ships in multiple pieces, bid shall include all
the material and field labor costs for factory authorized personnel to
install a trim kit to connect the pieces as well as all interconnecting
piping and wiring.
3. Compressors
5. Heat Exchangers
a. Evaporator:
6. Air-Cooled Condenser:
b. Ultra Quiet Fans: Provide reduced sound fans. Unit should have the
following sound criteria as the maximum allowed:
Sound
Full
Value 63
Load 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
dB(A) Hz
Stage
1 95 99 94 93 94 88 87 82 80
2 94 99 94 92 93 88 87 82 79
3 94 98 94 92 93 87 86 81 79
4 91 96 91 89 90 85 84 79 76
5 88 92 88 86 87 81 79 75 74
a. Power/Control Panel:
8. Controls
d. Manufacturer shall provide any controls not listed above, necessary for
automatic chiller operation. Mechanical Contractor shall provide field
control wiring necessary to interface sensors to the chiller control
system.
l. BACnet Interface
F. Execution
1. Installation
A. Provide each side of the expansion joints as shown and as recommended by the
expansion joint manufacturer alignment guides fabricated of steel plate and structural
steel angles KEFLEX Series P Pipe Alignment Guides, Adsco Model E pipe alignment
guides or equal. Units shall consist of a guide spider clamped and/or welded to the pipe
and a guide body that is anchored to the structure of the building. The spider shall move
through the guide body as the pipe expands and contracts.
B. Guides shall be sized to allow for the thickness of insulation specified for the service in
accordance with this specification. The first guide at each side of the bellows expansion
joint shall be located four pipe diameters from the joint. The second guide shall be
located fourteen pipe diameters from the first guide. Intermediate guides shall be spaced
as shown on the drawings between the second guides and the anchors.
B. Units shall consist of coils, with integral subcooling, and casing with stand. Coil shall be
aluminum plate fins on mechanically-expanded copper tubes. Coils shall be cleaned,
dehydrated, sealed, leak tested at 150 psig, and pressure tested at 420 psig.
C. Fans shall be direct-drive, propeller, protected with guards. Condensers shall have two
3-phase motors and one permanent split capacitor motor for use with accessory speed
control suitable for reduced voltage starting. Motors shall be prelubricated, with built-in
overload protection.
D. Fan shaft shall be corrosion protected. Fan blades shall have irradiated or aluminum
finish. Magnetic contactor shall be field supplied. Provide magnetic contactors in
accessory fan cycling control package to cycle fans in response to outdoor ambient
temperature.
E. Casing shall have baked enamel finish. Access panels shall be provided for electrical
connections.
1. Scope
2. Quality Assurance
a. Unit shall be delivered to job site fully assembled, and given a holding
charge of nitrogen and a full oil charge by the Manufacturer. (R-410A
refrigerant supplied by others).
4. Acceptable Manufacturers
H. Products
2. Compressors
4. Heat Exchangers
5. Controls
d. Manufacturer shall provide any controls not listed above, necessary for
automatic condensing unit operation. Mechanical Contractor shall
provide field control wiring necessary to interface sensors to the
condensing unit control system.
a. Power Panels:
b. Exposed compressor, control and fan motor power wiring shall be routed
through liquid tight conduit.
SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YLUA0098YE46 ( Equipped with Ultra Quiet Fans )
Load % Ambient 63 125 250 500 1K 2K 4K 8K LWA
(°F)
100.0 95.0 100.0 95.0 93.0 94.0 89.0 88.0 83.0 80.0 95.0
83.8 80.0 99.0 95.0 92.0 93.0 88.0 87.0 82.0 78.0 95.0
50.0 80.0 98.0 95.0 92.0 92.0 87.0 86.0 81.0 78.0 94.0
16.2 80.0 93.0 89.0 87.0 88.0 82.0 80.0 76.0 75.0 89.0
I. Execution
1. Installation
A. Provide centrifugal fans by Buffalo, Chicago, Cook, Trane, Peerless, ILG, Barry, Twin
Cities, Greenheck, Aerovent, Avaho, Bayley, Hartzell or New York Blower with welded
steel housing and wheel, balanced dynamically and statically. Fans shall be
AMCA-certified and sealed.
B. Backdraft dampers shall not be provided when fans are specified or scheduled to be
equipped with automatic control dampers in or immediately below curb.
C. Provide V-belt, variable-pitch drives for +10% speed variation and with spring loaded
belt tensioner.
D. Fans shall have centrifugal with backward-curved blades fan connected to electric motor
so selected that in no instance can fan motor be overloaded at capacities shown on
schedule on Drawings. Provide open drip-proof motor on adjustable base. Motors shall
be high or premium efficiency type. See "Motors and Starters" paragraph of this
specification for required efficiencies and other requirements.
F. Provide belt guards of 18 gauge steel mesh or perforated or expanded steel sheets with
angle frames and galvanized steel or iron trim, rigidly-braced. Provide ports for
tachometer speed measurements at fan shafts.
A. Provide Vibration Isolation and Seismic Restraints as specified under Section 20 05 48.
A. General
1. Work Included
B. Coordination
1. Installing contractor will coordinate the following items with applicable trades:
3. Unit sound ratings will be reported in accordance with AHRI 260 for inlet and
discharge sound power levels.
4. Unit casing radiated sound ratings will be reported in accordance with ISO 9614
parts 1&2 and ANSI S12.12.
5. Unit will conform to AHRI 410 for capacities, pressure drops, and selection
procedures of air coils.
6. Unit will conform to ANSI/AHRI 430 for all fabrication procedures of air
handling units.
7. Motors covered by the Federal Energy Policy Act (EPACT) will meet EPACT
requirements.
9. Airflow Monitoring Stations will be rated in accordance with AMCA 611-95 and
bear a Certified Ratings Seal for Airflow Measurement Performance.
D. Delivery
3. Loose-shipped items will be packed, protected and secured with units. Detailed
packing list of loose-shipped items, illustrations and instructions for application
will be included.
E. Warranty
1. Manufacturer will warranty unit and factory packaged controls for eighteen (18)
months from date of shipment. Warranty work shall be performed by
manufacturers factory-trained and factory-employed technician.
F. General Description
1. Unit will be complete with fans, motors, dampers, controls, access doors and
other components/options, as shown on product drawings, wiring diagrams, and
as described in performance specifications.
3. Unit will ship in one (1) piece whenever possible. Shipping splits will be
provided when necessary. Lifting lugs will be provided where required for
proper lifting.
G. Unit Casing
1. Unit casing will consist of a structural frame and insulated roof, wall, and floor
panels.
3. Unit casing will be insulated with spray injected foam to achieve a minimum
thermal resistance of R13 hr-ft2-°F/BTU. Insulation application will meet the
requirements of NFPA 90A
5. Unit will conform to ASHRAE Standard 111 Class 6 for casing leakage no more
than 1% of design airflow at 1.25 times design static pressure up to a maximum
of +8 inches w.g. in positive pressure sections and -8 inches w.g. in negative
pressure sections.
6. Wall panels and access doors will deflect no more than L/240 when subjected to
1.5 times design static pressure up to a maximum of +8 inches w.g. in positive
pressure sections and -8 inches w.g. in negative pressure sections. L is the
panel-span length and L/240 is the deflection at panel midpoint.
7. Unit will have double wall, 2 insulated panels for walls, roof, and floor.
Exterior skin will be galvanized sheet steel. Individual segments will have
galvanized sheet steel, stainless sheet steel, or perforated galvanized interior
liner, as described in performance specifications.
a. Provide panels with optional perforated liner in the fan section and other
sections as shown on the drawings. Interior liner will be perforated
galvanized. Minimum perforated panel thermal resistance (R-Value)
will be R11 hr-ft2-°F/BTU.
8. Floor panels will be double wall construction, designed to provide at most L/240
deflection when subjected to a 300 lb. load at mid-span.
H. Fans
2. Fans will be Class I, II, or III, as required to meet selected RPM and horsepower
shown in performance specifications.
3. Airfoil fans will bear the AMCA Seal. Airfoil fan performance will be based on
tests in accordance with AMCA standard 210 and will comply with the
requirements of AMCA certified ratings programs for air and sound. Airfoil
wheels will comply with AMCA standards 99-2408-69 and 99-2401-82.
4. Fans shafts will be polished steel and sized such that the first critical speed will
be at least 125% of the maximum operating speed for the fan pressure class.
Shaft will be coated with an anti-corrosion coating.
5. Fan and motor assembly will be internally mounted on a common base. Fan and
motor base will be spring isolated on a full width isolator support channel.
6. Multiple Fans will be Model MPQS centrifugal plenum type. Fans will have a
sharply rising pressure characteristic extending through the operating range and
continuing to rise beyond the peak efficiency to ensure quiet and stable
operation. Fans will have a non-overloading design with self-limiting horsepower
characteristics and will reach a peak in the normal selection area.
1. Fan bearings will have average life (L50) of at least 200,000 hours. Bearing
fatigue life ratings will comply with ANSI/AFBMA 9.
2. DWDI fans will be belt-driven. SWSI fans will be belt driven or direct driven, as
shown on product drawings.
3. Re-greaseable fan bearings will be factory lubricated and equipped with standard
hydraulic grease fittings. Fan drives will be selected for a 1.5 service factor and
will be furnished with anti-static belts.
J. Electrical Motors
1. Fan motors will be built in accordance with the latest NEMA and IEEE
standards.
2. Fan motors comply with ASHRAE Standard 90.1.
3. Fan motors will be furnished in sizes, electrical power and starting characteristics
as shown in performance specifications.
a. Fan motors will be rated for continuous, full load duty at 104 F (40 C)
ambient temperature and 1.15 service factor.
c. Motors will be suitable for use with variable frequency drives, per
NEMA MG-1 Part 30.
K. Fan-Motor Disconnects
a. 16A to 100A disconnects will have two (2) #14 ground wires.
b. 200A to 400A disconnects will have one (1) #6-250 ground wire.
c. Hand-Off-Auto switch
1. Provide (2) VFDs on Fan Array for redundancy upon the failure of one VFD.
3. VFDs will be UL or ETL listed and comply with applicable provisions of the
National Electric Code.
a. Shipped loose VFDs and VFDs provided on units without single point
power will be housed in a NEMA 3R enclosure.
b. Weatherproof compartments will be provided on units with single point
power.
1) over current
2) ground fault
3) over voltage
4) under voltage
5) over temperature
6) input power loss of phase
7) loss of reference/feedback
8) adjustable current limit regulator
9. VFD will include high input transient protection and surge suppression:
a. Premagnetization on start
b. DC braking/hold at stop
c. Ramp or coast to stop
d. Seven preset speeds
e. Three critical frequency lockout bands
f. Start function will include ramp, flying start, automatic torque boost, and
automatic torque boost with flying start
M. Finishes
e. Variable speed fan vibration limits: filter -in measurements will not
exceed 7 mils.
2. Unit wiring with voltage greater than 30VAC will be hipot tested prior to
shipping.
A. Magnetic window interlocks shall be provided at each operable window and tied to the
Automated Logic BAS. The installation of the interlocks shall be coordinated with and
maintain the integrity of the window framing. Refer to controls sequence for details of
controls integration. When multiple windows exist in a single space, the opening of any
window shall close the spaces associated dampers, valves and provide alarm at BAS as
required.
PART 3 - EXECUTION
3.1 REFERENCE
A. Cooperate and coordinate with work of other Sections in executing work of this Section.
3. Ensure tightness of plenums and chases used as part of air distribution system.
System will not be accepted until proved tight, without leakage. Notify Architect
in writing after system test for leakage, if construction and finish of plenums and
ducts are not satisfactory.
A. Install chiller on flat surface level within 1/8-in. and of sufficient strength to support
concentrated loading. Place isolation pad assemblies furnished by manufacturer under
unit. Use spring type isolators for upper floor installation.
C. Connect water piping so centrifugal unit and water circuits are serviceable.
D. Provide valves in water piping upstream and downstream of evaporator and condenser
water boxes to provide means of isolating shells for maintenance and to balance and trim
system as specified.
E. Install flow switch in both chilled water and condenser water piping, properly interlocked
to ensure that unit can operate only when flow is established.
F. Provide taps for thermometers and pressure gauges in water piping adjacent to inlet and
outlet connections of both evaporator and condenser.
J. Provide necessary auxiliary water piping for oil cooler, purge condenser and pumpout.
K. Provide pressure relief piping from chillers relief device, to atmosphere, at the exterior of
the building. Discharge location must be pre-approved by Architect before installation.
Provide one relief line, to atmosphere, for each chiller; relief piping line size must be
equal or greater than size of relief valve outlet. All aspects of relief piping installation
shall be in accordance with the latest edition of the ASHRAE (ANSI-15 Safety Code).
L. Furnish sufficient refrigerant charge and dry nitrogen for pressure testing under
manufacturer's supervision.
N. Insulate evaporator and other portions of machine which have not been insulated at
factory, as required to prevent sweating under normal operating conditions.
B. Clean internally as specified in Section VI of ASME Boiler Pressure Vessel Code. Use
boil-out compound of caustic soda or trisodium phosphate at one pound 50 gallons of
water as follows:
1. Remove pressure relief valve. Pour solution into boiler through tapping and
replace relief valve.
2. Start burner and circulate water throughout system and terminal heaters.
3. Allow water temperature to reach operating temperature, at least 180 deg. F and
vent system.
6. Remove pressure relief valve, wash boiler water side surfaces with high pressure
water and drain residue. Replace pressure relief valve at completion.
7. Refill system with fresh water and start burner. Bring water temperature to at
least 180 deg. F and vent system to eliminate entrained air.
B. Burner lightoff and adjustment shall include combustion efficiency tests using batch or
electronic analyzing apparatus, in presence of the Owners Representative.
2. Control operating tests including adjustment and check out of limits, switches,
operating controls, interlocks, low water cutoff devices and alarms, gas valves,
pressure regulators, scanners and combustion controls.
5. Gross and net stack temperatures. Presence of CO (if any) and adjustment to
reduce as necessary.
D. Pressure Tests
1. Subject pressure parts to hydrostatic test of 125 psi at factory. Field tests shall be
limited to no more than maximum intended working pressure.
2. Furnish equipment, piping, labor, staging, fittings, valves, hoses and other
material required to perform hydrostatic tests as directed.
3. Perform hydrostatic test of at least 40 psig for 5 hours. Tests shall be of duration
necessary to satisfy Architect and Boiler Inspector that boiler has been erected
correctly with no leaks.
G. Provide reference card (Lynn Products) at burner; note combustion data test readings.
A. No tests shall be started until systems have been cleaned. Provide temporary piping and
connections for testing, flushing or draining systems to be tested. If leaks develop,
repairs shall be made and tests repeated. Tests shall be continued until systems operate
without adjustments and repair to equipment or piping. Tests are further specified under
other paragraphs of this Section. Test requirement specifically includes, but is not
limited to, the following:
2. Pumps
4. Boilers
1. Take field measurements on vibration and alignment of pumps, chillers and fans
driven by motors over 10 hp. Readings shall include:
a. Shaft alignment
b. Equipment vibration
d. Foundation vibration
2. Refrigeration Systems
a. Test water chilling unit and other refrigeration systems for refrigerant
and air leaks at least twice: Approximately six months after start-up and
at end of guarantee period.
d. Test pressures shall be 300 psi for high pressure side and 150 psi for low
pressure side.
C. When testing is complete fill in the following checklist certifying satisfactory completion
of testing. Make multiple copies of checklist as required, edit out items which are not
appropriate.
A. No test shall be started until systems have been cleaned. Provide temporary piping and
connections for cleaning, testing, flushing or draining systems. If leaks develop, repairs
shall be made and tests repeated. Tests shall be continued until systems operate without
adjustments and repair to piping.
B. Cleaning
1. Prior to assembly of pipe and piping components, all loose dirt, scale, oil and
other foreign matter on internal or external surfaces shall be removed by means
consistent with good piping practice. Chips and burrs from machinery or thread
cutting operations shall be blown out of pipe before assembly. Cutting oil shall
be wiped from internal and external surfaces.
2. During fabrication and assembly, slag and weld spatter shall be removed from
both internal and external pipe joints.
6. Flush pipe and components with clean water after cleaning until all discharge
from system is clean. Maintain minimum velocities of 5 feet per second at all
points. Flow shall be in same direction as when system is in normal operation.
Discharge shall be from low points of lines, ends of headers and as otherwise
required to flush entire system.
7. After cleaning and flushing piping system, but before balancing, remove
disposable fine mesh screens in strainers and pump suction diffusers.
1. General
b. The mechanical contractor shall provide chemicals and labor for the pre-
operational cleaning of all hydronic water systems including but not
limited to: condenser, chilled, glycol, hot water and related equipment
piping systems. This cleaning method is not intended for potable water
systems.
3. Chemicals
d. Enough cleaner should be used to treat all of the piping to remove oil and
grease to permit a uniform passivating film to form. This aids in the
prevention of flash corrosion when the system is most vulnerable to
corrosive attack.
e. The mechanical contractor will provide the water treatment vendor with
an estimate of system volume for proper dosage of cleaner.
4. Pre-operational Cleaning
1. General
b. The mechanical contractor shall provide chemicals and labor for the pre-
operational cleaning of all condensers, chilled, glycol or hot water and
related equipment piping systems. This cleaning method is not intended
for potable water systems.
3. Chemicals
4. Pre-operational Cleaning
1. General
b. The mechanical contractor shall provide chemicals and labor for the pre-
operational cleaning of the closed system. This cleaning method is not
intended for potable water systems.
3. Chemicals
4. Pre-operational Cleaning
a. There is no need to flush the present treatment chemical from the system.
b. Add cartridges to filtration device. Filter must be sized for 3 5 % of
system flow. If there is no filter on site, mechanical contractor must
supply a filter for permanent use. See filter schedule for the appropriately
sized filter.
c. Add biocide at a dosage of 500 ppm (0.5 gallons per 1000 gallons of
system volume). Add biocide one day prior to addition of cleaning
compound.
d. Circulate a cleaning solution, made up at a minimum rate of 3.7
gal/1000gallon system volume (follow the specific dose
recommendation) as a guideline.
e. Recirculation for 3 - 4 days is recommended for best results. Inspecting
the filter to monitor the progress of the cleaning process. Change filters
as needed.
f. No special passivation is required. Add the closed system treatment
product at the recommended dosage to protect the operating system
against corrosion, scale and deposits.
c. Isolate equipment that is not to be subjected to the test pressure from the
piping. If a valve is used to isolate the equipment, its closure shall be
capable of sealing against the test pressure without damage to the valve.
Flanged joints at which blinds are inserted to isolate equipment need not
be tested.
d. Install relief valve set at a pressure no more than 1/3 higher than the test
pressure, to protect against damage by expansion of liquid or other
source of overpressure during the test.
a. Use ambient temperature water as the testing medium except where there
is a risk of damage due to freezing. Another liquid may be used if it safe
for workmen and compatible with the piping system components.
b. Use vents installed at high points in the system to release trapped air
while filling the system. Use drains installed at low points for complete
removal of that liquid.
c. Examine system to see that equipment and parts that cannot withstand
test pressure are properly isolated. Examine test equipment to ensure
that it is tight and that low pressure filling lines are disconnected.
e. After the hydrostatic test pressure has been applied for at least 10
minutes, examine piping, joints and connections for leakage. Eliminate
leaks by tightening, repairing, or replacing components as appropriate,
and repeat hydrostatic test until there are no leaks.
a. Fill system and perform initial chemical treatment. Initial fill of system
shall be with chemically treated water. For system using glycol, fill
system with specified glycol mixture.
b. Check expansion tanks to determine that they are not air bound and that
the system is completely full.
G. Maintain records of each system or section of system tested. Test reports shall include,
but are not necessarily limited to the following:
H. Notify the Architect prior to starting any post-erection cleaning operation in sufficient
time to allow witnessing the operation.
A. This report is for use in the LEED Version 2009 EA Credit 5 Measurement and
Verification validation of the energy model.
2. Monthly Total
a. Weather outputs: T_DB, Carbon Dioxide, Dew Point, RH, Solar Direct?,
Solar Indirect?
b. Building Electric Meter (kWh):
c. Building Chilled Water Meter (kBTU):
d. Space temperature set points
e. Hours of operation Unocc, Standby, Occ
f. Fans( kWh):
g. Pumps(kWh):
h. Chilled Water (kBTU):
i. Hot Water (kBTU):
j. Lighting (kWh): kWhr By Building, Lighting By Room Number
k. Occupancy Schedule: Average Hourly 0-1. By Room Number
l. Water: Lavatory, Irrigation, process
E. Energy Reports. System shall include an easily configured energy reporting tool that
provides the capabilities described in this section.
1. The energy reporting tool shall be accessible through the same user interface as is
used to manage the BAS.
2. The energy reporting tool shall be preconfigured by the Contractor to gather and
store energy demand and consumption data from each energy source that
provides metered data to the BAS. Meter data shall be stored at 5 minute
intervals. This data shall be maintained in a database for a period of not less than
five years.
3. The energy reporting tool shall allow the operator to select an energy source and
a time period of interest (day, week, month, year, or date range) and shall provide
options to view the data in a table, line graph, bar graph, or pie chart. The tool
shall also allow the operator to select two or more data sources and display a
comparison of the energy used over this period in any of the listed graph formats,
or to total the energy used by the selected sources and display that data in the
supported formats.
4. The energy reporting tool shall allow the operator to select an energy source and
two time periods of interest (day, week, month, year, or date range) and display a
graph that compares the energy use over the two time periods in any of the graph
formats listed in the previous paragraph. The tool shall also allow the operator to
select multiple energy sources and display a graph that compares the total energy
used by these sources over the two time periods.
5. The energy reporting tool shall allow the operator to easily generate the
previously described graphs "on the fly," and shall provide an option to store the
report format so the operator can select that format to regenerate the graph at a
future date. The tool shall also allow the user to schedule these reports to run on a
recurring basis using relative time periods, such as automatically generating a
consumption report on the first Monday of each month showing consumption
over the previous month. Automatically generated reports shall be archived on
the server in a common industry format such as Adobe PDF or Microsoft Excel
with copies e-mailed to a user editable list of recipients.
6. The energy reporting tool shall be capable of collecting and displaying data from
the following types of meters:
a. Electricity
b. Gas
c. Chilled Water
d. Hot Water
e. Potable Water
f. Heating and cooling degree days. (May be calculated from sensor data
rather than metered.)
7. The user shall have the option of using Kw (Kwh) or Btu/hr (Btu) as the units for
demand and consumption reports. Multiples of these units (MWH, kBtu, etc.)
shall be used as appropriate. All selected sources shall be automatically
converted to the selected units. The user shall similarly have the option of
entering facility area and occupancy hours and creating reports that are
normalized on an area basis, an annual use basis, or an occupied hour basis.
8. The user shall have the option of entering benchmark data for an individual
facility or a group of facilities.
9. The user shall have the option of displaying any or all of the following data on
any chart, line, or bar graph generated by the energy reporting tool:
a. Low/High/Average value of the metered value being displayed.
b. Heating and/or Cooling Degree Days for the time period(s) being
displayed.
c. The Environmental Index for the facilities and time periods being
displayed.
A. Pressure test ducts after takeoffs and wall penetrations are in place and before applying
exterior insulation. Correct any leaks.
B. Pressure and leak test all ductwork of 3 H20 or higher (pos. or neg.) duct construction
class ductwork at 100% of duct construction class pressure. Pressure test all grease
exhaust ductwork.
C. Note: For supply systems, perform positive pressure test. For return and exhaust systems
on suction side, perform negative pressure test. Duct shall be constructed so there is no
joint or structural failure at the test pressure.
D. Leak testing shall be per SMACNA HVAC Air Duct Leakage Test Manual. Provide
orifice assembly including straightening vanes, orifice-plate mounted in straight tube
with properly located pressure taps, and U-tube manometer or other device as specified
by SMACNA. Orifice assembly shall be calibrated accurately and shall come with
calibration curve. Leakage classes shall be as previously specified.
E. Submittal
1. Submit leak test report (per SMACNA format) for review approval.
2. Drawings of ductwork tested shall also be submitted with report, indicating
presence of takeoffs, wall penetrations, joints, etc.
A. All controls shall be by Automated Logic and tied into the existing campus system.
B. The contractor shall ensure that original equipment manufacturers (OEM), providing
equipment with integral controllers (DDC, electric, electronic or pneumatic), shall
coordinate with the Building Controls System (BCS) contractor to ensure complete
integration of the OEM controls with the BCS. Provision of any gateways, wiring, etc.,
shall be by the BCS contractor.
C. The mechanical contractor shall refer to the Building Controls Systems drawings to
ensure the sequences required by OEM equipment are followed.
D. The OEM controllers shall coordinate with the BCS contractor to provide for the
following, as applicable to the device, for connection by the BCS contractor.
1. Remote start/stop.
2. Remote set-point adjust.
3. Remote alarming.
4. Remote status.
5. Remote monitoring of all process variables measured by the OEM controller. In
short, all information that is available on the local OEM control panel shall be
communicated to the BCS.
1. Boilers
2. Chiller
3. Cooling towers
4. Pumps
5. Air handlers
6. Fans
B. Complete the following checklist to certify to the Architect that start up of the above
pieces of equipment has successfully been accomplished. Copy multiple checklists as
required. Edit inappropriate items as required.
Chillers
(List Nos. Below)
Pumps
(List Nos. Below)
Air Handlers
(List Nos. Below)
Fans
(List Nos. Below)
END OF SECTION
SECTION 2308
SECTION 23 080000- COMMISSIONING
- COMMISSIONING
OF OF HVAC
HVAC SYSTEMS
SYSTEMS
PART 1 - GENERAL
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and other Division 01 Specification Sections, apply to this Section.
B. ASHRAE Guideline 1-2007, HVAC&R Technical Requirements for the Commissioning
Process
C. OPR and BoD documentation are included by reference for information only.
1.2 SUMMARY
A. This Section includes general requirements that apply to implementation of the commissioning
process without regard to specific systems, assemblies, and components.
B. Related Sections include the following:
1. Division 01 Section 01 91 13 Commissioning General Requirements for general
commissioning process activities.
2. Division 23 Mechanical
3. Division 28 Electronic Safety and Security for interaction with fire alarm systems
1.3 DEFINITIONS
A. Commissioning Plan: A document, prepared by CxA, that outlines the organization, schedule,
allocation of resources, and documentation requirements of the commissioning process.
B. CxA: Commissioning Authority.
C. Quality Assurance: A program for the systematic monitoring and evaluation of the various
aspects of a system, assembly, or component to ensure that standards of quality are being met.
This is the responsibility of the CxA.
D. Quality Control: A system for ensuring the maintenance of proper standards in systems,
assemblies, and components. This is the responsibility of the Contractor.
E. Official: State or Local official having jurisdiction over the HVAC&R systems
F. Systems, Assemblies, Equipment, and Components: Where these terms are used together or
separately, they shall mean “as-built” systems, assemblies, equipment, and components.
PART 2 - PRODUCTS (NOT USED)
PART 3 - EXECUTION
A. The CxA shall provide Construction Checklists to the Contractors for execution that will
indicate expected Quality Control features required for a highest-quality installation. The
contractor shall complete the checklists as construction progresses and return them to the CxA
as indicated in Section 019113 Commissioning General Requirements.
B. Checklists for this section will include:
1. All mechanical equipment
2. Testing and Balancing verification
3. Building automation system components
A sample installation checklist is included to show the typical scope and rigor of the process.
3.2 PREREQUISITES TO TESTING
A. Prior to the testing of these systems or assemblies, the Contractor shall certify that:
1. The system or assembly is completely installed, functional, and documented through
checklists.
2. Work performed by other trades, but essential for this system or assembly’s operation, is
complete (e.g., electrical components are wired and power is provided)
3. All contractor-performed start-up procedures and tests are complete and documented.
4. Preliminary trending data provided to verify actual system operation.
5. The system or assembly is ready for the Owner to take beneficial use.
3.3 SYSTEM OR ASSEMBLY TEST REQUIREMENTS
A. The CxA will provide Functional Performance Test procedures to the Contractor for execution
for the following specific systems, assemblies, and components:
4. All mechanical equipment
5. Building automation system
6. Testing and Balancing verification
7. Direct Digital Controls and system interlocks
B. Acceptance criteria and test details will be in accordance with the related sections including the
following:
1. Division 01 Section 01 91 13 Commissioning General Requirements for general
commissioning process activities.
2. Division 23 Mechanical
3. Division 28 Electronic Safety and Security.
C. A sample functional performance test is included to show the typical scope and rigor of the
process.
3.4 TEST REPORTS
A. Provide copies of all reports required in the listed reference sections (see Section 1.2
SUMMARY above for the sections) for review.
3.5 SAMPLE FORMS
Installation Checks
ID Description Pass/fail Comments
Verify that the piping materials conform to the specified materials listed is section 15500:
1
A. Hot water Supply and Return Piping is copper or steel
Route all piping in an orderly manner, plumb and parallel to building structure. Present a
2 neat and workmanlike appearance. Group piping whenever practical at common elevations.
(15010-3.4 & 15050-3.1)
Provide temporary caps or covers for all open ends of piping and equipment during
3
construction to keep foreign material out of system. (15050-1.4)
Verify that piping hangers have been installed as follows: (15500-2.5.K)
4 A. Vertical pipe risers are supported at every floor.
B. Hanger Spacing shall be per the tables listed in the specifications.
Slope water piping and arrange to drain at low points. Low point drain valves on mains shall
5
be 1” ball valves with hose end and cap. (15500-3.2.B.4)
Verify that valves are installed with actuators upright or horizontal and that operator
6
extensions have been provided to accommodate insulation. Provide (15110-3.3 & 15500-2.2)
Verify that Di-electric fittings are provided and installed at connections between all
7 dissimilar materials.
(15050-2.3)
Sleeve piping passing through partitions, walls, and floors. Size sleeves large enough to
8 accommodate expansion and contraction and allow for continuous insulation and vapor
barrier. (15050) (15250-3.2)
Verify that piping expansion joint alignment guides and anchors are provided where
9
required. (15500-2.4/5)
Verify that all piping and associated fittings are insulated. Pipe exposed in mechanical
10
rooms or in finished spaces less than 10’-0” A.F.F. shall be finished with PVC jackets.
Verify that all valves and piping have been tagged and/or identified with directional arrows
11
and service labels.(15500)
Verify that isolation valves have been installed as follows: (15500-2.2)
12 A. Ball valves installed for piping 2-1/2” and smaller.
B. Butterfly valves installed for piping 3” and larger.
13 Verify that piping has been identified for system and direction of flow. (15050-3.4)
14 Verify that valve tags have been provided as scheduled. (15050-3.4)
1. Participants
Name/Representing Participation (Testing, Witness, etc)
/
/
/
2. Prerequisite Checklist
a. A completed and approved balancing report has been provided.
b. An as-built version of the controls submittal has been provided.
c. The controls contractor has certified that their internal commissioning is complete and the project is ready for third-
party verification. CC initials: ________. Date: ________.
d. The general contractor has certified that the construction is substantially complete and ready for third-party
verification. GC initials: ________. Date: ________.
e. Record all values for setpoints, control parameters, limits, delays, lockouts,
schedules, etc., that have been changed to accommodate testing:
Returned to Returned to
Pre-Test Pre-Test
Parameter Pre-Test Parameter Pre-Test
Values Values
Values Values
Occupied space Unoccupied space
temperature heating temperature heating
setpoint setpoint
Occupied space Unoccupied space
temperature cooling temperature cooling
setpoint setpoint
Frost Control Occupied low space
temperature alarm temperature alarm
setpoint setpoint
Occupied/Unoccupied
Occupancy Schedule
mode
Occupied Space
Low Limit Switch SP
Humidity Setpoint
3. Sensor Calibration Checks. The sensors listed below are to be checked for calibration and adequate location.
4. Device Calibration Checks. The actuators or devices listed below are to be checked for proper operation and/or
calibration.
Site Pass
Device or Actuator Procedure / State BAS Value
Observation Y/N
1. Observe OA damper modulating
Outside air damper / actuator Y/N
in unison with RA and EA damper.
1. Observe EA damper modulating
Exhaust air damper / actuator Y/N
in unison with RA and OA damper.
Stop Y/N
Exhaust air fan status
Start Y/N
5. Notes
FREEZE
1. With the unit running in the occupied 1. The unit will shut down, and all dampers
STAT
mode, trip the low limit thermostat will go to their fail state, and DTW (HCV)
ALARM
9. located upstream of the HC coil. valve will fail open to the coil. The BAS Y/N
AND
2. Manually reset the freeze alarm at the will indicate a freeze alarm.
SHUTDO
BAS. 2. The unit will start in occupied mode.
WN
1. Space temperature.
11 TRENDS 2. 4. Mixed air temperature. Trend Data Y/N
5. Outside air temperature.
6. Mixed air damper position
7. Room Humidity
8. Supply Air Temperature
-- END OF TEST --
END OF SECTION 23 08 00
SECTION 23 09 00
BUILDING CONTROLS SYSTEM (BCS)
TABLE OF CONTENTS
SECTION 23 09 00
BUILDING CONTROLS SYSTEM (BCS)
PART 1 - GENERAL
1.1 SUMMARY
A. The work of this section is governed by the General Conditions, Supplementary Conditions,
Sections in Division 1 and section 20 05 00 of the Project Manual.
B. Perform work and provide materials and equipment as shown on the drawings and as specified
or indicated in this section of the specifications. Completely coordinate work of this section
with work of other trades and provide complete and fully functional systems installation.
C. Commissioning
a. In addition to the startup of equipment and systems, include the time required
to be on site to perform functional testing of the equipment and systems
being commissioned as specified in the Commissioning Specification in
Section 01 91 13.
D. Related work specified in other sections includes, but is not necessarily limited to:
A. Automatic Logic (ALC) shall be the sole provider to match the existing CRH campus BAS.
A. The Contractor shall furnish and install a complete building automation system including all
necessary hardware and all operating and applications software necessary to perform the
control sequences of operation as called for in this specification and as shown on the drawings.
All components of the system – workstations, application controllers, unitary controllers, etc.
shall communicate using the BACnet protocol, as defined by ASHRAE Standard 135-2001.
No gateways shall be used for communication to controllers furnished under this section. At a
minimum, provide controls for the following:
8. Power wiring for control equipment including panels, dampers, filters, actuators and
other control equipment specified under ATC shall be by this Section. Wire to
closest emergency (when available) normal electrical branch circuit panel for final
connection to 20A-1P circuit breaker by Section 26 10 00.
B. The work included under this section of the specifications and drawings includes the complete
installation of a building controls system utilizing digital controllers.
C. The Contractor shall furnish and install a complete building control system including all
necessary hardware and all operating and applications software necessary to perform the
control sequences of operation as called for in the documents. All required operation
parameters, setpoints, schedules, and software shall be submitted to the Owner ready for use.
D. The Drawings and Specifications are not intended to show all details. The Contractor shall
secure satisfactory information before submitting the proposal and include in the proposal a
sum sufficient to cover all items of labor and material required for the complete installation of
the devices and system described.
E. All work performed under this section of the specifications shall comply with all codes, laws
and governing bodies. If the drawings and/or specifications are in conflict with governing
codes, the more stringent requirement shall apply.
F. The Contractor, as part of the bid proposal, shall indicate the manufacturer of the controllers
being proposed for this project and the model numbers. This information shall be indicated on
the Bid Form.
G. The Contractor shall obtain and pay for all necessary construction permits and licenses.
H. The Contractor shall furnish all control valves and control dampers (except valves and
dampers inside air handling units where only actuators may be required if not provided by
equipment manufacturer) indicated on control drawings. Installation shall be by Section 23 06
00, supervised by this section contractor.
I. The Contractor shall furnish and install all actuators including necessary linkages, wiring and
conduit.
J. The Contractor shall provide all necessary field control and interlock wiring including
auxiliary contacts, push buttons, switches and indicating lamps necessary. Division 26 shall
provide circuit breakers in electric panels. This contractor shall provide wiring and conduit
from the circuit breakers to the control panels. Power provided by Division 26 will be 120
Volts. This contractor shall provide transformers to reduce the voltage if required by this
contractor's equipment. This Contractor shall coordinate with the Division 26 Contractor for
locations of panels.
K. The Contractor shall provide all sensors, transducers and miscellaneous equipment to provide
the specified control sequences. The terminal volume box controllers provided by this
Contractor shall be mounted on the individual boxes at the terminal volume box
manufacturer's factory.
L. Provide services and manpower necessary for commissioning of system in coordination with
the HVAC Contractor, Balancing Contractor and Owner’s representative.
A. The Contractor shall cooperate with others performing work on this project as necessary to
achieve a complete and neat installation. Consult the drawings and specifications of all trades
to determine the nature and extent of others' work.
B. It will be the duty of the Contractor to work in cooperation with the Owner’s Representative,
and with other Contractors and Employees, rendering assistance and arranging his work so
that the entire project will be delivered in the best possible condition and in the shortest time.
C. The Contractor and Manufacturers supplying equipment with packaged controls (boilers,
computer room units, chillers, etc.) shall coordinate with each other to develop program code
to interface all packaged controllers to the BCS to perform all monitoring, alarming and/or
control required by the drawings and specifications. It shall be incumbent upon this
Contractor to ensure such coordination occurs.
B. Installer's Qualifications: Firms specializing and experienced in the specified style of control
systems installations for not less than 5 years.
1. Electrical Standards: Provide electrical products, which have been tested, listed and
labeled by (UL) and comply with NEMA standards.
3. NFPA Compliance: Comply with NFPA 90A "Standard for the Installation of Air
Conditioning and Ventilating Systems" where applicable to controls and control
sequences.
4. NFPA 92A “Smoke Control Systems” where applicable to controls and control
systems.
1.6 SUBMITTALS
A. Product Data: Submit manufacturer's technical product data for each control device furnished,
indicating dimensions, capacities, performance characteristics, electrical characteristics,
finishes of materials, and including installation instructions and start-up instructions.
B. Shop Drawings: Submit shop drawings for each control system, containing the following
information:
2. Label each control device with setting and adjustable range of control.
5. Database list showing point tag, point description type, processor address, module
address, termination point and channel number, signal range, power source and
remarks.
6. SAMA type functional logic diagrams showing analog loop and digital logic. These
drawings shall show complete configuration details including I/O address, register
values, function generator values, block numbers, connection points, ranges and all
necessary configuration specifications.
13. List of process variables, which will be monitored from the OEM controllers.
15. Valve and damper schedules showing sizes, capacities, flow coefficient, pressure
drop, configuration and location.
C. Maintenance Data: Submit maintenance instructions and spare parts lists. Include this data,
product data, and shop drawings in maintenance manuals; in accordance with requirements of
Division 1.
D. All shop drawings shall be prepared on computer aided drafting software or equivalent.
Drawing sheet size shall be 11" x 17".
E. Shop drawings shall include a riser diagram depicting locations of all controllers and
workstations, with associated network wiring. Also included shall be individual schematics of
each mechanical system showing all connected points with reference to their associated
controller.
F. Submittal data shall contain manufacturer's data on all products used in the project. In
addition, submittals shall contain sequences of operation, program listings, point lists, and a
complete description of the graphics, reports, alarms and configuration to be furnished with
the workstation software. Information shall be bound.
G. Prior to ordering or fabricating equipment, submit shop drawings in accordance with Section
20 05 00 “Basic Mechanical and Electrical”.
A. Provide factory-shipping cartons for each piece of equipment and control device. Maintain
cartons through shipping, storage and handling as required to prevent equipment damage, and
to eliminate dirt and moisture from equipment. Store equipment and materials inside and
protected from weather.
D. Equipment, piping and wiring installed in conditioned air streams, spaces or plenums shall
comply with NFPA 90A flame/smoke/fuel contributing rating of 25/50/0.
E. Comply with FCC rules Part 15 regarding Class A radiation from computing devices and low
power communication equipment operating in commercial environments.
F. Comply with FCC rules, Part 68 for telephone modems and data sets.
A. The Contractor shall provide operating and maintenance manuals consisting of, at a minimum,
component data sheets, maintenance and calibration procedures, software print-outs, code
documentation and point-to-point wiring diagrams.
1.10 WARRANTY
A. The Contractor shall provide a warranty against defects in materials or workmanship in the
BCS as described in this specification. Term of warranty is as follows (after system start-up
has been completed and accepted by the Owner):
B. Updates to the manufacturer’s software shall be provided at no charge during the warranty
period.
1.11 AS-BUILTS
A. Within 90 days following project completion and testing, the Contractor shall submit as-built
drawings reflecting the exact installation of the system. The as-built documentation shall also
include a copy of all application software both in written form and on DVD.
1.12 INSPECTION
A. Examine areas and conditions under which control systems are to be installed. Do not proceed
with work until unsatisfactory conditions have been corrected in manner acceptable to
Installer.
A. General: Install systems and materials in accordance with manufacturer's instructions and
roughing-in drawings, and details on drawings. Install electrical components and use electrical
products complying with requirements of applicable Division-16 sections of these
specifications. Mount controllers at convenient locations and heights.
B. Control Wiring: The term "control wiring" is defined to include providing of wire, conduit
and miscellaneous materials as required for mounting and connecting electric control devices.
C. Wiring System: Install complete control wiring system for control systems. Following
manufacturer's recommendations for use of shielded cable for field signal wiring, wire and
cable separation criteria by type of point and signal level, power supply and grounding. Wire
and cable shall be run in EMT conduit except in control rooms where wireway may be used
and outdoors where rigid steel conduit shall be used. Final connection to devices shall be made
in flexible steel sealed conduit. The length of flexible sealed steel conduit shall not exceed 3
feet. Provide multi-conductor multi-pair instrumentation cable (bundle) in place of single pair
cable where number of conductors (pairs) can be run along common path. Do not run conduit
over equipment removal areas or under the path of movable cranes or monorails. Coordinate
conduit runs with other contractors on coordination drawings before installation. Obtain
approval for conduit drawings prior to installation. Fasten flexible conductors bridging
cabinets and doors, neatly along hinge side, and protect against abrasion. Tie and support
conductors and cable neatly. Single pair instrumentation cable shall be 300 volt insulation No.
16 AWG shielded and twisted with half-lap aluminum mylar wrap with copper drain wire with
flame retardant jacket. Multi-pair instrumentation cable shall of the same construction as
single pair except that the minimum wire size shall be No. 20 AWG.
D. Number code conductors and pneumatic tubing with permanent wire markers and labeling
system for future identification and servicing of control system.
F. Unit Mounted Equipment: Where control devices provided by this Contractor are indicated to
be unit-mounted, ship relays, switches, valves, dampers, and damper motors to unit
manufacturer for mounting and wiring at factory. Coordinate all shipping with the unit
manufacturers.
A. Start-Up: Start-up, test, and adjust control systems in presence of manufacturer's authorized
representative and the Owner’s Representative. Demonstrate compliance with requirements.
Replace damaged or malfunctioning controls and equipment.
B. Field Testing and Start-up: The Contractor shall provide the services of a qualified service
representative to check system installation and supervise the system power up and initial
check-out. All travel and living expenses shall be included in the bid.
C. The Contractor shall include 30 days of on-site start-up engineering service in his bid. All
travel and living expenses shall be included in the bid.
1. Schedule instruction with the Owner’s Representative, provide at least 14-day notice
to the Owner’s Representative of training date.
1.16 TRAINING
A. The Contractor shall include in his proposal 40 hours of on-site operator training.
1. Instruction in programming.
C. Provide for the training sessions, text books, workbooks and similar materials for personnel,
which shall be retained by those personnel upon completion of training. Provide an extra
clean copy of the material to be filed with the O&M manuals.
A. After all field connections have been made and control power is available to each control
panel, the Owner’s Representative shall be notified and the control system shall be enabled by
the BCS Contractor. Any software loading shall be done at this time and the start-up of the
mechanical or electrical system shall commence.
1.18 TESTING
A. Each point in the system shall be tested for both hardware and software functionality. In
addition, each mechanical and electrical system under control of the BCS will be tested against
the appropriate sequence of operation specified herein. Successful completion of the system
test shall constitute the beginning of the warranty period. A written report will be submitted to
the owner indicating that the installed system functions in accordance with the plans and
specifications.
B. The BCS Contractor shall commission and set in operating condition all major equipment and
systems, such as the chilled water, hot water and all air handling systems, in the presence of
the equipment manufacturer’s representatives, as applicable, and the Owner’s representatives.
C. The BCS Contractor shall provide all manpower and engineering services required to assist the
HVAC Contractor and Balancing Contractor in testing, adjusting and balancing all systems in
the building. The BCS Contractor shall have a trained technician available on request during
the balancing of the systems. The BCS Contractor shall coordinate all requirements to provide
a complete air balance with the Balancing Contractor and shall include all labor and materials
in his contract.
A. All Controllers and Building Controls System shall be manufactured by the Controls System
Manufacturer. All manufacturers shall meet all of the requirements of this specification.
B. The equipment and software proposed by the supplier shall be currently in manufacture. No
custom products shall be allowed. The Manufacturer shall support all products for a minimum
of 5 years, including spare parts, board repairs and software revisions.
C. Subject to compliance with requirements, the Manufacturer shall have at least 10 years of
experience in production of control systems of the type specified for commercial applications
and shall be Automated Logic.
A. The Building controls system shall consist of peer to peer network controllers and
workstations on a high speed backbone (Ethernet), supporting peer to peer distributed
controllers on a field bus.
B. In addition to the specified hardware, software and field devices, the contractor shall furnish
all labor to design, program and install the BCS.
C. The scope of work includes testing, startup training and warranty work specified.
D. The Building Controls System (BCS) shall be designed in strict accordance with ASHRAE’s
BACnet standard, 135-2001 to provide interoperability between different building subsystems.
The system shall also provide a graphical, web-based operator interface that allows for instant
access to any system through a standard browser. The system shall use BACnet network types
and protocols exclusively. Non-BACnet based systems are not acceptable. The contractor
must provide PC-based programming workstations, operator workstations and microcomputer
controllers of modular design providing distributed processing capability, and allowing future
expansion of both input/output points and processing/control functions. Contractor must
provide manufacturer’s Protocol Implementation Conformance Statement (PICS) for
workstation software and every controller model that is installed.
1.22 DEFINITIONS
A. The term "implement" means to develop and/or utilize a software and/or hardware component
to meet the system criteria or system verification as part of the work covered in this section.
B. The term "multi-vendor integration" when referenced herein shall imply the hardware
equipment and software programs needed for communications to the various mechanical
and/or electrical systems contained in the scope of work.
C. BCS: The environmental monitoring and control system including lighting, inclusive of all
appurtenances required for the control and monitoring of the mechanical, electrical, or other
systems unless specifically exempted within this specification. This definition includes both
hardware devices and software components that are integrated to form a working system.
D. The term "BCS Contractor" is the successful offerer of the building controls system as
specified in Section 23 09 00.
F. Stand-Alone System: Performs all control functions independently without direction from a
central unit.
I. Control Wiring: All wiring, 120 VAC line voltage or lower other than power wiring, required
for the proper operation of the mechanical system and the BCS. This includes applications
where line voltage also serves as a control circuit such as a line voltage thermostat or involves
interlocking with a damper.
J. Power Wiring: All line voltage wiring to the mechanical and BCS equipment that is required
for proper operation of the equipment. Typically, this wiring will support voltage at or above
120 VAC and is connected to the equipment for the purpose of providing motive power.
K. Ethernet: Broadcast networking system that carries digital data packets to local nodes. It is a
(10, 100) Mbps base-band LAN.
1.23 SOFTWARE
A. Controller software refers to the capabilities of the firmware resident in each Level 1 or Level
2 controller. As such it describes the overall operating capabilities, communications, and
application level function of the particular controller. All controller level firmware is to be
resident in ROM, and must be socketable to allow for future upgrades.
B. Workstation software encompasses the operating system, database and application software
for use on the personal computer workstations. This software may be provided on diskettes,
tapes or CD ROMs. It is sold as a software license and is intended to be upgraded over time as
new features become available.
C. Upgrade the existing system to the latest software version if available at the time of
installation.
A. All operator interface hardware including workstations and laptop computer shall be IBM
compatible.
A. All software, including the energy management system, shall become the property of the
Owner. The Owner shall have rights to use and/or alter any part of the system without
restriction.
B. Ownership of the software shall not allow infringement upon the supplier's copyrights.
1.26 UPGRADES
A. Provide software upgrades during the warranty period as the manufacturer's product is
improved at no cost to the Owner. Furnish confirmation letter to the Owner before system
acceptance indicating that the latest software versions are installed as of turn-over date and at
the end of the warranty period that all upgrades have been provided.
A. Included with field devices are all gauges, sensors, transmitters, transducers, wells, relays,
switches and power supplies necessary for the operation of the BCS System.
B. All field devices shall include the associated tubing, wiring, conduit, mounting, and
enclosures.
C. Also included are sensors, control valves, control dampers, smoke dampers, valve actuators,
damper actuators, relays, and conventional controls necessary for a completely functioning
system in accordance with the sequences of operation.
1.29 COMPLIANCE
A. All wiring shall be installed in accordance with all applicable electrical codes and Division 26,
and shall comply with equipment manufacturer's recommendations.
PART 2 - PRODUCTS
A. System Overview
2. There shall be two levels of controllers. Level 1 controllers shall contain a high
speed LAN communication bus capable of sharing data among personal computer
work stations, other Level 1 controllers, and a central file server. Level 1 controllers
shall also contain a communication bus to Level 2 controllers, referred to throughout
the specification as the field bus. Level 1 controllers are primarily central plant
controllers and network integrators. Level 2 controllers are dedicated DDC
controllers for standalone operation of HVAC equipment, lighting and plumbing
equipment. These controllers shall communicate to either a work station on the high
speed LAN via a level 1 controller or a portable laptop computer for the purposes of
monitoring and programming.
1. A host computer shall be the existing machine. The building automation software
shall be capable of communication to all Level 1 and Level 2 controllers, feature
high-resolution color graphics, alarming, reporting, and be user configurable for all
data collection and data presentation functions. The Level 1 network shall be
capable of supporting at least 16 work stations. On systems that are file server
based, each work station shall reference a central file server for its database
inquiries. On systems that are not file server based the system shall be capable of
storing system trend data, which shall be accessible from other workstations on the
network.
1. The BAS Contractor shall furnish licenses for (20) concurrent users to the BAS
system. Web-based users shall have access to all system points and graphics, shall
be able to receive and acknowledge alarms, and shall be able to control setpoints
and other parameters. A central web server shall be provided to manage the web-
based users. The web-based interface must conform to the B-OWS BACnet device
profile.
F. System Architecture
1. General: The network architecture shall consist of two levels. The top level shall be
a high speed LAN designed to support network controllers, central plant controllers,
work stations and a file server and shall operate on the Ethernet protocol. The
second level shall be a field bus to support a family of dedicated local controllers for
control of HVAC equipment, lighting, and plumbing equipment. The second level
bus shall communicate bi-directionally with the high speed LAN through Level 1
controllers for transmission of global data.
2. High Speed LAN: This local area network shall operate at a minimum speed of 100
Mbps. The high speed LAN shall provide transfer of point data, alarms and file
activity among Level 1 controllers, work stations and the file server. The high speed
LAN shall support a minimum of 50 nodes consisting of Level 1 controllers or work
stations.
3. Any data from a Level 2 controller shall also be transmitted onto this LAN through
a Level 1 controller. The high speed LAN shall support multi-user communications
and multi-session activity. That is, all global data sharing shall occur
simultaneously with the transmission of alarm data or user activity.
4. Field Bus: The level 2 bus, or field bus, shall support local control units of modular
size for operation of the building's HVAC, lighting and plumbing control systems.
The field bus shall operate at a minimum speed of76.8 kbps, with a minimum length
of 4000 feet or 32 nodes before requiring a network repeater.
5. Manufacturers with baud rates of less than 76.8 kbps shall be accepted, but shall be
limited to 32 Level 2 controllers to insure adequate global data and alarm response
times. The minimum acceptable baud rate shall be 9,600.
7. Work Station Communications: The BAS shall be connected directly to the high
speed LAN. Remote workstations shall be able to communicate to any Level 1
controller, Level 2 controller, additional work stations or the file server. Remote
workstations shall also be able to communicate via modems to remote controllers.
Telephone communications shall operate simultaneously with communication to any
controllers connected on the high speed LAN.
10. Third Party Communications: The network shall be capable of communicating with
third party controllers for the system. Two way communications shall be possible
with the original equipment manufacturers controllers.
1. All hardware and software included under this section shall conform to BACnet
standard 135-2001, to promote interoperability between building subsystems.
Additionally, the BAS design must include solutions for the integration of the
following “open systems” protocols: LonTalkTM, Modbus and digital data
communication to third party microprocessors such as chiller controllers, fire panels
and variable frequency drives (VFDs).
4. Level 1 controllers shall synchronize their resident real time clocks to each
controller on the high speed LAN. Additionally, the Level 1 controller shall
synchronize the clocks in the Level 2 controllers on its field bus.
5. Input
c. Analog Inputs - The Analog Input (AI) function shall monitor each analog
input, perform A/D conversion, and hold the digital value in a buffer for
interrogation. The A/D conversion shall have a minimum resolution of 12
bits. Input ranges shall be within 0-10 VDC or 4-20 mA.
d. Digital Inputs - the Digital Input (DI) function shall accept dry contact
closures and voltage level transitions. A voltage level below 1 volt shall be
read as ON (closed), a voltage level above 3 volts shall be read as OFF
(open).
e. Pulse Accumulator Inputs - the pulse accumulator input function shall have
the same characteristics as the DI, except that, in addition a buffer shall be
included to totalize pulses between interrogations. Each input shall accept
pulses at a minimum of 5 per second.
g. Input Wiring - all inputs shall be two wire devices and shall not require
shielded wire for accurate operation.
6. Output
a. Output types shall include digital, universal and tri-state. Outputs shall be
available with easily accessible built-in hand-off-auto (HOA) switches for
local overrides. DIP switches are not acceptable. Analog output override
switches shall be provided with potentiometers to simulate the output range.
b. Digital Output - the Digital Output (DO) function shall provide contact
closure for momentary (Pulse Width Modulation) and maintained operation
of field devices. Output pulse width shall be selectable between 0.1 and
3200 seconds with a minimum resolution of 0.1 seconds. Isolation and
protection against voltage surges up to 180 VAC peak shall be provided.
Contact rating shall be a minimum of 1 amp at 24 VAC. Each digital output
shall be equipped with an HOA switch to manually obtain either output state.
Manual overrides shall be reported to the controller at each update. An LED
shall be provided to indicate the state of each digital output.
d. Tri-State Outputs - tri-state outputs shall consist of two 24 VAC relays for
control of bi-directional motors and actuators. Each tri-state output is
capable of PWM (pulse width modulation) to a resolution of .1 second.
2. Communication Ports
b. In addition, a minimum of one RS232 and one RS485 port shall be provided
for connection to a workstation or laptop service tool. When the port is
RS232, it shall support communication to a modem or printer. Where
multiple RS232 ports are available, multi-user communications shall be
supported.
c. Any RS232C ports shall also be usable for connection to tank probes, fire
alarm panels, and other microprocessor-based devices, which communicate
in ASCII.
3. Communication Protocols
6. Power Supply
a. Level 1 LAN-based network controllers will operate from 120, 240 VAC,
60/50 Hz power, with a tolerance of +/- 20%. Line voltage below the
operating range of the system shall be considered outages. The controller
shall contain over voltage surge protection and require no additional AC
power signal conditioning. If required by the controller, a transformer to
reduce the voltage from 120/220 shall be supplied in the cabinet by the
contractor.
8. Battery Back-Up/UPS
9. Indicator Lamps
a. A touch screen LCD display shall be available for every Level 1 LAN-based
network controller for readout of point values in the network, and to allow
operators to change setpoints and other operating parameters.
11. Packaging
1. Memory
2. Communication Ports
3. Network Communications
a. Each controller will have access to any of the inputs, outputs, and calculated
variables contained in Level 2 controllers that are connected to it through its
local field bus as well as any other information available on the Ethernet.
5. Power Supply
a. The power supply will operate from 120/220 VAC, 60/50 Hz power, with a
tolerance of +20%. Line voltage below the operating range of the system
shall be considered outages. The controller shall contain over voltage surge
protection, and require no additional AC power signal conditioning. If
required by the controller, a transformer to reduce the voltage from 120/220
shall be provided in the cabinet by the contractor
7. Battery Back-Up/UPS
8. Indicator Lamps
9. Packaging
1. Description
c. Each Level 2 controller shall be able to have its program edited and/or
modified either locally through a laptop computer service tool or through a
workstation connected to a Level 1 controller. Each Level 2 controller shall
complete its internal scan in less than one second. Each scan shall consist of
updating of inputs, importing of data from other controllers, performing
mathematical calculations and sequencing appropriate outputs for local loop
control.
2. Noise Protection
a. Level 2 controllers that power with 120 VAC shall permit continuous
shorting of any input to 120 VAC. Level 2 controllers that power with 24
VAC shall permit continuous shorting of any input to 24 VAC. All outputs
shall be isolated to a minimum of 1500 VAC.
3. Communication Ports
4. Network Communications
7. Indicator Lamps
1. Description
a. The Level 2 system controller shall provide direct digital control of hot water
and chilled water plants, and all other large systems.
2. Memory
3. Input/Output
a. Inputs - the input section of the system controller shall provide a minimum of
16 universal inputs. Each input shall be configurable through software as a
digital (dry contact), analog (0-10V or 4-20 mA), pulse (up to 5 Hz)
thermistor, RTD or Thermocouple point. The analog to digital resolution
shall be a minimum of 12 bits.
d. Expansion port - the system controller shall have a port to accept a family of
I/O modules. Up to two modules shall be powered directly from the power
supply of the system controller.
a. The system controller shall contain a real time clock, accurate to 10 seconds
per month. The RTC shall provide the following information; time of day,
day, month, year, and day of week. Each controller shall be capable of
receiving a signal over the network from the Level 1 controller to
synchronize all clocks to the same time.
5. Power Supply
6. Packaging
7. Local Display
a. Each system controller shall have a built-in LCD display and keypad. The
display shall have a minimum size of 2 lines by 16 characters. From the
keypad, operators shall be able to view point status, adjust setpoints and
change parameters according to password level.
1. Description
2. Memory
a. Local controllers shall have a minimum of 32kB bytes of user RAM memory
and 128kB of EEPROM.
3. Input/Output
a. Inputs - the input section of the local controller shall provide a minimum of 8
universal inputs. Each input shall be configurable through software as a
digital (dry contact), analog (0-10V, or 4-20mA), pulse (up to 5 Hz),
thermistor, RTD or thermocouple point. The analog to digital resolution
shall be a minimum of 10 bits.
c. Overrides - each output shall have a built-in override switch capable of auto-
on-off operation. DIP switches shall not be acceptable. In addition, each
analog output shall include a potentiometer that can simulate the range of the
output signal.
d. Expansion Port - the local controller shall have an optional port to accept a
family of I/O modules. Up to two modules shall be powered directly from
the power supply of the controller.
a. The local controller shall contain a real time clock, accurate to 10 seconds
per month. The RTC shall provide the following information; time of day,
day, month, year, and day of week. Each controller shall be capable of
receiving a signal over the network from the Level 1 controller to
synchronize all clocks to the same time.
5. Power Supply
a. The local controller shall have a built-in power supply of selectable 120/220
VAC, 50/60 Hz. The power supply will tolerate 20% swings in supply
voltage. If required by the controller, a transformer to reduce voltage shall
be provided by this contractor within the cabinet.
6. Packaging
7. Local Display
a. Local controllers shall have a built-in LCD display and keypad. The display
shall have a minimum size of 2 lines by 16 characters. From the keypad,
operators shall be able to view point status.
1. Description
2. Memory
3. Input/Output
a. Inputs - the input section of the terminal equipment controller shall provide a
minimum of 6 universal inputs. Each input shall be configurable through
software as a digital (dry contact), analog (0-10V or 4-20mA), pulse (up to 5
Hz) thermistor, RTD or thermocouple point. The analog to digital
resolution shall be a minimum of 10 bits. A fifth input shall be available for
measuring air flow. The air flow sensor shall be included as part of the
controller, and accurate to +5% over a range of 0 to 1 inch w.g.
d. Overrides - Each output shall have a built-in override switch capable of auto-
on-off operation. DIP switches are not acceptable. Analog outputs overrides
shall be equipped with potentiometers to simulate the range of the output.
4. Power Supply
5. Packaging
b. Outputs - There shall be a minimum of one form A relay, one form K relay
and one analog (0-10V or 4-20mA) outputs.
1. Description
2. Input Modules
3. Output Modules
a. Each module shall provide either two digital, analog or pneumatic outputs.
Digital outputs shall be available in either 24 VAC or 120 VAC/220 VAC
rated relays. Analog outputs shall provide either 0-10 VDC or 4-20 mA.
Pneumatic outputs shall provide a 3-15 psi signal, with built-in feedback of
the branch pressure. All output modules shall include easily accessible 3
position override switches and potentiometers. (DIP switches shall not be
acceptable).
1. General
2. Communication Ports
a. In addition to its on-board Ethernet port, the Gateway shall have at least two
serial communications ports for interfaces to third-party systems.
3. Memory
a. The Gateway shall have enough RAM memory to store all point
configuration data, plus required history logging and alarm buffering.
Minimum RAM shall be 8 MB. The operating system of the gateway must
be stored in FLASH non-volatile memory.
a. The Gateway shall employ the same user programmable application software
that NRCs and SDCUs use.
5. History Logging
A. Network Drivers
a. Drivers shall be available for twisted pair cabling, coaxial cabling, and fiber
optic networks.
b. Coaxial drivers shall support both bus and star network topologies. Fiber
optic and twisted pair drivers shall operate in star topologies.
3. Field Bus: The field bus driver shall provide amplification to allow for expansion
beyond 32 nodes or 4000 feet. For each additional group of 32 nodes or 4000 feet,
an additional driver shall be required. Drivers that can provide multiple channels
from a single card are acceptable.
1. Software Description: The application software shall be configured for each Level 1
controller either locally, through a laptop computer service tool, or through a work
station. Level 1 controllers shall contain PROM as the resident operating system.
Application software shall be RAM resident. Application software shall only be
limited by the amount of RAM. There shall be no restrictions placed on the type of
application programs in the system.
d. System self-testing
e. Multi-user
f. Multi-tasking
c. Comments
d. Scrolling
4. When programming in terminal mode, the system shall allow full screen, character
editing for correction or modification of any portion of a program. Syntax errors
shall be highlighted, and programmers must make corrections prior to the program
being compiled.
6. Point Identification: Users must be able to assign unique identifiers for each
connected point. Identifiers must have at least sixteen alpha/numeric characters. All
references to these points in programs, reports, and command messages shall be by
these identifiers.
b. The BCS contractor shall submit a list of all point names to the Owner’s
Representative for approval prior to programming the system.
b. The language shall allow the creation of timers anywhere in the logic of a
program. Each timer shall increment in seconds and increment to a minimum
of 365 days.
8. Application Software: The system shall contain ROM based, built-in software
modules for the creation of standard application programs. Modules shall include as
a minimum:
a. PID Algorithm
d. Curve fit
e. Optimum Start
10. The controllers shall be capable of performing complex logical statements including
operators such as >,<,=, and, or, exclusive or, etc. These must be able to be used in
the same equations with the mathematical operators and nested up to five
parentheses deep.
11. Passwords: Level 1 controllers shall have 5 levels of passwords. The highest level
shall allow access to all functions within the system. The remaining 4 levels will be
definable by the Owner to include any subset of system commands.
12. History Logging: Each controller shall be capable of logging any system variable
over user defined time intervals ranging from 1 second to 365 days. Any system
variables (inputs, outputs, math calculations, flags, etc.) can be logged in history. A
minimum of 32767 values may be stored in each log. Each log shall record either
the instantaneous, average, minimum or maximum value of the point. Logs can be
automatic or manual.
a. It shall be possible to find the average of a log, the standard deviation, the
sum, minimum or maximum. It shall also be possible to reference any value
within a log for use in a control program.
13. Reporting: The system shall be able to create user definable reports containing any
combination of text and system variables. Report templates will be created by users
in a word processing environment. Reports can be displayed based on any logical
condition or through a user command.
14. Alarming: For each system point, alarms can be created based on high/low limits or
conditional expressions. All alarms shall be tested. Each alarm can result in the
display of one or more alarm messages or reports. Messages and reports can be sent
to the display panel, a local terminal, to the Work Station, via modem to a remote
computing device, or all of the above.
15. Overriding Programs: It shall be possible to disable any point in the system and
modify it to a user definable value. Any points that have been disabled shall be kept
in a log and viewable by an operator at any time.
16. I/O Configuration: All input, output, and internal software points shall be
configurable from menus in the operator workstation and laptop service tool
connected to a Level 1 network or remote site master controller. Each input shall be
software selectable to operate as a digital point, analog voltage, analog ampere,
analog resistance, temperature sensor, or a pulsed signal. Each output point shall be
software selectable to operate as a digital, analog or tri-state. The software shall
permit scaling of analog inputs and outputs in engineering units, with automatic
conversions for both linear and non-linear devices.
2. The database shall also contain host level points consisting of variables, which can
be used for host level reports and alarming. These variables can be setpoints or the
result of any Boolean algebra expression.
3. The BCS contractor shall provide graphics at the user workstation that display at
least the information indicated on the control diagrams in the drawing package.
Additionally, the graphics shall contain the following information for each device:
4) VFD alarms.
1) Control Setpoint
4) Positioner feedback
1) Control Setpoint
e. Monitoring Devices
4. Where applicable, all readings, setpoints and conditions shall be expressed with
their engineering units (i.e., temperature shall be expressed in degrees Fahrenheit).
By use of a function key on the keyboard, the user shall be able to toggle between SI
units and English units. The program shall contain all necessary conversion factors
accurate to two decimal places. Graphics shall be a minimum of six (6) colors in
display of various systems.
5. Automatic Monitoring: The software shall allow for the collection of data and
reports from any Level 1 or Level 2 controller through either a hardwire or modem
communication link. The time schedules and content of the polling shall be user
configurable and include any subset of the controller's data base including
application programs.
a. A minimum of 255 alarm levels. Each alarm level shall establish a unique
set of parameters for controlling alarm display, acknowledgment, keyboard
annunciation, alarm printout and record keeping.
7. Report Generation: The software shall contain a built-in report generator, featuring
word processing tools for the creation of custom building reports.
a. Reports can be of any length and contain any points with the database of
Level 1 and Level 2 controllers.
b. The report generator shall have access to the user programming language in
order to perform mathematical calculations inside the body of the report,
control the display output of the report, or prompt the user for additional
information needed by the report.
8. Scheduling: It shall be possible to configure and download from the work station
schedules for any of the controllers on the network.
9. Time of day schedules shall be in a calendar style configured for either monthly or
weekly operation. Scheduling shall be programmable up to one year in advance.
10. Each schedule shall appear on the screen as a monthly calendar correctly showing
the day, weekday, month and year. It shall be possible to scroll from one month to
the next and view or alter any of the schedule times.
11. Schedules shall be assigned to specific controllers and stored in their local RAM
memory. Any changes made at the work station shall be automatically updated to
the corresponding schedule in the controller.
13. There shall also be a provision for Special Day schedules. Special Day schedules
shall override both the standard schedule and its associated Holiday schedule.
Special Days shall be differentiated on the calendar through color coding of the date.
Any changes to a Special Day schedule shall be automatically updated to the
standard schedule to which it has been superimposed.
14. The Scheduling application shall include built-in editing tools to permit users to
copy and paste portions of schedules to different days, weeks or months. Users can
15. Trending: The software shall be capable of displaying historical data in either a
tabular or graphical format. The requirements of this trending capability shall
include the following:
b. In a tabular form, the trend display can have up to 16 columns. Each column
shall contain a minimum of 6500 rows.
c. In the graphical format, the trend shall plot up to 16 separate variables over
the requested time period.
d. The time period for each trend shall be user selectable, from 1 minute to 1
year.
e.
When using the tabular form, the user shall be able to select from displays
that show the actual value at each interval, the interpolated value, or the
value of the last change.
D. Level 1 - Lan-based Network Controllers
d. System self-testing.
e. Multi-user capability.
f. Multi-tasking capability.
c. System Self-Testing.
d. Multi-User Capability.
e. Multi-Tasking Capabilities.
4. Alarming: For each system point, up to 8 alarms can be created based on high/low
limits or conditional expressions. All alarms will be tested each scan and can result
in the display of one or more alarm messages or reports through a host work station.
5. History Logging: Each controller shall be capable of logging any point over user
defined time intervals ranging from 1 second to 365 days. Points include inputs,
outputs, math calculations, setpoints, and internal variables. A minimum of 2000
values can be stored in each log. Each log will record either the instantaneous,
average, minimum, or maximum value of the point. Logs can be automatic or
manual.
F. Level 2 Controllers
1. All input, output, and internal software points shall be configurable from menus in
the operator workstations, the laptop service tool, or through a dumb terminal
connected to a Level 1 network or remote site master controller. Each input shall be
software selectable to operate as a digital point, analog voltage, analog ampere,
temperature sensor, or a pulsed signal. Output point types may include digital,
analog or tri-state. The software shall permit scaling of analog inputs and outputs in
engineering units, with automatic conversions for both linear and non-linear devices.
Where Level 2 controllers contain override switches, the software shall detect the
override position of the switch and record the actual value of the override for both
digital and analog output types.
2. Data Identification: Users must be able to assign unique identifiers for each
connected I/O point, variable, or controller in the system. Identifiers may have up to
sixteen (16) alpha/numeric characters. All references in the programs, reports, and
command messages shall be by these identifiers. Each point name can have up to a
40 character description, and engineering units (up to 8 characters). All analog
points shall be stored as floating point numbers and displayable in integer or
scientific notation formats.
b. Local Display: All points and system variables contained in the system
controller shall be displayable through the optional LCD display. In
addition, it shall be possible through a keypad to modify variables such as
setpoints and operating parameters. The software will allow any point to be
selectively removed from access through the display.
A. General:
B. Scope
1. Control system shall consist of thermostats, humidistats, temperature transmitters,
controllers, automatic valves and dampers, damper operators, control panels,
electrical wiring and other components required to fill intent of Specifications and
provide for complete and operable system. Control equipment shall be fully
proportioning, except as noted otherwise. Sequence of operation shall be as
indicated on Drawings.
1. Controllers, relays, switches, etc. shall be mounted on enclosed control panels with
hinge lock type door mounted adjacent to system controlled. Temperature settings,
adjustments and calibrations shall be made at system control panel. Panel shall have
canopy light and on-off switch.
3. Details of each panel shall be submitted for approval prior to fabrication. Locations
of each panel shall be convenient for adjustment and service. Provide engraved
nameplates beneath each panel mounted control device. Manual switches, dial
thermometers and indicating gauges shall be flush mounted on hinged door.
5. Following items shall be mounted on control panels: water supply and return
temperature indicators, 7 day time clock, selector switches, occupied/ unoccupied
switch and humidity indicators.
unless specified otherwise. Time clocks shall be seven day program type with ten hour spring
reserve and manual override.
E. Thermometers:
1. Thermometers shall be flush mounted on local panels. These thermometers shall be
electronic transmission type with dials with minimum 3-1/2" diameter. Accuracy
shall be +2% of full scale values. Linear scale shall be -40 deg. F to 150 deg. F.
Indication meter shall be suitable for use with 1000 ohm temperature sensors.
1. Provide optimal start logic network programmer to start air handling equipment to
properly condition spaces prior to occupancy. Optimal time to start primary
equipment shall be determined by external conditions, building construction and
conditioning equipment. Factors to be considered in determining warm-up period
for air handling systems shall be type of building construction, U factor and outside
air temperature.
A. Input Devices
1. The system shall maintain the specified analog end-to-end accuracy throughout the
warranty period from sensor to controller readout.
2. Transducers may be supplied as an integral unit with the field sensor, or mounted
separately in a field interface panel, or as part of the controller. All transducers
shall be calibrated in the field for mounting and connected to the final terminations.
7. Sensors in the return or discharge duct shall be of the single point type. Sensors in
the mixed air shall be of the averaging type.
8. Thermowells shall be brass or steel for non- corrosive fluids below 250 deg.F and
300 series stainless steel for all other applications.
9. All digital inputs shall be provided by dry contacts. The contacts shall be wired
normally open or normally closed as required.
10. Temperature sensors shall be by the use of thermistors or Resistance Temperature
Detectors (RTD).
19. Water flow status shall be sensed by differential pressure switch piped across all
pumps. One piping connection shall be made at pump suction, the other at pump
discharge before the discharge check valve.
20. Common alarms shall be wired relay coils in parallel with common alarm pilot light.
Contacts shall input to BCS.
21. Wire contacts normally open (NO). When in an alarm condition the contact shall
open and the BCS shall sense alarm condition.
22. Air flow transducers for volume control terminals shall have the ability to control air
flow with a velocity pressure signal of 0.02" WC or less with an accuracy of +10%
of reading.
B. Output Devices
2. All digital outputs shall be electrically isolated from the digital controller by
interface relays.
3. Field relays shall have a minimum life of 1 million cycles without failure.
4. Electric to pneumatic transducers (E/P) shall operate from an analog signal. E/P
transducers shall be rated for 0 -20 PSIG operation and accurate to 1% of full scale.
E/P transducers shall have a maximum air consumption of 100 SCIM.
5. Electric solenoid operated pneumatic valves (EP's) shall have a three port operation:
common, normally open and normally closed. They shall be rated for 50 psig when
used for 25 psig or less applications, or rated for 150 psig when used for 100 psig or
less applications. The coils shall be equipped with transient suppression devices to
limit transients to 150 percent of the rated coil voltage.
C. Actuators
a. Actuators for valves and dampers servicing terminal equipment (i.e. reheat
coil valves, fan coil unit valves, variable air volume boxes, etc.). Shall be
electric.
b. Actuators for valves servicing the fuel oil system and valves located outdoors
shall be electric.
c. Actuators serving VAV boxes and laboratory areas (supply, exhaust, return)
shall have a maximum stroke timing of six seconds from full closed to full
open to full closed.
2. Damper actuator mounting shall be outside of the air stream. The actuators shall
have external adjustable stops to limit the stroke. The linkage arrangement shall
permit normally open or normally closed positions as indicated on the drawings.
3. Modulating damper and control valve actuators and actuators operating valves or
dampers which must be sequenced with other valves or dampers shall be equipped
with pilot positioners to provide feedback, repeatability and rapid response.
6. Provide two adjustable restrictors on each pneumatic damper actuator to adjust the
speed of opening and closing.
7. Electric Motors: Size to operate with sufficient reserve power to provide smooth
modulating action or two position action.
D. Control Valves
1. Control valves shall be rated for 150 percent of system operating pressure at the
valve location, but not less than 125 psig.
2. Close off rating shall be no less than 150 percent of system pressure at the valve
location.
1. The modulating valve shall be pressure independent. The valve shall maintain a
constant differential pressure across the valve orifice and a constant flow rate with
varying differential pressure. No balancing valve upstream of the valve will be
required.
3. The valve shall be factory fabricated of body material, and pressure class based on
maximum and temperature rating of the piping system shown in Valve Chart. (insert
Chart Name)
4. The control valve shall accurately control the flow from 0 to 100% full rated flow.
The flow shall not vary more than +/ 5% due to system pressure fluctuations across
the valve with a minimum of 6 PSID across the valve. The maximum pressure
across the valve shall be 9 PSID.
6. Control Valve bodies shall be brass, ductile iron, carbon steel or stainless steel. All
internal parts shall be brass, bronze, carbon steel, stainless steel, Teflon or EPDM.
7. It shall be possible to adjust the flow in the field without removing the valve from
the piping or closing off flow.
8. Actuators shall modulate from 0 to 100% design flow by rotating the stem.
Limiting stem rotation will not be allowed to limit flow.
11. All valves shall have integral ports, factory installed capable of being used to
measure pressure or temperature. Visual indication which shows the flow rate shall
be permitted as long as there are ports to measure as well.
12. Each valve shall be individually flow tested, factory tested and have a label tag
affixed verify its setting and Flow capability with no more than +/-5% of the full
flow through the operating range.
13. The valve and all its additional components shall have a minimum 5 year warranty.
F. Control Dampers
4. Dampers shall be opposed blade in all locations except mixing plenums, where
parallel blades shall be positioned to direct air streams into each other, thus
facilitating mixing.
5. Furnish single or multiple blade automatic and smoke (UL555S) rated dampers for
installation under ductwork paragraph as required.
6. Provide one linkage connection point per eight square feet of section area, equally
spaced. Sections shall not exceed 48" x 48". Provide shaft linkage (1/2" minimum
bar with crankdown arms attached to blades) on dampers 12 feet or wider. Dampers
12 feet or wider and more than four feet high shall have one line shaft for each four
feet of height, or any increment thereof; where size of damper required more than
one line shaft, spacing shall be equal.
8. Damper frames shall be 13 gauge galvanized sheet metal with flanges for duct-
mounting.
9. Damper blades shall not exceed 6" in width. Blades shall be suitable for duct
velocity performance.
10. Damper bearings shall be nylon. Bushings that turn in bearings shall be oil-
impregnated, sintered metal.
11. Assembled multiple damper sections shall incorporate mullion supports to prevent
failure of sectional assembly.
12. Provide replaceable butyl rubber seals, along top, bottom and sides of frame and
along each blade edge. Seals shall provide tight closing and low leakage. 48" x 48"
damper section shall have leakage less than 8 cfm/sf at 4" WG differential pressure.
Submit leakage and flow characteristic charts for approval. Dampers shall be
Honeywell, Inc. #D643 Series, Johnson Controls, Inc., #D-1330 Series, Ruskin SD-
50 or Vent Products 5900.
1. Install duct smoke detectors furnished under Division 26 where shown on Drawings.
Wire to fan shutdown. Wiring to fire alarm system shall be part of work of Division
26.
2. Provide normally-closed smoke dampers in return and supply air ducts where shown
to close automatically upon fan shutdown due to fire or smoke detection or upon
manual shutdown.
3. Smoke dampers shall be controlled so that fans shall not start until dampers are open
and fans shall stop before smoke dampers are fully closed. End switches, damper
switches, and other components required shall be by the BCS Contractor.
H. Freezestat
I. Flow Instruments
b. Sensor shall be sized for 110% of maximum flow and shall not exceed
manufacturer's flow rating.
f. Sensor shall be factory calibrated for the specific application according to the
range, fluid density, and specific gravity.
2. All traverse stations must be shown on the sheet metal shop drawings and
coordination drawings.
3. Provide for each station a Magnehelic gauge by Dwyer Inc. Gauges shall have dual
scales calibrated in both CFM and FPM increments. Gauge face scale shall be
matched to duct cross section and CFM involved. Gauge must be calibrated for
actual areas. For fan inlets, the shafts and bearing areas must be subtracted if
applicable. Mount gauge vertically on ductwork or air handling unit next to or close
to the traverse station. Provide two Dwyer A-313 vent valves for each gauge to
allow gauges to be removed from connecting tubing. Connect vent valves to
traverse stations with copper tubing as shown on detail - Do Not Crimp Tubing.
c. The airflow traverse probe shall not induce a measurable pressure drop, nor
shall the sound level within the duct be amplified by its singular or multiple
presence in the air stream. Each airflow measuring probe shall contain
multiple total and static pressure sensors placed at equal distances along the
probe length. The number of sensors on each probe and the quantity of
probes utilized at each installation shall comply with the ASHRAE Standards
for duct traversing.
a. Each device shall be designed and built to comply with, and provide results
in accordance with, accepted practice as defined for system testing in the
ASHRAE Handbook of Fundamentals, as well as in the Industrial Ventilation
Handbook.
e. Traverse stations shall be constructed out of the same type material as the
duct material.
f. Total and static pressure manifolds shall terminate with external ports for
connection to control tubing. An identification label shall be placed on each
unit casing, listing model number, size, area, and specified airflow capacity.
d. The Outside Airflow Measurement System shall measure inlet airflow with
an accuracy of ±5% of reading over a range of 150-600 FPM, 250-1,000
FPM, 150-2,000 FPM, and 500-2,000 FPM and not have its reading affected
by the presence of directional or gusting wind. Measured airflow shall be
density corrected for ambient temperature variances, and atmospheric
pressure due to site altitude.
e. The Outside Airflow Measurement System shall interface with the building
automation systems (BAS), accepting inputs for fan system start, economizer
mode operation, and an external controller setpoint, and provide flow
deviation alarm outputs.
f. The sensors shall be constructed of materials that resist corrosion due to the
presence of salt or chemicals in the air; all non-painted surfaces shall be
constructed of stainless steel.
1. Diaphragm type with dial and pointer in metal case, adjustable flag, vent valves,
black figures on white background, and front recalibration adjustment.
3. Accessories: Static pressure tips, tubing, gauge connections, and mounting bracket.
1. All wire shall be copper and meet the minimum wire size and insulation class listed
below:
2. Power and Digital I/O wiring may be run in the same conduit. Analog Input and
Analog Output wiring may be run in the same conduit provided they are shielded.
3. Where different wiring classes terminate within the same enclosure, maintain
clearances and install barriers per the National Electric Code.
6. Junction boxes shall be provided at all cable splices, equipment terminations, and
transitions from rigid to flexible conduit. Interior dry location J-boxes shall be
galvanized pressed steel, nominal four-inch square with blank cover. Exterior and
damp location J-boxes shall be cast alloy FS boxes with threaded hubs and gasketed
covers.
PART 3 - EXECUTION
A. This section specifies the requirements for interfacing to the original equipment manufacturers
(OEM) packaged control systems provided with the equipment specified in the sections listed
in Par 1 of this specification.
B. The BCS Contractor shall be responsible for the development and application of all necessary
programming code and the provision of all necessary hardware to allow the OEM packaged
control system and the BCS to communicate with one another.
C. The BCS Contractor shall, at his option, provide communication systems developed by the
OEM, if available, for the purposes set forth here-in.
1. Provide for monitoring, alarming, start/stop and setpoint reset control for all
equipment as applicable.
2. Communications from equipment shall provide for real time process variable
(temperature pressure, etc.) and status information.
E. Software Installation:
1. The BCS Contractor shall provide all labor necessary to install, initialize, start-up
and debug all system software as described in this section. This includes any
operating system software or other third party software necessary for successful
operation of the system.
3.2 PROCEDURES
A. Provide qualified personnel, equipment, apparatus and services for start-up, testing and
balancing of mechanical systems, to performance data shown in schedules, as specified, and as
required by codes, standards, regulations and authorities having jurisdiction including City,
Town or County Inspectors, Owners and Architect. Note that some BCS start-up procedures
require the cooperation of the balancing contractor, the equipment manufacturer's
representative and the BCS contractor. Ensure that all contractors are present on site during
the entire time that these procedures take place. Note that some procedures listed below have
a distinct order of precedence, e.g., the testing of the temperature control system shall not
occur until major pieces of mechanical equipment have been started up and testing is
complete. Ensure that any listed orders of precedence for procedures are followed.
C. Notify the Owner’s Representative at least two weeks before startup testing and balancing
begins.
D. Before control testing begins a meeting shall be held between the Owner’s Representative, the
balancing contractor, the BCS contractor, the mechanical and general contractor. The
mechanical contractor shall present the Owner’s Representative with the completed checklists
certifying that equipment startup and testing has been completed. The BCS contractor shall
then present his procedures for testing the BCS system to the Owner’s Representative for
review and approval. Allow one full day for this meeting.
E. When the control testing has been completed a second meeting will be held between the
parties mentioned above. At this time the BCS contractor shall present to the Owner’s
Representative the completed controls startup checklist. The balancing contractor shall
present to the Owner’s Representative certificates of calibration for balancing instruments,
proposed balancing forms and proposed balancing procedures for review and approval. Allow
one full day for this meeting.
F. It shall be the responsibility of the general contractor to set up these meetings. If, through no
fault of the Owner’s Representative, the above two meetings do not take place and the BCS
and balancing proceeds, the contractor shall be fully responsible to solve any ensuing
performance problems.
G. Do not cover or conceal work before testing and inspection has been approved by the Owner’s
Representative.
H. Instruments for testing shall have been calibrated in the installed position within one month
prior to testing. Calibration shall be traceable to NIST Standards. Provide certificate of
calibration to the Owner’s Representative at meeting demonstrating procedures mentioned
above.
I. Leaks, damage and defects discovered during or resulting from startup, testing and balancing
shall be repaired or replaced to like-new condition with acceptable materials. Tests shall be
continued until system operates without adjustments or repairs.
J. Report on reporting forms, submitted to the Owner’s Representative for approval in advance.
K. Submit six copies of testing reports to the Owner’s Representative for approval.
L. Install equipment and instruments required for testing, thermo-wells and gauge connections at
no additional cost to the Owner.
N. Startup and testing procedures outlined below are the minimum effort required for the project.
Contractor shall use any additional procedures he feels will be necessary to properly startup
and test the job.
A. Include time to be on site to participate in the startup of the following equipment. The
following pieces of equipment will be started in strict accordance with manufacturer’s
instructions and with manufacturer’s representative present:
1. Boilers
2. Chiller
3. Pumps
4. Air handlers
5. Fans
6. VFDs
1. Test Control System after all major pieces of equipment have been started up and
after all tests have been completed. Note portions of BCS test procedures below,
which require cooperation of balancing contractor. Ensure that balancing contractor
is present during entire time when these test procedures take place.
3. Perform any additional checkout test required by manufacturer for proper system
operation whether or not listed below. If any checkout test below conflicts with a
6. Where it is said below to simulate the operation of a particular cycle for the BCS,
actual control signal inputs at the time of the test shall be temporarily overridden
and test values substituted. For example to simulate an economizer switchover
temperature of 70 F outside temperature with the actual outdoor air input is 45 F,
temporarily substitute 70 F for 45 F, perform the test then switch back to the actual
input when the simulation is complete.
1. With the air handlers supply fan turned off and locked out/tagged out at the
disconnect, perform the following tests: (Contractor shall ENSURE that electric
power to air handler is OFF).
a. Visually inspect all fans interlocked with the supply fan to ensure that they
are off.
b. Visually inspect all control dampers and ensure that they are in positions that
the control sequences call for them to be when the fan is off. Particularly
ensure that the outdoor air damper is fully closed.
c. Note outputs to all control valves, and ensure that the valves are in position
that the control sequence require them to be when the fan is off.
d. For DDC system confirmed by checking workstation or laptop that fan status
is off.
2. Ensure that all personnel and tools are out of air handler casing, ensure that casing is
closed and locked; put any disconnect other than that locked out to the on position.
Then have fan started at the locked out disconnect and perform the following
procedures.
a. For units which are not supposed to start until smoke or outdoor air dampers
are proven fully open via limit switches visually observe the damper
operators and limit switches when the signal is given to start the fan and
ensure that the fan does not start until contact with the limit switch is made.
b. Ensure that fans interlocked to air handler supply fan run after AHU fan
starts. Visually observe each fan.
c. Adjust freezestat setpoint upwards until freezestat trips confirm stat has
tripped with continuity tester. Ensure that fan stops and dampers and valves
go to positions outlined in control sequences. Particularly ensure that
outdoor air damper is fully closed (and heating coil valve is fully open).
After test, set freezestat setpoint to design, press manual reset button and
confirm that fan restarts. (For DDC system ensure that freezestat alarm
condition is reported at workstations and printer when freezestat is activated).
d. With balancing contractor present, test static pressure low and high limit
switches as follows: Connect pneumatic tubing to high or low port of limit
switch (depending on whether switch is to trip on low or high pressure)
connect via a tee, the same pneumatic line to manometer. For a high pressure
switch connect tubing to manometer port used for measuring positive static
pressure. For a low pressure switch connect tubing to port used for
measuring negative static pressure. Slowly pressurize tubing and observe
manometer. Ensure that switch trips and fan shuts down at pressure called
for by control sequence. Confirm that switch has tripped with continuity
tester. After test remove test tubing and press manual reset button ensure that
fan restarts. (For DDC systems ensure that correct alarm message registers at
workstations and line printer when switch trips).
e. For DDC systems ensure correct status signal registers at workstations and
line printer when fan is on.
f. For DDC system with differential pressure switches across filter bank repeat
procedure used to test limit switches and ensure switch trips at correct
setpoint. Confirm switch has tripped with continuity tester only (fan should
not stop). Confirm dirty filter alarm registers at workstations and printer
when switch has tripped.
g. To test units with dry bulb economizer cycles do the following: Simulate
outdoor temperature greater than economizer switchover temperature.
Ensure that outdoor air damper is in minimum position (or variable outdoor
air damper is fully closed if minimum damper is called for in the control
sequences). Change discharge air setpoint downwards confirm cooling coil
valve modulates open. Change discharge setpoint upwards confirm cooling
coil valve modulates closed. Simulate outdoor air temperature below
economizer switchover setpoint-above discharge air setpoint. Ensure that
outdoor air damper (or variable outdoor air damper) fully opens. Change
discharge setpoints and ensure cooling coil valve modulates properly.
Simulate at least three outdoor air temperature below discharge air setpoint.
Ensure that cooling coil valve is closed and that as simulated outdoor
temperature is reduced the outdoor air damper and relief damper modulate
closed, while the return damper modulates open.
i. Confirm that toilet and other exhaust fans start and stop properly via (time
clock) (time clock function in DDC systems).
j. Verify that differential pressure switches across pumps give correct pump
status when pumps are on or off.
l. For VAV systems with volumetric controls confirm that velocity pressure
transducers are piped correctly to flow measuring stations in both supply and
return ductwork. Balancer shall measure supply and return air flows with
manometer (take velocity pressure reading convert to velocity then multiply
by duct area to get cfm). BCS contractor shall adjust output to return fan to
maintain cfm differential with supply. BCS contractor shall simulate
changed input from duct mounted static pressure transducer and shall note
that supply and return fan (VFD) modulate appropriately. Balancer shall
repeat measurements at flow measuring stations, BCS contractor shall adjust
output to return fan (VFD). Above procedure shall be repeated as often as
necessary to maintain constant cfm differential between supply and return
fans between 30% and 100% of maximum flow.
m. Initiate warmup cycle; ensure ALL control components operate as called for
in control sequence of operation.
n. Initiate occupied cycle; ensure ALL control components operate as called for
in control sequence of operation.
1. Fill out the following controls testing checklist for each system on the job.
Checklist shall be signed by both representative of controls vendor and of the
general contractor. If a cycle listed below does not apply to a particular system
write N.A. (not applicable) under the heading "Date Confirmed". Make as many
copies of checklist, and add systems to it as required to list testing of all systems.
System No.
General Contractor
ATC Representative Representative
ATC Cycle Date Confirmed Name and Signature Name and Signature
Fan Differential
Pressure Switches
VFD Posi-
tion at Startup
Freezestats
Filter Differ-
ential Pressure
Switches
Static Pressure
Limit Switches
Smoke Detectors
Valves Damper
Position when Fans
are Off
Smoke Damper
Limit Switches
Fan Interlocks
Economizer
Cycle
Face and
Bypass Dampers
Air Handler Operation
System No.
General Contractor
ATC Representative Representative
ATC Cycle Date Confirmed Name and Signature Name and Signature
Static Pressure
Transducer
Calibration
Room Thermostat
Calibration
Emergency Genera-
to Controls
Toilet Exhaust
Fans Start/Stop
Chiller Differ-
ential Pressure
Switches
Pumps Differ-
ential Pressure
Switches
Differential
Pressure Bypass
Valves
Alarms
VAV Volumetric
Controls
Warmup Cycle
Occupied Cycle
Unoccupied Cycle
2. At each constant volume box, use magnehelic gauge to adjust setpoint of box
controller to differential pressure corresponding to velocity (airflow) scheduled for
box.
A. The BCS Contractor shall provide all labor necessary to install, initialize, start-up and debug
all system software. This includes any operating system software or other third party software
necessary for successful operation of the system.
A. The BCS Contractor shall provide all labor to configure those portions of the database that are
required by the sequence of operation shown on the drawings.
A. Unless otherwise directed by the Owner, the BCS Contractor shall provide color graphic
displays as depicted in the mechanical drawings for each system and floor plan. For each
system or floor plan, the display shall contain the associated points identified and allow for
setpoint changes as required by the operator.
A. Well-mounted sensors shall include thermal conducting compound within the well to insure
good heat transfer to the sensor.
B. Control dampers shall be furnished by this Contractor and installed by Section 23 06 00.
C. Automatic control valves shall be furnished by this Contractor and installed by Section 23 06
00.
D. Actuators shall be firmly mounted to give positive movement. Linkage shall be adjusted to
give smooth continuous movement throughout 100 percent of the stroke.
E. Water line mounted sensors shall be removable without shutting down the system in which
they are installed (provide valves).
F. For duct static pressure sensors, the high pressure port shall be connected to a metal static
pressure probe inserted into the duct pointing upstream. The low pressure port shall be left
open to the plenum area at the point that the high pressure port is tapped into the ductwork.
G. For building static pressure sensors, the high pressure port shall be inserted into the space via a
metal tube & static sensing tip. Pipe the low pressure port to the outside of the building.
H. Conduit, in finished areas, shall be concealed in ceiling cavity spaces, plenums, furred spaces
and wall construction.
I. Conduit, in non-finished areas where possible, shall be concealed in ceiling cavity spaces,
plenums, furred spaces, and wall construction. Exposed conduit shall run parallel to or at right
angles to the building structure.
J. Conduit shall be kept a minimum of three (3) inches from hot water, steam, or condensate
piping.
K. Where sensor wires leave the conduit system, they shall be protected by a plastic insert.
L. Wire or pneumatic tubing shall not be allowed to run across telephone equipment areas.
M. Control air tubing shall be run concealed wherever possible, properly supported, and installed
in a neat and workmanlike manner. Tubing shall not be exposed in occupied areas.
N. Tubing run in equipment rooms, apparatus rooms, mechanical shafts, and return air plenums
shall be installed in conduit. Tubing at air handling units may be installed in metal raceway
with connections to devices exposed.
O. All control tubing or wiring running down exposed walls to controls or control panels shall be
run in conduit.
P. All control tubing or wiring in floor slabs shall run in rigid conduit.
R. All control air tubing installed for the project shall be thoroughly cleaned before placing in
operation to rid the system of dirt, piping compound, mill scale, oil, and any other material
foreign to the air being circulated.
3.9 ENCLOSURES
A. For all input/output devices, which require field interface devices, these devices shall be
mounted in a field interface panel (FIP). All other field interface devices shall be mounted at
the point of field interface in a separate enclosure suitable for the location. The Contractor
shall provide an enclosure, which protects the devices from dust and moisture, and conceals
integral wiring and moving parts.
B. Field Interface Panels shall contain power supplies for sensors, interface relays and contactors,
safety circuits, and I/P transducers.
C. The FIP enclosure shall be of steel construction with baked enamel finish, with a hinged door
and keyed lock. The enclosure shall be sized for twenty percent spare mounting space. All
locks will be keyed identically.
D. All wiring to and from the FIP shall be to screw type terminals. Analog or communications
wiring may use the FIP as a raceway without terminating. The use of wire nuts within the FIP
shall not be allowed.
E. All wiring within the FIP shall be run in plastic raceway to provide a neat and workmanlike
appearance.
3.10 LOCATION
B. Space humidity and temperature sensors shall be mounted away from machinery generating
heat, direct light and diffuser air streams.
C. Outdoor air sensors shall be mounted on the north building face directly in the outside air.
Install these sensors such that the effects of heat radiated from the building or sunlight is
minimized.
D. Field enclosures shall be located immediately adjacent to the controller panel(s) to which it is
being interfaced.
3.11 IDENTIFICATION
A. All field devices that are not mounted within panels shall be identified with permanent labels.
C. The identification shall match the point description as approved by the Owner’s
Representative.
D. Each terminal strip termination shall be tagged with an identification that matches the as-built
control drawings.
E. The outside of each FIP shall be identified with a permanent label matching the identification
name shown on the as-built control drawings.
G. Identify all control wires with labeling tape or sleeves at each termination using either words,
letters, or numbers that can be exactly cross-referenced with as-built drawings.
H. Identify all pneumatic tubing with labeling tape or sleeves at each termination using either
words, letters, or numbers that can be exactly cross referenced with as-built drawings.
I. All field enclosures, other than controllers, shall be identified with a permanent nameplate.
J. Junction box covers shall be marked to indicate that they are a part of the BCS system.
3.12 CLEANUP
A. At the completion of the work, all equipment pertinent to this contract shall be checked and
thoroughly cleaned, and all other areas shall be cleaned around equipment provided under this
contract. Clean the exposed surfaces of tubing, hangers, and other exposed metal of grease,
plaster, or other foreign materials.
B. At the completion of work at the end of each day, remove from the building, premises, and
surrounding streets, etc. all rubbish and debris resulting from the operations and leave all
equipment spaces clean and ready for use.
A. All BCS equipment power shall be powered from the electric panels provided by Division 26.
B. It is the responsibility of the BCS Contractor to provide 120V power wiring from the breaker
provided by Division 26 to the final locations of the BCS equipment.
C. The power shall be obtained from dedicated circuits 120V panels and clearly labeled by the
BCS Contractor. (Refer to the electrical drawings for panel schedules). Any breakers not used
by the BCS shall be labeled “spare” by the BCS Contractor.
D. All power wiring for the BCS equipment shall be done with a dedicated earth ground by
means of copper wire media only, originating at the power service source earth ground. This
applies to all Level 1 and Level 2 controllers along with work stations and the file server.
END OF SECTION