• Network Structures
- Distance Protection
Building A
Building B
Building C
Building D
open point
U0 = Un/√3
www.ProtectionRelay.ir
Siemens LV-Fuses:
Selectivity (only
Fuse F3 blows) is
guranteed at high
currents up to a
ratio of :
I K1
≤ 0.8
I K1 + I K 2
•Cable of same cross-section
•Same LV fuses
Copyright © Siemens AG 2007. All rights reserved.
Page 122 2007-08 Author PTD SE PTI
Selectivity: Circuit Breaker → Downstream Fuse
> 1s
Overload
range Selectivity check
in the short-circuit range by
> 70ms I2t - comparison
I> I>
www.ProtectionRelay.ir
I>
I>
I>
Obsolete!
Only in old Obsolete!
substations, Practised only with
no more electromechanical
recommended! protection. !
L3 L1
L2
L3
www.ProtectionRelay.ir
L2
E
IR
L3 L2
relay Digital relay
c.t.s c.t.s
L1 L1
L2 L2
L3 L3
Calculated:
IR = IL1 + IL2 + IL3 IR = I1 + I2 + I3
„Holmgreen“ connection
L3
L1 L2
IFault Ishield
Iearth
Ιf
~
Ιf
www.ProtectionRelay.ir
U {kV}
2
ZN = N {Ω}
Current grading S'K {MVA}
U {%} UN {kV}
2
ZTr = K Ω
100 SN {MVA}
fault location
Example: Ι >> for faults at HV-side
1 2
Netz
ΙK
UN = 100 kV 110 kV
SK = 5 GVA in 1 ΙK = = 26,5 kA
3 ⋅ 2,4 Ω line impedance
ZN = 2,4 Ω neglected!
SN = 20 MVA 110 kV
uK = 10% in 2 ΙK = = 2,4 kA
ZTr = 60,5 Ω 3 ⋅ 62,9 Ω
~ ~
www.ProtectionRelay.ir
Ι >>
Ι>
t
t2
t1 t3
t = 700 ms
t = 400 ms
t = 100 ms
100
Normal inverse:
t
www.ProtectionRelay.ir
[s]
0.14
t= x Tp
0.02
⎛ I ⎞
⎜⎜ ⎟⎟ −1
⎝ Ip ⎠
10 Very inverse:
DT (4 s) 13.5
t= x Tp
1
⎛ I ⎞
⎜⎜ ⎟⎟ − 1
NI ⎝ Ip ⎠
0.1
1 10 100 I / Ip
Copyright © Siemens AG 2007. All rights reserved.
Page 134 2007-08 Author PTD SE PTI
Normal inverse setting characteristic
t
[s]
www.ProtectionRelay.ir
Normal inverse:
0.14
t= x Tp
0.02
⎛ I ⎞
⎜⎜ ⎟⎟ −1
⎝ Ip ⎠
NI setting characterisic of
the relay 7SJ6 (Siemens)
I / Ip
ZS ZL
www.ProtectionRelay.ir
Equivalent circuit
100%
fault
current Current grading
0.4 Ω/km (OH-Line) depends on the SIR ratio!
1km
fault location
A B C D
ZS
www.ProtectionRelay.ir
~ X X X
51 51 51
IF
fault location
t
tg
tg
Grading requirement:
tg23
0.14 ⋅ Tp ,n 0.14 ⋅ Tp ,n +1 ⎡⎛
200 − 400 ms ⎜ Isc ⎟ ⎞
0.02
⎤
⇒ = 200 − 400 ms + ⇒ Tp,n = Tp,n +1 + ⋅ ⎢⎜ ⎟ − 1⎥
⎢⎝ I p ⎠ ⎥
0.02 0.02
⎛ Isc ⎞ ⎛ Isc ⎞ 0.14
⎣ ⎦
⎜ ⎟ −1 ⎜ ⎟ −1
⎜I ⎟ ⎜I ⎟
⎝ p⎠ ⎝ p⎠
Disk
position
www.ProtectionRelay.ir
∆t
Trip
3 Ip
2 Ip 0,4 Ip
With
Without
Disc emulation
Reset
0 0,2 0,4 0,6 0,8 1
t [s]
ms
gain of
tripping
time
A B
1
www.ProtectionRelay.ir
Fault at busbar B
www.ProtectionRelay.ir
A B C D
- Distance Protection
breaker failure
Graphical
representations:
X
Line characteristic
for
• Distance zones
wa
X
rds
Line
– Inclined with line angle ϕ
www.ProtectionRelay.ir
Z5
Load ϕ Load
Z3
www.ProtectionRelay.ir
Z2
A Z1 B C D
ZT
D D D Ι>>
Ι>t
∆Ι
Z1 = 0.85 ZA-B
grading time
www.ProtectionRelay.ir
(s)
0.6
0.3
A B A B C
A B A B
Z1.zone = 1.20 x ZA,B Z1.zone=Z2.zone=Z3zone Z1.Zone = 0.85 x Ztransf. Z1.zone=Z2.zone=Z3.zone
A C
Z2.zone = 0.90 x ( ZA,B + 0.85 x min {ZB…} )
B F
Example
Protection strategy 2
A B C
A E
C F
B D G
I>
Phase Fault : Ip Tp
I> T> *)
I >> T >> T>
I >>> T >>>
I >>
T >>
Earth Fault : I Ep TEp
I E> T E> *) I >>>
I E>> T E>>
T >>>
*) characteristic
time [s]
www.ProtectionRelay.ir
I>
T>
I >>
T >>
current [A]
time [s]
www.ProtectionRelay.ir
Ip
Tp normal inverse
extremly inverse
I>
T>
current [A]
Phase Fault : Ir tc
Id td Ir
Ii ti tc
Id
td
Earth Fault : Ig tg
Ii
I2t=const.
ti
thermal
Motor curve
I rated
thermal
Curve
SC limit
secondary
In
Rush SC limit
primary
time limit of
Protection below
Requirements:
Ip ~ 110 % * In,motor
Requirements HV side:
I> ~ I>>sec.side
T> = T>>sec side + 1 time step
Requirements LV side:
Ip ~ 1.1 * In,tr
I>> ~ 3 – 4 * In,tr
I>> < Isc,min