Anda di halaman 1dari 5

Exchange of puls/mA converter A10 in separator control panel type SCS 45D from

old design to the new design.

In the SCS 45D, there is a puls/mA converter A10 (Peppler & Fuchs, green relay) with
article number 31801-5215-1. The old relay has been changed by the manufacturer and
is replaced by a similar relay. The settings and electrical connections are however
different.

While the old relay had mechanically adjustable numbers in the front (five numbers for
example set on “10040”), the new relay have an LCD display in the front showing the
speed (rpm) while running, and parameters while programming.

If the old A10 relay is broken and has to be replaced by the new type, use the following
instructions of parameter settings and electrical connections.

A10 P&F KFU8


Programming Flow Chart

Measured
value
indication

Unit Hz Error

rpm Smoothning

Pulses / Turn
Input
Contact
bounce filter

Startup
override

Output Relay 1 Line switch Min / Max

Relay 2 Serial switch Trip

OT1 Pulse divider Divider ratio Hysteresis

Pulse duration Mode

Error indication Alarm Freeze Alarm Freeze

I out Characteristic

Fault current

Start value

End value

Inverted

Service Password

Language

J:\1.1 CentriSep\SID\SCS\SCS45\A10 PA10 PF puls_mA KHD2 to KFU8-UFC-Ex1D1.xls puls_mA KHD2 to KFU8-UFC-Ex1D.xls


Settings for PEPPERL & FUCHS KFU8-UFC-(Ex) 1.D

Unit rpm

Input Pulses / Turn 4

Output Relay 1 Line switch On

Relay 2 Line switch On

OT1 Serial switch On

I out Characteristic 4-20 mA NE 43

Fault current Down

Start value 0,000 rpm

End value Set to maximum


syncronous motor
speed, see table 1

Inverted norm.

Table 1.
Hz End Value Remark
50 1500 Sep. with 50 Hz gear
60 1800 Sep. with 60 Hz gear
55 1650 818HGV with 50 Hz gear
66 1980 818HGV with 60 Hz gear

J:\1.1 CentriSep\SID\SCS\SCS45\A10 PA10 PF puls_mA KHD2 to KFU8-UFC-Ex1D1.xls puls_mA KHD2 to KFU8-UFC-Ex1D.xls