Anda di halaman 1dari 5

ABB Grid Automation Products

Bay control REC670/650 2.1


Overview

1MRG023693 A

Chapter 2
Contents

§ Bay control REC670/650


§ Configuration alternatives REC670/650
§ Control functions REC670
§ Protection functions REC670
§ Communication REC670
§ Control functions REC650
§ Protection functions REC650
§ Communication REC650

© ABB Group
April 7, 2016 | Slide 2
Chapter 2
Bay control REC670/650
Relion® 670 and 650 series

§ The REC670 and REC650 Bay control IEDs are designed for control,
monitoring and protection of circuit breakers, disconnectors, and
earthing switches in different switchgear configurations.

© ABB Group
April 7, 2016 | Slide 3

Chapter 2
Configuration alternatives REC670/650

Maximum flexibility and Ease of use from ready-to-use


perfomance solutions
§ REC670 provides: § REC650 provides:
§ Fully customized solutions § Customized version
§ Pre-configured solutions § For 1.3 available but not in 2.1

§ A30: Double busbar single breaker § Configured solutions


arrangement
§ A02: Double busbar single breaker
§ A31: Bus coupler arrangement
§ B30: Double busbar double breaker
§ From ver. 2.1, only control functions
arrangement
§ C30: 1 1/2 breaker arrangement

© ABB Group
April 7, 2016 | Slide 4
Chapter 2
Bay control REC670
Control functions

§ Apparatus control for up to six bays


and 30 apparatus
§ Number of instances are set to
cover a full diameter with one
REC670
§ Ready to use interlocking modules
for different switchgear
arrangements
§ Several alternatives for reservation
functionality
§ Synchronizing, synchro-check and
energizing check
§ Auto-recloser
§ Automatic/Manual voltage control
for a single transformer or for up to
four/eight parallel transformers

© ABB Group
April 7, 2016 | Slide 5

Chapter 2
Bay control REC670
Back-up protection functions
§ Six independent parameter setting groups
§ Current protection
§ Instantaneous phase- and residual overcurrent
protection, Breaker failure protection, Stub
protection, Pole discordance protection, Capacitor
bank protection, etc…

§ Voltage
§ Over- and under-voltage protection with definite
and inverse time characteristics, Voltage three-
phase differential for capacitor banks, Loss of
voltage etc…

§ Secondary system supervision


§ Fuse failure supervision, Current circuit
supervision

§ Frequency functions
§ Over- and under-frequency protection, Rate-of-
change frequency protection

§ Multipurpose function
§ General current and voltage protection

© ABB Group
April 7, 2016 | Slide 6
Chapter 2
Bay control REC670
Station Communication
§ IEC 61850-8-1 Ed1&Ed2
§ IEC 61850-9-2 LE Process bus
§ Individually supervised redundant station
bus with zero seconds recovery time.
§ IEC 60870-5-103 slave protocol
§ DNP 3.0 slave protocol
§ LON
§ SPA
§ Remote end communication for transfer
of up to 192 binary signals when no
analog signal and 8 binary signals + 4
analogue signals
§ Cyber security support for compliance to
NERC CIP and IEC 62351-8 with
Centralized Account Management

© ABB Group
April 7, 2016 | Slide 7

Chapter 2
Bay control REC650
Control functions

§ Six independent parameter setting


groups
§ Apparatus control for one bay and up
to 10 apparatuses
§ Ready to use interlocking modules
§ Reservation function
§ Synchronizing, synchro-check and
energizing check

© ABB Group
April 7, 2016 | Slide 8
Chapter 2
Bay control REC650
Station Communication
§ IEC 61850-8-1 Ed1&Ed2
§ DNP 3.0 slave protocol
§ IEC 60870-5-103 serial communication
§ IEC 62439-3 Ed. 2 Parallel Redundancy Protocol (PRP)
§ Cyber security support for compliance to NERC CIP and IEC 62351-8
with Centralized Account Management

© ABB Group
April 7, 2016 | Slide 9

Chapter 2

© SA-T Training
Slide 10
© ABB Group
1MRG004730
April 7, 2016 | Slide 10