PCS-9705 BCU

NR Electric Co., Ltd.


System architecture
Dispatching Center

Network Operator Operator Engineering RCS9785C


Printer Workstation Workstation Workstation RCS-9698G GPS
Gateway

PCS-9882
Ethernet switcher LAN
Control Room

PCS-9882 PCS-9882
Ethernet switcher Ethernet switcher

GPS Clock Syschronication


Protection protection BCU Protection protection BCU

IED Room 1 www.nrelect.com


IED Room 2 2
Communication model
• Communication model

LDC

Clint Clint
Operator station
Gateway

Server BI Server BI
BO AI BO AI
BCU BCU

GOOSE
MMS
LAN MMS

www.nrelect.com 3
Bay Control Unit
• Functions
- Object-oriented designed

- Binary inputs acquisition

- Voltage and current acquisition

- Measure analog quantity from transducer

- Tap changer position acquisition and control

- Remote control

www.nrelect.com 4
Bay Control Unit
• Application configuration
App 1 App 2 App 3 App 4 App 5
12CT
AI input 4CT 5VT 13VT 7CT 8VT 24VT
12VT
Transducer
0 or 8 or 16
input

DC output 0 or 4 / /

BI 14 fixed + up to 106 14 fixed + up to 106

BO 15 groups (30 contacts) 25 groups (50 contacts)

Synchronism-
1 0 Up to 2 0 1
check channel
BO Up to 10 groups
Up to 15 group (30 contacts)
(interlocking) (20 contacts)

www.nrelect.com 5
Bay Control Unit
• Hardware

 LED indicator
HEALTHY
PCS-9705
ALARM BAY CONTROL UNIT

C GRP
ENT

ES
HEALTHY  Testing port
ALARM

 LCD displayer  Keyboard

2010-06-08 18:00:02

P
GR
ENT

C
Ia 0.00A

ES
Ib 0.00A
Ic 0.00A
P 0.00MW
Q 0.00MVar

Addr 12345 Group 01

www.nrelect.com 6
Bay Control Unit
• Hardware

NR4106MB NR4138 NR4402 NR4501 NR4501 NR4501 NR4501 NR4501 NR4410 NR4410 NR4522 NR4522 NR4522 NR4522 NR4522 NR4522 NR4301

ON

OFF
RX

RX

www.nrelect.com 7
Bay Control Unit
• LCD display

2010-06-08 18:00:02 2010-06-08 18:00:02

Ia 0.00A
Ib 0.00A
Ic 0.00A
P 0.00MW Ia 0.00A
Q 0.00MVar Ib 0.00A
Ic 0.00A
P 0.00MW
Q 0.00MVar

Addr 12345 Group 01 Addr 12345 Group 01

www.nrelect.com 8
Hardware
• MON module No. Description
NR4106MA 101 RS-485A_1
No. description setting 102 RS-485B_1
1 000.000.000.000~ 103 SGND
IP_LAN1
255.255.255.255 104

2 000.000.000.000~ 105 RS-485A_2


Mask_LAN1
255.255.255.255 106 RS-485B_2

3 En_LAN2 0 or 1 107 SGND


108
4 000.000.000.000~
Gateway 109
255.255.255.255
110 SYN +
5 000.000.000.000~
SNTP 111 SYN -
255.255.255.255
112 SGND
113
114 RXD
115 TXD
116 SGND
www.nrelect.com 9
Hardware
• AI module

4402
No. Description No. Description No. Description
301 302 301 Ia 310 319 U0
303 304
305 306 302 Ian 311 320 U0n
307 308 303 Ib 312 321 Usyn
309 310
311 312
304 Ibn 313 Ua 322 Usyn_n
313 314 305 Ic 314 Uan 323
315 316
317 318
306 Icn 315 Ub 324
319 320 307 I0 316 Ubn
321 322
323 324
308 I0n 317 Uc
309 318 Ucn

www.nrelect.com 10
Hardware

www.nrelect.com 11
Hardware
• AI module

4402

301 302 No. Description No. Description No. Description


303 304 301 U1 310 U5n 319 U10
305 306
307 308
302 U1n 311 U6 320 U10n
309 310 303 U2 312 U6n 321 U11
311 312
304 U2n 313 U7 322 U11n
313 314
315 316 305 U3 314 U7n 323 U12
317 318
306 U3n 315 U8 324 U12n
319 320
321 322 307 U4 316 U8n 325 U13
323 324
308 U4n 317 U9 326 U13n
325 326
309 U5 318 U9n

www.nrelect.com 12
Hardware

www.nrelect.com 13
Hardware

www.nrelect.com 14
Hardware
• AI module

4402
No. Description No. Description No. Description
301 302
301 Ia1 310 Ib2n 319 Usyn1
303 304
305 306 302 Ia1n 311 Ic2 320 Un_syn1
307 308
303 Ib1 312 Ic2n 321 Ua2
309 310
311 312 304 Ib1n 313 Iext 322 Ub2
313 314
305 Ic1 314 Iextn 323 Uc2
315 316
317 318 306 Ic1n 315 Ua1 324 Un2
319 320
307 Ia2 316 Ub1 325 Usyn2
321 322
323 324 308 Ia2n 317 Uc1 326 Un_syn2
325 326
309 Ib2 318 Un1

www.nrelect.com 15
Hardware

www.nrelect.com 16
Hardware
• NET-DSP

www.nrelect.com 17
Hardware
• BI Module 4501 4504
01 Opto+ 01 Opto+

ˉ Type A: 110Vdc to 250Vdc 02 BI_01 02 BI_01

03 BI_02 03 Opto-_1

ˉ Type D: 24Vdc to 48Vdc 04 BI_03 04 BI_02

05 BI_04 05 BI_03

06 BI_05 06 Opto-_2

07 BI_06 07 BI_04

08 BI_07 08 BI_05

09 BI_08 09 Opto-_3

10 BI_09 10 BI_06

11 BI_10 11 BI_07

12 BI_11 12 Opto-_4

13 BI_12 13 BI_08

14 BI_13 14 BI_09

15 BI_14 15 Opto-_5

16 BI_15 16 BI_10

17 BI_16 17 BI_11

18 BI_17 18 Opto-_6

19 BI_18 19 BI_12

20 BI_19 20 BI_13

21 BI_20 21 Opto-_7

22 Opto- 22
www.nrelect.com 18
Hardware
• Special binary inputs
- BI_maintenance

- CILO.BI_Disable

- BI_Rmt/Loc

- BI_Manual_Synchro

- BI_manual_Open

www.nrelect.com 19
Bay Control Unit
• Binary Inputs

HV switchyard
+5V
+220Vdc
Auxiliary
Contacts Validate the change of
binary input state &
CPU write it into SOE
record
CB

Debouncing time
t
t0 t1

www.nrelect.com 20
Hardware
NR4410
• DI Module (DC analog input) 01 +
DI1
02 –
03 GND1
Signal input range SX JPX-1 JPX-2 04 +
DI2
0~20mA/4~20mA DC ON OFF ON 05 –
06 GND2
0~5V DC OFF OFF ON 07 +
DI3
0~250V DC OFF ON OFF 08 –
09 GND3
10 +
DI4
11 –
12 GND4
13 +
DI5
14 –
15 GND5
16 +
DI6
17 –
18 GND6
19 +
DI7
20 –
21 +
DI8
22 –

www.nrelect.com 21
Hardware
4522
• BO Module 01 BO_01+
02 BO_01-
03 BO_02+
04 BO_02-
05 BO_03+
06 BO_03-
Control output 07 BO_04+
08 BO_04-
09 BO_05+
10 BO_05-
Signals from Driver 11 BO_06+
CPU Module Circuit 12 BO_06-
13 BO_07+
14 BO_07-

Signal output 15 BO_08+


16 BO_08-
17 BO_09+
18 BO_09-
19 BO_10+
20 BO_10-
21 BO_11+
22 BO_11-
www.nrelect.com 22
Bay Control Unit
• Control circuit
BCU
+DC
Blocking Relay
for close

Blocking Relay
Interlocking for open
Logic

Opening execution
selection relay relay

Closing execution
relay

Manual close close

Manual open open


www.nrelect.com 23
Bay Control Unit
• Control circuit
BCU
+DC
Blocking Relay
for close

Blocking Relay
Interlocking for open
Logic
close

Opening execution
selection relay relay
Manual close
open
BI (Manual close)
Manual open
Closing execution
BI (Manual open)
relay

www.nrelect.com 24
Bay Control Unit
• Synchronization check
• 3 check modes
- No check mode
- Dead check mode
- Synchronism check mode

• 4 types of command
- No check command
- Dead check command
- Synchronism check command
- Normal remote control command

www.nrelect.com 25
Bay Control Unit
• RSYN check setting
- 25.Link_DeadChk
- 25.Link_SynChk

• 25.HMI_Mode

www.nrelect.com 26
Bay Control Unit
• Syn_setting
No. Name Range Step (Unit)
1 25.U_UV_SynChk 1%-100% Un 1%
2 25.U_Diff_SynChk 1%-100% Un 1%
3 25.f_Diff_SynChk 0.00-3.00 Hz 0.01
4 25.df/dt_SynChk 0.10-5.00 Hz/s 0.01
5 25.phi_Diff_SynChk 0.10-180.00 Deg 0.01
6 25.Opt_Mode_DeadChk 1-7 1
7 25.En_VTS_Blk_DeadChk 0-1 1
8 25.En_VTS_Blk_SynChk 0-1 1
9 25.t_Reset_SynChk 5000-30000 ms 1
10 25.U_DeadChk 1%-100% Un 1%
11 25.U_LiveChk 1%-100% Un 1%
12 25.Opt_U_Synchk 0-5 1
13 25.Phi_Comp_Diff 0-360 Deg 1
14 25.t_Close_CB 0-1000 ms 1
www.nrelect.com 27
Bay Control Unit
• Troubleshooting for BCU
- Alm_OptoDC

* Check whether the BI module is connected to the power supply

* Check whether the voltage of power supply is in the required range

- Alarm_TimeSyn

* Check whether the selected clock synchronization mode matches the clock
synchronization source

* Check whether the wiring connection between the device and the clock
source is correct

www.nrelect.com 28